Академический Документы
Профессиональный Документы
Культура Документы
IM 01R04B04-00E-E
Contents
1. Introduction ......................................................................................... 1-1
1.1 Using the Coriolis Flowmeter Safely ...............................................................1-2
1.2 Warranty ............................................................................................................1-3
1.3 Instruction according EMC ..............................................................................1-3
1.4 ATEX Documentation .......................................................................................1-4
1.5 Disposal, Cleaning and Return ........................................................................1-6
2. Transportation and Storage ............................................................... 2-1
3. Product description ............................................................................ 3-1
3.1 The Coriolis principle .......................................................................................3-1
3.2The Integral Type RCCT3 ..................................................................................3-2
3.3 The Remote Converter RCCF31 .......................................................................3-3
3.4 The Remote Detector RCCS30 to 33 ...............................................................3-4
3.5 The Remote Detector RCCS34 to 39/IR ...........................................................3-5
3.6 Measurement system and applications ..........................................................3-6
4. Installation ........................................................................................... 4-1
4.1 Piping .................................................................................................................4-1
4.2 Installing of the flowmeter ................................................................................4-2
4.3 Alteration of display..........................................................................................4-3
4.4 Wiring .................................................................................................................4-4
4.4.1 Assembling and connecting the Remote Cable RCCY03 .................................. 4-4
4.4.2 Power supply wiring .............................................................................................. 4-6
4.4.3 Connecting to external instruments ..................................................................... 4-8
4.4.4 Connecting HART- Communication ................................................................... 4-11
4.4.5 Flowmeters with intrinsic safe outputs .............................................................. 4-11
5. Basic operating procedures ............................................................... 5-1
5.1 Liquid crystal display .......................................................................................5-1
5.2 Display modes ...................................................................................................5-3
5.3 Setting via keys .................................................................................................5-4
5.4 Examples of parameter settings via keys .......................................................5-5
5.4.1 Display configuration, set volume flow to line 1 ................................................. 5-5
5.4.2 Setting Temperature 20-120°C to Analog Output 2 ............................................. 5-6
5.5 Setting parameters in converter with option /NC ...........................................5-8
5.6 Zero adjustment (Autozero) .............................................................................5-8
IM 01R04B04-00E-E i IM 01R04B04-00E-E
5th edition Nov. 2005 5th edition Nov. 2005
All Rights Reserved, Copyright 2003. Rota Yokogawa GmbH & Co. KG
CONTENTS
IM 01R04B04-00E-E ii
5th edition Nov. 2005
CONTENTS
iii IM 01R04B04-00E-E
5th edition Nov. 2005
CONTENTS
IM 01R04B04-00E-E iv
5th edition Nov. 2005
1. INTRODUCTION
1. Introduction
This instrument has been adjusted at the factory Safety and Modification Precautions
before shipment. • The following general safety precautions must
be observed during all phases of operation,
To ensure correct use of the instrument, please
service, and repair of this instrument. Failure to
read this manual thoroughly and fully understand
comply with these precautions or with specific
how to operate the instrument before operating it.
WARNINGS given elsewhere in this manual
violates safety standards of design,manufacture,
NOTE and intended use of the instrument. Yokogawa
This manual describes the hardware and soft- assumes no liability for the customer's failure to
ware configurations of the Rotamass Coriolis comply with these requirements. If this
Massflowmeter. instrument is used in a manner not specified in
this manual, the protection provided by this
instrument may be impaired.
Regarding This User's Manual • The following safety symbol marks are used in
• This manual should be provided to the end this user's manual and instrument.
user.
• Before use, read this manual thoroughly to WARNING
comprehend its contents.
• The contents of this manual may be changed A WARNING sign denotes a hazard. It calls
without prior notice. attention to procedure, practice, condition or the
• All rights are reserved. No part of this manual like, which, if not correctly performed or adhered
may be reproduced in any form without to, could result in injury or death of personnel.
Yokogawa's written permission.
• Yokogawa makes no warranty of any kind with
regard to this material, including, but not limited
CAUTION
to, implied warranties of merchantability and
suitability for a particular purpose. A CAUTION sign denotes a hazard. It calls
• All reasonable effort has been made to ensure attention to procedure, practice, condition or the
the accuracy of the contents of this manual. like, which, if not correctly performed or adhered
However, if any errors or omissions are found, to, could result in damage to or destruction of
please inform Yokogawa. part or all of the product.
• Yokogawa assumes no responsibilities for this
product except as stated in the warranty.
• Please note that this user's manual may not be
revised for any specification changes, IMPORTANT
construction changes or operating part changes
that are not considered to affect function or An IMPORTANT sign denotes that attention is
performance. required to avoid damage to the instrument or
• If the customer or any third party is harmed by system failure.
the use of this product, Yokogawa assumes no
responsibility for any such harm owing to any
defects in the product which were not
predictable, or for any indirect damages. NOTE
1-1 IM 01R04B04-00E-E
5th edition Nov. 2005
1. INTRODUCTION
IM 01R04B04-00E-E 1-2
5th edition Nov. 2005
1. INTRODUCTION
1-3 IM 01R04B04-00E-E
5th edition Nov. 2005
1. INTRODUCTION
IM 01R04B04-00E-E 1-4
5th edition Nov. 2005
1. INTRODUCTION
GR PL
Ολα τα εγχειριδια λειτουργιαζ τωυ προιουτϖυ µε Wszystkie instrukcje obs³ugi dla urz¹dzeñ w
ΑΤΕX Εx διατιΘευται στα Αγγλικα, Γερµαυικα wykonaniu przeciwwybuchowym Ex, zgodnych z
και Γαλλικα. Σε περιπτωση που χρειαζεοτε wymaganiami ATEX, dostêpne s¹ w jêzyku
οδηγιεζ σχετικα µε Ex στηυ τοπικη γλωσσα angielskim, niemieckim i francuskim.
παρακαλουµε επικοιυωυηστε µε το πλησιεστερο Je¿eli wymagana jest instrukcja obs³ugi w
γραϕειο τηζ Yokogawa η αντιπροσωπο τηζ. Pañstwa lokalnym jêzyku, prosimy o kontakt z
najbli¿szym biurem Yokogawy.
SK SLO
Vsi predpisi in navodila za ATEX Ex sorodni
Všetky návody na obsluhu pre prístroje s ATEX pridelki so pri roki v anglišèini, nemšèini ter
Ex sú k dispozícii v jazyku anglickom, nemeckom francošèini. Èe so Ex sorodna navodila potrebna
a francúzskom. V prípade potreby návodu pre Ex- v vašem tukejnjem jeziku, kontaktirajte vaš najbliši
prístroje vo Vašom národnom jazyku, skontaktujte Yokogawa office ili predstaunika.
prosím miestnu kanceláriu firmy Yokogawa.
H
CZ
Az ATEX Ex mûszerek gépkönyveit angol, német
és francia nyelven adjuk ki. Amennyiben helyi
Všechny u•ivatelské pøíruèky pro výrobky, na nì• nyelven kérik az Ex eszközök leírásait, kérjük
se vztahuje nevýbušné schválení ATEX Ex, jsou keressék fel a legközelebbi Yokogawa irodát, vagy
dostupné v angliètinì, nìmèinì a francouzštinì. képviseletet.
Po•adujete-li pokyny týkající se výrobkù
s nevýbušným schválením ve vašem lokálním
jazyku, kontaktujte prosím vaši nejbli•ší
M
reprezentaèní kanceláø Yokogawa.
not yet available
LT
LV
Visas ATEX Ex kategorijas izstrâdâjumu
Lietoðanas instrukcijas tiek piegâdâtas angïu,
vâcu un franèu valodâs. Ja vçlaties saòemt Ex
ierîèu dokumentâciju citâ valodâ, Jums ir
jâsazinâs ar firmas Jokogava (Yokogawa) tuvâko
ofisu vai pârstâvi.
EST
Kõik ATEX Ex toodete kasutamisjuhendid on
esitatud inglise, saksa ja prantsuse keeles. Ex
seadmete muukeelse dokumentatsiooni
saamiseks pöörduge lähima Iokagava
(Yokogawa) kontori või esindaja poole.
1-5 IM 01R04B04-00E-E
5th edition Nov. 2005
1. INTRODUCTION
The warranty of the instruments shall cover the Name of Body Converter Cap with Electronics
Product housing window
period noted on the quotation presented to the
Al +
purchaser at the time of purchase. The Seller Rotamass SS R Al R D Sd
glass
shall repair the instrument free of charge when T1.EPS
IM 01R04B04-00E-E 1-6
5th edition Nov. 2005
1. INTRODUCTION
Receiver : Sender :
Type (MS-Code)
________________________________ € __________ €__________
(nominal value)
Charges for airworthy packing
and delivery FOB €___________
SPECIMEN Certificate
checked, that all cavities in the flowmeter are free from such substances
Company stamp:
1-7 IM 01R04B04-00E-E
5th edition Nov. 2005
1. INTRODUCTION
Receiver : Sender :
Type (MS-Code)
________________________________ € __________ €__________
(nominal value)
Charges for airworthy packing
and delivery FOB €___________
SPECIMEN Certificate
checked, that all cavities in the flowmeter are free from such substances
Company stamp:
IM 01R04B04-00E-E 1-8
5th edition Nov. 2005
2. TRANSPORTATION AND STORAGE
When transporting the instrument, you must observe the following safety instructions in order to avoid
lethal injury, damage to the instrument and other material damage.
The steps involved in transport may only be carried out by qualified persons taking into
account the safety instructions.
WARNING
ROTAMASS is a heavy instrument. Please be careful to prevent persons from injuring when it is handled.
Storage conditions
Before storing a used flowmeter remove any fluid from the flowmeter line completely.
Properties of the instrument can change when stored outdoors.
2-1 IM 01R04B04-00E-E
5th edition Nov. 2005
2. TRANSPORTATION AND STORAGE
IM 01R04B04-00E-E 2-2
5th edition Nov. 2005
3. Product description
3. Product description
3.1 The Coriolis principle
The ROTAMASS instrument measures the mass flow with the help of the so-called Coriolis force. This
force occurs, when the medium being measured is flowing at velocity ν through a tube that is rotating
around an axis perpendicular to the direction of flow at angular velocity ϖ .
When the medium moves away from the axis of rotation it must be accelerated to an increasingly high
peripheral velocity. The force required for this is called Coriolis force, after its discoverer. The Coriolis
force reduces the rotation. The opposite effect occurs, when the medium flows towards the axis of
rotation. Then the Coriolis force amplifies the rotation.
Fc = - 2 m (ϖ xν)
The entire measurement tube is deformed slightly by the Coriolis forces, in the way shown. This
deformation is registered by movement sensors at points S1 and S2 .
For practical exploitation of this physical principle, it is sufficient for the tube to perform sympathetic
oscillations on a small section of a circular path. This is achieved by exciting the measurement tube at
point E by means of an electromagnetic exciter.
3-1 IM 01R04B04-00E-E
5th edition Nov. 2005
3. Product description
Detector Assembly
F31.EPS
METER FACTORS
MASSFLOW METER
PS is the max. process pressure at room temp.
TS are the process temp. limits
-20 to +55˚C VDC 10W
4 - 20mA VAC~ 47-63Hz 10W
(20 - 600 Ω) 30VDC 200mA max.
PS is the max. process pressure at room temp.
TS are the process temp. limits see: N200
Instruction
Manual
number of certified body according PED, only for sizes greater than DN25
IM 01R04B04-00E-E 3-2
5th edition Nov. 2005
3. Product description
Display
F32.EPS
MASSFLOW CONVERTER
VDC 10W N200
-20 to +55˚C VAC ~ 47-63Hz 10W
4-20mA (20-600Ω)
30VDC 200mA max
30VDC 200mA max
3-3 IM 01R04B04-00E-E
5th edition Nov. 2005
3. Product description
Driving Coil
Fluid containing measuring tubes
Sensor Coils
Pt100
F33.EPS
MASSFLOW METER
METER FACTORS
PS is the max. process pressure at room temp.
TS are the process temp. limits N200
PS is the max. process pressure at room temp.
TS are the process temp. limits see:
Instruction
Manual
IM 01R04B04-00E-E 3-4
5th edition Nov. 2005
3. Product description
The following drawing shows the general construction of remote detector RCCS34 to 39.
Terminal Box
METER FACTORS
MASSFLOW METER
PS is the max. process pressure at room temp.
TS are the process temp. limits
see: N200
Instruction
Manual
number of certified body according PED, only for sizes greater than DN25
3-5 IM 01R04B04-00E-E
5th edition Nov. 2005
3. Product description
The values are displayed or outputed as electrical values for use by other systems.
The converter is operated with the help of three infra-red keys and a 4-line display and is equipped with
HART-communication protocol.
ROTAMASS is suitable for
ROTAMASS provides the following I/O-connections and can be configured for a wide variety of different
measurement applications (controlling, checking, monitoring, metering, mixing, filling).
2 analog outputs
2 passive pulse outputs / status outputs
1 status input
optional (/AP) :
1 active pulse output / status output
optional (/NM) :
1 pulse output / status output according EN50227 (NAMUR)
optional (/KF2) :
1 analog output (EEx ia)
1 passive pulse output (EEx ia) / status output
These capabilities make ROTAMASS ideal for the increasing demand of requirements for automation and
the growing trend towards batch processes.
IM 01R04B04-00E-E 3-6
5th edition Nov. 2005
4. INSTALLATION
4. Installation
WARNING
This instrument must be installed by an expert engineer or skilled personal. The procedures described in
this chapter are not permitted for operators.
For explosion protected instruments see chapter „Explosion Protected Type Instruments”.
4.1 Piping
1. The upstream and downstream piping length has no influence on the functioning of the instrument.
• A Coriolis mass flowmeter can be installed vertically, horizontally or at any angle from the horizontal
position.
• However, the piping must be installed to ensure that the measuring tube is always filled with liquid.
• The position of installation of the detector is arbitrary. A vertical mounting is recommended however.
Horizontal installation :
For liquids: Measuring tube downwards so that no
gas can collect if “no flow”.
Flow
Flow
F41.EPS
4-1 IM 01R04B04-00E-E
5th edition Nov. 2005
4. INSTALLATION
CAUTION
A stable zero is mandatory for a good mass flow measurement. Mechanical installation stress and flow
noise influence zero stability. Action has to be taken to avoid any generation of sound.
Recommendations:
• Support the weight of the detector by soft coupling (silicon or other kind of rubber support.
• Do not bend or stress the detector via the adjacent pipe. This is achieved by supporting the pipe 10D
or more away from the detector.
• Pipe reduction or extension should be avoided directly before or after the meter.
• Avoid any control valves or orifices or any other sound generator near the detector.
1. Do not stress the detector mechanically. Fix the pipe not on both ends of the detector but only at one
side. Let the other side run free for minimum mechanical stress on the detector.
2. Please use the standard reducers if the piping’s cross- section differs at the inlet or outlet point of the
flowmeter.
3. For RCCT3 or RCCF31 at ambient temperature above 50°C a sunshade is recommended. This is
particularly important in countries with high ambient temperatures.
4.
IMPORTANT
After installation an autozero according chapter 5.6 must be executed.
When carrying out the zero-adjustment, the measuring tube should be filled with the liquid at “no flow”.
It is therefore recommended to have shut-off valves at appropriate points of the upstream (vertical
installation) and downstream (horizontal installation) of the flowmeter.
5. A newly installed piping-line often contains foreign matters (such as welding scrap and wood chips).
Remove them by flushing the piping before installing the flowmeter. This will help to prevent not only
damaging the flowmeter, but making erroneous signal generated by foreign matters.
6. Keep protection sheet on the flanges attached until the flowmeter is installed to piping.
7. Don’t open the terminal box until the wiring procedure. Leaving the box opened can result in insulation
deterioration.
IMPORTANT
For the installation of EEx version, refer to chapter “Explosion Protected Type Instruments”.
IM 01R04B04-00E-E 4-2
5th edition Nov. 2005
4. INSTALLATION
The converter RCCF31 can be mounted on a 2-inch pipe. Therefore use the delivered bracket and U-bolt
assy.
The detector RCCS30 to 33 can be mounted on a 2-inch pipe (option /PD). with a bracket and U-bolt
assy.
F43.EPS
WARNING
Fix the lock screw for use in hazardous area.
4-3 IM 01R04B04-00E-E
5th edition Nov. 2005
4. INSTALLATION
4.4 Wiring
IMPORTANT
NOTE
Careful assembly of the cable is indispensable for correct connection between the detector and the
converter. This ensures good measuring results.
Termination procedure :
Cable end detector
• Remove PVC outer sheeting and full shielding 100mm from the end.
• Insulate the wire endings.
• Cut off one pair of wires and one additional wire and the core wire (black).
• Cut the layers of shielding and the filler flexes down to 15mm.
• Slide a shrink down plastic tube (∅ 3.2mm, l=20mm) over each of the five pairs of wires, push it
to its limits and heat with hot air.
• Attach the terminal sleeves (0.25mm2) to the wire endings.
• Make a radial cut into the PVC outer sheeting 25mm from the end and cut lengthways.
IM 01R04B04-00E-E 4-4
5th edition Nov. 2005
4. INSTALLATION
Slide the conductor markers onto the pairs of wires on both sides of the cable, so that the pairs are
numbered 1-2,3-4,5-6,7-8,9. Each cable must have the same number on detector and on converter side.
Inner shields
1
2
4
Cut
5
8
25 9
F44.EPS
Shrinkdown
plastic tube
1
2
4
Cut
5
8
25 9
F45.EPS
Shrinkdown
plastic tube
Cable Connection :
1. Remove connection box cover and unscrew the upper part of the cable gland.
2. Slide the upper part and the plastic clamp onto the cable end.
3. Remove the 25mm section of PVC outer sheathing from the cable and pull the shielding harness
over the plastic clamp of the cable gland (see left figure below).
4. Insert the prepared cable into the cable gland and tighten the cable gland.
5. Connect the numbered leads to the terminals as shown in the right figure below.
6. Connect inner shields to terminal COM.
Detector Converter
D+ 1 1 D+
D- 2 2 D-
S1+ 3 3 S1+
S1- 4 4 S1-
S2+ 5 5 S2+
S2- 6 6 S2-
TP1 7 7 TP1
F46.EPS
TP2 8 8 TP2
TP3 9 9 TP3
Shields COM
4-5 IM 01R04B04-00E-E
5th edition Nov. 2005
4. INSTALLATION
F48.EPS
CAUTION
1. Before starting the wiring, turn off the source of the supply power and check with the tester that there
is no voltage at the cable.
2. The protective ground conductor must be connected to the separate PE terminal in the terminal box
with Crimp-on ring-type terminal in order to avoid personal shock hazard.
3. An exclusive external circuit breaker must be placed near each flowmeter.
4. Check the external circuit breaker’s rating conforms to the requirements specified in the specification
of this instrument.
5. Wire the power supply cable keeping the distance of 1 cm or more from other signal wires.
6. Confirm the operating voltage of the converter before operation.
7. Please lock the cover of the converter with hexagon lock screw before operation.
IM 01R04B04-00E-E 4-6
5th edition Nov. 2005
4. INSTALLATION
CAUTION
Special connections for EEx version :
The converter case must be connected to the potential equalisation facility of the hazardous area , e.g. to
the U-clamp PA terminal on the outside at the converter. Please refer to chapter 9 “Explosion Protected
Type Instruments”.
24V DC connections
For the DC power supply type, connect a 24V DC power supply, following the precautions below.
+ -
20.5 to 28.8 V DC F49.EPS
4-7 IM 01R04B04-00E-E
5th edition Nov. 2005
4. INSTALLATION
I/O-Terminal Overview :
F416.EPS
Iout +
- Iout - -
Load resistance max. 600 Ω
F411.EPS
IM 01R04B04-00E-E 4-8
5th edition Nov. 2005
4. INSTALLATION
Protective diode
ROTAMASS
Pout +/Sout +
Pout - /
Sout-
30VDC, 200mA
ROTAMASS
Pout + /Sout +
Pout - /
Sout- F412.EPS
Protective diode
ROTAMASS
Pout + /Sout +
Load
Pout - /
Sout-
30VDC, 200mA
ROTAMASS
Pout + /Sout +
Magnetic
valve
Pout - /
Sout- F413.EPS
4-9 IM 01R04B04-00E-E
5th edition Nov. 2005
4. INSTALLATION
ROTAMASS
- Pout - F414.EPS
ROTAMASS
Pout +
Load
Pout -
Pout +
Magnetic
valve
Pout -
F421.EPS
IM 01R04B04-00E-E 4-10
5th edition Nov. 2005
4. INSTALLATION
Sin-
Voltage-free
contact input
F415.EPS
Control room
4 to 20mA DC Receiving
signal trans- instrument
Intermediate mission line
terminals Terminal board
RCCT_F3
Receiver resistance
230 Ω to 600 Ω
HART HART HART
Communicator Communicator Communicator F417.EPS
Current output : The intrinsic safe current output is passive and an external power supply with Shunt-
Diode type barrier or isolation type barrier should be connected.
4-11 IM 01R04B04-00E-E
5th edition Nov. 2005
4. INSTALLATION
Example of installation :
Hazardous area Safe area
RCCT3/KF2 Vin
Iout +
R barrier
Iout - V out
4-20mA R load
Ground
F418.EPS
Pulse output :
The intrinsic safe pulse output is passive and an external power supply with Shunt-Diode type barrier or
isolation type barrier should be connected.
Maximum voltage : 30V DC
Maximum current : 100mA
Example of installation :
RCCT3/KF2 Vin
Pout 1
R barrier
Pout 1 - V out
R load counter
Ground
F420.EPS
IM 01R04B04-00E-E 4-12
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
F52.EPS
5-1 IM 01R04B04-00E-E
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
MFR
+123.45 kg/h 3 line indication
+123.45
kg/h
F53.EPS
NOTE
The infrared switches operate as ON status by detecting the infrared ray reflection from a finger put over
the switches through the glass plate of the cover. Switches are just below the printed letters SET, SHIFT,
∇ on the faceplate.
The switches may operate even when you do not touch the glass plate, if your fingers come near the
glass plate, so please touch the switches sliding with your finger from the lower part of the glass plate.
Also be sure not to touch more than one switch at one time by covering your other fingers over the
faceplate, unless you would like to push “SHIFT+SET”.
You can increase the sensitivity of the infrared switches by sticking a white piece of tape on your finger tip.
Setting via the infrared buttons can be blocked via the HART protocol. If HART protocol is not used the
infrared buttons can be blocked by a black tape glued behind the window.
IM 01R04B04-00E-E 5-2
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
Number of figures :
totalizer ≤ 999999 : 1 sign + 6 figures (e.g. +123456)
totalizer > 999999 : Exponential view (e.g. +1.23E12)
measured value : 7 figures + 1 sign (e.g. +1234567) or
6 figures + 1 sign + 1 decimal point (e.g. +123.456)
unit : 10 figures
title : 3 figures
The contrast of the display can be adjusted with parameter
Detailed setup/ Display Config/Disp contrast .
The indication period of the display can be adjusted with parameter
Detailed setup/ Display Config/Disp period.
In measuring mode the actual measured values according the display select parameters are indicated as
shown in chapter 5.1. How to set display settings see chapter 5.4.
Parameter setting mode is described in chapter 5.3.
The language of the parameter setting mode can be selected in parameter
Language / or Detailed setup / Display config / language .
English, German or French can be selected.
5-3 IM 01R04B04-00E-E
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
Chapter 7.2 shows the display parameter list and chapter 7.3 shows the parameter tree.
Measuring mode
SET > 2s
*)
Entry mode SHIFT+SET
Indicate "Setting enable?"
SET
SET
SET
SET
IMPORTANT
The infrared keys can be locked via HART by Hot Key / Key Status .
IMPORTANT
Depending on parameter setting, only relating parameters are visible in the menu.
E.g., if Pulse/Stat 1 select is set to Pulse, the parameters concerning status out 1 (SO1) do not appear in
the menu. Such dependences are described later in the concerning chapters.
IM 01R04B04-00E-E 5-4
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
SET> 2s SET
3x
2x F55.EPS
Basic Setup
Display Config
Mass flow
Density
5-5 IM 01R04B04-00E-E
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
SET
SET > 2s
SET SET
3x SHIFT and
SET 2x SET
5x
F56.EPS
IM 01R04B04-00E-E 5-6
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
SET
SHIFTand 2x SET
Basic Setup
Temperature
Analog 1 select
Analog 2 select
2x
Basic Setup
Analog 2 select
Pulse/Status out 1
Pulse/Status out 2
SET
Analog 2 select
Density
Density
Temperature
5-7 IM 01R04B04-00E-E
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
In parameter Detailed Setup / Sensor model the sensor model must be selected. Then, the sensor model
depending parameters are set automatically to default value :
Qnom, Mass flow unit, Mass flow LRV, Mass flow URV, Vol flow unit, Vol flow LRV, Vol flow URV,
Autozero range, Autozero fluctuation range.
In parameter Detailed Setup / Sensor constants…. the sensor constants SK20, KD, fl20 must be set.
These constants are printed on the name plate of the detector.
If material of wetted parts is TI or HC see instruction attached to the converter.
In Parameter Basic setup / Tag or Basic setup / Long tag the tag number must be set if necessary.
CAUTION
Because the real Factory Zero Value and Autozero Fluctuation are not set, warnings W06 or W07 may
appear after autozero. These warnings can be ignored.
• Zero adjustment is required before beginning operation in order to obtain a 4 to 20mA signal that is
accurately proportional to the flow.
Zero adjustment is performed to set the instrument to 0% (4mA) when the flow rate is 0.
The detector must be filled with fluid and let it stand until all motion has ceased. If zero
adjustment is performed before all fluid motion has stopped, the flow rate at the time will become the
zero point, and a significant error may result.
The zero adjustment should be performed at the earliest 2 minutes after power on. Do not change fluid
within 2 minutes after power on.
• Reset totalizer, if necessary, as described in chapter 7.14.
• If an alarm or error occures, see chapter 8 for troubleshooting and caution in chapter 5.5.
IMPORTANT
- Stop flow before starting autozero.
- During autozero time
- Analog outputs are fixed to 4mA
- Pulse outputs are fixed to zero.
- Totalizer stops counting.
- Display switches do not work.
- In HART communication write- and exe-commands are not accepted.
- Status input does not work
IM 01R04B04-00E-E 5-8
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
2x 2x
Diag/Service Autozero
Autozero check Auto zero exe
Autozero Autozero value
Output trim
SET
F58.EPS
5-9 IM 01R04B04-00E-E
5th edition Nov. 2005
5. BASIC OPERATING PROCEDURES
Autozero Autozero
Diag/Service Autozero
Selftest/Status 05/05/2003
Input/Output test 10/06/2003
Autozero check 15/07/2004
2x F59.EPS
IM 01R04B04-00E-E 5-10
5th edition Nov. 2005
6. OPERATION VIA HART
Control room
4 to 20mA DC Receiving
signal trans- instrument
Intermediate mission line
terminals Terminal board
RCCT_F3
Receiver resistance
230 Ω to 600 Ω
HART HART HART
Communicator Communicator Communicator F61.EPS
Use the following formula to determine cable length for a specific application :
L = (65x106) / (RxC) - (Ci + 10,000) /C)
Where : L = length in feet or meters
R = resistance in ohms, current sense resistance
C = cable capacitance in pF/ft or pF/m
Ci = 50,000pF
6-1 IM 01R04B04-00E-E
5th edition Nov. 2005
6. OPERATION VIA HART
F63.EPS
The HART-communicator automatically searches for ROTAMASS RCCT_F3 on the 4-20mA loop, when it
is turned on. When HART- communicator is connected to RCCT_F3, it displays the online menu.
(If RCCT_F3 is not found, it displays “No device found. Press OK…”. Press OK ´F4´ function key and the
main menu appears. Please retry after confirming the connection with RCCT_F3).
If there is no device specific DD installed in the HHT275 (RCCT_F3, Dev v1, DD v1), the functionality of
the HART Menu as listed in chapter 7.4 is not total supported.
In this case the HHT275 works in the “Generic Mode”, which allows configuring the ROTAMASS with
limited functionality.
For upgrading your HHT275 please contact the YOKOGAWA service.
Online Menu Summary
No. Display item Contents
1 Device setup Set parameters for ROTAMASS
2 PV Display process value in engineering unit.
3 PV AO Display analog output in mA.
4 Review Review parameters for ROTAMASS
5 Service Not open
T61.EPS
IM 01R04B04-00E-E 6-2
5th edition Nov. 2005
6. OPERATION VIA HART
The menu tree in chapter 8.3 shows the configuration of the online menu, which is needed for the
operation with HART communicator. Select ´Device Setup´ to call up the desired item as follows:
IMPORTANT
Parameter setting on the display with the infrared keys is prohibited during HART communication.
IMPORTANT
Do not turn power off just after HART Communicator settings (sending) have been made. If ROTAMASS is
turned off less than 30 seconds after parameters have been set, the set data will not be stored and the
data returns to previous settings.
6-3 IM 01R04B04-00E-E
5th edition Nov. 2005
6. OPERATION VIA HART
While write protect status is released, enter a new password twice, within 30 sec in “New Password”.
It will not be possible to set a new password when 10 minutes have elapsed.
If a parameter, which is write enabled , is changed while the device is in “Enable wrt 10min”, release time
is extended for further 10 minutes.
NOTE
• When the write protect function is active (its menu bar shows “Yes”), data setting changes in all
parameters of RCCT_F3 are inhibited and cannot be changed using the HART communicator. Also the
setting via the infrared pushbuttons is prohibited.
• If 8 characters are input as “space”, the Write protect function is in release status irrespective of time.
• If both RCCT_F3 and HART Communicator power off and on again within 10 minutes after releasing of
write protect status, “Enable Write” becomes unavailable.
Software seal :
The “Software seal” menu is reserved as evidence so that user is able to confirm whether the Joker
password is used or not. This evidence is saved.
Hotkey → Software seal
The first indication in Software seal menu is ´keep´.
After the joker password setting it shows ´break´.
After setting a new password and release via “Enable wrt 10 min”, the Software seal shows “keep” again.
Key Status :
Enable: Infrared keys are activated. Inhibit: Infrared keys are deactivated.
Master Reset :
Default : all parameters set to default except board constants, calibration constants, detector depending
parameter and Concentration measuring settings in service menu.
CPU Board
JP1
Cable to display
Enable
Protect F64.EPS
IM 01R04B04-00E-E 6-4
5th edition Nov. 2005
Hot key Write Protect Enable wrt New Password Software seal Key Status Hardware Write Protect
(6.3)
HART
10min. HART
HART HART HART (6.4)
7.
Mass flow Mass flow unit Mass flow Mass flow LRV Mass flow URV Mass flow Mass flow Mass flow alm Mass flow alm Mass flow alm Mass flow alm MF fix val sel MF fixed value
(7.5) format damping lowcut 1 sel 1 crit 2 sel 2 crit
Volume flow Vol flow unit Vol flow format Vol flow LRV Vol flow URV Vol flow Vol flow lowcut Vol flow alm 1 Vol flow alm 1 Vol flow alm 2 Vol flow alm 2
(7.6) damping sel crit sel crit
Density Density unit Density format Density LRV Density URV Density Density lowcut Density alm 1 Density alm 1 Density alm 2 Density alm 2 Density fix val Density fixed Static pressure
(7.7) damping sel crit sel crit sel value control
Temperature
7.1 Overview
Temperature Temperature Temperature Temperature Temperature Temperature Temperature Temperature Temperature Temperature Temperature Temperature
(7.8) unit format LRV URV damping alm 1 sel alm 1 crit alm 2 sel alm 2 crit fix val select fixed value gain adjust
Analog Analog 1 select Analog 1 alarm Analog 1 low Analog 1 high Analog 1 rev
output 1 (7.9) out LMT LMT mode
chapters in this manual are indicated.
Analog Analog 2 select Analog 2 alarm Analog 2 low Analog 2 high Analog 2 rev
output 2 (7.10) out LMT LMT mode
Pulse/Status Pulse/Stat 1 Pulse 1 select Pulse 1 unit Pulse 1 rate Pulse 1 active Pulse 1 width Pulse1 at alarm SO1 function SO1 active
out 1 (7.11) select mode mode
Pulse/Status Pulse/Stat 2 Pulse 2 select Pulse 2 unit Pulse 2 rate Pulse 2 active Pulse 2 width Pulse2 at alarm SO2 function SO2 active
out 2 (7.12) select mode mode
7-1
Status input SI function SI active mode
(7.13)
Totalizer Total select Total unit Total switch Total at alarm Total reset cntrl Total reset
(7.14)
Parameter description
Diag/Service Self test/status Input/Output Autozero check Autozero Output trim History over- Error history
(8) (8.3) Test (8.4) (5.6) (7.22) (8.5) view (8.2) (8.2)
Special Flow direction Concentratiom Net flow Slug detection Empty pipe Corrosion Fluid max. Gas
functions (7.15) measurement (7.167 (7.18) detection (7.19) detection (7.20) Temp. measurement
(7.156 (7.23) (7.24)
Device data Distributor Tag Descriptor Message Date Dev id Universal rev Fld dev rev Software rev Hardware rev
HART data Poll address Num req Num resp Master reset
(6.3) preams preams
The table below shows an overview of functions of ROTAMASS RCCT3/RCCF31. In brackets the related
T71.EPS
7. PARAMETER DESCRIPTION
The ROTAMASS software is continuously improved. This leads to functionalities, which are different in
HART (DD version 0101) and display setting (software version from 1.04.00).
The following functions have only effect via display :
1. Multi total : Via “Display setting” totalizer indication is different to "HART setting".See chapter 7.14 + 5.1. *)
2. FPC (pressure correction coefficient) : The FPC corrects static pressure effects.*)
3. Pressure unit : In the item Density , the pressure unit can also be set in psi. *)
4. Volume flow unit bbl/d. *)
5. Pulse width 500ms and 1000ms. *)
6. Density unit g/cc. *)
7. SO1/2 function All alarms *)
The functions Analog 1/2 rev mode are deleted in the display menu. If the parameter Analog 1/2 rev
mode / measured value is selected in HART, invalid selection... is indicated.
*) HART shows "Unknown enumerator" if a parameter was selected via display which is unknown in HART.
IM 01R04B04-00E-E 7-2
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
7-3 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Volume flow
Density
Temperature
F-Total mass
R-Total mass
D-Total mass
F-Total volume
R-Total volume
D-Total volume
F-Total net
R-Total net
D-Total net
Concentration
meas
Net flow
Volume flow
Density
Temperature
F-Total mass
R-Total mass
D-Total mass
F-Total volume
R-Total volume
D-Total volume
F-Total net
R-Total net
D-Total net
Concentration
meas
Net flow
None
Disp select 3 Select Mass flow - - R/W X Temperature
Volume flow
Density
Temperature
F-Total mass
R-Total mass
D-Total mass
F-Total volume
R-Total volume
D-Total volume
F-Total net
R-Total net
D-Total net
Concentration
meas
Net flow
None
IM 01R04B04-00E-E 7-4
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Volume flow
Density
Temperature
F-Total mass
R-Total mass
D-Total mass
F-Total volume
R-Total volume
D-Total volume
F-Total net
R-Total net
D-Total net
Concentration
meas
Net flow
None
Disp Contrast Decimal -5 …+5 - - R/W 0
1.0 s
2.0 s
Reverse
Mass flow unit Select g/s - - R/W RCCS30 .. 33
g/min Kg/h
RCCS34 …39
g/h
t/h
kg/s
kg/min
kg/h
t/min
t/h
xxxxx.X
xxxx.XX
xxx.XXX
xx.XXXX
x.XXXXX
Mass flow LRV Decimal -Qmax to Qmax 0 to 5 Mass flow unit R/W 0
Mass flow URV Decimal 0 to Qmax 0 to 5 Mass flow unit R/W Qnom
Mass flow lowcut Decimal 0 to 10% of Qmax 0 to 5 Mass flow unit R/W 0
7-5 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Enable
Mass flow fixed val Decimal 0 to Qnom 0 to 5 Mass flow unit R/W X 0
xxxxx.X
xxxx.XX
xxx.XXX
xx.XXXX
x.XXXXX
Vol flow LRV Decimal -Qvmax to Qvmax 0 to 5 Vol flow unit R/W 0
Vol flow URV Decimal 0 to Qvmax 0 to 5 Vol flow unit R/W Qvnom
IM 01R04B04-00E-E 7-6
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
xxxxx.X
xxxx.XX
xxx.XXX
xx.XXXX
x.XXXXX
Density LRV Decimal 0 to 5 kg/l 0 to 5 Density Unit R/W X 0.0
Density URV Decimal 0 to 5 kg/l 0 to 5 Density Unit R/W X 1.5
Density damping Decimal 0.1 to 200 1 Sec R/W X 15.0
Density lowcut Decimal 0 to 110% of URV 0 to 5 Density Unit R/W X 0.0
Density alm 1 sel Select No Function - - R/W X No Function
More Than
Less Than
Density alm 1 crit Decimal 0 to 5 kg/l 0 to 5 Density Unit R/W X LRV
Density alm 2 sel Select No Function - - R/W X No Function
More Than
Less Than
Density alm 2 crit Decimal 0 to 5 kg/l 0 to 5 Density Unit R/W X URV
Density fix val sel Select Inhibit - - R/W X X Inhibit
Enable
Density fixed value Decimal 0 to 5 kg/l 0 to 5 Density Unit R/W X X 1.0
Pressure Decimal 0 to 400 2 bar R/W X X 0.0
Pressure Unit Select bar - - R/W X bar
psi
Temperature unit Select degC - - R/W X degC
degF
K
Temperature format Select Xxxxxxx - - R/W X xxxxx.X
xxxxx.X
xxxx.XX
xxx.XXX
xx.XXXX
x.XXXXX
Temperature LRV Decimal Standard : -200 to 0 to 5 Temperature unit R/W X 0.0
230 °C
High Temp. : 0 to
400 °C
Temperature URV Decimal Standard : -200 to 0 to 5 Temperature unit R/W X 150.0
230 °C
High Temp. : 0 to
400 °C
Temperature damping Decimal 0.1 to 200 1 Sec R/W X 15.0
Temp alm 1 sel Select No Function - - R/W X No Function
More Than
Less Than
7-7 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Temp alm 1 crit Decimal Standard : -200 to 0 to 5 Temperature unit R/W X LRV
200 °C
Temp alm 2 sel Select No Function - - R/W X No Function
More Than
Less Than
Temp alm 2 crit Decimal Standard : -200 to 0 to 5 Temperature unit R/W X URV
230 °C
High Temp. : 0 to
400 °C
Temp fix val select Select Inhibit - - R/W X X Inhibit
Enable
Temp fixed value Decimal Standard : -200 to 1 Temperature unit R/W X X 30.0
230 °C
High Temp. : 0 to
400 °C
Temp gain Decimal 0.8 … 1.2 3 - R/W 1.000
Analog 1 select Select None - - R/W X Mass flow
Mass flow
Volume flow
Density
Temperature
Concentration
meas
Netflow
Analog 1 alarm out Select <2.4mA - - R/W X <3.6mA
<3.6mA
4.0mA
>21mA
>21.6mA
Hold
Measured Value
Analog 1 low LMT Decimal Namur : 3.8 to 2 mA R/W X 3.8 (Namur) ;
20.5 mA 2.4 (not Namur)
Not Namur : 2.4 to
21.6 mA
Analog 1 high LMT Decimal Namur : 3.8 to 2 mA R/W X 20.5 (Namur) ;
20.5 mA 21.6 (not Namur)
IM 01R04B04-00E-E 7-8
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Analog 2 low LMT Decimal Namur : 3.8 to 2 mA R/W X 3.8 (Namur); 2.4
20.5 mA (Not Namur)
Not Namur : 2.4 to
21.6 mA
Analog 2 high LMT Decimal Namur : 3.8 to 2 mA R/W X 20.5 (Namur);
20.5 mA 21.6 (Not
Namur)
Not Namur : 2.4 to
21.6 mA
Pulse/Stat 1 select Select Pulse - - R/W X Pulse
Status out
No Function
Mass forward
Mass reverse
Volume forward
Volume reverse
Mass flow
Volume flow
Density
Temperature
Concentration
meas
Net forward
Net reverse
Net flow
Pulse 1 unit Select Hz - - R/W X kg/P
g/P
kg/P
t/P
lb/P
Cucm/P
l/P
Cum/P
gal/P
kgal/P
Cuft/P
bbl/P
Impgal/P
kImpgal/P
Pulse 1 rate Decimal 0 to 10000 0 Pulse 1 unit R/W X 1
Pulse 1 active mode Select On Active - - R/W X On active
Off Active
7-9 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Temp alm 1
Temp alm 2
Temp alm 1+2
Concentr. meas
alm 1
Concentr. meas
alm 2
Concentr. meas
alm 1+2
Net flow alm 1
Net flow alm 2
Net flow alm 1+2
Slug alarm
Empty alarm
Corrosion alarm
All alarms
SO 1 active mode Select On Active - - R/W X On active
Off Active
Pulse/Stat 2 select Select Pulse - - R/W X Status out
Status out
No Function
IM 01R04B04-00E-E 7-10
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
7-11 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Autozero
Total reset
0% Signal lock
SI active mode Select On Active - - R/W X On active
Off Active
Total select Select Mass - - R/W X Mass
Volume
Net
Total unit mass / net Select g - - R/W X kg
kg
t
lb
IM 01R04B04-00E-E 7-12
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
7-13 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
IM 01R04B04-00E-E 7-14
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Empty pipe alm sel Select Not Apply - - R/W X Not Apply
Apply
Empty pipe crit Decimal 0 to Density URV 0 to 5 Density unit R/W X 0
After empty pipe Select Massflow = Zero - - R/W X Massflow =
Zero
Measured Value
Hold
Corrosion alm sel Select Not Apply - - R/W X Not Apply
Apply
Corrosion criteria Decimal 0 to Density URV 0 to 5 Density unit R/W X 0
Corrosion damp Decimal 0.1 to 10 1 h R/W X 10
Fluid max temp Decimal - 1 Temperature unit R -
Distributor ASCII - - - R Yokogawa
Descriptor ASCII 16 characters - - R/W X Space
Message ASCII 32 characters - - R/W X Space
Date ASCII mm/dd/yy - - R/W X Space
Sensor model Select RCCS30 - - R/W RCCS36
RCCS31
RCCS32
RCCS33
RCCS34
RCCS36
RCCS38
RCCS39
RCCS39/IR
Sensor S/N Decimal 7 digits - - R Comm.no. (1)
Assembly number Decimal 7 digits - - R Comm.no. (2)
Universal rev Decimal 7 digits - - R fix
Fld. dev rev. Decimal - - - R fix
Software rev Decimal - - - R fix
Hardware rev Decimal - - - R fix
Device id Decimal 7 digits - - R 7xxxxxx
7-15 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Volume flow R
Density R
Temperature R
F-Total R
R-Total R
D-Total R
Concentration meas R
Net flow R
View Input R
Error History R
Autozero initial R
Autozero range R
Autozero fluctuation R
IM 01R04B04-00E-E 7-16
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Autozero value R
Tag R/W
Basic Setup
D-Total volume
F-Total net
R-Total net
D-Total net
Concentration meas
Net flow
None
Density
Temperature
F-Total mass
R-Total mass
D -Total mass
F-Total volume
R-Total volume
D-Total volume
F-Total net
R-Total net
D-Total net
Concentration meas
Net flow
None
7-17 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Concentration meas
Net flow
Net flow
IM 01R04B04-00E-E 7-18
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
g/P
Kg/P
t/P
lb/P
Cucm/P
l/P
Cum/P
gal/P
kgal/P
Cuft/P
bbl/P
Impgal/P
kImpgal/P
7-19 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Volume
Net
Volume flow
Density
Temperature
F-Total mass
R-Total mass
D-Total mass
F-Total volume
R-Total volume
D-Total volume
F-Total net
R-Total net
D-Total net
Concentration meas
Net flow
IM 01R04B04-00E-E 7-20
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Volume flow
Density
Temperature
F-Total mass
R-Total mass
D-Total mass
F-Total volume
R-Total volume
D-Total volume
F-Total net
R-Total net
D-Total net
Concentration meas
Net flow
None
2.0 s
SKT R/W
RV R/W
Qnom R
SKP R/W
Density KD R/W
fl20 R/W
FTC1 R/W
FTCK R/W
FPC R/W
Detailed Setup
7-21 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Mass flow m
al 2 crit R/W
Cum/min
Cum/h
gal/s
gal/min
gal/h
Cuft/s
Cuft/min
Cuft/h
bbl/s
bbl/min
bbl/h
Impgal/s
Impgal/min
Impgal/h
bbl/d
x.XXXXX
Less than
Vol flow alm 2 crit R/W
IM 01R04B04-00E-E 7-22
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Pressure R/W
Pressure Unit bar Sel
psi
Temperature Temperature unit degC Sel
degF
K
7-23 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Detailed Setup
Analog 1 low LMT R/W
Hold
Measured value
Cucm/P
l/P
Cum/P
gal/P
kgal/P
Cuft/P
bbl/P
Impgal/P
kImpgal/P
0.5ms
1ms
5ms
10ms
50ms
100ms
500ms
1000ms
IM 01R04B04-00E-E 7-24
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Net flow
Off Active
7-25 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
t
lb
Sel
Total select Mass
Volume
Net
IM 01R04B04-00E-E 7-26
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Measuring Range R
Drive gain R
Empty pipe detect Empty pipe alm sel Not apply Sel
Apply
7-27 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Descriptor R/W
Message R/W
Date R/W
Sensor model R
Sensor S/N R
Assembly number R
Distributor R
Review device info
Sensor model R
Sensor S/N R
Assembly number R
Tag R
Long Tag R
Descriptor R
Message R
Date R
Device id R
Review device info
Universal rev R
Software rev R
Hardware rev R
SK20 R
Review sensor
SKT R
RV R
Qnom R
SKP R
KD R
fl20 R
FTC1 R
FTCK R
FPC R
Autozero value R
IM 01R04B04-00E-E 7-28
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Flow direction R
Review FldDev vars 1
Mass flow unit R
MF fixed value R
Density unit R
Review FldDev vars 1
Density LRV R
Density URV R
Density damping R
Density lowcut R
Pressure R
Pressure unit R
Review FldDev vars 1
Temperature unit R
Temperature LRV R
Temperature URV R
Temperature damping R
7-29 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Analog 1 select R
Review Outputs/ Input
Analog 2 select R
Pulse/Status 1 select R
Pulse 1 select R
Pulse 1 unit R
Review Outputs/ Input
Pulse 1 rate R
Pulse 1 width R
Pulse 1 at alarm R
SO 1 function R
Pulse/Status 2 select R
Pulse 2 select R
Pulse 2 unit R
Pulse 2 rate R
Review Outputs/ Input
Pulse 2 width R
Pulse 2 at alarm R
SO 2 function R
SI function R
SI active mode R
Total select R
IM 01R04B04-00E-E 7-30
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Analog output 2 SV R
SV AO R
% rnge R
SO 2 function R
7-31 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
AZ range R
AZ fluctuation R
Enable
Autozero value R
Tag R/W
Basic Setup
Temp
F-Total
R-Total
D-Total
Conc meas
Net flo
None
Net flo
None
IM 01R04B04-00E-E 7-32
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Dens
Temp
Conc meas
Net flo
7-33 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
TV unit Hz Sel
g/P
kg/P
t/P
Basic Setup
lb/P
Cucm/P
l/P
Cum/P
gal/P
kgal/P
Cuft/P
bbl/P
Impgal/P
kImpgal/P
TV rate R/W
Bi-directional
Total Switch
Mass flo alm 1
Mass flo alm 2
Mass flo alm 1+2
Vol flo alm 1
Vol flo alm 2
Vol flo alm 1+2
Dens alm 1
Dens alm 2
Dens alm 1+2
Temp alm 1
Temp alm 2
Basic Setup
TV unit Hz Sel
g/P
kg/P
t/P
lb/P
Cucm/P
l/P
Cum/P
gal/P
kgal/P
Cuft/P
bbl/P
Impgal/P
kImpgal/P
TV rate R/W
IM 01R04B04-00E-E 7-34
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Volume flo
Dens
Temp
F-Total
R-Total
D-Total
Conc meas
Net flo
R-Total
D-Total
Conc meas
Netflo
None
7-35 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
RCCS36
RCCS38
RCCS39
RCCS39/IR
SKT R/W
RV R/W
Qnom R/W
SKP R/W
Dens KD R/W
Fl20 R/W
Detailed Setup
FTC1 R/W
FTCK R/W
lb/h
IM 01R04B04-00E-E 7-36
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
I/min
l/h
Cum/s
Cum/min
Cum/h
gal/s
gal/min
gal/h
Cuft/s
Cuft/min
Cuft/h
bbl/s
bbl/min
bbl/h
Impgal/s
Impgal/min
Detailed Setup
Impgal/h
lb/gal
lb/Cuft
7-37 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Pressure R
xx.XXXX
x.XXXXX
IM 01R04B04-00E-E 7-38
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Mass flo
Vol flo
Dens
Temp
Conc meas
Net flow
Cum/P
gal/P
kgal/P
Cuft/P
bbl/P
Impgal/P
kImpgal/P
0.5ms
1ms
5ms
10ms
50ms
100ms
7-39 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Status out
No function
Hz
g/P
kg/P
t/P
lb/P
Cucm/P
l/P
Cum/P
gal/P
kgal/P
Cuft/P
bbl/P
Impgal/P
kImpgal/P
IM 01R04B04-00E-E 7-40
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Conc alm 1
Conc alm 2
Conc alm 1+2
Net flo alm 1
Net flo alm 2
Net flo alm 1+2
Slug alarm
Empty alarm
Corrosion alarm
7-41 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
xxx.XXX
xx.XXXX
x.XXXXX
Measuring Range R
IM 01R04B04-00E-E 7-42
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Empty pipe detect Empty pipe alm sel Not apply Sel
Detailed Setup
Apply
Descriptor R/W
Message R/W
Date R/W
Sensor model R
Sensor S/N R
Review Distributor R
Review device info
Sensor model R
Sensor S/N R
Tag R
Long Tag R
Descriptor R
Message R
Date R
Review device info
Device id R
Universal rev R
Software rev R
Hardware rev R
7-43 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
SK20 R
Review R
SKT
RV R
Qnom R
SKP R
KD R
Fl20 R
FTC1 R
FTCK R
FPC R
Autozero value R
Flow direction R
Rev FldDev vars 1
Dens unit R
Dens LRV R
Dens URV R
Dens damp R
Dens lowcut R
Pressure R
IM 01R04B04-00E-E 7-44
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Temp LRV R
Temp URV R
Temp damp R
Flow direction R
7-45 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Analog 1 select R
Rev Outputs/ Input
PV Alarm 1 select R
PV Analog 1 reverse R
mode
Analog 2 select R
SV Alarm 2 select R
SV Analog 2 reverse R
mode
Pulse/Stat 1 sel R
Pulse 1 select R
Pls Unit R
Pls Rate R
Pls Mode R
Pls Width R
Rev Outputs/ Input
Pls Alarm R
SO 1 function R
SO 1 active mode R
Pulse/Stat 2 sel R
Pulse 2 select R
Pls Unit R
Pls Rate R
Pls Mode R
Pls Width R
Pls Alarm R
SO 2 function R
SO 2 active mode R
Input function R
SI active mode R
Totalizer sel R
F-Total Unit R
F-Total switch R
Total at alarm R
Poll addr R
HART
Review
IM 01R04B04-00E-E 7-46
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Mass flow LRV (low range value) Set a mass flow value to the 4mA or 0 Hz.
LRV can also be negative to measure reverse
flow. In this case set the lowcut to Zero.
Mass flow URV (upper range value) Set a mass flow value to the 20mA
or xxxxx Hz.
URV - LRV ≥ 5% of Qnom
Mass flow lowcut Set the low cut. Low cut effects output
and display. A hysteresis of 0.05% of Qnom
is given by the system.
Mass flow alm 1 sel Select : no function, more than, less than
Mass flow alm 1 crit Select a mass flow alarm level. What happens
in case of an alarm has to be defined in
Status out (7.11, 7.12).
Mass flow alm 2 sel Select : no function, more than, less than
Mass flow alm 2 crit Select a mass flow alarm level. What happens
in case of an alarm has to be
Restrictions: defined in Status out (7.11, 7.12).
All alarms have to be in 0 - 110% of URV-LRV
Alarm criteria 2 must always be larger than
alarm criteria 1.
Mass flow fixed value Select a fix Mass flow value (only for test
purpose or in case of maintenance).
The set value is added to the actual value.
In case of no flow it will vary with the zero
fluctuation.
T72.EPS
7-47 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Vol flow LRV (low range value) Set a volume flow value to the 4mA or 0 Hz.
LRV can also be negative to measure reverse
flow. In this case set the lowcut to Zero.
Vol flow URV (upper range value) Set a volume flow value to the 20mA or xxxxx Hz.
URV - LRV ≥ 5% of Qnom
Vol flow damping Set the damping time in s. Damping time effects
outputs and display. After 5 times damping time
the given value is displayed (t=63%).
Vol flow lowcut Set the low cut. Low cut effects output and
display. A hysteresis of 0.05% of Qnom
(mass flow) is given by the system.
Vol flow alm 1 sel Select: no function, more than, less than
Vol flow alm 1 crit Select a volume flow alarm level. What
happe
ns in case of an alarm has to be
defined in Status out (7.11, 7.12).
Vol flow alm 2 sel Select: no function, more than, less than
Vol flow alm 2 crit Select a volume flow alarm level. What happens
Restrictions: in case of an alarm has to be defined in Status
out (7.11, 7.12).
All alarms have to be in 0 - 110% of URV-LRV
Alarm criteria 2 must always be larger than alarm
criteria 1.
T73.EPS
IM 01R04B04-00E-E 7-48
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Density LRV (low range value) Set a density value to the 4mA or 0 Hz.
Density URV (upper range value) Set a density value to the 20mA or xxxxx Hz.
URV - LRV ≥ 0.05% kg/l
Density lowcut Set the low cut. Low cut effects output and
and display.
7-49 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
T74a.EPS
IM 01R04B04-00E-E 7-50
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Temperature URV (upper range value) Set a temperature value to the 20mA or xxxxx Hz.
URV - LRV ≥ 10 K
7-51 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
70
Output current [%]
60 13.6
50 12
40 10.4
30 8.8
20 7.2
10 5.6
possible Low cut
0 4 Low-LMT 3.8 mA
-110
-10
-90 -70 -50 -30 -10 0 10 30 50 70 90 1102.4
Reverse ← Flow [%] → Forward T76a.EPS
IM 01R04B04-00E-E 7-52
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
7-53 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Pulse 1 rate The Pulse rate can be set according to the unit
set in Pulse 1 unit.
T78.EPS
IM 01R04B04-00E-E 7-54
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
7-55 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
How to set status, pulse or frequency output Differences between Pulse and Frequency output
(using the display keys, equivalent via HART) For pulse output the mass (or volume) is internally
Status totalized and if the increment is reached, one
Basic Setup or Detailed Setup pulse is send.
Pulse/Status out 1
Pulse/Stat 1 select For a frequency output the measured value is
Select : Status out calculated in actual frequency according to the
definition of the user (e.g. 10000Hz = 54321kg/h)
Pulse or Frequency with 50% duty cycle. This calculation is not always
Basic Setup or Detailed Setup 100% correct, therefore the frequency output is
Pulse/Status out 1 less accurate than the pulse output.
Pulse/Stat 1 select
Select : Pulse Set as frequency output the pulse length is
Pulse 1 select changing with the change of the measured value.
Mass Forward → Pulse
Mass Reverse → Pulse Set as a pulse output the pulse length is constant
Volume Forward → Pulse but the time between the pulses varies. Even at
Volume Reverse → Pulse constant flow the time between the pulses might
Mass Flow → Frequency vary because the microprocessor has to find a
Volume Flow → Frequency suitable gap in its timing to send the pulse.
Density → Frequency
Temperature → Frequency Typical pattern for frequency output :
IM 01R04B04-00E-E 7-56
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Setting the pulse output For a first orientation the max.Q for certain pulse
Because the duty cycle of pulses is max. 50%, the widths and units for a pulse rate of 0.1 , 1 and 10
max. flowrate is restricted by the pulse width, the are given in the table below.
unit and the pulse rate :
Max. flow rate = Max. flow restriction :
1s/(pulse width*2) *pulse rate *time factor
Example : this amount will
be lost
Max. Q should be calculated in kg/min flow
Pulse width = 50ms/P Max flow from pulse width, unit, rate
Grey zone
Pulse rate = 0.1kg/P
Time factor (related to s) = 60/min
Max. Q =
1/ (0.05s/P *2) *0.1kg/P * 60/min = 60kg/min
7-57 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
The following tables show the physical output levels of the pulse / status outputs depending on the setting
of parameter Pulse x active mode or SOx active mode.
On Active
Output Situation Output Transistor Level Pout+ Level Pout+
Passive Active (/AP)
Pulse /Status Out 1 No Alarm / No Pulse open (OFF) High (Us) *) High (15 VDC)
Alarm / Pulse closed (ON) Low (1 VDC) Low (1 VDC)
Level Sout+
Pulse /Status Out 2 No Alarm / No Pulse open (OFF) High (Us) *)
Alarm / Pulse closed (ON) Low (1 VDC)
Off Active
Output Situation Output Transistor Level on Pout+ Level on Pout+
Passive Active (/AP)
Pulse /Status Out 1 No Alarm / No Pulse closed (ON) Low (1 VDC) Low (1 VDC)
Alarm / Pulse open (OFF) High (Us) *) High (15 VDC)
Level on Sout+
Pulse /Status Out 2 No Alarm / No Pulse closed (ON) Low (1 VDC)
Alarm / Pulse open (OFF) High (Us) *)
*) Us is the external power supply voltage of the pulse / status output T93.EPS
IM 01R04B04-00E-E 7-58
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Pulse 2 rate The Pulse rate can be set according to the unit
set in Pulse 2 unit.
Maximum pulse rate for rectangular pulses is
2000Hz. The output can be set to 10000Hz, if
deformed pulses can be clearly identified by the
follow up system.
T80.EPS
7-59 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Detailed information about using the pulse and status output see chapter 7.11.
IM 01R04B04-00E-E 7-60
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
T82.EPS
7-61 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
T83.EPS
IM 01R04B04-00E-E 7-62
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
7-63 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Concentration meas LRV (low range Set a concentration value to the 4mA or 0 Hz.
value)
Concentration meas lowcut Set the low cut. Low cut effects output
and display. A hysteresis of 0.05% of Qnom is
given by the system.
Concentration meas alm 1 sel Select : no function, more than, less than
Concentration meas alm 2 sel Select : no function, more than, less than
IM 01R04B04-00E-E 7-64
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Net flow LRV (low range value) Set a net flow value to the 4mA or 0 Hz..
Net flow URV (upper range value) Set a net flow value to the 20mA or xxxxx = Hz.
URV - LRV ≥ 5% of Qnom
Net flow lowcut Set the low cut. Low cut effects output
and display. A hysteresis of 0.05% of Qnom is
given by the system.
Net flow alm 1 sel Select : no function, more than, less than
Net flow alm 1 crit Select a net flow alarm level. What happens in
case of an alarm has to be defined in
Status out (7.11, 7.12).
Net flow alm 2 sel Select : no function, more than, less than
Net flow alm 2 crit Select a net flow alarm level. What happens in
case of an alarm has to be defined in
Restrictions: Status out (7.11, 7.12).
All alarms have to be in 0 - 110% of URV-LRV
Alarm criteria 2 must always be
larger than alarm criteria 1.
T86.EPS
7-65 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Not available if gas measurement is ordered. After slug criteria is reached, slug is
supervised during slug duration. If slug is still
detected after slug duration, the selected item in
After slug is executed.
See below table.
Drive gain damping Set drive gain damping time to get a constant
drive gain level.
T87.EPS
IM 01R04B04-00E-E 7-66
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Gas selected ?
Yes No
Alarm select = Apply ?
Yes No
Drive gain > Criteria value ?
Yes No
Duration active ?
Slug Detect OFF after
Yes duration,
Function Slug detect Slug detect OFF
active ON
Alarm off Alarm ON Alarm Off
measurement measurement
continue continue
or value hold
Influence of slug on mass flow, density and drive gain :
mass flow, if
Hold
duration time mass flow, if
mass flow Measured value
density
drive gain
time
slug flow
single
bubble
T88.EPS
7-67 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Not available if gas measurement After Empty pipe crit is reached, alarm output
(option /GA) is ordered. is activated if selected.
Gas selected ?
Yes No
Alarm select = Apply ?
Yes No
Density < Criteria value ?
Yes No
IM 01R04B04-00E-E 7-68
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
T90.EPS
WARNING
The function Sensor model is only for changing a converter in case of maintenance. Never change the
sensor model if the sensor is not changed.
The sensor constants for the selected detector are stored in parameters Detailed Setup / Sensor constants.
You find the main sensor constants on the name plate. In case of doubt of the measured value please
confirm that the proper sensor constants are stored.
The first part of the comission number is stored in Detailed setup / Device information / Sensor S/N.
The second part of the comission number is stored in Detailed setup / Device information / Assembly
number.
The tag number, if provided by the customer (option /BG), is stored in Basic setup / Tag.
For integral type RCCT3x and remote type RCCF31 combined ordered with RCCS3x the detector data are
factory stored in the concerning parameters. For not combined remote type RCCF31 with option /NC see
chapter 5.5.
If the parameter Detailed setup / Sensor model is changed to annother type, the following parameters are
changed to new default values corrersponding to the selected model :
Qnom, Mass flow unit, Mass flow LRV, Mass flow URV, Vol flow unit, Vol flow LRV, Vol flow URV, Autozero
range, Autozero fluctuation range and the sensor constants.
In this case the sensor constants, the detector serial number and, if available, the tag number must be set
to the values corresponding to the used detector as described above.
7-69 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
Autozero check: Autozero history Indicates 5 latest autozero values with date of
execution, temperature and density during
execution.
This function allows checking the quality
of autozero condition and long terming zero
drift, if happen.
IM 01R04B04-00E-E 7-70
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
IMPORTANT
- Stop flow before starting autozero.
- During autozero time
- Analog output are fixed to 4mA
- Pulse outputs are fixed to zero
- Totalizer stops counting
- Display keys to not work
- In HART communication write- and exe- commands are not accepted
- Status input does not work
Additional information and how to start autozero and how to read autozero history is described in chapter
5.6 " Zero adjustment".
The instrument is mass balanced with air at normal pressure. It can be used for liquids with reduced
accuracy.
The URV-LRV range for mass flow, volume flow and net flow is 1% of Qnom.
7-71 IM 01R04B04-00E-E
5th edition Nov. 2005
7. PARAMETER DESCRIPTION
IM 01R04B04-00E-E 7-72
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
nc nc nc nc nc *)
A-09 Conc 1 criteria Conc meas alm 1
nc nc nc nc nc *)
A-10 Conc 2 criteria Conc meas alm 2
hold; continue
A-13 Total thr exceed nc nc 1) nc nc Total switch*)
MFL: meas.;
A-14 Slug Detection nc nc nc nc Slug alarm*)
hold 4)
MFL: meas.;
A-15 Empty pipe det. nc nc nc nc Empty pipe alm*)
hold; 0 2)
8-1 IM 01R04B04-00E-E
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
Warning (W) Flow Density, Temp. Totalizer Analog Frequ./Pulse Status outputs *)
Name on display on display on display outputs outputs
Error (E)
nc = no change nd = not defined
Density = 0
E-01 Frequency Fault nd nc 3,6 mA;…3) nc nc
Temp = nc
E-02 Signal Fault nd nc nc 3,6 mA;…3) nc nc
1)
Choice of “Total at alarm” (Detailed Setup / Totalizer)
2)
Choice of “Output after Empty pipe” (Detailed Setup / Empty pipe detect)
3)
Choice of “Analog 1/2 alarm out” (Detailed Setup / Config Output) and NAMUR / NOT NAMUR
(Measuring range)
4)
Choice of “After Slug” (Detailed Setup / Slug detection)
5)
Only if “Liquid” is selected (Detailed Setup / Liquid/gas selection)
*) Status outputs acc. SO 1/2 function and SO 1/2 active mode
The following table shows possible countermeasures :
Alarm (A);
Warning (W); Name Description Countermeasure
Error (E)
A-01 Mass flow L Alarm Mass flow below Mass flow LRV Increase mass flow / Change setting
A-02 Mass flow H Alarm Mass flow above Mass flow URV Reduce mass flow / Change setting
A-03 Vol flow L Alarm Volume flow below Vol flow LRV Increase volume flow / Change setting
A-04 Vol flow H Alarm Volume flow above Vol flow URV Reduce volume flow / Change setting
A-05 Density L Alarm Density below Density LRV Increase density / Change setting
A-06 Density H Alarm Density above Density URV Reduce density / Change setting
A-07 Temperature L Alarm Temp. below Temp LRV Increase temperature / Change setting
A-08 Temperature H Alarm Temp. above Temp URV Reduce temperature / Change setting
A-09 Concentration L Alarm Concentration below Conc LRV Increase concentration / Change setting
A-10 Concentration H Alarm Concentration above Conc URV Reduce concentration / Change setting
A-11 Net Flow L Alarm Net flow below Net flow LRV Increase net flow / Change setting
A-12 Net Flow H Alarm Net flow above Net flow URV Reduce net flow / Change setting
T83.EPS
IM 01R04B04-00E-E 8-2
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
A-15 Empty Pipe Detection Empty pipe criterion is reached Fill pipe
W-01 Density lower 0.3kg/l Density lower than 0.3 kg/l Fill the detector with fluid
W-02 Fixed Dens selected Parameter Dens fix val sel is enable Set Parameter Dens fix val sel to inhibit
Parameter Temp fix val sel is
W-03 Fixed Temp selected Set Parameter Temp fix val sel to inhibit
enable
W-04 Fixed Mass flow selected Parameter MF fix val sel is enable Set Parameter MF fix val sel to inhibit
E-02 Signal Fault Phase difference out of range Check cable (Remote) and detector
E-06 Sensor 1 Signal Fault Sensor 1 signal below 7% for 3 min. Check cable (Remote) and detector
E-07 Sensor 2 Signal Fault Sensor 2 signal below 7% for 3 min. Check cable (Remote) and detector
Check cable (Remote) and detector
E-08 Temperature Sensor fault T<-210°C or T>450°C
Check temperature
T84.EPS
8-3 IM 01R04B04-00E-E
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
T85.EPS
IM 01R04B04-00E-E 8-4
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
AO 1 trim 4mA / AO 1 trim 20mA The analog output 1 is set to the internal 4mA or
20mA value. Connect a load resistor between 20
and 600 Ω and measure the current.
This current value must be entered on request on
display. The deviation to 4mA is corrected by the
AO 2 trim (same as AO 1 trim) converter itself.
T88.EPS
8-5 IM 01R04B04-00E-E
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
The equipment can be CIP-cleaned. Steam below 230°C is not a problem. However, you should take
care that the cleaning operation does not last so long that the converter temperature exceed 55°C.
Switch power off during cleaning.
8.7 Troubleshooting
IMPORTANT
If the indicated countermeasures do not remedy the fault or in case of troubles which can not be
remedied by the user, please contact your Yokogawa service centre.
If there is an error, alarm or warning displayed, deal with the error according to 8.1 „Error descriptions and
countermeasure”.
In the following some problems are listed which may not be indicated as error, alarm or warning. First
make sure, that no error, alarm or warning is displayed.
8.7.1 No indication
yes
yes
Is display cable connected no Connect the cable in the
correct to CPU board ? correct position.
yes
yes
Contact the nearest
YOKOGAWA office or
service center.
F81.EPS
IM 01R04B04-00E-E 8-6
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
yes
yes
yes
yes
8-7 IM 01R04B04-00E-E
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
yes
no
yes
no
Loose the process
connections and make
Is the detector installed no sure that they are in line.
free of mechanical stress? Support only one
adjacent pipe, let one
side of the adjacent pipe
be “soft”.
yes
yes
IM 01R04B04-00E-E 8-8
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
yes
yes
yes
no
yes
yes
8-9 IM 01R04B04-00E-E
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
yes
no
yes
yes
yes
no
no
IM 01R04B04-00E-E 8-10
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
yes
yes
yes
yes
PT 100 fault.
Resistance values are as no Simulate the correct
stored ? temp. by a fixed temp,
value or connect an
external PT100.
yes
yes
F87.EPS
8-11 IM 01R04B04-00E-E
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
no
Measured temperature Converter fault.
values OK ? Contact the nearest
YOKOGAWA office or
service center.
yes
yes
yes
Check measurand.
F89.EPS
IM 01R04B04-00E-E 8-12
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
Low : I ≤ 3.6mA
High : I ≥ 21.6mA
CPU Board
JP2 (Burn out)
Cable to display
F810.EPS
8-13 IM 01R04B04-00E-E
5th edition Nov. 2005
8. SELF-DIAGNOSTIC AND TROUBLESHOOTING
IM 01R04B04-00E-E 8-14
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
II 2GD T150°C
9.1.1 Technical Data
Remote detector RCCS30 ... 39/IR (option /KS1): Integral type RCCT34 .. 39 (option /KF2) :
- KEMA 01ATEX 1075 X - KEMA 02ATEX 2183 X
- Intrinsically safe - Flame proof with intrinsic safe connection to
- EEx ib IIC T1 ... T6 detector (ib) and intrinsic safe outputs
- Group II, Category 2 GD (1x current and 1x pulse) (ia).
- Max. surface temperature for dust application: 150°C - EEx d(e) [ia] [ib] IIC T6 ... T3
- Marking : - Group II, Category 2 GD
- Max. surface temp. for dust application: 150°C
Standard : II 2GD T150°C - Marking :
II 2GD T150°C
/MT : II 2GD T220°C
The electronics are placed in a pressure tight
section of the converter housing EEx d.
/HT : II 2GD T350°C
The protection class of the terminal enclosure is “e”,
but can become “d” with EEx-d certified cable glands.
Remote converter RCCF31 (option /KF1) : Degree of protection : IP67
- KEMA 02ATEX 2183 X
Power supply : 90 to 250V AC, 50/60 Hz
- Flame proof with intrinsic safe connection to
detector (ib) 20.5 to 28.8V DC
- EEx d(e) [ib] IIC T6 Power consumption : max. 25VA / 10W
- Group II, Category 2 GD Ambient humidity : 0 to 95% RH
- Max. surface temperature for dust application : 70°C
Ambient temperature range
- Marking :
RCCF31 / RCCT3: −20°C to +50°C
II 2GD T70°C RCCS3 : −50°C to +80°C
RCCS3 /HT : −50°C to +75°C
9-1 IM 01R04B04-00E-E
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
Coherence between temperature class, ambient- and medium temperature/ temperature of heat carrier :
RCCS30 to RCCS33 RCCS34 to RCCS39/IR RCCS34 to RCCS39/IR RCCT34 to RCCT39/IR
without insulation with factory insulation /T1.../T3
Max. Max.
Temp. Max. Max. Max. medium Max. Max. Max.
medium
class ambient medium ambient temperature / ambient ambient medium
temperature /
temperature temperature temperature temperature of temperature temperature of temperature temperature
heat carrier heat carrier
T6 ≤ 50°C / 122°F ≤ 60°C / 140°F ≤ 40°C / 104°F ≤ 40°C / 104°F ≤ 65°C / 149°F ≤ 65°C / 149°F ≤ 50°C / 122°F ≤ 65°C / 149°F
T5 ≤ 50°C / 122°F ≤ 80°C / 176°F ≤ 55°C / 131°F ≤ 55°C / 131°F ≤ 75°C / 167°F ≤ 75°C / 167°F ≤ 50°C / 122°F ≤ 80°C / 176°F
≤ 80°C / 176°F ≤ 100°C / 212°F ≤ 80°C / 176°F ≤ 100°C / 212°F ≤ 70°C / 158°F ≤ 115°C / 239°F ≤ 50°C / 122°F ≤ 115°C / 239°F
T4
≤ 50°C / 122°F ≤ 120°C / 248°F ≤ 40°C / 104°F ≤ 120°C / 248°F
T3 ≤ 80°C / 176°F ≤ 150°C / 302°F ≤ 80°C / 176°F ≤ 160°C / 320°F ≤ 70°C / 158°F ≤ 180°C / 356°F ≤ 50°C / 122°F ≤ 150°C / 302°F
NOTE
For customer insulation of RCCS34 to 39/IR the following must be regarded :
The table "with factory insulation" is calculated with 80mm insulation and k-factor = 0.4 W/m2K.
If your insulation data are worse than these use table "without insulation" !
IM 01R04B04-00E-E 9-2
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
9.1.2 Installation
Integral type RCCT3
WARNING
1. EEx type of ROTAMASS must be connected to the suitable IS earthing system (see installation
diagram). Converter case must have connection to the potential equalisation facility. If the connecting
process tubing is part of the potential equalisation, no additional connection is required .
2. Use the certified cable glands, suitable for the conditions of use. The delivered cable glands are only
for EEx e use. For EEx d use d-type cable glands.
3. Please confirm that the ground terminal (inside the terminal enclosure) is firmly
connected by means of a clip-on eye-let.
Installation diagram :
L/+
N/- Power supply
G
Terminal Box
Rotamass RCCT3
F91.EPS
9-3 IM 01R04B04-00E-E
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
WARNING
1. EEx type RCCF31 and RCCS3 must be connected to the suitable IS earthing system
(see installation diagram). Converter and detector case must have connection to the
potential equalisation facility.
2. Use the certified cable glands, suitable for the conditions of use.
3. Please confirm that the ground terminal (inside the terminal enclosure) is firmly
connected by means of a clip-on eye-let.
4. For EMC technical reasons the case of the detector is connected to the case of the
converter via the shielding of the interconnecting cable.
For “dust application” (D) use cable glands with minimum IP67 protection !
Installation diagram :
RCCS3 RCCF31
D+ D+ L/+
N/- Power supply
D- D-
G
Terminal Box
S1+ S1+
S1- S1-
S2+ S2+
S2- S2-
TP1 TP1
TP2 TP2 I/O I/O control
TP3 TP3
COM
The inner shields (shields of the cable pairs) are connected together to COM –terminal on converter side.
The outer shield of the cable is connected on both sides to the cases by cable gland.
IM 01R04B04-00E-E 9-4
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
9.1.3 Operation
If the cover of the converter case has to be opened, following instructions must be followed.
CAUTION
1. Confirm that the power cables to the instrument are disconnected.
2. Wait 15 minures after power is turned off before openeing the covers.
3. The covers of display side and terminal box are fixed with special screws, please use Hexagonal
Wrench to open the covers.
4. Be sure to lock the cover with special screw using the Hexagonal Wrench after tightening the cover.
(see drawing chapter 4.3)
5. Before starting the operation again, be sure to lock the cover with the locking screws.
6. Prohibition of specification changes and modifications. Users are prohibited from making any
modifications of specifications or physical configuration, such as adding or changing the configuration
of external wiring ports.
WARNING
The instrument modification of parts replacement by other than authorized representatives of YOKOGAWA
is prohibited and will void the certification.
METER FACTORS
MASSFLOW METER
beside CE mark : number of notified body acc. PED, only for sizes greater than DN25
METER FACTORS
MASSFLOW METER
beside CE mark : number of notified body acc. PED, only for sizes greater than DN25
9-5 IM 01R04B04-00E-E
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
MASSFLOW CONVERTER
VDC 10W N200
-20 to +50˚C VAC~ 47-63Hz 10W
4-20mA (20-600Ω)
30VDC 200mA max
0344 II 2 GD T 70˚C 30VDC 200mA max
KEMA02ATEX2183X
EEx d [ib] II C T6 or EEx de [ib] II C T6 ! WARNING
DIODE SAFETY BARRIER U : 250V WAIT 15 MIN. AFTER POWER-DISCONNECTION
ENCLOSURE: IP67 BEFORE OPENING THE ENCLOSURE.
SEE CERTIFICATE FOR DATA
BARRIER TYPE 1
MASSFLOW CONVERTER
VDC 10W N200
-20 to +50˚C VAC~ 47-63Hz 10W
4-20mA (20-600Ω)
30VDC 200mA max
0344 II 2 GD T 70˚C 30VDC 200mA max
KEMA02ATEX2183X
EEx d [ia][ib] II C T6 or EEx de [ia][ib] II C T6 ! WARNING
DIODE SAFETY BARRIER U : 250V WAIT 15 MIN. AFTER POWER-DISCONNECTION
ENCLOSURE: IP67 BEFORE OPENING THE ENCLOSURE.
SEE CERTIFICATE FOR DATA
BARRIER TYPE 1
MASSFLOW METER
METER FACTORS
N200
II 2 GD see:
0344 T150˚C Instruction
Manual
KEMA 01 ATEX 1075 X
EEx ib IIC / IIB T1 ... T6 Enclosure: IP67
Bitte Bescheinigung beachten
Certification kindly to be noticed
Veuillez faire attention au certificat
beside CE mark : number of notified body acc. PED, only for sizes greater than DN25
METER FACTORS
MASSFLOW METER
0344 II 2 GD T150°C
KEMA 01ATEX1075 X see: N200
EEx ib IIC / IIB T1 ... T6 Instruction
Manual
Bitte Bescheinigung beachten
Certification kindly to be noticed Enclosure: IP67
Veuillez faire attention au certificat
Made in Germany by ROTA YOKOGAWA, Rheinstraße 8, D-79664 Wehr 22-5479.41/C
beside CE mark : number of notified body acc. PED, only for sizes greater than DN25
IM 01R04B04-00E-E 9-6
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
METER FACTORS
MASSFLOW METER
0344 II 2 GD T220°C
KEMA 01ATEX1075 X see: N200
EEx ib IIC / IIB T1 ... T6 Instruction
Manual
Bitte Bescheinigung beachten
Certification kindly to be noticed Enclosure: IP67
Veuillez faire attention au certificat
Made in Germany by ROTA YOKOGAWA, Rheinstraße 8, D-79664 Wehr 22-5479.41/C
beside CE mark : number of notified body acc. PED, only for sizes greater than DN25
METER FACTORS
MASSFLOW METER
0344 II 2 GD T350°C
KEMA 01ATEX1075 X see: N200
EEx ib IIC / IIB T1 ... T6 Instruction
Manual
Bitte Bescheinigung beachten
Certification kindly to be noticed Enclosure: IP67
Veuillez faire attention au certificat
Made in Germany by ROTA YOKOGAWA, Rheinstraße 8, D-79664 Wehr 22-5479.41/C
beside CE mark : number of notified body acc. PED, only for sizes greater than DN25
9-7 IM 01R04B04-00E-E
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
Max. Max.
Temp. Max. Max. Max. medium Max. Max. Max.
medium
class ambient medium ambient temperature / ambient ambient medium
temperature /
temperature temperature temperature temperature of temperature temperature of temperature temperature
heat carrier heat carrier
T6 ≤ 50°C / 122°F ≤ 60°C / 140°F ≤ 40°C / 104°F ≤ 40°C / 104°F ≤ 65°C / 149°F ≤ 65°C / 149°F ≤ 50°C / 122°F ≤ 65°C / 149°F
T5 ≤ 50°C / 122°F ≤ 80°C / 176°F ≤ 55°C / 131°F ≤ 55°C / 131°F ≤ 75°C / 167°F ≤ 75°C / 167°F ≤ 50°C / 122°F ≤ 80°C / 176°F
≤ 80°C / 176°F ≤ 100°C / 212°F ≤ 80°C / 176°F ≤ 100°C / 212°F ≤ 70°C / 158°F ≤ 115°C / 239°F ≤ 50°C / 122°F ≤ 115°C / 239°F
T4
≤ 50°C / 122°F ≤ 120°C / 248°F ≤ 40°C / 104°F ≤ 120°C / 248°F
T3 ≤ 80°C / 176°F ≤ 150°C / 302°F ≤ 80°C / 176°F ≤ 160°C / 320°F ≤ 70°C / 158°F ≤ 180°C / 356°F ≤ 50°C / 122°F ≤ 150°C / 302°F
NOTE
For customer insulation of RCCS34 to 39/IR the following must be regarded :
The table "with factory insulation" is calculated with 80mm insulation and k-factor = 0.4 W/m2K.
If your insulation data are worse than these use table "without insulation" !
IM 01R04B04-00E-E 9-8
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
9.2.2 Installation
Integral type RCCT3 :
L/+
N/- Power supply
G
Terminal Box
Rotamass RCCT3
F91.EPS
Remote type RCCS3 with RCCF31 :
Hazardous area Safe area
RCCS3 RCCF31
D+ D+ L/+
N/- Power supply
D- D-
G
Terminal Box
S1+ S1+
S1- S1-
S2+ S2+
S2- S2-
TP1 TP1
TP2 TP2 I/O I/O control
TP3 TP3
COM
CAUTION
- The flowmeter must be connected to the potential equalization system. For remote type Converter and
detector case must have connection to the potential equalisation facility.
- For remote type at ambient temperature up to 60°C / 140°F use remote cable RCCY031 or RCCY032.
- For remote type at ambient temperature up to 80°C / 176°F use remote cable RCCY033.
- Maximum length of remote cable is 50m/164ft.
- Specified maximum ambient temperature of cables (power supply-, I/O- and remote cable) must be 20°C
/ 41°F above maximum ambient temperature of flowmeter.
- For AC-version maximum power supply is 250V AC.
- Install according National Electrical Code. Intrinsically safe circuits must be installed according NEC ANSI
/ NPFA 70 amd ISA RP 12.6.
- Use certified XP (explosion proof) cable glands for power supply and I/O.
- Please confirm that the ground terminal (inside the terminal enclosure) is firmly connected by means of
a clip-on eye-let.
- For EMC technical reasons the case of the detector is connected to the case of the converter via the
shielding of the interconnecting cable.
9-9 IM 01R04B04-00E-E
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
Installation of separate intrinsic safe ground for Remote type RCCS3 with RCCF31
(see Control Drawing 8300027) :
- Remove the stopping plug on dector connecting side and replace it by a dust proofed cable gland.
- Open the cover on detector connecting side of RCCF31.
- Remove the cable between COM-terminal and the ground screw.
- Put the intrinsic safe ground cable through the new installed cable gland.
- Connect the IS-ground cable to the COM-terminal.
- Install the remote cable between detector RCCS3 and converter RCCF31 as shown in this chapter.
WARNING
- Substitution of components may impair intrinsic safety !
- Only trained persons may use the instrument in industrial location.
- The instrument modification of parts replacement by other than authorized representatives of
YOKOGAWA is prohibited and will void the certification.
- If the cover of the converter case has to be opened, following instructions must be followed:
- Confirm that the power cables to the instrument are disconnected.
- Wait 15 minutes after power is turned off before opening the covers.
- The covers of display side and terminal box are fixed with special screws, please use
Hexagonal Wrench to open the covers.
- Be sure to lock the cover with special screw using the Hexagonal Wrench after tightening the
cover (see drawing chapter 4.3).
- Prohibition of specification changes and modifications. Users are prohibited from making any
modifications of specifications or physical configuration, such as adding or changing the
configuration of external wiring ports.
IM 01R04B04-00E-E 9-10
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
METER FACTORS
MASSFLOW METER
PS is the max. process pressure at room temp.
TS are the process temp. limits
MASSFLOW CONVERTER
VDC 10W N200
-40 to +50°C VAC ~ 47-63Hz 10W
Control Drawing No.:8300027 4-20mA (20-600Ω)
CL. I DIV 1 GP A,B,C,D 30VDC 200mA
AIS CL. I/II/III , DIV 1, GP A,B,C,D,E,F,G 30VDC 200mA
CL. II DIV 1 GP E,F,G
CL. III ! WARNING
AEx d [ia] IIC , Class I , Zone 1, T6 WAIT 15 MIN. AFTER POWER-DISCONNECTION
Type NEMA 4X, IP67 BEFORE OPENING THE ENCLOSURE.
Conduit Seals required within 18 inches.
Use Conductors rated 70°C.
Made in Germany by ROTA YOKOGAWA, Rheinstraße 8, D-79664 Wehr 30-0220.3/B
MASSFLOW METER
METER FACTORS
PS is the max. process pressure at room temp.
TS are the process temp. limits N200
Control Drawing No.: 8300027
IS Class I , DIV 1, GP A,B,C,D, T6 see:
CL. II , DIV 1, GP E,F,G Instruction
Manual
CL. III
AEx ia IIC, Class I , Zone 0
Use Conductors rated 20°C above
max. Ambient Temp. Type 4X, IP67
Temperature Class see Control Drawing
Made in Germany by ROTA YOKOGAWA, Rheinstraße 8, D-79664 Wehr 22-7017.2/C
METER FACTORS
MASSFLOW METER
PS is the max. process pressure at room temp.
TS are the process temp. limits
9-11 IM 01R04B04-00E-E
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
METER FACTORS
MASSFLOW METER
PS is the max. process pressure at room temp.
TS are the process temp. limits
-40 to +50°C VDC 10W
VAC~ 47-63Hz 10W
Fieldbus H1 9-32VDC
Control Drawing No.:8300026 WARNING
CL. I DIV 1 GP A,B,C,D
!
see: N200
WAIT 15 MIN. AFTER Instruction
CL. II DIV 1 GP E,F,G POWER-DISCONNECTION Manual
CL. III BEFORE OPENING
AEx d [ia] IIC , Class I , Zone 1, T6 THE ENCLOSURE.
Conduit Seals required within 18 inches.
Use Conductors rated 70°C. Type NEMA 4X, IP67
Made in Germany by ROTA YOKOGAWA, Rheinstraße 8, D-79664 Wehr 22-5479.34/A
MASSFLOW CONVERTER
VDC 10W N200
-40 to +50°C VAC ~ 47-63Hz 10W
Control Drawing No.:8300027 Fieldbus H1 9-32VDC
CL. I DIV 1 GP A,B,C,D
AIS CL. I/II/III , DIV 1, GP A,B,C,D,E,F,G
CL. II DIV 1 GP E,F,G
CL. III ! WARNING
AEx d [ia] IIC , Class I , Zone 1, T6 WAIT 15 MIN. AFTER POWER-DISCONNECTION
Type NEMA 4X, IP67 BEFORE OPENING THE ENCLOSURE.
Conduit Seals required within 18 inches.
Use Conductors rated 70°C.
Made in Germany by ROTA YOKOGAWA, Rheinstraße 8, D-79664 Wehr 30-0220.4/A
IM 01R04B04-00E-E 9-12
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
Hazardous Locations :
Class I Division 1 Groups A,B,C,D or Class I Zone 1 Group IIC
and Class II and III Division 1 Groups E,F,G
Temperature classification :
Temp. RCCT34 to RCCT39/IR
class
Max. Max.
Ambient Medium
temperature temperature or
temperature of
heat carrier
T6 ≤ 50°C / 122°F ≤ 65°C / 149°F
T5 ≤ 50°C / 122°F ≤ 80°C / 176°F
T4 ≤ 50°C / 122°F ≤ 115°C / 239°F
T3 ≤ 50°C / 122°F ≤ 150°C / 302°F NPT 1/2"
The minimum ambient temperature is -40°C / -40°F
Installation :
L/+
N/- Power supply
G
Rotamass RCCT3
Note :
- For AC-version maximum power supply is 250V AC.
- For DC-version maximum power supply is 28.8V DC.
- The installation must be in accordance with the national electrical code, NFPA70, article 504 to 510
and ANSI/ISA RP 12.06.01.
- The non intrinsically safe terminals must not be connected to any device that uses or generates more
than 250Vrms or dc unless it has been determined that the voltage was adequately isolated.
- Installation must be in accordance with the Canadian Electrical Code, when installed in Canada.
9-13 IM 01R04B04-00E-E
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
Hazardous Locations :
Remote Detectotr RCCS3 : Class I Division 1 Groups A B C D
Class II and III Division 1 Groups E F G
Remote Converter RCCF31 : Class I Division 1 Groups A B C D or Class I Zone 1 Group IIC
Class II and III Division 1 Groups E F G
Temperature classification :
RCCS30 to RCCS33 RCCS34 to RCCS39/IR RCCS34 to RCCS39/IR
without insulation with factory insulation /T1 ... T3
Max. Max. Max.
Temp. Max. medium Max. medium Max. medium
class ambient temperature / ambient temperature / ambient temperature /
temperature temperature of temperature temperature of temperature temperature of
heat carrier heat carrier heat carrier
T6 ≤ 50°C / 122°F ≤ 60°C / 140°F ≤ 40°C / 104°F ≤ 40°C / 104°F ≤ 65°C / 149°F ≤ 65°C / 149°F
T5 ≤ 50°C / 122°F ≤ 80°C / 176°F ≤ 55°C / 131°F ≤ 55°C / 131°F ≤ 75°C / 167°F ≤ 75°C / 167°F
≤ 80°C / 176°F ≤ 100°C / 212°F ≤ 80°C / 176°F ≤ 100°C / 212°F ≤ 70°C / 158°F ≤ 115°C / 239°F
T4
≤ 50°C / 122°F ≤ 120°C / 248°F ≤ 40°C / 104°F ≤ 120°C / 248°F
≤ 80°C / 176°F≤ ≤ 150°C / 302°F ≤ 80°C / 176°F ≤ 160°C / 320°F ≤ 70°C / 158°F ≤ 180°C / 356°F
T3
≤ 40°C / 104°F ≤ 180°C / 356°F
T2 ≤ 80°C / 176°F ≤ 150°C / 302°F ≤ 80°C / 176°F ≤ 220°C / 428°F ≤ 65°C / 149°F ≤ 275°C / 527°F
T1 ≤ 45°C / 113°F ≤ 350°C / 662°F
The maximum ambient temperature for remote converter RCCF31 is 50°C / 122°F.
The minimum ambient temperature for remote converter RCCF31 is -40°C / -40°F.
The minimum ambient temperature for remote detector RCCS3 is -50°C / -58°F.
Installation :
RCCS3 RCCF31
D+ D+ L/+
N/- Power supply
D- D-
G
S1+ S1+
S1- S1-
S2+ S2+
S2- S2-
TP1 TP1
TP2 TP2 I/O I/O control
09.02.2005
TP3 TP3
COM
Case earth clamp
Exclusive remote cable
For installation of separate intrinsic safe ground see page 2. WARNING : Substitution
of components may impair
intrinsic safety.
DATE NAME TITEL:
DRAWED 09.02.2005 Butz FM/CSA CONTROL DRAWING
CKECKED 09.02.2005 Rü ROTAMASS REMOTE TYPE
RCCF31 + RCCS3
b --------- 1.9.05 Butz Rü YOKOGAWA DWG. No.:
a 79664 WEHR
Rev. UPDATE No. DATE EDITOR CHECKED GERMANY 8300027 1 2
IM 01R04B04-00E-E 9-14
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
COM - terminal
Remove cable
IS earth
Note :
- For AC-version of RCCF31 maximum power supply is 250V AC.
- For DC-version maximum power supply is 28.8V DC.
- Install in accordance with NFPA 70
- Max. cable length of remote cable 50m / 164ft.
- Connect inner shields of remote cable together to COM-terminal on converter side.
- Connect outer shield of remote cable on both sides to case by cable gland.
- The installation must be in accordance with the national electrical code, NFPA70, article 504 to 510
and ANSI/ISA RP 12.06.01.
- The non intrinsically safe terminals must not be connected to any device that uses or generates more
than 250Vrms or dc unless it has been determined that the voltage was adequately isolated.
- Installation must be in accordance with the Canadian Electrical Code, when installed in Canada
WARNING : Substitution
of components may impair
intrinsic safety.
DATE NAME TITEL:
DRAWED 09.02.2005 Butz FM/CSA CONTROL DRAWING
CKECKED 09.02.2005 Rü ROTAMASS REMOTE TYPE
RCCF31 + RCCS3
b ---------- 1.9.05 Butz Rü YOKOGAWA DWG. No.:
a 79664 WEHR
Rev. UPDATE No. DATE EDITOR CHECKED GERMANY 8300027 2 2
9-15 IM 01R04B04-00E-E
5th edition Nov. 2005
9. EXPLOSION PROTECTED TYPE INSTRUMENTS
IM 01R04B04-00E-E 9-16
5th edition Nov. 2005
10. PED (PRESSURE EQUIPMENT DIRECTIVE
WARNING
The given temperature /pressure ranges are calculated and approved without corrosion or erosion. The
customer is fully responsible to select proper materials to withstand his corrosive or erosive conditions. In
case of heavy corrosion and/or erosion the instrument may not withstand the pressure and an incident
may happen with human and/or environmental harm. Yokogawa will not take any liability regarding
damage caused by corrosion/erosion. If corrosion/erosion may happen, the user has to check periodically
if the necessary wall thickness is still in place.
ROTAMASS is produced according the determinations of directive 97/23/EG (Directive for Pressure –
Equipment / PED).The units are classified as pipe according item 3, number 1, 3. letter, a) first dash or
according diagram 6 after appendix II :
Classification as pipe
For Fluid Group 1 and 2 (article 9 chapter (2))
Medium liquid and gas
The basic safety requests (for design, production and testing) for all units according to category I to III are
generally determined for the requests of category III. The units, which are not included by PED, article 3
paragraph 3, are checked by a conformity-valuation–methode according appendix III “module H”.
The complete quality assurance system according PED appendix III module H was certified by the notified body :
Lloyd’s Register Nederland B.V.; Weena-Zuid 170; NL-3012 NC Rotterdam
ID-No. 0343
Number is printed on name plates (see chapter 1.2).
10-1 IM 01R04B04-00E-E
5th edition Nov. 2005
10. PED (PRESSURE EQUIPMENT DIRECTIVE)
Medium Temperature
up to 120°C 220°C 300°C 350°C
J1 Flange acc. JIS B 2220 10K 14 bar 12 bar 10 bar -----
J2 Flange acc. JIS B 2220 20K 34 bar 31 bar 29 bar 26 bar
Medium Temperature
up to 140°C *)
up to DN40 40 bar
Pipe conection *) under the restriction using
S2 DN50 to DN100 25 bar suitable gasket materials
acc. DIN11851
above DN100 16 bar
Medium Temperature
up to 150°C **)
Clamp connection up to DN50 16 bar
S4
acc. DIN32676 above DN50 10 bar
**) under the restriction using
Clamp acc. Tri-Clamp up to 2 in (2") 16 bar suitable gasket materials
S8
above 2 in (2") 10 bar
1
) all process connections acc. AISI 316L (1.4404 / 1.4435) T8.EPS
b) for Special-Process-Connections
For customer-built models with Z-No. (Option /Z) different values may be valid.
These details are written on the name plate (field 13).
Medium temperature
Special connections
-200°C RT 50°C 100°C 150°C 200°C 250°C 300°C 350°C
Flange ASME >300 100% 100% 94,2% 83,3% 75,8% 69,5% 64,3% 60,8% 58,0%
Flange DIN PNx x x 100% 100% 96,5% 55,5% 80,5% 74,3% 69,8% 64,5% 61,8%
other connections **) 100% 100% 96,5% 55,5% 80,5% 74,3% 69,8% 64,5% 61,8%
PS *) T102.EPS
IM 01R04B04-00E-E 10-2
5th edition Nov. 2005
10. PED (PRESSURE EQUIPMENT DIRECTIVE
1) Year of manufacturing
2) Max. permitted pressure at room temperature, for other temperatures see table
3) Max. permitted temperature range
4) Test pressure, for standard units without value, because in this case generally
PT=1.43 x PS
5) Material of medium wetted parts with pressure load
Operation restriction :
The operator is responsible that no corrosion and/or erosion is caused by the medium, which reduces the
safety of the unit as pressure vessel. Corrosion and erosion can make the unit fail and can lead to the
endangering of persons and facilities. If corrosion and erosion are possible, the integrity of the tubes has
to be checked periodically.
10-3 IM 01R04B04-00E-E
5th edition Nov. 2005
10. PED (PRESSURE EQUIPMENT DIRECTIVE)
External fire External fire can result in The instrument itself does not
Outer - Rise in pressure by temperature contain flammable materials.
influence - Damage of gaskets
It is in the sole responsibility of the
user to implement suitable means to
prevent large damage in the case of
fire.
Earthquake resistance Damage of the mounting screws Check by user
T101.EPS
IM 01R04B04-00E-E 10-4
5th edition Nov. 2005
11. TECHNICAL DATA
Pressure dependency:
Fluid to be measured : Liquid, gas or slurries
The stiffness of the Rotamass tubes is slighty line pressure
dependent. The static pressure effect of mass flow and density
Measurement items : Mass flow, density, temperature
can be corrected by setting the static pressure manual via
and derived from these values:
menue.
concentration, volume flow and
RCCS30-RCCS34 : no relevant pressure effect
net flow
Table 3 : Pressure effect on mass flow (not corrected)
Mass flow measurement Type RCCS36 RCCS38 RCCS39 RCCS/T
RCCT36 RCCT38 RCCT39 39 /IR
Table 1 : Measuring range
% of SS -0.0033 -0.0085 -0.009 -0.0456
Type RCCS30 RCCS31 RCCS32 RCCS33 rate per HC -0.0049 -0.0126 -0.0133 -0.0675
Qmax 0.1 bar Ti -0.0055 -0.0143 ---- ----
t/h 0.3 0.6 1.5
Qnom t/h 0.045 0.17 0.37 0.9 T3.EPS
T1a.EPS
Density measurement
Type RCCS34 RCCS36 RCCS38 RCCS39 RCCS/T Measuring range : 0.3kg/l to 5 kg/l
RCCT34 RCCT36 RCCT38 RCCT39 39 /IR
Qmax 50 No density measurement for gas application
t/h 5 15 120 300
Qnom t/h 2.7 9 32 85 250 Accuracy (at calibration conditions)
T1b.EPS - RCCS30 : ± 8 g/l
- RCCS31-33 : ± 4 g/l
Qnom is the water flow rate at about 1 bar pressure drop.
- RCCS/T34 : ± 3 g/l
The flowmeter has an automatical low cut at 0.05% of
- RCCS/T36 : ± 2.2 g/l
Qnom.
- RCCS/T38, 39 : ± 1.5 g/l
Accuracy - RCCS/T34-39 : ± 1 g/l (with special calibration option/ K3)
Liquid : - RCCS30-33 : ± 2 g/l (with special calibration option /K3,
- RCCS3 + RCCF31, :+/-0.1% of measured value good thermal isolation of the detector,
RCCT3 +/- zero stability (refer to table 2) fixed temp. or external temp. sensor)
Gas (option /GA) :
- RCCS3 + RCCF31, : ±0.5% of measured value Temperature measurement
RCCT3 ± zero stability (refer to table 2) Temperature measuring range of converter :
Accuracy based on the frequency output includes the Standard and with /MT:-200°C to 230°C
combined effects of repeatability, linearity and With /HT : 0°C to 400°C
hysteresis. Accuracy : ± 1°C ± 0.5% of reading
For operating temperatures more than 80°C higher/lower than
Repeatability for liquids :±0.05% ± zero stability/2 ambient temperature the detector should be insulated to
maintain optimum accuracy.
Repeatability for gases :±0.25% ± zero stability
Batch process :above specified accuracy if the Heating Tracing (Remote detector RCCS34 to 39/IR, for
batch process is >1min. For RCCS30-33 on request) :
shorter batch time (dt in s) the Heating with heat carrier, insulation and protection housing.
accuracy decreases with the The max. surface temperature at the protection housing from
square root of 60/dt inner heating is 40°C. Above 150° process temperature
insulation from the manufacturer is recommended. However
up to 230°C process temperature the customer can insulate
1.0
0.9 the detector themselves.
0.8
0.7 Option /T1: only insulation and protection;
0.6
0.5
0.4
Option /T2 insulation, protection and heating line;
0.3 Option /T3 like /T2 but with ventilation.
Error in %
0.2
0.1
0
Process connection for the heat carrier fluid is :
-0.1
-0.2 for D-type flanges : EN DN15 PN40 Form B1
-0.3
-0.4 for A-type flanges : ANSI ½ - 150 lbs.
-0.5
-0.6 for J-type flanges : JIS DN15 10K
-0.7
-0.8 Max. pressure : PN40
-0.9
-1.0
0 50 100 150
Protection class : IP54, install roof protected
Flow in % of Qnom
For low temperature fluids ask for special insulation.
F10.EPS
11-1 IM 01R04B04-00E-E
5th edition Nov. 2005
11. TECHNICAL DATA
IM 01R04B04-00E-E 11-2
5th edition Nov. 2005
11. TECHNICAL DATA
Power supply and power consumption - Two Pulse outputs / status outputs :
- AC-type : 90V to 264V AC, 47-63 Hz passive Transistor contact output , 30V DC, 200mA
For Ex- version 250V AC max. Output 1 : 0 to 10000 pulses/s
- DC-type : 20.5V to 28.8V DC Output 2 : 0 to 2000 pulses/s
Consumption : max. 25VA / 10W Active pulse output is not isolated from current output 2.
Option /NM : passive, according EN 60947-5-6
Option /AP : active output, 12V,6mA,RL> 10kΩ
MECHANICAL SPECIFICATIONS As frequency output :
Protection class : IP67 Output 1 : 20Hz to10000Hz
Output 2 : 20Hz to 2000Hz
Materials Additional error of 0.1% may occur below 800 Hz
- Detector housing : Stainless steel 316
- Status input : Voltage-free contact,
- Converter and detector (RCCS34 to 39/IR) terminal box :
closed : < 200Ω
: Aluminium alloy with Polyurethane
open : > 100 kΩ
corrosion-resistant coating
Intrinsic safe outputs (/KF2), a total of 2 outputs
Coating colour
- One passive current output (additional power supply needed) :
- Converter case : Mint green
4 to 20 mA DC, galvanic separated from other signals.
- Terminal box cover : Mint green
Supply voltage 10.5-30V DC (without HART), 165mA
Wetted parts Supply voltage 16.75-30V DC (with HART), 165mA.
- RCCS30 to 33 : Load resistance : 20 to 600Ω
Tubes : HC22/2.4602 Ambient temperature effect : < 0.05% of span/10°C
Process connections : 316L/1.4404 - One pulse output / status output :
- RCCS34 to 39 and RCCT34 to 39 : passive Transistor contact output , 30 V DC, 100 mA
Tubes and process connection Output rate : 0 to 2000 pulses/s
: 316L/1.4404 or Hastelloy C22/ As frequency output : 20 – 2000Hz
2.4602 Option /NM : passive, according EN 60947-5-6
- RCCS34 to 38 and RCCT34 to 39 : Additional error of 0.1% may occur below 800 Hz.
Tubes and process connection
: Titanium B265 Gr.2 / 3.7035 Digital communication
- RCCS39/IR : - HART communication signal, superimposed on 4 -20 mA
Tubes and process connection DC signal (Iout1)
: 316L/1.4404 - Load resistance : 230 - 600 Ω (including cable)
Table 4 : Diameter of measuring tubes - Power line spacing : 15 cm or more, avoid parallel
wiring
Type RCCS30 RCCS31 RCCS32 RCCS33 - Cable length : ≤ 2 km if „CEV” cables are used
Inner diameter mm 1.2 2.1 3 4.5
Wall thickness mm
Setting functions : Parameter setting is possible by
0.2 0.25 0.25 0.25
using the switches on the display
T5a.EPS
or with HART communication.
Type RCCS34 RCCS36 RCCS38 RCCS39 RCCS39
RCCT34 RCCT36 RCCT38 RCCT39 /IR Display function
Inner diameter mm 7.6 13.4 22.1 37.2 55.1 - Up to 4 lines.
Wall thickness mm 0.91 1.24 1.65 2.6 2.6 - 3 languages selectable (English, German, French)
T5b.EPS
- Instantaneous flow rate, density, temperature or
PRESSURE EQUIPMENT DIRECTIVE 97/23/EC totalized flow can be displayed.
- Module : H; Fluid group : 1; Category : III
Damping functions : Settable from 0.4 seconds (63%
response time) to 200 seconds, controls display and outputs.
ELECTRICAL SPECIFICATIONS
Power supply Isolation resistance of converter
- AC- type : 90V to 264V
90V to 250V for Ex-type When surge arrestors are removed
- DC- type : 20.5V ~ 28.8 V - between power and ground terminal : 100 MΩ / 500 V DC
External circuit breaker rating : 5A, 250V (In the converter - between power and I/O terminals : 20 MΩ / 100 V DC
no power switch is installed). - between I/O terminals and ground : 20 MΩ / 100 V DC
11-3 IM 01R04B04-00E-E
5th edition Nov. 2005
11. TECHNICAL DATA
average. 100
50
10
0 1
10
Fig.1: Pressure loss RCCS30 0.1
5
10
Viscosity (mPas) -2
10
10 100 1000
Pressure loss (mbar)
10
1
0.1 Fig.6 : Pressure loss RCCS/RCCT36
1
10
Viscosity (mPas)
4
10
Pressure loss (mbar)
10-1 1000
1 10 100 1000
2 500
10
Flow (kg/h)
F1.EPS 100
50
10
1
Fig.2 : Pressure loss RCCS31 100
0.1
Viscosity (mPas)
104
500
Pressure loss (mbar)
10-2
100 1000 10000
100
10 2 50 Flow (kg/h) F6.EPS
10
1
0.1
100
Fig.7 : Pressure loss RCCS/RCCT38
-2
10
1 10 100 1000 104 Viscosity (mPas)
Pressure loss (mbar)
Flow (kg/h)
F2.EPS
2
Fig.3 : Pressure loss RCCS32 10 1000
500
100
104
Viscosity (mPas) 0 50
10
Pressure loss (mbar)
10
500 1
0.1
10
2 100
-2
50 10
100 1000 10000
10 Flow (kg/h)
F7.EPS
100 1
0,1
-2
10
1 10 100 1000
Flow (kg/h)
F3.EPS
IM 01R04B04-00E-E 11-4
5th edition Nov. 2005
11. TECHNICAL DATA
Cavitation
To avoid cavitation keep the back pressure of the fluid
sufficiently above the vapor pressure of the fluid. For low
viscous fluids following condition should be fulfilled at the
given temperature:
pback > pboiling + 0.7*∆p
With ∆p = pressure loss (e.g. given by the sizing program)
Recalibration Service
Yokogawa offers via its European flow centre (Rota
Yokogawa, Germany) full recalibration service, if necessary
with a certificate traceable to German national standards.
Please contact your Yokogawa affiliate or directly ROTA
YOKOGAWA, Germany.
11-5 IM 01R04B04-00E-E
5th edition Nov. 2005
11. TECHNICAL DATA
IM 01R04B04-00E-E 11-6
5th edition Nov. 2005
11. TECHNICAL DATA
11.2 Dimensions
Integral type RCCT3
(246)
122 124
Without Indicator 30 32 30
(266)
With Indicator (147) 122 144
85 30 32 50
(66)
Ø123
49
H3
H2
52
H4
H1
L3 W1
L2 W2
L1±5
Note : the flange dimensions depend on size and pressure rating of the flange
Model L1 L2 L3 H1 H2 H3 H4 W1 W2 Weight
RCCT34 [mm] see table 10 272 212 180 212 278 80 60 80 13 kg
RCCT36 [mm] see table 10 400 266 233 212 278 80 76 90 17 kg
RCCT38 [mm] see table 10 490 267 274 222 288 100 89 110 26 kg
RCCT39 [mm] see table 10 850 379 430 240 306 135 129 160 64 kg
RCCT39/IR [mm] see table 10 870 455 453 272 338 200 155 200 92 kg
Dimensions are given in mm
F12.EPS
11-7 IM 01R04B04-00E-E
5th edition Nov. 2005
11. TECHNICAL DATA
Without Indicator
Ø102 75
17
120
91.6
201
Ø123
63.5
30 32 30 85
124 122 (147)
(246)
With Indicator
Ø102 75
17
120
91.6
201
Ø123
50 32 30 85
63.5
IM 01R04B04-00E-E 11-8
5th edition Nov. 2005
11. TECHNICAL DATA
±3
±3
F15.EPS
Dimensions in mm.
Weight (without flanges): 3.5kg
Ø116
L1±5 Ø116
80
H6
117
H5
H4
H1
L2 W2
Model L1 L2 L3 W1 W2 H1 H4 H5 H6 Weight
RCCS34 [mm] see table 10 272 212 60.3 80 180 80 157 237 9.5 kg
RCCS36 [mm] see table 10 400 266 76.1 90 233 80 157 237 13 kg
RCCS38 [mm] see table 10 490 267 88.9 110 265 100 167 247 22 kg
RCCS39 [mm] see table 10 850 379 129 160 430 135 185 265 60 kg
RCCS39/IR [mm] see table 10 870 455 155 200 453 200 217 297 88 kg
F14.EPS
11-9 IM 01R04B04-00E-E
5th edition Nov. 2005
11. TECHNICAL DATA
L1±5
Ø116
L5
D2±5
ventilation D1±5 H6
optional /T3
W3
H8 H9
H7
Model L1 L4 L5 D1 D2 H6 H7 H8 H9 W3 weight
RCCS34 [mm] see table 10 420 310 200 330 237 411 273 138 240 18 kg
RCCS36 [mm] see table 10 540 439 250 380 237 464 326 138 260 25 kg
RCCS38 [mm] see table 10 640 530 250 430 247 524 376 148 260 37 kg
RCCS39 [mm] see table 10 1000 884 350 580 265 684 520 165 304 95 kg
RCCS39/IR [mm] see table 10 1040 932 350 590 297 730 530 200 343 125kg
Heating connection standard : EN DN15 PN40, ASME 1/2 - 150, JIS DN15 10K according process connection
F16.EPS
IM 01R04B04-00E-E 11-10
5th edition Nov. 2005
11. TECHNICAL DATA
11-11 IM 01R04B04-00E-E
5th edition Nov. 2005
11. TECHNICAL DATA
IM 01R04B04-00E-E 11-12
5th edition Nov. 2005
11. TECHNICAL DATA
Material of wetted parts *) SH 316L (1.4404) and Hastelloy C-22 (2.4602) for tube only RCCS30 ... 33
SL Stainless steel 316L (1.4404) only RCCS34 … 39IR
HC Hastelloy C-22 (2.4602) only RCCS34 … 39
TI Titanium B265 Gr.2 (3.7035) only RCCS34 … 38
*) see selection table process connection and materials (table 10)
11-13 IM 01R04B04-00E-E
5th edition Nov. 2005
11. TECHNICAL DATA
IM 01R04B04-00E-E 11-14
5th edition Nov. 2005
11. TECHNICAL DATA
/C03 WT% KOH /water 0 - 60 WT% 54-100°C D´Ans-Lax, Handbook for chemists and physicists Vol.1, 3rd Edition, 1967
/C04 WT% NH4NO3 / water 1 - 50 WT% 0 - 80°C Source undefined
/C05 WT% NH4NO3 / water 20 -70 WT% 20 -100°C Source undefined
/C06 WT% HCl / water 22 -34 WT% 20 – 60°C D´Ans-Lax, Handbook for chemists and physicists Vol.1, 3rd Edition, 1967
/C08 WT% H 2 SO4 / water 2 –80 WT % 0 – 100°C D´Ans-Lax, Handbook for chemists and physicists Vol.1, 3rd Edition, 1967
/C09 WT% H2 O 2 / water 30 -75 WT% 4 - 44°C Source undefined
/C10 WT% Ethylen Glycole / water 10 -50 WT% 2
- 0 - 40°C Source undefined
/C11 WT% Amylum = starch /water 33 - 43 WT% 35 - 45°C Source undefined
/C12 WT% Methanol / water 35-60 WT% 0 - 40°C Source undefined
/C20 Vol% Alcohol / water 55-100 Vol% 10 - 40°C Source undefined
/C21 °Brix Sugar / water 40-80 °Brix 75 -100°C Source undefined
T9.EPS
11-15 IM 01R04B04-00E-E
5th edition Nov. 2005
11. TECHNICAL DATA
04A4 1½"-900 ---- ---- ---- ---- ---- ---- ---- 640 ---- ---- ---- ---- ----
04A5 1½"-1500 340 470 ---- ---- 600 ---- ---- ---- ---- ---- ---- ---- ----
05A1 2"-150 ---- ---- ---- ---- 510 500 520 600 600 620 ---- ---- ----
05A2 2"-300 ---- ---- ---- ---- 510 500 520 600 600 620 ---- ---- ----
05A3 2"-600 ---- ---- ---- ---- 540 ---- ---- 630 ---- ---- ---- ---- ----
05A4 2"-900 ---- ---- ---- ---- ---- ---- ---- 720 ---- ---- ---- ---- ----
05A5 2"-1500 ---- ---- ---- ---- 660 ---- ---- ---- ---- ---- ---- ---- ----
06A1 2½"-150 ---- ---- ---- ---- ---- ---- ---- 610 600 620 ---- ---- ----
06A2 2½"-300 ---- ---- ---- ---- ---- ---- ---- 610 600 620 ---- ---- ----
06A3 2½"-600 ---- ---- ---- ---- ---- ---- ---- 640 ---- ---- ---- ---- ----
06A4 2½"-900 ---- ---- ---- ---- ---- ---- ---- 760 ---- ---- ---- ---- ----
08A1 3"-150 ---- ---- ---- ---- ---- ---- ---- 610 600 620 1000 1000 ----
08A2 3"-300 ---- ---- ---- ---- ---- ---- ---- 620 600 620 1000 1000 ----
08A3 3"-600 ---- ---- ---- ---- ---- ---- ---- 640 ---- ---- 1000 ---- ----
08A4 3"-900 ---- ---- ---- ---- ---- ---- ---- 760 ---- ---- ---- ---- ----
10A1 4"-150 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 1000 1100
10A2 4"-300 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 1000 1100
10A3 4"-600 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1030 ---- ----
12A1 5"-150 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 1000 1100
12A2 5"-300 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 1000 1100
12A3 5"-600 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1040 ---- ----
15A1 6"-150 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1100
15A2 6"-300 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1100
01D4 DN15 PN40 240 370 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
01D6 DN15 PN100 250 380 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
02D4 DN25 PN40 240 370 370 390 500 500 520 ---- ---- ---- ---- ---- ----
02D6 DN25 PN100 260 390 ---- ---- 520 ---- ---- ---- ---- ---- ---- ---- ----
Flanges according EN1092-1
04D4 DN40 PN40 240 370 370 390 500 500 520 600 ---- ---- ---- ---- ----
04D6 DN40 PN100 320 450 ---- ---- 560 ---- ---- 620 ---- ---- ---- ---- ----
05D4 DN50 PN40 ---- ---- ---- ---- 500 500 520 600 600 620 ---- ---- ----
05D5 DN50 PN63 ---- ---- ---- ---- 520 ---- ---- 620 ---- ---- ---- ---- ----
05D6 DN50 PN100 ---- ---- ---- ---- 590 ---- ---- 660 ---- ---- ---- ---- ----
08D4 DN80 PN40 ---- ---- ---- ---- ---- ---- ---- 610 600 620 1000 1000 ----
08D5 DN80 PN63 ---- ---- ---- ---- ---- ---- ---- 620 ---- ---- 1000 ---- ----
08D6 DN80 PN100 ---- ---- ---- ---- ---- ---- ---- 730 ---- ---- ---- ---- ----
10D2 DN100 PN16 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1100
10D4 DN100 PN40 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 1000 1100
10D5 DN100 PN63 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 ---- ----
12D2 DN125 PN16 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1100
12D4 DN125 PN40 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 1000 1100
12D5 DN125 PN63 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 ---- ----
15D2 DN150 PN16 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1100
15D4 DN150 PN40 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1100
01J1 DN15 10K 240 370 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
01J2 DN15 20K 240 370 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
02J1 DN25 10K 240 370 ---- ---- 500 ---- ---- ---- ---- ---- ---- ---- ----
Flanges according JIS B 2220
02J2 DN25 20K 240 370 ---- ---- 500 ---- ---- ---- ---- ---- ---- ---- ----
04J1 DN40 10K 240 370 ---- ---- 500 ---- ---- 600 ---- ---- ---- ---- ----
04J2 DN40 20K 240 370 ---- ---- 500 ---- ---- 600 ---- ---- ---- ---- ----
05J1 DN50 10K ---- ---- ---- ---- 500 ---- ---- 600 ---- ---- ---- ---- ----
05J2 DN50 20K ---- ---- ---- ---- 500 ---- ---- 600 ---- ---- ---- ---- ----
08J1 DN80 10K ---- ---- ---- ---- ---- ---- ---- 600 ---- ---- 1000 ---- ----
08J2 DN80 20K ---- ---- ---- ---- ---- ---- ---- 600 ---- ---- 1000 ---- ----
10J1 DN100 10K ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 ---- 1100
10J2 DN100 20K ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 ---- 1100
12J1 DN125 10K ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 ---- 1100
12J2 DN125 20K ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 ---- 1100
15J1 DN150 10K ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1100
15J2 DN150 20K ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1100
01S4 DN15 240 *) ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
Clamp DIN
02S4 DN25 240 *) 370 *) ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
04S4 DN40 240 370 ---- ---- 500 *) ---- ---- ---- ---- ---- ---- ---- ----
05S4 DN50 ---- ---- ---- ---- 500 ---- ---- 600 *) ---- ---- ---- ---- ----
06S4 DN65 ---- ---- ---- ---- ---- ---- ---- 600 ---- ---- ---- ---- ----
10S4 DN100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 ---- ----
01S8 ½" 240 *) ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
02S8 1" 240 *) 370 *) ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
Tri-Clamp
04S8 1½" 240 370 ---- ---- 500 *) ---- ---- ---- ---- ---- ---- ---- ----
05S8 2" ---- ---- ---- ---- 500 ---- ---- 600 *) ---- ---- ---- ---- ----
08S8 3" ---- ---- ---- ---- ---- ---- ---- 600 ---- ---- ---- ---- ----
10S8 4" ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 ---- ----
02S2 DN25 240 370 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
DIN11851
04S2 DN40 ---- ---- ---- ---- 500 ---- ---- ---- ---- ---- ---- ---- ----
05S2 DN50 ---- ---- ---- ---- ---- ---- ---- 600 ---- ---- ---- ---- ----
10S2 DN100 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- 1000 ---- ----
41G9 G¼" female 240 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
01G9 G½" female 240 370 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
23G9 G¾" female 240 370 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
41T9 NPT¼" female 240 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
01T9 NPT½" female 240 370 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
23T9 NPT¾" female 240 370 ---- ---- ---- ---- ---- ---- ---- ---- ---- ---- ----
dimensions in [mm] *) not possible with option /SFx, /SA, /SE T10.EPS
IM 01R04B04-00E-E 11-16
5th edition Nov. 2005
IM 01R04B04-00E-E
5th edition Nov. 2005
IM 01R04B04-00E-E
5th edition Nov. 2005