Electrical Notes & Articles

GO
Sharing Abstracts,Notes on various Electrical Engineering Topics.

HOME ABSTRACT ELECTRICAL NOTES ELECTRICAL. Q&A ELECTRICAL.TOOL EXCEL TOOL POSTS COMMENTS

UNCATEGORIZED

← Electrical Programs( Excel Base) Specification for Rewireable Porcelain Cut Out Fuse Unit

Low Voltage and High Voltage Cable Testing
JUNE 7, 2011 67 COMMENTS
Jignesh.Parmar

Low Voltage and High Voltage Cable Testing


Low Voltage XLPE Distribution Cables: Blog Stats
15,295,254 hits
Insulation Resistance:
Cables shall be tested for insulation resistance with an insulation tester (i.e. Megger) at 1000 Volts for 1 minute.
The minimum insulation resistance to earth or between phases shall be 100 meg-ohms. About Jignesh Parmar:
The instrument used for this measurement shall have a minimum resolution of 10 meg-ohms on the 0 to 500 meg-
Jignesh Parmar has completed M.Tech (Power
ohm range.
System Control), B.E(Electrical). He is member
At the conclusion of LV insulation resistance testing, the neutrals must be connected to the earth stakes.
of Institution of Engineers (MIE) and CEng,India.
Membership No:M-1473586.He has more than
Phasing Test:
16 years experience in Transmission -
The correct phasing of all LV circuits shall be checked at all positions where the LV cables are terminated into fuse
Distribution-Electrical Energy theft detection-
bases and where any LV cable is run from point to point.
Electrical Maintenance-Electrical Projects
This test shall be performed with an instrument designed for the purpose. Mains frequency voltage of 240 Volts is
(Planning-Designing-Technical Review-
not acceptable for this test.
coordination -Execution). He is Presently
The neutral conductor shall be connected to the earth stake for this test.
associate with one of the leading business group
as a Deputy Manager at Ahmedabad,India. He
Continuity Test (resistance of bolted connections):
has published numbers of Technical Articles in
For loop LV systems, a continuity test shall be carried out on each LV circuit to ensure that all bolted connections
“Electrical Mirror”, “Electrical India”, “Lighting
are complete and adequate. The test shall be carried out as follows:
India”,”Smart Energy”, “Industrial
(1) At the transformer firmly bond all 4 conductors together
Electrix”(Australian Power Publications)
(2) Undertake a continuity test at every point where there is a service provision or open point. In a fused service
Magazines. He is Freelancer Programmer of
pillar the bottom row of fuses bases must be the point at which the test is undertaken as that is the furthest extent
Advance Excel and design useful Excel base
of the network.
Electrical Programs as per IS, NEC, IEC,IEEE
The difference between the readings of each phase conductor and the neutral for each individual test shall not be
codes. He is Technical Blogger and Familiar with
greater than 10% of each other. Any difference greater than this may indicate a loose or dirty connection and will
English, Hindi, Gujarati, French languages. He
require further investigation.
wants to Share his experience & Knowledge and
The instrument used for this measurement should have a resolution to the second decimal point in the 0 to 5 ohm
help technical enthusiasts to find suitable
range.
solutions and updating themselves on various
A typical instrument would be the earth “Megger” type and taking into account the resistance values of the test
Engineering Topics.
leads.

Earth Resistance Test:


Follow Blog via Email
In any overhead or underground network the earth resistance at any point along the length of a LV feeder is to
have a maximum resistance of 10 ohms prior to connection to the existing network. Enter your email address to follow this blog and
In any overhead or underground network the overall resistance to earth Shall be less than 1 ohm prior to receive notifications of new posts by email.
connection to the existing network.
Join 12,051 other followers

11 KV AND 33 KV XLPE Cables: Enter your email address

Phasing Test Follow This Blog by Email


The correct phasing of all HV circuits shall be checked at all positions where the HV cables have been terminated.
This test shall be performed with an instrument designed for the purpose. 240 Volt mains frequency is not
acceptable for the performance of this test. The test may be conducted on either the wire screens or the aluminum
Privacy & Cookies: This site uses cookies. By continuing to use this website, you agree to their use.
Close and accept
Toconductors.
find out more, including how to control cookies, see here: Cookie Policy
Where the test is performed on the wire screens, they shall be disconnected from earth. Follow
Outer Sheath Insulation Resistance (Screen wire test) Electrical Notes-…
22K likes
The purpose of the test is to determine soundness of the outer polyethylene sheath against water ingress,
mechanical damage and termite attack.
Values below 0.5 meg-ohms (500 kΩ) can indicate sheath damage. Values between 1.0 and 10 meg-ohms may
not indicate damage in a single location. Fault finding can often be very difficult. In new cables, values of greater Like Page
than 100 mega ohms are required.
The integrity of the outer sheath shall be checked after cables have been buried by an insulation tester (Megger) at
1000 Volts. BUY ELECTRICAL NOTES IN PDF
The test shall be conducted for 1 minute between each wire screen and earth after the cable has been jointed and
terminations installed.
For cables after repairs, the resistance must not be less than 10 meg-ohms.
Where HV cable circuits are cut and joined to new circuits, sheath testing must be carried out on the existing old
circuit prior to joining to the new cable.

HV test on XLPE cables already in service or previously


energized BUY ELECTRICAL SOFTWARES
Except for New Cables, Testing at Voltage greater than 5.0KV is not permitted

Studies carried out on DC high voltage testing of XLPE cables now conclude that;
DC testing above 5kV of field aged XLPE cables generally increases water tree growth and reduces service life.
5kV is not considered a “High Voltage DC Test”. The test voltages for tests on XLPE cables is now limited to 5kV
after in service repairs and 10kV for new installations.
A 5kV Megger is suitable for a 5kV test on cables after repairs.
The changes to this section will also make it possible for a repaired cable to be tested by repair crews and made
BUY ELECTRICAL NOTE IN PDF
available for immediate return to service.

Application Test Voltage Criteria

After repairs – Sheath 1kV Megger 1 minute 10 meg-ohms min.

After repairs – Insulation 5kV Megger 1 minute 1000 meg-ohms min. BUY ELECTRICAL SOFTWARES.

After repairs – Insulation 5kV DC 1 minute 5.0 μA (micro-amps) max.

HV test on new XLPE cable:


Prior to the performance of this test, the screen wires must be connected to the permanent earth position.
The cable shall be tested at the test voltage and the pass criteria shall be in accordance with the following table:
Proud to be an IndiBlogger
Application Test Voltage Criteria electricalnotes.wordpress.c...

New cables – Sheath

New cables – Insulation


1kV Megger 1 minute

10kV DC 15 minute
100 meg-ohms min.

1.0 μA (micro-amps) max


85 /100

New cables – Insulation 10kV DC 15 minute 1000 meg-ohms min.

SEARCH
If further repair works are undertaken, and they require additional joints to be installed, the complete HV testing
procedure shall be repeated.
Copyright © 2018
Alternative HV Test Requirement on Insulation for 11kV Cables
The content in electricalnotes.wordpress.com is
Where it is not practical to conduct a high voltage test, the test requirements for insulation (core to screen wire)
for personal, non-commercial use only. you can
may be limited to testing for the condition of “safe to energize”. The following list of circumstances and conditions
not reproduce,republish or communicate any of
must be met as a minimum requirement:
the content , including files downloadable from
The cable circuit voltage shall be 11kV,
this website, without the permission of the
The circuit outage duration shall be not more than 48 hours,
copyright owner.The use of this content on any
The work shall involve extending or repairs to existing circuits,
other websites breaches copyright Act. If You
The insulation test shall be applied for 1 minute between each
find this content in any other site,it makes the
phase core and screen with a 1000 Volt minimum insulation tester (Megger),
page you are viewing an infringement of the
Typically the test result should be in the order of 1000 meg-ohms.
copyright.
Paper Insulated Cables:
Tests on LV Cables Recent Posts
An insulation resistance test shall be conducted with a 1000 Volt megger. Test results as low as 10 meg-ohms on Electrical Thumb Rules-VENTILATION &
old cable circuits are common and therefore considered safe to energies. CEILING FAN

Electrical Thumb Rules-Light Sources


Test on 11kV and 33kV Cables between Cores and Earth
For three core belted cables, the test on any core shall be conducted between the core and lead sheath with the Quick Reference-Fire Fighting (Part-2)
remaining two cores connected to earth. Quick Reference-Fire Fighting (Part-1)
The test voltages and pass criteria shall be in accordance with the table below.
Electrical Thumb Rule- High Rise Building (As
per NBC)
Application Test Voltage Criteria
Calculate Motor Pump Size

11kV new cables 5kV Megger 1 minute 100 meg-ohms. Calculate Size of Cable for Motor (As NEC)

How to Design efficient Street lighting-(Part-6)


11kV after repairs 5kV Megger 1 minute 100 meg-ohms.
How to Design efficient Street lighting-(Part-5)

33kV – no TF’s connected 5kV Megger 1 minute 1000 meg-ohms. How to Design efficient Street lighting-(Part-4)

How to Design efficient Street lighting-(Part-3)


33kV – with TF’s connected 5kV Megger 1 minute 15 meg-ohms.
How to Design efficient Street lighting-(Part-2)

How to Design efficient Street lighting-(Part-1)

66kV XLPE CABLES Calculate Size of Pole Foundation & Wind


Pressure on Pole
Core to Sheath Test after Repairs:
Calculate Size of Circuit Breaker/ Fuse for
After repairs have been carried out, the 66kV XLPE cable shall be energized at power frequency for 24 hours
Transformer (As per NEC)
without load. DC testing is not permitted.
The cable sheath link box/cross bonding system shall be put into its normal condition. Selection of Various Types of UPS (Part-2)

Selection of Various Types of UPS (Part-1)


Outer Sheath Integrity Test:
Electrical Thumb Rules-Illumination-(Part-19).
An insulation resistance test between the metallic sheath and earth shall be conducted. The anti-termite barrier
must be connected to the metallic sheath and the insulation test performed to earth. Electrical Thumb Rules-Illumination-(Part-18).
The test voltage applied for 1 minute shall be 5kV DC applied with either a high voltage test set or insulation
Electrical Thumb Rules-Illumination-(Part-17).
resistance tester (Megger).

References:
Archives
ETSA TECHNICAL STANDARD November 2019 (1)

October 2019 (2)

Rate this: September 2019 (2)

10 Votes August 2019 (2)

July 2019 (2)


Share this:
   
June 2019 (1)
Facebook Email LinkedIn More
May 2019 (2)

Like April 2019 (3)

Be the first to like this. March 2019 (2)

February 2019 (2)

Related January 2019 (3)

December 2018 (2)


Insulation Resistance (IR) Values Various Routine Test of Power Transformer-
With 198 comments (Part-1) November 2018 (2)

With 26 comments October 2018 (1)

September 2018 (2)


HIPOT Testing
August 2018 (3)
With 36 comments
July 2018 (1)

June 2018 (1)


FILED UNDER UNCATEGORIZED May 2018 (1)
April 2018 (1)
About Jignesh.Parmar
Jignesh Parmar has completed M.Tech (Power System Control), B.E(Electrical). He is member of March 2018 (1)
Institution of Engineers (MIE) and CEng,India. Membership No:M-1473586.He has more than 16 February 2018 (2)
years experience in Transmission -Distribution-Electrical Energy theft detection-Electrical
January 2018 (1)
Maintenance-Electrical Projects (Planning-Designing-Technical Review-coordination -Execution). He is Presently
associate with one of the leading business group as a Deputy Manager at Ahmedabad,India. He has published December 2017 (1)
numbers of Technical Articles in “Electrical Mirror”, “Electrical India”, “Lighting India”,”Smart Energy”, “Industrial November 2017 (1)
Electrix”(Australian Power Publications) Magazines. He is Freelancer Programmer of Advance Excel and design
October 2017 (1)
useful Excel base Electrical Programs as per IS, NEC, IEC,IEEE codes. He is Technical Blogger and Familiar with
English, Hindi, Gujarati, French languages. He wants to Share his experience & Knowledge and help technical September 2017 (1)
enthusiasts to find suitable solutions and updating themselves on various Engineering Topics. August 2017 (1)

July 2017 (2)

June 2017 (1)


67 Responses to Low Voltage and High Voltage Cable Testing
May 2017 (1)

farouq faisal says: April 2017 (1)


July 11, 2011 at 10:29 pm March 2017 (1)

thank you very much it is realy importent programs thank you so much February 2017 (1)

Reply January 2017 (1)

December 2016 (1)


MUBARAK says: November 2016 (1)
February 26, 2014 at 6:02 am
October 2016 (1)
Dear sir,
September 2016 (1)
could you provide
me your Email Address please August 2016 (1)

July 2016 (1)


Reply
June 2016 (1)

May 2016 (1)

Irwan Chargeman says: April 2016 (2)


August 28, 2011 at 2:44 am
March 2016 (2)
Thank you…..for info thank UUUuuuuuuuu Mr Jignesh.Parmar February 2016 (2)

Reply January 2016 (2)

December 2015 (1)

Murali says: November 2015 (1)


September 15, 2011 at 2:17 pm
October 2015 (2)
My Salute to your knowledge & your wish to share September 2015 (1)

Reply August 2015 (1)

July 2015 (1)

Ginju Thomas says: June 2015 (1)


October 28, 2011 at 7:01 am May 2015 (1)

Sir, actually during meggaring of cables the polarisation index is considered…can u give me the tabulation of April 2015 (1)
values of polarisation index
March 2015 (2)
Reply February 2015 (2)

January 2015 (2)

kameshwar mehta says: December 2014 (2)


December 11, 2011 at 3:25 pm
November 2014 (2)
thank u sir for sharing elect. notes,can u give installation of UPS,Lighting and power layout,equipment layout and
October 2014 (2)
LV wiring details.
September 2014 (2)
Reply
August 2014 (3)

July 2014 (2)


Mohammad Arif Hussain says:
June 2014 (2)
December 28, 2011 at 10:03 am May 2014 (2)

God bless you my dear really are you doing very good job keep continue Thanks, April 2014 (2)

March 2014 (3)


Reply
February 2014 (4)

January 2014 (2)


rao says:
January 18, 2012 at 11:05 pm December 2013 (1)

Thank You sir.. November 2013 (1)

October 2013 (2)


Reply
September 2013 (3)

August 2013 (3)


moahmmed akber ahmed says:
March 18, 2012 at 6:46 am July 2013 (3)

June 2013 (3)


thanks for sharing knowledge on tht net it is very beneficial for all god bless u
May 2013 (3)
Reply
April 2013 (2)

March 2013 (3)


Trajanco says:
March 19, 2012 at 9:12 am
February 2013 (2)

January 2013 (3)


Dear Sir,
December 2012 (2)
I have one question:
November 2012 (3)
Quote: Cables shall be tested for insulation resistance with an insulation tester (i.e. Megger) at 1000 Volts for 1
October 2012 (1)
minute.
September 2012 (3)
Can you please provide schematic/wiring diagram for this type of test, and also the length of the cable to measure.
August 2012 (7)
Reply
July 2012 (2)

May 2012 (7)


hussain says:
April 2012 (2)
April 3, 2012 at 6:40 am
March 2012 (3)
Dear Sir,
February 2012 (2)
thank you for these valuable information
I have the following points : January 2012 (1)
You mentioned that ” Except for New Cables, Testing at Voltage greater than 5.0KV is not permitted” how about
December 2011 (3)
VLF test.
During fault location some time you need to surge the fault to reduce its resistance , please explain. November 2011 (2)

Now HV Ac Test is using for new cables ( i.e 2Uo). October 2011 (4)
Do you have any idea for the testing of in service oil filled cable
September 2011 (2)
Reply
August 2011 (1)

June 2011 (5)


Jignesh.Parmar says:
April 3, 2012 at 2:51 pm
May 2011 (3)

April 2011 (12)


Agree with You.
In used cable more than 5KV may be damage insulation resistance of Cable. Even For new cable more than March 2011 (17)
one time HIPOT test at site is not advisable by manufacturer also (Manufacturer also do HIPOT at time of
manufacture).
We use High voltage spike to detect Fault in HT cable by Thumber but it may be affect property of Cable.
EEP

Reply

azeem says:
April 26, 2012 at 10:03 am

Dear sir,
thanks a lot, for that type of informations.
I m Azeem Electrical Officer in Karachi Electric Supply Company.
sir i have a question?
that why manufacturing fault is produce as a pin hole fault in H.T 11kv 3 core armur cables.
Ahmed says:
March 30, 2015 at 8:08 am

Is there any test for cable outer sheath

jewan seepersad says:


May 21, 2012 at 1:17 am

Very helpful and important information. Thank you!

Reply

sumesh says:
July 24, 2012 at 9:07 am Pages
tks for your good information…. i m sumesh working as an electrical engineer in a construction company Abstract

Reply Abstract of CPWD-Part 1

Abstract of IE Rules

Abstract of IS Code.
vinod says:
July 24, 2012 at 1:44 pm IS 1255

IS 15652/11171/1445/1678
Dear Sir,
IS 3043 / 5039
Hatss off to u. Hope person like can make our world more beautyfull.
IS 5613
All the very best
IS 694 / 1554 / 11892
Reply
IE Rules for DP Structure

GS says: Electrical Notes


November 7, 2012 at 2:49 am ElectRICAL. Q&A

Dear Sir, Electrical Q&A Part-1

Thank you for the excellent information, is it possible to share how frequent we should do the sheath test and Electrical Q&A Part-2

insulation test? (yearly? half yearly?) Thanks Electrical Q&A Part-3

Reply Electrical Q&A Part-4

Electrical.Tool
Tom Burnett says: EXCEL TOOL
November 12, 2012 at 3:08 pm

When performing hi-pot or better yet, megger testing, what is the closest the tester can be to the conductors that
Top Clicks
are being tested? I understand there is an approach boundary for unqualified persons, but what about the tester?
Please advise or direct me to where I can find the information. The tester manufacturers do not specify a safe electricalnotes.files.wor…
distance in their manuals. electricalnotes.files.wor…
Thanks
mediafire.com/file/5040ut…
Reply
instamojo.com/jiguparmar/…

mediafire.com/file/0qu8mt…
srinivas says:
mediafire.com/file/bkzwat…
November 20, 2012 at 1:00 pm
electricalnotes.files.wor…
thank you sir.
mediafire.com/file/vc7vfk…
its very useful

Reply
Recent Comments
Dr Mukesh Kumar on Electrical Thumb
High Voltage Testing Set says:
Rules-VENTILA…
November 24, 2012 at 9:34 am
Muhammad Mohsin Ansa… on Electrical
Thanks For Important Information Keep Sharing Thumb Rules-VENTILA…
Muhammad Mohsin Ansa… on Electrical
Reply
Thumb Rules-Light…
Muhammad Mohsin Ansa… on Quick
D.Thirunavukkarasu says:
Reference-Fire Fighting…
February 7, 2013 at 8:26 am
Nikhil Garde on Quick Reference-Fire
33kv cable single core after sheath fault repair what is the minimum sheath insultion resistance requried to Fighting…
declare fit for service.Can you please update with relavant standard J.Sridharan on Electrical Thumb Rule- High
Ri…
Reply
Muhammad Mohsin Ansa… on Electrical
Thumb Rule- High Ri…
AKHIL S M on Current Transformer
kuda says: Subhabrata Sarkar on Calculate Motor
March 12, 2013 at 3:42 pm
Pump Size

How can you test that there is no breakage on sheath for PVC(non metallic sheathed acbles) with Galvanised Muhammad Mohsin Ansa… on Calculate
steel armour wire?I need a test method that is not passing the cable through a spark tester,like testing Insulation Motor Pump Size
resistances?

Reply

prajod k says:
May 21, 2013 at 5:17 am

sir
plse give me the wiring details of meggring of 11kv armoured cble for insulation resistance test…

Reply

Jignesh.Parmar says:
May 21, 2013 at 2:15 pm

Wiring Detail!!!. Connect Megger L and E Terminal between Phase to phase and Phase to armored.. No need
for wiring diagram…for more detail read the post of “IR Value ” of this Blog..

Reply

Shehzad Rana says:


June 12, 2013 at 12:17 pm

Thanks a lot sir for share your great experience and knowledge with us really its very fruitful for me and other fresh
engineers thanks

Reply

Rahul says:
June 25, 2013 at 6:50 am

Is there any test to find out a damage on outer PVC sheath of an 11kV cable?

( In case during installation / pulling on tray a minor cut has occurred on cable which was not identified during
physical investigation )

Reply

kameswar Behera says:


July 22, 2013 at 6:00 am

how to found the resistance fault of 33KV HT cable having 300 mtr length and how to rectfy.

Reply

Juan 1120 says:


July 30, 2013 at 11:14 pm
Dear Sr. I’m in the case of receiving a new MV (72,5 kV) cable at site for installation. The client is
asking me to do a Megger test between core and screen/earth to verify the insulation resistance. I
assume the test shall be done at 10 kV, 10 min; but I would like to know the acceptace criteria for this
kind of test. The cable is completely new.

Reply

Shiekh Tariq says:


August 29, 2013 at 4:37 pm

Dear sir I have a question cable shell be tested for insulation resistance with an insulation tester 1st test we do
with 5 kV magger then the value is 5000 mo this time the cable length is 500mts then 2nd test we do then cable
length is 1000mts then value is 1500 to 2000 mo why

Reply

tanvirsarfaraz says:
September 15, 2013 at 9:54 am

sir.whn we test 11kv dead cable.From one it shows ok but from other end it shows faulty what is the reason

Reply

Desderius Luhaga says:


October 13, 2013 at 2:51 pm

Dear Sir,I have a question,I have insulation resistance test of 500v,what would be the results,would you help me to
know the governing equestion for insulation resistance test?

Reply

High voltage test set says:


October 18, 2013 at 6:52 am

I really appreciate your post and it was superb .Thanks for sharing information.
Regards

Reply

VAISHALI says:
October 19, 2013 at 4:45 am

Very useful information thanks sir.

Reply

kumar says:
December 3, 2013 at 6:02 am

thanks………

Reply

karthi says:
March 5, 2014 at 9:27 am

thanks sir its very useful to every electrical engg

Reply

MOHAMMED AZEEM says:


July 12, 2014 at 7:58 am

Thanks for it all,it,s good way for help to people.


Reply

Hayder I Khairi says:


August 18, 2014 at 10:52 am

Thanks for this information,


I am very interesting to know the standard that we based on when test insulation of cable, applied voltage and
time of test. Would you please tell me when can I find it?

Reply

Ashok Prajapati says:


November 26, 2014 at 1:20 pm

hi jigneshbhai

can u give brif detail for 11kv 630A indoor panel how to do high voltage test ?

Reply

Dhayalan.S says:
December 4, 2014 at 7:26 am

I need to test 11KV 3core 120 Sqmm cable how to test using Megger

Reply

Kamalraj says:
March 25, 2015 at 1:22 am

sir how do hi-pot test for enamoured 132kV single core cable

Reply

vignesh says:
March 25, 2015 at 1:29 am

how to do hi-pot test for 138kv outer sheeth for xple cable

Reply

Lakshmi kanth says:


March 28, 2015 at 6:58 am

Tank you

Reply

abdul waheed says:


April 10, 2015 at 12:07 pm

respect sir

i have one question ?? give me cable formula according to load

ex ,,maximum demand is 500 amps incoming supply if i use copper cable how can i measure if i use aluminium
cable how can i measure exact formula i want can send me please sir ( cable 3phase )

Reply

medy says:
June 5, 2015 at 11:00 pm

Thanks

Reply
Kay Ido says:
June 18, 2015 at 7:14 am

Sir. If i use high voltage cable for low voltage load, what would be the implication?

Reply

Sunil says:
July 9, 2015 at 6:49 pm

Good method for clear the topic.

Reply

Prasanth Nair says:


August 22, 2015 at 4:22 am

Sir,
I am an Electrical Engineer working in Kerala. I need an advice on the Testing of wires used for Low voltage and
High voltage. As per Indian standards what all tests are to be done to assess the quality of wires/cables. Thanks
for the consideration

Reply

kapil says:
August 31, 2015 at 10:26 am

33kV – no TF’s connected 5kV Megger 1 minute 1000 meg-ohms.

33kV – with TF’s connected 5kV Megger 1 minute 15 meg-ohms.

What is “TF” ?

thanks.

Reply

subhash champaneri says:


September 11, 2015 at 6:47 pm

How to test cable Armour healthy


continuity in loading condition ?

Reply

arundas says:
December 27, 2015 at 11:52 am

sir
can you tell me how to measure the insulation test of 240 sq mm single core cable .please provide one example

thank you

Reply

md.faisal says:
December 31, 2015 at 5:25 am

i have doubt on insulation resistance test. why the values are in mega ,giga ohms.

Reply

Vusi says:
February 26, 2016 at 4:14 am
What is the minimum and maximum pressure testing voltage on a new installation of xlpe cable at 11kv using a AC
pressure tester . ?

Reply

sukumar Bhattacharya says:


March 23, 2016 at 7:58 pm

Thank you so much sar for the information

Reply

john says:
April 4, 2016 at 7:24 am

Dear Sir,
There is any calculation formula for to calculate acceptable leakage current while applying high voltage test for
medium voltage lead sheathed cables.
what is the criteria?

Reply

Chandrakant Ghan says:


April 11, 2016 at 1:36 pm

Chandrakant Ghan
Dear Sir, You have not coverd FRLS (Fire resistant Low smoke cables) in your main types of cabales. Rest of
course as per your normal practice EXCELLENT!

Reply

Srimanta Banerjee says:


May 10, 2016 at 6:19 am

Dear Mr. Parmar,

I was looking for HV cables sheath integrity test criteria and range etc, and found your article.

Thanks for your write -up covering the details of cables test.

In one of our new project installation we found Outer Sheath Insulation Resistance is less than .5 M Ohm for 11kV
Cables and pretending some cable sheath damage could be.

While referring the IEC cl. associated with Sheath test, noted that the requirement is after applying 4kv/mm or
maxi, 10kv for 1 minute and to check “” No breakdown of the over sheath shall occur during the test”.

Is there any definition of Breakdown ?? What does it mean ? orcan you please advise on the reference in your
write up under cl no. “Outer Sheath Insulation Resistance (Screen wire test)” for 11kV/33 kV XLPE cables ..

Many thanks in advance.

Reply

nitin says:
June 14, 2016 at 2:48 am

how to check HT/MV cable is dead or live we dont have drawing

Reply

Sankeerthan says:
July 5, 2016 at 8:53 am

Dear Sir,
Kindly provide me the applicable IEC standards for the above mentioned tests.
Thank You in advance

Reply
William Wilima says:
September 11, 2016 at 5:13 pm

We are glad to know about your company and what you are able to do. We are are urgently looking for Voltage
Detectors for immediate purchase.

We are a Zambian Company based in Ndola dealing in electrical supplies. We wish to urgently purchase 20 Live
line testers which can work for 11, 33 and 66 kV, switchable, for our client. Kindly give us your best quote.

Description:
TYPE
1. With Housing made of polycarbonate with high mechanical properties and dielectric strength.
2. Supplied with insulated switch stick, extendable to 12.5m height or more
3. With universal tool end for test on Overhead Power Lines
VOLTAGE: 11/33/66 kV switchable
INDICATION:
Double signaling; extremely bright red light signfying presence of voltage and powerful rated audible signal >60
dB/2meters or Equivalent
SELF TESTING
Test Button when pressed a timed green LED lights to indicate detector is operational and the self-testing of the
unit continues or equivalent.
POWER SUPPLY
1. Rechargeable Battery
2. With Portable Battery charger
END FITTING: Universal Stick type
TEMPERATURE: -1 to 40 degrees Celcius
ALTITUDE ABOVE SEA LEVEL: 1400m
SUPPLIED WITH: Carrying case, Batteries and two contact electrodes
APPLICABLE STANDARD: IEC/BS/SANS/EN
PREVIOUS TYPE TEST REPORT: YES

ROUTINE TESTS CERTIFICATE: YES

I shall be very glad if before the end of tomorrow, Monday we can reach a conclusion whereby we can have the
quote and Pictures plus copies of Test Certificates, sent to us.

The quote may be CIF Ndola, Zambia.


Waiting to hear from you.

Reply

Mohammed Yousuf Ahmed N says:


October 23, 2016 at 10:24 pm

Thanks To Jinesh Excellent Result shown by Jinish I am satisfied from Your Answer ,I am Instrumentation Projects
Engineer Construction Al Jubail KSA,We are use this type cable in Oil & Gas Company in KSA

Reply

Care Labs says:


December 4, 2016 at 9:48 am

Really a great support for the megger testing work. This like blogs will really touch with the importance.

Reply

Haydar says:
December 29, 2016 at 8:47 am

why do we use 5KV for testing 11kv cable ?


shouldn’t be use more then how much it carry ?
for example we use 500v for IR test of 400v LV cable

Reply
Wahid says:
January 31, 2017 at 6:24 pm

Sir wich insulation tester better for meggering. Name plz i want 2 go buy now.

Reply

Katerita Tairati says:


August 3, 2017 at 10:21 pm

Sir If the result gives you a greater than 1 mega Ohm between all phases and neutral + earth(Megger results), so
if you put back the cable on the main source and check the voltages which is 240V but if you go and check the
other end which is 50V. SO please what happen to that fault?

Reply

Sunil Kumar Yadav says:


August 19, 2017 at 6:55 pm

Good work ht power work

Reply

Raul says:
September 10, 2017 at 10:41 am

Hi Sir!

Sir, it is still safe for me to energize my project despite a poor result of megger testing? The reading is just 0.50
mega ohms.

Reply

Leave a Reply

Enter your comment here...

This site uses Akismet to reduce spam. Learn how your comment data is processed.