The following presentation gives step by • Practical Test 1: Function Key LED 3
step instructions to 3 practical examples
with Reyrolle protection relays. • Practical Test 2: Reverse Interlocking 33
The examples show some of the • Practical Test 3: LED Loop Test 60
functionalities available with IEC-61850
Intern © Siemens
Restricted © Siemens
AG 20XX
AG 2013
Alle All
Rechte
rights
vorbehalten.
reserved.
Seite
Page 3 XX.XX.20XX Reyrolle Protection
AutorDevices
/ Abteilung
Ltd.
Function LED - Overview
Description of Example:
Test Communication between IED’s
Configure function Key 1 on IED-A to: Configure function Key 2 on IED-A to:
LED Displays
LCD Display
Function Keys
Navigation Keys
Ethernet Switch
IEC61850
IP 192.168.1.10
GOOSE
ReyDisp Manager PC
IP: 192.168.1.1
Function keys:
F1 (signal ON)
IED A IED A
F2 (signal OFF)
IP: 192.168.1.100 IP: 192.168.1.101
• Select DeviceA
• Select “Setting Editor”
• Settings required for DeviceA:
“Auto IP”
• Select “Network” Tab
• Select “DeviceA”
In the “Properties” window (Right-side)
Insert IP address “192.168.1.100” & Subnet Mask
“255.255.255.0”
• Select Device
• Select “Comms Settings”
Reverse Interlocking
Intern © Siemens
Restricted © Siemens
AG 20XX
AG 2013
Alle All
Rechte
rights
vorbehalten.
reserved.
Seite
Page 33 XX.XX.20XX Reyrolle Protection
AutorDevices
/ Abteilung
Ltd.
Reverse Interlocking - Overview
Description of example:
Create the reverse interlocking for 2 devices in the outgoing unit (Devices B/C) and for 1 device (Device
A) in the incoming unit via the IEC61850 station
Proceed as follows:
1. Create device parameter sets
2. Parameterize off-line: Select the information in the individual devices
3. Save the parameter sets
4. Create the IEC61850 station
5. Add the devices to the IEC61850 station
6. In the IEC61850 station, set the IP addresses and configure GOOSE
7. Save and update the IEC61850 station
8. Initialize the protection devices
9. With testing equipment: Simulate faults within / outside the busbar
10. Check the reaction in the incoming unit
11. Check all signals with the troubleshooting tools
Intern © Siemens AG 20XX Alle Rechte vorbehalten.
Seite 34 XX.XX.20XX Autor / Abteilung
Reverse Interlocking - Overview
Switch
ReyDisp Manager PC
IP: 192.168.1.1
• Three devices (Device A, Device B & Device C) assigned to the same station.
• 50-1 Enabled on Device A with 100ms operate time. 50-2 Enabled on Device A with 900ms operate time (failsafe).
• 50-1 Pick Up on Device B or C generates a GOOSE mapped to the inhibit of 50-1 on Device A.
“Auto IP”
• Select “Network” Tab
• Select “DeviceA”
In the “Properties” window (Right-side)
Insert IP address “192.168.1.100” & Subnet Mask
“255.255.255.0”
Destination:
DeviceB/CTRL/SPI64GGIO1 (User SP Input
Blocks)/SPCSO1 (Single Point Data 01)
• Select Device
• Select “Comms Settings”
1. With testing equipment: Simulate faults I (outside busbar) & Fault 2 (within busbar)
Intern © Siemens
Restricted © Siemens
AG 20XX
AG 2013
Alle All
Rechte
rights
vorbehalten.
reserved.
Seite
Page 61 XX.XX.20XX Reyrolle Protection
AutorDevices
/ Abteilung
Ltd.
LED Loop Test - Overview
4. A Pickup/Dropoff timer & NOT gate applys a delay for change of signal
Ethernet Switch
IEC61850
IP 192.168.1.10
GOOSE
ReyDisp Manager PC
IP: 192.168.1.1
IED A IED A
“Auto IP”
• Select “Network” Tab
• Select “DeviceA”
In the “Properties” window (Right-side)
Insert IP address “192.168.1.100” & Subnet Mask