External Static Pressure

SPF @11,772 cfm


Node Duct Element CFM DIMENSION LENGTH VELOCITY VELOCITY FITTING LOSS
(FT) (FT/MIN) PRESSURE (in. COEFFICIENT PRESSURE TOTAL
WC) LOSS PER PRESSURE
100FT LOSS
1 DUCT 11,772.0 1300x500 0 1681.71 0.08 0.000
FITTINGS 0.1763191104 0.25 0.044

2 DUCT 11,772.00 1300X500 7 1681.71 0.116 0.0084


FITTINGS 0.1763191104 0.01572 0.003

3 DUCT 9,417.00 1300X500 27.5 1345.29 0.08 0.022


FITTINGS 0.1128298524 0.01601 0.002

4 DUCT 7,062.00 1300X500 25.09 1008.86 0.043 0.011


FITTINGS 0.0634533135 0.01644 0.001

5 DUCT 4,707.00 1300X500 31.4 672.43 0.02 0.006


FITTINGS 0.0281894937 0.0172 0.000

6 DUCT 4,707.00 1300X500 0 672.43 0.08 0.000


FITTINGS 0.0281894937 1.3 0.037

7 DUCT 4,707.00 1300X500 0 672.43 0.08 0.000


FITTINGS 0.0281894937 1.3 0.037

8 DUCT 4,707.00 1300X500 7 672.43 0.02 0.001


FITTINGS 0.0281894937 0.0335 0.001

9 DUCT 2,355.00 1300X500 14.09 336.43 0.006 0.001


FITTINGS 0.0070563596 0.0084 0.000

Friction loss @fittings and duct = 0.174


FAN DISCHARGE = 0.15
GRILLE = 0.15
VOLUME DAMPER = 0.15

----------------------------------
EXTERNAL STATIC PRESSURE 0.624
FS +10% 0.687
Q(ft^
3/min
)
16940

16495

16495

16051

16051

15606

15606

4707

2355

----------------------------------

0
Fitting
loss
coefficien
friction loss vel. pressure t Pressure loss
0 0.58 0.91 0.5278
0 0.53 0.91 0.4823
0 0.49 0.91 0.4459
0 0.45 0.91 0.4095
0 0.41 0.91 0.3731
0 0.37 0.91 0.3367