Вы находитесь на странице: 1из 8

Synchronization Methods for Three Phase Distributed Power Generation Systems.

An Overview and Evaluation

Adrian Timbus, Remus Teodorescu and Frede Blaabjerg Marco Liserre


Institute of Energy Technology Polytechnic of Bari
Aalborg University Dept. of Electrotechnical and Electronic Eng.
DK-9220 Aalborg, Denmark 70125-Bari, Italy
Email: avt@iet.aau.dk, ret@iet.aau.dk, fbl@iet.aau.dk Email: liserre@poliba.it

Abstract— Nowadays, it is a general trend to increase the elec- lower production cost. Actually, a large interest is payed on PV
tricity production using Distributed Power Generation Systems systems based on organic materials. One type of organic device
(DPGS) based on renewable energy resources such as wind, is the dye sensitized solar cell which uses an organic dye to
sun or hydrogen. If these systems are not properly controlled,
their connection to the utility network can generate problems on absorb the solar radiation and generate electronic carriers [1].
the grid side. Therefore, considerations about power generation, Fuel-cell technology is also under many companies and
safe running and grid synchronization must be done before governmental interest as an alternative energy source and this
connecting these systems to the utility network. This paper is is mainly due to its potential of high efficiency (around 70%)
mainly dealing with the grid synchronization issues of distributed which is higher related to the wind energy transformation
systems. An overview of the synchronization methods as well as
their major characteristics is given. New solutions to optimize (around 45%) and photovoltaic (around 20% using the new
the synchronization methods when running on distorted grid technologies of polycrystalline silicon wafers) [1].
conditions are discussed. Simulation and experimental results Due to the increased number of distributed power systems
are used to evaluate the behavior of the synchronization methods connected to utility network, instability of the these system and
under different kind of grid disturbances such as voltage dips, of the grid itself can occur. As a consequence, new and more
harmonics and notches.
Index Terms— Distributed Generation Systems, renewable en- stringent standards are issued in respect to power distribution.
ergy, grid synchronization, Phase-Looked Look (PLL), voltage One of the most important issue of the DPGS connected to
dips, notches the utility network is the synchronization with the grid voltage
vector. The synchronization algorithm mainly outputs the
I. I NTRODUCTION phase of the grid voltage vector. The phase angle of the utility

T HE worldwide economy is mainly running on fossil


fuels which is largely recognized as a major cause of
environmental problems. As a consequence, an overall growth
voltage is a critical piece of information for grid connected
systems. This information can be used to synchronize the
turning on/off of the power devices, calculate and control
in alternative energy generation technologies and markets has the flow of active/reactive power or transform the feedback
been registered in the last decade. The demand for alternative variables to a reference frame suitable for control purposes
and renewable energy generation systems has been growing [4].
about 25% per year. This is mainly due to a general increasing The content of this paper describes the structures and
demand for electricity, a rising interest in clean technologies main characteristics of grid synchronization algorithms used
and the saturation of oil resources [1]. for distributed generation systems. An evaluation in terms
Among the renewable energy sources (RES), the wind of precision of estimating the grid voltage angle as well as
energy knows the largest utilization nowadays. The wind influence of the grid disturbances on this precision will be
potential in some countries like Denmark, Germany, Spain, US given. Capability of the algorithms to keep synchronization
led to a large interest and fast development of wind turbines over short grid faults will be discussed as well. It has to
technology in the last decade. Today, a total capacity of 39294 be mentioned here that only three phase systems are under
MW wind power is installed around the world, with 8133 MW investigation.
installed in 2003 only [2].
Another renewable energy technology which gains accep- II. G RID SYNCHRONIZATION METHODS FOR THREE PHASE
tance as a way of maintaining and improving living standards DPGS
without harming the environment is the photovoltaic technol- Among the literature papers for grid synchronization of
ogy. The annual number of PV installations knows an increas- distributed generation systems, a few methods are noticed.
ing growth, mainly due to the government or utility companies, In the following, an overview of their structure and main
that support programs which focus on grid connected PV characteristics are given.
systems [3]. The advances in solar cell technology also sustain
this continuous growth of PV systems. Most systems today A. Zero crossing method
use sliced crystalline or polycrystalline silicon wafers that can One of the simplest methods for obtaining the phase infor-
have an efficiency up to 20 % but with the pay of quite large mation is to detect the zero crossing of the utility voltages
production cost. A new trend in this field is the production of [5]. However, the zero crossing points can only be detected
ribbon silicon which can have the same efficiency but with a at every half cycle of the utility voltage frequency; thus the

0-7803-9033-4/05/$20.00 ©2005 IEEE. 2474


Ua abc Uα αβ Ud dq Uα Uα
DSC θ
Ub atan Ua abc Uα
Uβ Uq Uβ U θ
Uc αβ dq DSC αβ Ub Uβ
RF
U= U 2α + U 2β atan
Uc αβ
θ θ
RF Uβ
U

(a) (b)
Fig. 1. Synchronization method using (a) filtering on the dq synchronous rotating reference frame and (b) filtering on αβ stationary frame.

dynamic performance of this technique is quite low. Hence, its C. dqF ilter algorithm
discussion has been considered less relevant for this overview. Another synchronization algorithm, this time implemented
B. αβ Filter algorithm in the dq reference frame is shown in Fig. 1(a). Since the Ud
and Uq voltage components are dc variables, more filtering
The phase angle of the utility grid voltage can also simply techniques can be applied to obtain clear signals, i.e. notch
be obtained by filtering the input signals, i.e. the three phase
filter, low-pass filter, band-stop filter, etc. [10].
voltages (Ua , Ub , Uc ). Depending on the reference frame where
In this work, the delay signal cancellation method described
the filtering is applied, two structures can be obtain: in [10] and [11] is used. When applied to αβ reference frame,
• filtering in αβ stationary reference frame the method is described by:
• filtering in dq synchronous rotating reference frame  
Fig. 1(b) depicts one way to obtain the phase angle of αβ αβ αβ
epos (t) = 0.5 · e (t) + je (t − T /4) (1)
the utility network in stationary reference frame. After the  
three phase voltages are transformed in αβ reference frame eαβ αβ
(t) − jeαβ (t − T /4) (2)
neg (t) = 0.5 · e
using a proper matrix transform, filtering is applied for both
components of the grid voltage. In [6], different filter types where T is the period of the fundamental frequency. The
such as low pass filter, notch filter, space vector filter, etc. method implies a delay with T /4 of the signals which makes
are investigated and their effectiveness when implemented in the method vulnerable if the fundamental frequency experience
a stationary reference frame is discussed. It is well known that variations due to different grid faults. Experimental results will
using filtering, delays will be introduced in the signal which validate this later.
is unacceptable in the case of grid voltage angle; therefore a
proper filter design has to be made. An other alternative, as D. dqP LL
suggested in [7], is to compensate for the filter delay. A PI The third method for synchronization is the phase locked
controller, monitoring the q component of the voltage can be loop (PLL) technique. The PLL can be defined as a device
used to correct the displacement introduced by the filter. One which causes one signal to track another. It keeps an output
more method can be the use of band-pass filters as explained signal synchronizing with a reference input signal in frequency
in [8] and [9]. In order to obtain satisfactory results under the as well as in phase [12].
unbalanced grid conditions, the authors implemented a “wave A common structure for grid synchronization used nowa-
shaping and normalization module” which keeps the α and β days [4], [13], [14], [15] and [16], is the phase locked
components of the voltage sinusoidal and in quadrature. loop implemented in dq synchronous reference frame and its
In this paper, a resonant filter is proposed to be used to filter schematic is illustrated in Fig. 2(a).
the αβ voltages. The resonant filter has a similar characteristic As it can be noticed, this structure uses the coordinate
as a band-pass filter but is not introducing delay. transformation form abc → dq and the lock is realized by

PLL controller
ωff

Loop Filter
+ VCO U θ
Ua Voltage observer Phase observer
Vd* + + ω θ
1/s
PI

Vd dq αβ Ua
Ub
Vq αβ abc Uc Frequency observer ω

Transformation module

(a) (b)
Fig. 2. (a) General structure of dq PLL method and (b) adaptive PLL comprising a voltage observer, a frequency observer and a phase angle observer.

2475
setting the Vd∗ to zero. A regulator, usually PI, can be used The time domain transfer function of the dqP LL system
to control this variable and the output of this regulator is the depicted in Fig. 2(a) can be derived as:
grid frequency. After the integration of the grid frequency, the Kp
Kp · s +
utility voltage angle is obtained, which is fed back into the H(s) = Ti
(3)
Kp
αβ → dq transformation module in order to transform into s2 + K p · s + Ti
the synchronous rotating reference frame.
This expression is similar to the standard second order transfer
This structure of PLL consists of two major parts, the function having a zero:
phase detection and the loop filter. The phase detection can be
readily implemented by using abc → dq transform in the three 2ζωn · s + ωn2
G(s) = (4)
phase system. On the other hand, the loop filter determines s2 + 2ζωn · s + ωn2
the dynamics of the system. Therefore, the bandwidth of the therefore the controller gains can be derived from (3) and (4)
filter is a trade off between the filtering performance and the as follows:
time response. As a consequence, parameters of the loop filter 9.2 Ts ζ 2 4.6
have a significant influence on the lock quality and the PLL Kp = , Ti = , where ωn = (5)
Ts 2.3 ζTs
dynamics.
Considering a damping factor ζ = 0.707, which should
give an overshoot of 5% in the case of step response [19],
E. Adaptive PLL
and selecting a desired settling time of Ts = 0.02, the step
A more advanced PLL structure, based on adaptive algo- response and Bode diagram of (3) is shown in Fig. 3.
rithm is presented in [17] and it is shown in Fig. 2(b). The As it can be noticed from the Fig. 3(a), the overshoot is
author suggests that three PLL systems (one for each phase) increased to 20% and this is due to the zero exhibited by the
will have better performance than one common system for all transfer function in (3), which is neglected when doing the
phases. The adaptive PLL consists of three control units that design. In order to eliminate this effect, a compensator (lag
individually control the frequency, phase angle and voltage term) can be introduced in the loop [20]. The step response
magnitude. The disadvantage of this structure can be the large of the system having the compensator term included is shown
algorithm necessary to implement (3x3 controllers) and the with dotted line in Fig. 3(a). As it can be observed, the effect of
fact that controllers involve a moving average algorithm that the compensator diminishes the overshoot to 5%, maintaining
is computationally heavy but very precise. Anyway, one of the the imposed settling time of the system. From the Bode plot
advantages is that it provides the information about each phase shown in Fig. 3(b), for the case with and without compensator,
amplitude, frequency and phase. This issue makes this method
suitable for grid monitoring, and thus islanding detection and Step Response
safety improvement.
1.2

1
III. D ESIGN OF THE dqP LL SYSTEM
Amplitude

0.8
The PLL system, when used for grid connected applications, 0.6
can be influenced by the distortions taking place in the utility 0.4
network [4], [10], [16], [18]. As noticed, the synchronization without compensator
0.2
algorithm dynamic is closely related to the bandwidth of its with compensator
filter. As a consequence, a low dynamic filter will produce 0
0 0.005 0.01 0.015 0.02 0.025
a very filtered and stable output but with a longer synchro- Time (sec)
nization time. On the other hand, a design for fast dynamics
(a)
will produce an output which is able quick to synchronize to
Bode Diagram
the input but distortions in the input signal will pass through 20
Magnitude (dB)

the filter and become part of the output signal. Therefore, 0


when designing a synchronization system, one should be aware −20
of the purpose of this system. If the algorithm is only used −40
for synchronizing the control variables to the utility voltage
−60
0
vector in order to have a precise synchronization necessary
Phase (deg)

−45
for control, then a slow dynamic algorithm can be used. If the
−90
synchronization algorithm is employed in grid monitoring (to
−135
detect grid faults), a fast dynamic system needs to be used.
−180
In the following, a tuning method for the dqP LL controller 10
0 1
10 10
2 3
10
is given. The method gives access to the settling time Ts and Frequency (Hz)
damping ratio ζ of the system. Thus, one can design a low (b)
dynamics or fast dynamics system by accordingly selecting
these two parameters. The tuning method is derived from the Fig. 3. (a) Step response and (b) Bode plot of the dqPLL system with and
transfer function of dqPLL shown in Fig. 2(a). without a lag compensator.

2476
TABLE I
it can be concluded that both systems have considerably phase
P ROPAGATION OF VOLTAGE DIPS THROUGH ∆/Y TRANSFORMER .
margin in order to ensure system stability.
IV. G RID FAULTS Fault type Dips seen at bus 1 Dips seen at bus 2
3 phase fault type A type A
No matter how stiff the transmission and distribution system 1 phase fault type B type C
is, grid faults can occur due to different reasons. As the 2 phase to ground type E type F
synchronization algorithms used by the distributed systems phase-to-phase type C type D
have the grid voltages as input, it is expected that the grid
faults will have a significant influence on the behavior of the
Due to the use of abc → αβ transformation module in the
synchronization algorithms.
synchronization algorithms, which is only valid for symmet-
Considering the distributed system connected to the utility
rical systems, it will be interesting to observe the behavior of
network as shown in Fig. 4, the grid behavior due to the short
these algorithms under different kind of unsymmetrical faults.
circuit faults should be discussed.
Transformer V. E XPERIMENTAL SYSTEM
Distributed In order to test the PLL structures and observe their behavior
generation under different grid conditions, an experimental system was
system Zg
bus 2
Grid
built in laboratory, as shown in Fig. 6.

Zf Transformer
fault bus 1 DC power PWM
supply inverter
Fig. 4. Distributed system connected to the utility network using a ∆/Y sa sb sc
ia ib ic Ua Ub Uc
Grid
transformer. Current abc
PLL Local
controller αβ load
i iβ θ
− α
Assuming a grid fault taking place at the bus 1, the voltage i*
α id*
− i*β αβ
here will be directly proportional to the grid (Zg ) and the dq iq*

fault impedance (Zf ). Moreover, if the X/R ratio of the two Fig. 6. Schematic of the experimental system used for testing.
impedances differs, the voltage will also experience a phase
jump [21]. It has been analyzed in [22] that usually six types The system comprises the PWM inverter supplied by a DC
of faults can occur due to the short circuit fault. These faults power source which ensures the DC-link voltage necessary for
are graphically expressed in Fig. 5. the application. The connection to the grid is made through
an isolation transformer. The three phase voltages are sampled
Ub Type C
Ub Type A Ub Type B and used by the synchronization algorithm which provides
Ub dip Ubdip
the grid voltage vector angle. Using this angle, the reference
Ub dip
currents in the stationary reference frame are constructed using
Ub
Ub

Ua Ua Ua
Ua dip Ua dip Ua dip a dq → αβ transformation module. In this way, the control of
Ucdip Ucdip Ucdip
active and reactive current reference is ensured. The sampled
Uc Uc Uc
phase currents are transformed into αβ reference frame as
well and subtracted from their reference. The resonant current
(a) (b) (c) controller implemented in stationary reference frame controls
Ub Type D Ub Type E Ub Type F the input error to zero and sets the PWM pattern for the
Ubdip inverter.
Ub
Ub dip Ubdip

Ua Ua Ua VI. E VALUATION OF THE SYNCHRONIZATION


Ua dip Uadip Ua dip ALGORITHMS
Ucdip
Ucdip Ucdip In the following, an evaluation of the synchronization al-
Uc Uc Uc gorithms described above is made. The following tests, since
they are most common to occur in the utility network, were
(d) (e) (f) chosen to be done:
Fig. 5. Classification of voltage dips due to short circuit. Solid lines represent
• 6% total harmonic distortion (THD) of the grid voltages
the voltage before the dip and dotted lines represent the voltage after the dip.
• 30% notches

If the distributed system is connected to the utility network • 30% voltage dip type A

through the standard distribution transformer ∆/Y , the voltage • 40% voltage dip type C

dips at bus 2 are as listed in Table I. In order to achieve all the disturbances in the grid voltages, a
In Fig. 5 it can be noticed that only three of the grid faults grid power simulator, e.g. California Instruments has been used
are symmetrically (1200 shifted), the other three, i.e. C, D, F in laboratory setup. The grid simulator can be controlled from
experiencing both amplitude and phase variations. Moreover, the computer and voltage dips, sags, harmonics or frequency
from Table I it can be observed that only one fault out of four shift can be programed to appear in the outputted waveforms.
is symmetrical at bus 2. Anyway, in case of voltage dip type C, simulations results are

2477
Grid voltages having 6% THD Phase angle estimation of αβFilter algorithm
400 7
6
200
Amplitude [V]

Theta [rad]
0 4
3
−200 2
Ua
Ub 1
−400 Uc
0
0.01 0.02 0.03 0.04 0.05 0.06 0.01 0.02 0.03 0.04 0.05 0.06
Time [sec] Time [sec]

(a) (b)

Fig. 7. The behavior of αβF ilter algorithm under 6% THD of the utility grid: (a) the voltage waveforms and (b) estimation of the phase angle.

provided since the grid simulator is not able to create phase high power switching devices (mostly thyristors) are running,
shift of the output voltages. notches can appear into the grid voltages. Thus, it is worth to
Since the adaptive PLL is implemented for each phase, investigate the behavior of synchronization algorithms under
some of the above listed test, will not have a big influence such conditions.
on its behavior. Moreover, this algorithm is able to estimate The grid simulator has been programmed to output the
the voltage amplitude, its frequency and its phase. As a grid voltages as shown in Fig. 8(a). Since notches have even
consequence, the adaptive PLL will be investigated separately. higher frequencies than the harmonics inserted in the previous
test, a proper behavior of the synchronization algorithms is
A. Harmonics test expected. As it can be observed in Fig. 8(b), the αβF ilter
As mentioned above, 6% THD of the voltage has been set algorithm provides a clean synchronization signal. Similar
for the harmonic test. As a consequence, the voltage input into behavior has been registered in the case of dqP LL having
the synchronization algorithms look as shown in Fig. 7(a). again a settling time of 0.2 seconds. In Fig. 8(c), the output
Since all algorithms make use of a filter in one way or of dqF ilter is shown. Small oscillations can be observed
another, it is expected that the harmonics content shown in in the synchronization signal. This is caused by the settings
Fig. 7(a) to be filtered out. In Fig. 8(c), the output of the of notches to occur close to zero crossing, modifying the
αβF ilter algorithm is shown. As expected, the resonant filter fundamental period. The Delay Signal Cancellation (DSC),
only pass through the 50 Hz component of the grid voltages, which uses a fixed delay of T /4, is not able to reject the
a clean synchronization signal being provided. The other two oscillation due to the disagreement of the fundamental period
algorithms, i.e. dqF ilter and dqP LL behave similarly. It has of the two signals it compares. As an alternative to the DSC
to be mentioned here that for the dqP LL system, a settling used for filtering purposes here, other types of filters can be
time of Tset = 0.2 seconds has to be set inside the PI controller used as suggested in [6].
in order to be able to filter out the harmonics. A drawback in
this case will be the low dynamics of the system. C. Voltage dip type A
As described in §IV, the type A voltage dip manifests a
B. Notches test suddenly drop in voltage magnitude in all three phases at the
It is not likely that the utility network is always polluted same time. No phase or frequency variations take place during
by notches, but when a distributed system is connected in this type of dip. In Fig. 9(a), the grid voltages register a 30%
the immediate vicinity of an industrial park, where lots of amplitude drop. Since the resulting voltages are still balanced

Grid voltages having 30% notches Phase angle estimation of αβFilter algorithm Phase angle estimation of dqFilter algorithm
400 7 7
6 6
200
5
Amplitude [V]

5
Theta [rad]
Theta [rad]

0 4 4
3 3
−200 2 2
Ua
Ub 1 1
−400 Uc
0 0
0 0.01 0.02 0.03 0.04 0.05 0.06 0 0.01 0.02 0.03 0.04 0.05 0.06 0 0.01 0.02 0.03 0.04 0.05 0.06
Time [sec] Time [sec] Time [sec]

(a) (b) (c)


Fig. 8. The behavior of dqF ilter and αβF ilter filtering algorithm with 30% notches distortion of the utility grid.

2478
Type A grid fault Phase angle estimation of dqPLL algorithm
400 7
6
200
5
Amplitude [V]

Theta [rad]
0 4
3
−200 2
Ua
Ub 1
−400 Uc
0
−0.02 0 0.02 0.04 0.06 −0.02 0 0.02 0.04 0.06
Time [sec] Time [sec]

(a) (b)

Fig. 9. The behavior of dqP LL under 30% type A voltage dip: (a) grid voltages and (b) phase angle estimation.

(120o shifted), no negative sequence is appearing in the line of α and β voltages are occurring. This difference will produce
voltages. This makes the synchronization algorithms to behave variations in the synchronization signal. This issue can be
normally, all of them producing a clean output signal (e.g. avoided by iterating the algorithm few times, as it is explained
dqP LL output shown in Fig. 9(b)). in [8] and [9].
D. Voltage dip type C E. Testing the adaptive PLL
This type of fault is maybe the most demanding one for Due to the different structure and behavior of the adaptive
the synchronization algorithms. Beside the amplitude drop in PLL, this is treated separately. The first major difference
two of the grid phases, these will also suffer a phase shift. between this algorithm and all the previous ones presented is
To simulate this situation, the amplitude of b and c phases are that the adaptive PLL is implemented for one phase. Therefore,
diminished 40% of their nominal value and a phase shift of 30 in a three phase system, three such algorithms have to be
degrees is registered for both these phases. The resulting grid implemented in order to synchronize the injected currents
voltages are shown in Fig. 10(a) and the output of the dqP LL with their corresponding grid voltages. Of course, there is
system in Fig. 10(b). As it can be observed, the low dynamics possibility to implement only one algorithm and then shift the
of the PI controller is able to filter out the negative sequence obtained phase angle with 120 and 240 degrees respectively,
of the d axis voltage, keeping the system synchronized with in order to obtain the phase angle for the other two voltages.
the positive sequence of the voltages. The power factor of the Anyway, when the grid become slightly unbalanced, the unity
system will not be unity anymore under the fault but the great power factor of the distributed system will be lost, thus this
advantage is that if the grid recovers, the dqP LL is able to solution in not recommended. Fig. 11 depicts a possible way
resynchronize the system with the positive sequence of the grid of using the adaptive PLL in a three phase control structure
voltages. This issue provides the distributed system with the of the DPGS.
so called ride through capability. Similar behavior has been As it is mentioned above, the adaptive PLL is able to track
noticed for the dqF ilter algorithm. the amplitude of the grid voltage, its frequency and its phase.
In Fig. 10(c), the synchronization signal of the αβF ilter In the tests below, simulation results for only one phase are
algorithm is shown. As it can be noticed, this fails to provide a presented.
clean signal. The 100 Hz frequency of the negative sequence is Since the adaptive PLL is implemented for each phase the
filtered out by the resonant filter but differences in amplitudes effect of unbalance should be minimal in this case. As a

Type C voltage fault Angle estimation of dqPLL Angle estimation of αβFilter algorithm
400 7 7
6 6
200
5
Amplitude [V]

5
Theta [rad]

Theta [rad]

0 4 4
3 3
−200 2 2
Ua
Ub 1 1
−400 Uc
0 0
0.18 0.2 0.22 0.24 0.26 0.18 0.2 0.22 0.24 0.26 0.18 0.2 0.22 0.24 0.26
Time [sec] Time [sec] Time [sec]

(a) (b) (c)

Fig. 10. Dip fault type C: (a) the grid voltages, (b) the output of dqP LL and (c) output of αβF ilter algorithm.

2479
Isolation TABLE II
transformer
DC power PWM
C OMPARISON OF THE PRESENTED SYNCHRONIZATION ALGORITHMS .
supply inverter
Ua Ub Uc
sa sb sc ia ib ic Grid
Current PLL PLL PLL Local
Algorithm Strong points Weak points
controller
θa θb θc
load dqF ilter simplicity on frequency shift

ia* (with DSC) variations
sin

ib* sin αβF ilter simplicity on unbalanced grid
− ic*
sin
dqP LL works on every grid type, slow dynamics
provides ride through
Fig. 11. Possible use of the adaptive PLL in a three phase control structure. capability
adaptiveP LL estimates amplitude,
frequency and phase angle complex structure
consequence, in order to test this structure, the following fault
was created (Fig. 12(a)):
systems. The ability of the synchronization algorithms to over-
8% THD in the grid voltages was set
come the grid fault and provide a clean synchronization signal

70% voltage drop at time instant 0.5 s
is closely related to its filter design. Filtering methods already

30o phase shift at the same time instant
existing in the literature as well as new filter procedures such

As can be noticed in Fig. 12(b), the voltage observer needs as resonant filters have been introduced and described.
one and a half fundamental periods to correctly detect the A controller design in the case of dqP LL have been made
voltage dip taking place in the utility network. This is fast in a way that gives access to the dynamics of the system. The
enough according to the grid codes for wind turbines as algorithms have been tested under different grid conditions
described in [23]. In Fig. 12(c), the phase observer response to and the results are commented.
the fault conditions is shown. Its output is able to follow the As a result of the experimental tests, the dqF ilter algorithm
new phase angle of the grid voltage within 0.35 seconds. The using delay signal cancellation has problems when the grid
overshoot occurring during the fault is due to the interaction frequency varies, as was the case in the notches test. Anyway,
of all three controllers of this structure, i.e. voltage controller, using another filter may improve the situation.
frequency controller and phase controller. If these controllers In order to properly work under unbalanced grid conditions,
are designed slower, the overshoot will be reduced but also the αβF ilter necessitates few iterations of the normalizing
a slower dynamic will be achieved. This will influence on and wave shaping stage.
the detection time of the grid variables, exceeding maybe the The low dynamic designed dqP LL and adaptive PLL prove
standard demands in the field. to overcome all the test conditions. This make them suitable
In Table II, a comparison in respect to the robustness for grid connected applications, such as wind turbines, PV or
and simplicity of the presented synchronization algorithms is fuel cell systems.
done. It can be concluded that some of the simple algorithms
can experience problems when running on different kind of R EFERENCES
distorted grid. Having a proper tuning, the more complex [1] J. P. Lyons and V. Vlatkovic, “Power Electronics and Alternative Energy
Generation,” Proc. of PESC’04, Achen, Germany, pp. 16–19, 2004.
structures manage to keep synchronization even when the grid [2] EWEA, “www.ewea.org/documents,” Online Documentation, March
is severely distorted. 2004.
[3] M. Shahidehpour and F. Schwartz, “Don’t Let the Sun Go Down on PV,”
IEEE Power & Energy Magazine, vol. 2, no. 3, pp. 40–48, May/June
VII. C ONCLUSION 2004.
[4] V. Kaura and V. Blasko, “Operation of Phase Loop System Under
This paper gives an overview of the synchronization al- Distorted Utility Conditions,” IEEE Trans. on Industry Applications,
gorithms and their structure for grid connected distributed vol. 33, no. 1, pp. 58–63, 1997.

Grid voltage on one phase Grid voltage estimation Phase observer response
1.5 1.5 60
Phase shift [degrees]

1 1 50
Magnitude [p.u.]

Magnitude [p.u.]

0.5 0.5 40

0 0 30

−0.5 −0.5 20
θ
10 ref
−1 −1 θ
PLL
0
−1.5 −1.5
0.45 0.5 0.55 0.6 0.45 0.5 0.55 0.6 0.5 0.6 0.7 0.8 0.9 1
Time (s) Time (s) Time (s)

(a) (b) (c)

Fig. 12. Adaptive PLL behavior under the fault: (a) 8% THD of grid voltages, (b) voltage estimation, and (c) phase angle detection.

2480
[5] F. M. Gardner, Phase Lock Techniques. New York: Wiley, 1979.
[6] J. Svensson, “Synchronization Methods for Grid-Connected Voltage
Source Converters,” IEE Proceedings in General Transmission Distri-
bution, vol. 148, no. 3, pp. 229–235, 2001.
[7] C. Klumpner, M. Liserre, and F. Blaabjerg, “Improved Control of
an Active-Front-End Adjustable Speed Drive with a Small DC-link
Capacitor under Real Grid Conditions,” Proc. of PESC’04, vol. 2, no.
1156-1162, 2004.
[8] H. Kim, S.-J. Lee, and S.-K. Sul, “Reference Wave Generator in
Dynamic Voltage Restorers by use of PQR Power Theory,” Proc. of
APEC’04, vol. 3, pp. 1452–1457, 2004.
[9] S.-J. Lee, H. Kim, S.-K. Sul, and F. Blaabjerg, “A Novel Control
Algorithm for Static Series Compensators by use of PQR instantaneous
Power Theory,” IEEE Trans. on Power Electronics, vol. 19, no. 3, pp.
814–827, 2004.
[10] G. Saccomando and J. Svensson, “Transient Operation of Grid-
connected Voltage Source Converter Under Unbalanced Voltage Con-
ditions,” Proc. of IAS’01, vol. 4, pp. 2419–2424, 2001.
[11] H. Awad, J. Svensson, and M. J. Bollen, “Tuning Software Phase-Locked
Loop for Series-Connected Converters,” IEEE Trans. on Power Delivery,
vol. 20, no. 1, pp. 300–308, 2005.
[12] G. Hsieh and J. Hung, “Phase-Locked Loop Techniques - A Survey,”
IEEE Trans. on Industrial Electronics, vol. 43, no. 6, pp. 609–615, 1996.
[13] S. Chung, “A Phase Tracking System for Three Phase Utility Interface
Inverters,” IEEE Trans. on Power Electronics, vol. 15, no. 3, pp. 431–
438, 2000.
[14] S.-K. Chung, “Phase-locked Loop for Grid-Connected Three-Phase
Power Conversion Systems,” IEE Proceedings on Electronic Power
Applications, vol. 147, no. 3, pp. 213–219, 2000.
[15] L. N. Arruda, S. M. Silva, and B. Filho, “PLL Structures for Utility
Connected Systems,” Proc. of IAS’01, vol. 4, pp. 2655–2660, 2001.
[16] S. Lee, J. Kang, and S. Sul, “A New Phase Detection Method for
Power Conversion Systems Considering Distorted Conditions in Power
System,” Proc. of IAS’99, vol. 4, pp. 2167–2172, 1999.
[17] D. Jovcic, “Phase Locked Loop System for FACTS,” IEEE Trans. on
Power Systems, vol. 18, no. 3, pp. 1116–1124, 2003.
[18] H. Song, H. Park, and K. Nam, “An Instantaneous Phase Angle
Detection Algorithm under Unbalanced Line Voltage Condition ,” Proc.
of PESC’99, vol. 1, pp. 533–537, 1999.
[19] G. F. Franklin, J. D. Powell, and A. Emami-Naeini, Feedback Control
of Dynamic Systems – Third Edition. Addison Wesley, 1995.
[20] W. Leonhard, Control of Electric Drives. Springer, 1996.
[21] G. Saccomando, J. Svensson, and A. Sannino, “Improving Voltage
Disturbance Rejection for Variable-Speed Wind Turbines,” IEEE Trans.
on Energy Conversion, vol. 17, no. 3, pp. 422–428, 2002.
[22] M. H. J. Bollen, Understanding Power Quality Problems: Voltage Sags
and interruptions. IEEE Press, 2002.
[23] J. Matevosyan, T. Ackermann, S. Bolik, and L. Söder, “Comparison
of International Regulations for Connection of Wind Turbines to the
Network,” Proc. of NPWC’04 (CDROM), 2004.

2481

Вам также может понравиться