Вы находитесь на странице: 1из 40

ALARM SCHEDULE

PROJECT: 4X270 MW BHADRADRI TPS


DRG. NO. PE-DG-411-145-I202; REV01

SL.
INSC1 INSC2 INSC3 KKS DESCRIPTION STATUS SET_PT SOURCE REMARKS REV
NO.

1 AH-A TRIPPED BY EDN AH-A TRIPPED --- DCS AH-A LOGIC 00

2 AH-A/B LUB OIL SYS/ TEMP TROUBL BY EDN AH-A SB LOP-A TRIPPED --- DCS AH-A LOGIC 01M

BY EDN AH-A SB LOP-B TRIPPED --- DCS

BY EDN AH-A SB LO SYS TRBL TRUE --- DCS

BY EDN AH-A GB LOP-A TRIPPED --- DCS

BY EDN AH-A GB LOP-B TRIPPED --- DCS

BY EDN AH-A GB LO SYS TRBL TRUE --- DCS

BY EDN AH-A GUIDE BRG TEMP HIGH 70 DEGC DCS

BY EDN AH-A SUPPORT BRG TEMP HIGH 70 DEGC DCS

BY EDN AH-B SB LOP-A TRIPPED --- DCS AH-B LOGIC

BY EDN AH-B SB LOP-B TRIPPED --- DCS

BY EDN AH-B SB LO SYS TRBL TRUE --- DCS

BY EDN AH-B GB LOP-A TRIPPED --- DCS

BY EDN AH-B GB LOP-B TRIPPED --- DCS

BY EDN AH-B GB LO SYS TRBL TRUE --- DCS

BY EDN AH-B GUIDE BRG TEMP HIGH 70 DEGC DCS

BY EDN AH-B SUPPORT BRG TEMP HIGH 70 DEGC DCS

BY EDN AH-A CE/HE TEMP ABNORMAL DCS

BY EDN AH-B CE/HE TEMP ABNORMAL DCS

BY EDN AH-A ROTOR SLOWING DOWN/ STOPPED/STALLED TRUE DCS 01A

BY EDN AH-B ROTOR SLOWING DOWN/ STOPPED/STALLED TRUE DCS 01A

3 AH-A/B FIRE BY EDN AH-A FIRE ALARM --- DCS AH-A LOGIC 01M

BY EDN AH-B FIRE ALARM --- DCS AH-B LOGIC 00

4 AH-B TRIPPED BY EDN AH-B TRIPPED --- DCS AH-B LOGIC 00

5 ID FAN-A TRIPPED BY EDN ID FAN-A TRIPPED --- DCS ID FAN-A LOGIC 00

6 IDF-A LUB/ CONT OIL SYS TROUBL BY EDN IDF-A LO SYS TROUBLE TRUE --- DCS ID FAN-A LOGIC 00

BY EDN IDF-A L/O FLTR DP HIGH >0.6 ATA DCS

BY EDN IDF-A LOP-A TRIPPED --- DCS

2 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN IDF-A LOP-B TRIPPED --- DCS

HNC11CP206 IDF-A HC LUB OIL PR LOW <0.8 BAR DCS

HNC11CT203 IDF-A HC WRKG OIL TEMP HIGH >100 DEGC DCS

HNC11CT204 IDF-A HC WO CLR O/L TEMP HIGH >80 DEGC DCS

BY EDN IDF-A LUB OIL PR LOW <0.6 ATA DCS

BY EDN IDF-A ON & BOTH LOPs OFF TRUE DCS 01A

7 ID FAN-A VIB/ BRG/WDG TEMP HIGH BY EDN IDF-A WDG TEMP HIGH 125 DEGC DCS ID FAN-A LOGIC 00

BY EDN IDF-A MTR BRG TEMP HIGH 85 DEGC DCS

BY EDN IDF-A BRG TEMP HIGH 95 DEGC DCS

BY EDN IDF-A BRG VIB HIGH 4.5 mm/s DCS

8 ID FAN-B TRIPPED BY EDN ID FAN-B TRIPPED --- DCS ID FAN-B LOGIC 00

9 IDF-B LUB/ CONT OIL SYS TROUBL BY EDN IDF-B LO SYS TROUBLE TRUE --- DCS ID FAN-B LOGIC 00

BY EDN IDF-B L/O FLTR DP HIGH >0.6 ATA DCS

BY EDN IDF-B LOP-A TRIPPED --- DCS

BY EDN IDF-B LOP-B TRIPPED --- DCS

HNC21CP206 IDF-B HC LUB OIL PR LOW <0.8 BAR DCS

HNC21CT203 IDF-B HC WRKG OIL TEMP HIGH >100 DEGC DCS

HNC21CT204 IDF-B HC WO CLR O/L TEMP HIGH >80 DEGC DCS

BY EDN IDF-B LUB OIL PR LOW <0.6 ATA DCS

BY EDN IDF-B ON & BOTH LOPs OFF TRUE DCS 01A

10 ID FAN-B VIB/ BRG/WDG TEMP HIGH BY EDN IDF-A WDG TEMP HIGH 125 DEGC DCS ID FAN-B LOGIC 00

BY EDN IDF-B MTR BRG TEMP HIGH 85 DEGC DCS

BY EDN IDF-B BRG TEMP HIGH 95 DEGC DCS

BY EDN IDF-B BRG VIB HIGH 4.5 mm/s DCS

11 FD FAN-A TRIPPED BY EDN FDF-A TRIPPED --- DCS FD FAN-A LOGIC 00

12 FDF-A LUB/ CONT OIL SYS TROUBL BY EDN FDF-B L/O SYS TROUBLE TROUBLE --- DCS FD FAN-A LOGIC 00

BY EDN FDF-A L/O FLTR DP HIGH > 5 BAR DCS

BY EDN FDF-A LOP-A TRIPPED --- DCS

BY EDN FDF-A LOP-B TRIPPED --- DCS

BY EDN FDF-A LUB OIL FLOW LOW <1.9 l/min DCS

BY EDN FDF-A CONT OIL PR LOW <9 BAR DCS

BY EDN FDF-A ON & BOTH LOPs OFF TRUE DCS 01A

3 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

13 FD FAN-A VIB/ BRG/WDG TEMP HIGH BY EDN FDF-A WDG TEMP HIGH 125 DEGC DCS FD FAN-A LOGIC 00

BY EDN FD FAN-A MTR BRG TEMP HIGH 85 DEGC DCS

BY EDN FD FAN-A BRG TEMP HIGH 95 DEGC DCS

BY EDN FD FAN-A BRG VIB HIGH 4.5 mm/s DCS

14 FD FAN-B TRIPPED BY EDN FDF-B TRIPPED --- DCS FD FAN-B LOGIC 00

15 FDF-B LUB/ CONT OIL SYS TROUBL BY EDN FDF-B L/O SYS TROUBLE TROUBLE --- DCS FD FAN-B LOGIC 00

BY EDN FDF-B L/O FLTR DP HIGH > 5 BAR DCS

BY EDN FDF-B LOP-A TRIPPED --- DCS

BY EDN FDF-B LOP-B TRIPPED --- DCS

BY EDN FDF-B LUB OIL FLOW LOW <1.9 l/min DCS

BY EDN FDF-B CONT OIL PR LOW <9 BAR DCS

BY EDN FDF-B ON & BOTH LOPs OFF TRUE DCS 01A

16 FD FAN-B VIB/ BRG/WDG TEMP HIGH BY EDN FDF-B WDG TEMP HIGH 125 DEGC DCS FD FAN-B LOGIC 00

BY EDN FD FAN-B MTR BRG TEMP HIGH 85 DEGC DCS

BY EDN FD FAN-B BRG TEMP HIGH 95 DEGC DCS

BY EDN FD FAN-B BRG VIB HIGH 4.5 mm/s DCS

17 SCANNER AIR SYS TROUBL BY EDN DP ACROSS SCNR AIR FLTR LOW 5 mmWC FSSS 00

BY EDN DP ACROSS SCNR AIR FLTR HIGH 15mmWC FSSS

BY EDN DC SCNR AIR FAN MTR O.L OPTD --- FSSS

4 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN DC SCNR AIR FAN MTR NOT STRD --- FSSS

BY EDN ALL FDF OFF & SCNR EMG DMP NOT OPEN TRUE --- FSSS

BY EDN SCANNER DUCT TO FURN DP LOW 3 mmWC FSSS

BY EDN DC SCANR AIR FAN MTR ON --- DC STR

18 FURN TO WINDBOX DP HIGH /V.HI BY EDN WINDBOX TO FURNACE DPT-1 FAILED --- SADC 00

BY EDN WINDBOX TO FURNACE DPT-2 FAILED --- SADC

BY EDN WINDBOX TO FURNACE DPT-3 FAILED --- SADC

BY EDN WINDBOX TO FURNACE DPT VARIATION HIGH --- SADC

BY EDN WINDBOX TO FURNACE DP V.HIGH >240 mmWCL SADC

19 FURN PRESS LOW/ HIGH BY EDN FURNACE PRESSURE LOW -100 mmWC DCS 01M

BY EDN FURNACE PRESSURE HIGH +75 mmWC DCS

20 BOILER TRIP BY EDN FURNACE PRESSURE V.LOW -175 mmWC FSSS 00

BY EDN FURNACE PRESSURE V.HIGH +150 mmWC FSSS

BY EDN LOSS OF REHEATER PROT TRIP TRUE --- FSSS

BY EDN REHEATER PROT ACTED TRUE --- FSSS

BY EDN LOSS OF UNIT 220V DC > 2 SEC TRUE --- FSSS

BY EDN AIR FLOW < 30% MCR TRUE --- FSSS

BY EDN UNIT FLAME FAILURE TRIP TRUE --- FSSS

BY EDN < FB & LOSS OF AC AT ANY EL. IN SERV TRUE --- FSSS

BY EDN LOSS OF ALL FUEL TRIP TRUE --- FSSS

BY EDN EMERGENCY TRIP TRUE --- FSSS

BY EDN ANY ELEV STRTD AND LOSS OF AC POWER TRUE --- FSSS

BY EDN ALL FD FANS OFF TRUE --- FSSS

BY EDN ALL ID FANS OFF TRUE --- FSSS

BY EDN DISCREPANCY IN MFT TRUE --- FSSS

BY EDN MFT OPERATED TRUE --- FSSS

BY EDN MFT OPERATED TRUE --- FSSS

BY EDN MFT OPERATED TRUE --- FSSS

BY EDN PURGE COMPLETED / NO MFT TRUE --- FSSS

BY EDN SPARE TRIP TRUE --- FSSS

BY EDN LOSS OF ANY EL. +24V DC TRUE --- FSSS

BY EDN EL. AB UNSUCCESSFUL STARTUP TRUE --- FSSS

5 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN EL. AB UNSUCCESSFUL SHUTDOWN TRUE --- FSSS

BY EDN EL. CD UNSUCCESSFUL STARTUP TRUE --- FSSS

BY EDN EL. CD UNSUCCESSFUL SHUTDOWN TRUE --- FSSS

21 FUEL OIL SYS TROUBLE BY EDN HFO HEADER TEMP V.LOW FSSS 00

BY EDN HFO HEADER PRESS V.LOW FSSS

BY EDN ATOMISING STM PRESS V.LOW 3.5Kg/cm2 FSSS

BY EDN HFOP-A SUCN STNR DP HIGH 0.3Kg/cm2 FSSS

BY EDN HFOP-B SUCN STRN DP HIGH 0.3Kg/cm2 FSSS

BY EDN HFOP-C SUCN STRN DP HIGH 0.3Kg/cm2 FSSS

BY EDN HFO PR BEF HOPCV LOW FSSS

BY EDN HFO TEMP AFT HEATER LOW 115 Deg. C FSSS

BY EDN DP ACRS HFO DISCH STNR HIGH 0.3 Kg/cm2 FSSS

6 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN HFO PR AFT HOFCV LOW 5 Kg/cm2 FSSS

BY EDN HFO TEMP AFT HOFCV LOW 115 Deg. C FSSS

BY EDN LFO PMP SUCN STNR DP HIGH 0.3Kg/cm2 FSSS

BY EDN LFO PR BEF LOFCV LOW 15 Kg/cm2 FSSS

BY EDN ATOM AIR PRESS V.LOW 4 Kg/cm2 FSSS

BY EDN LO HEADER PRESS V.LOW FSSS

BY EDN LO EL. TRIP TRUE FSSS

22 UPS SYS TROUBL BRV01EH101 Main Plant UPS-1 AC Input Failure. TRUE --- UPS PNL 00

BRV01EH102 Main Plant UPS-1 Charger Failure TRUE --- UPS PNL

BRV01EH103 Main Plant UPS-1 Battery Discharged TRUE --- UPS PNL

BRV01EH104 Main Plant UPS-1 Fan Failure TRUE --- UPS PNL

BRV01EH105 Main Plant UPS-1 Charger Fuse Failure TRUE --- UPS PNL

BRV01EH106 Main Plant UPS-1 DC Output LOW --- UPS PNL

BRV01EH107 Main Plant UPS-1 DC Output HIGH --- UPS PNL

BRV01EH108 Main Plant UPS-1 Inverter Failure TRUE --- UPS PNL

BRV01EH109 Main Plant UPS-1Inverter Output HIGH --- UPS PNL

BRV01EH110 Main Plant UPS-1Inverter Output LOW --- UPS PNL

BRV01EH111 Main Plant UPS-1 Over Temperature TRUE --- UPS PNL

BRV01EH112 Main Plant UPS-1Battery Voltage LOW --- UPS PNL

BRV01EH113 Main Plant UPS-1 DC Ground Fault. TRUE --- UPS PNL

BRV01EH114 Main Plant UPS-1 Inverter not Sync. TRUE --- UPS PNL

BRV01EH115 Main Plant UPS-1 Load on Battery. TRUE --- UPS PNL

BRV01EH116 Main Plant UPS-1 Bypass Fuse Failure. TRUE --- UPS PNL

BRV01EH117 Main Plant UPS-1 Load on Bypass. TRUE --- UPS PNL

BRV01EH118 Main Plant UPS-1 Bypass Switch opened TRUE --- UPS PNL

BRV02EH101 Main Plant UPS-2 AC Input Failure. TRUE --- UPS PNL

BRV02EH102 Main Plant UPS-2 Charger Failure TRUE --- UPS PNL

BRV02EH103 Main Plant UPS-2 Battery Discharged TRUE --- UPS PNL

BRV02EH104 Main Plant UPS-2 Fan Failure TRUE --- UPS PNL

BRV02EH105 Main Plant UPS-2 Charger Fuse Failure TRUE --- UPS PNL

BRV02EH106 Main Plant UPS-2 DC Output LOW --- UPS PNL

BRV02EH107 Main Plant UPS-2 DC Output HIGH --- UPS PNL

7 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BRV02EH108 Main Plant UPS-2 Inverter Failure TRUE --- UPS PNL

BRV02EH109 Main Plant UPS-2 Inverter Output HIGH --- UPS PNL

BRV02EH110 Main Plant UPS-2 Inverter Output LOW --- UPS PNL

BRV02EH111 Main Plant UPS-2 Over Temperature TRUE --- UPS PNL

BRV02EH112 Main Plant UPS-2 Battery Voltage LOW --- UPS PNL

BRV02EH113 Main Plant UPS-2 DC Ground Fault. TRUE --- UPS PNL

BRV02EH114 Main Plant UPS-2 Inverter not Sync. TRUE --- UPS PNL

BRV02EH115 Main Plant UPS-2 Load on Battery. TRUE --- UPS PNL

BRV02EH116 Main Plant UPS-2 Bypass Fuse Failure. TRUE --- UPS PNL

BRV02EH117 Main Plant UPS-2 Load on Bypass. TRUE --- UPS PNL

BRV02EH118 Main Plant UPS-2 Bypass Switch opened TRUE --- UPS PNL

23 PA FAN-A TRIPPED BY EDN PAF-A TRIPPED --- DCS PA FAN-A LOGIC 00

24 PAF-A LUB/ CONT OIL SYS TROUBL BY EDN PAF-A L/O TANK LVL <60% LOW <60% DCS PA FAN-A LOGIC 00

BY EDN PAF-A L/O FLTR DP HIGH >5 BAR DCS

BY EDN PAF-A LOP-A TRIPPED --- DCS

8 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN PAF-A LOP-B TRIPPED --- DCS

BY EDN PAF-A LUB OIL FLOW LOW <1.9 L/min DCS

BY EDN PAF-A CONT OIL PR LOW <14 BAR DCS

BY EDN PAF-A ON & O/L GATE NOT OPEN TRUE DCS 01A

25 PA FAN-A VIB/BRG/WDG TEMP HIGH BY EDN PA FAN-A MTR WDG TEMP HIGH 125 DEGC DCS PA FAN-A LOGIC 00

BY EDN PA FAN-A MTR BRG TEMP HIGH 85 DEGC DCS

BY EDN PA FAN-A BRG TEMP HIGH 95 DEGC DCS

BY EDN PA FAN-A BRG VIB HIGH 4.5 mm/s DCS

26 PA FAN-B TRIPPED BY EDN PAF-B TRIPPED --- DCS PA FAN-B LOGIC 00

27 PAF-B LUB/ CONT OIL SYS TROUBL BY EDN PAF-B L/O TANK LVL <60% LOW <60% DCS PA FAN-B LOGIC 00

BY EDN PAF-B L/O FLTR DP HIGH >5 BAR DCS

BY EDN PAF-B LOP-A TRIPPED --- DCS

BY EDN PAF-B LOP-B TRIPPED --- DCS

BY EDN PAF-B LUB OIL FLOW LOW <1.9 L/min DCS

BY EDN PAF-B CONT OIL PR LOW <14 BAR DCS

BY EDN PAF-B ON & O/L GATE NOT OPEN TRUE DCS 01A

28 PA FAN-B VIB/BRG/WDG TEMP HIGH BY EDN PA FAN-B MTR WDG TEMP HIGH 125 DEGC DCS PA FAN-B LOGIC 00

BY EDN PA FAN-B MTR BRG TEMP HIGH 85 DEGC DCS

BY EDN PA FAN-B BRG TEMP HIGH 95 DEGC DCS

BY EDN PAF-B BRG VIB HIGH 4.5 mm/s DCS

29 MILL-A TRIPPED BY EDN MILL-A TRIPPED --- FSSS 01A

30 MILL-B TRIPPED BY EDN MILL-B TRIPPED --- FSSS 01A

31 MILL-C TRIPPED BY EDN MILL-C TRIPPED --- FSSS 01A

32 MILL-D TRIPPED BY EDN MILL-D TRIPPED --- FSSS 01A

33 MILL-E TRIPPED BY EDN MILL-E TRIPPED --- FSSS 01A

34 MILL-F TRIPPED BY EDN MILL-F TRIPPED --- FSSS 01A

35 FEEDER-A TRIPPED BY EDN FEEDER-A TRIPPED --- FSSS 01A

36 FEEDER-B TRIPPED BY EDN FEEDER-B TRIPPED --- FSSS 01A

37 FEEDER-C TRIPPED BY EDN FEEDER-C TRIPPED --- FSSS 01A

38 FEEDER-D TRIPPED BY EDN FEEDER-D TRIPPED --- FSSS 01A

39 FEEDER-E TRIPPED BY EDN FEEDER-E TRIPPED --- FSSS 01A

40 FEEDER-F TRIPPED BY EDN FEEDER-F TRIPPED --- FSSS 01A

9 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

41 MIL-A BRG/WDG TEMP. HIGH BY EDN MILL-A MTR BRG TEMP-DE HIGH T+5 Deg C DCS ANALOG I/O LIST 00

BY EDN MILL-A MTR BRG TEMP-NDE HIGH T+5 Deg C DCS

BY EDN MILL-A WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-A WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-A WDG TEMP HIGH T+5 Deg C DCS

42 MIL-B BRG/WDG TEMP. HIGH BY EDN MILL-B MTR BRG TEMP-DE HIGH T+5 Deg C DCS ANALOG I/O LIST 00

BY EDN MILL-B MTR BRG TEMP-NDE HIGH T+5 Deg C DCS

BY EDN MILL-B WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-B WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-B WDG TEMP HIGH T+5 Deg C DCS

43 MIL-C BRG/WDG TEMP. HIGH BY EDN MILL-C MTR BRG TEMP-DE HIGH T+5 Deg C DCS ANALOG I/O LIST 00

BY EDN MILL-C MTR BRG TEMP-NDE HIGH T+5 Deg C DCS

BY EDN MILL-C WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-C WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-C WDG TEMP HIGH T+5 Deg C DCS

44 MIL-D BRG/WDG TEMP. HIGH BY EDN MILL-D MTR BRG TEMP-DE HIGH T+5 Deg C DCS ANALOG I/O LIST 00

BY EDN MILL-D MTR BRG TEMP-NDE HIGH T+5 Deg C DCS

BY EDN MILL-D WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-D WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-D WDG TEMP HIGH T+5 Deg C DCS

45 MIL-E BRG/WDG TEMP. HIGH BY EDN MILL-E MTR BRG TEMP-DE HIGH T+5 Deg C DCS ANALOG I/O LIST 00

BY EDN MILL-E MTR BRG TEMP-NDE HIGH T+5 Deg C DCS

BY EDN MILL-E WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-E WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-E WDG TEMP HIGH T+5 Deg C DCS

46 MIL-F BRG/WDG TEMP. HIGH BY EDN MILL-F MTR BRG TEMP-DE HIGH T+5 Deg C DCS ANALOG I/O LIST 00

BY EDN MILL-F MTR BRG TEMP-NDE HIGH T+5 Deg C DCS

BY EDN MILL-F WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-F WDG TEMP HIGH T+5 Deg C DCS

BY EDN MILL-F WDG TEMP HIGH T+5 Deg C DCS

47 BFP-A TRIPPED BY EDN BFP-A TRIPPED --- DCS BFP LOGIC 00

48 BFP-A LUB OIL SYS TROUBL LAC26CL201 BFP-A HYD COUPL OIL LVL HIGH 60 mm DCS BFP LOGIC 00

10 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN BFP-A AOP TRIPPED --- DCS

LAC26CL201 BFP-A HYD COUPL OIL LVL LOW 50 mm DCS

BY EDN BFP-A LUB OIL STNR DP HIGH 0.6 KG/cm2 DCS

LAC26CP206 BFP-A LO PR -HC COM HDR LOW 1.5 KG/cm2 DCS

BY EDN BFP-A LO CLR I/L TEMP HIGH 65 DegC DCS

BY EDN BFP-A LO CLR O/L TEMP HIGH 55 DegC DCS

BY EDN BFP-A WO CLR I/L TEMP HIGH 110 DegC DCS

BY EDN BFP-A WO CLR O/L TEMP HIGH 75 DegC DCS

BY EDN BFP-A ON & COOLING WTR VLV NOT OPEN TRUE DCS 01A

BY EDN BFP-A TOP/BOTTOM BARREL TEMP HIGH DCS 01A

49 BFP-A VIB/BRG/WDG TEMP HIGH BY EDN BFP-A BRG TEMP HIGH 90 DEGC DCS BFP LOGIC 00

BY EDN BFP-A MTR BRG TEMP HIGH 120 DEGC DCS

BY EDN BFP-A HC TEMP HIGH 90 DEGC DCS

BY EDN BFP-A MTR WDG TEMP HIGH 120 DEGC DCS

BY EDN BFP-A BRG VIB HIGH >14 mm DCS

BY EDN BFP-A BP DE JRNL BRG TEMP HIGH DCS 01A

BY EDN BFP-A BP NDE JRNL BRG TEMP HIGH DCS 01A

BY EDN BFP-A BP THRUST BRG TEMP HIGH DCS 01A

50 BFP-B TRIPPED BY EDN BFP-B TRIPPED --- DCS BFP LOGIC 00

51 BFP-B LUB OIL SYS TROUBL LAC26CL201 BFP-B HYD COUPL OIL LVL HIGH 60 mm DCS BFP LOGIC 00

BY EDN BFP-B AOP TRIPPED --- DCS

LAC26CL201 BFP-B HYD COUPL OIL LVL LOW 50 mm DCS

BY EDN BFP-B LUB OIL STNR DP HIGH 0.6 KG/cm2 DCS

LAC26CP206 BFP-B LO PR -HC COM HDR LOW 1.5 KG/cm2 DCS

BY EDN BFP-B LO CLR I/L TEMP HIGH 65 DegC DCS

BY EDN BFP-B LO CLR O/L TEMP HIGH 55 DegC DCS

BY EDN BFP-B WO CLR I/L TEMP HIGH 110 DegC DCS

BY EDN BFP-B WO CLR O/L TEMP HIGH 75 DegC DCS

BY EDN BFP-B ON & COOLING WTR VLV NOT OPEN TRUE DCS 01A

BY EDN BFP-B TOP/BOTTOM BARREL TEMP HIGH DCS 01A

52 BFP-B VIB/BRG/WDG TEMP HIGH BY EDN BFP-B BRG TEMP HIGH 90 DEGC DCS BFP LOGIC 00

BY EDN BFP-B MTR BRG TEMP HIGH 120 DEGC DCS

11 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN BFP-B HC TEMP HIGH 90 DEGC DCS

BY EDN BFP-B MTR WDG TEMP HIGH 120 DEGC DCS

BY EDN BFP-B BRG VIB HIGH >14 mm DCS

BY EDN BFP-B BP DE JRNL BRG TEMP HIGH DCS 01A

BY EDN BFP-B BP NDE JRNL BRG TEMP HIGH DCS 01A

BY EDN BFP-B BP THRUST BRG TEMP HIGH DCS 01A

53 BFP-C TRIPPED BY EDN BFP-C TRIPPED --- DCS BFP LOGIC 00

54 BFP-C LUB OIL SYS TROUBL LAC26CL201 BFP-C HYD COUPL OIL LVL HIGH 60 mm DCS BFP LOGIC 00

BY EDN BFP-C AOP TRIPPED --- DCS

LAC26CL201 BFP-C HYD COUPL OIL LVL LOW 50 mm DCS

BY EDN BFP-C LUB OIL STNR DP HIGH 0.6 KG/cm2 DCS

LAC26CP206 BFP-C LO PR -HC COM HDR LOW 1.5 KG/cm2 DCS

BY EDN BFP-C LO CLR I/L TEMP HIGH 65 DegC DCS

BY EDN BFP-C LO CLR O/L TEMP HIGH 55 DegC DCS

BY EDN BFP-C WO CLR I/L TEMP HIGH 110 DegC DCS

BY EDN BFP-C WO CLR O/L TEMP HIGH 75 DegC DCS

BY EDN BFP-C ON & COOLING WTR VLV NOT OPEN TRUE DCS 01A

BY EDN BFP-C TOP/BOTTOM BARREL TEMP HIGH DCS 01A

55 BFP-C VIB/BRG/WDG TEMP HIGH BY EDN BFP-C BRG TEMP HIGH 90 DEGC DCS BFP LOGIC 00

BY EDN BFP-C MTR BRG TEMP HIGH 120 DEGC DCS

BY EDN BFP-C HC TEMP HIGH 90 DEGC DCS

BY EDN BFP-C MTR WDG TEMP HIGH 120 DEGC DCS

BY EDN BFP-C BRG VIB HIGH >14 mm DCS

BY EDN BFP-C BP DE JRNL BRG TEMP HIGH DCS 01A

BY EDN BFP-C BP NDE JRNL BRG TEMP HIGH DCS 01A

BY EDN BFP-C BP THRUST BRG TEMP HIGH DCS 01A

56 DEAERATOR LEVEL ABNORMAL BY EDN DEAERATOR LEVEL V.HIGH --- DCS ACS 00

BY EDN DEAERATOR LEVEL HIGH --- DCS

BY EDN DEAERATOR LEVEL LOW --- DCS

BY EDN DEAERATOR LEVEL LOW LOW --- DCS 01A

57 HPH-5 LEVEL ABNORMAL BY EDN HPH-5 LEVEL V.HIGH --- DCS ACS 00

BY EDN HPH-5 LEVEL HIGH --- DCS

12 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN HPH-5 LEVEL LOW --- DCS

BY EDN EX-5 STM PR AT HPH-5 I/L LOW --- DCS

58 HPH-6 LEVEL ABNORMAL BY EDN HPH-6 LEVEL HIGH --- DCS ACS 00

BY EDN HPH-6 LEVEL LOW --- DCS

59 LPH-1 LEVEL ABNORMAL BY EDN LPH-1 LEVEL V.HIGH --- DCS ACS 00

BY EDN LPH-1 LEVEL HIGH --- DCS

60 LPH-2 LEVEL ABNORMAL BY EDN LPH-2 LEVEL V.HIGH --- DCS ACS 00

BY EDN LPH-2 LEVEL HIGH --- DCS

BY EDN LPH-2 LEVEL LOW --- DCS

61 LPH-3 LEVEL ABNORMAL BY EDN LPH-3 LEVEL V.HIGH --- DCS ACS 00

BY EDN LPH-3 LEVEL HIGH --- DCS

BY EDN LPH-3 LEVEL LOW --- DCS

62 HOTWELL LEVEL ABNORMAL BY EDN HOTWELL LVL V.HIGH --- DCS ACS 00

BY EDN HOTWELL LVL HIGH --- DCS

BY EDN HOTWELL LVL LOW --- DCS

BY EDN HOTWELL LVL V.LOW --- DCS

63 CEP-A TRIPPED BY EDN CEP-A TRIPPED --- DCS CEP LOGIC 00

64 CEP-A VIB/BRG/WDG TEMP HIGH BY EDN CEP-A THRUST BRG TEMP HIGH 85 DEGC DCS CEP LOGIC 00

BY EDN CEP-A THRUST BRG TEMP HIGH 95 DEGC DCS

BY EDN CEP-A JOURNAL BRG TEMP HIGH 85 DEGC DCS

BY EDN CEP-A MTR BRG TEMP - DE HIGH 80 DEGC DCS

BY EDN CEP-A MTR BRG TEMP - NDE HIGH 80 DEGC DCS

BY EDN CEP-A MTR WDG TEMP - 1 HIGH 110 DEGC DCS

BY EDN CEP-A MTR WDG TEMP - 2 HIGH 110 DEGC DCS

BY EDN CEP-A MTR WDG TEMP - 3 HIGH 110 DEGC DCS

BY EDN CEP-A MTR WDG TEMP - 4 HIGH 110 DEGC DCS

BY EDN CEP-A MTR WDG TEMP - 5 HIGH 110 DEGC DCS

BY EDN CEP-A MTR WDG TEMP - 6 HIGH 110 DEGC DCS

BY EDN CEP-A BRG VIB-HOZ HIGH 11 mm DCS

BY EDN CEP-A BRG VIB-VERT HIGH 11 mm DCS

65 CEP-B TRIPPED BY EDN CEP-B TRIPPED --- DCS CEP LOGIC 00

66 CEP-B VIB/BRG/WDG TEMP HIGH BY EDN CEP-B THRUST BRG TEMP HIGH 85 DEGC DCS CEP LOGIC 00

13 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN CEP-B THRUST BRG TEMP HIGH 95 DEGC DCS

BY EDN CEP-B JOURNAL BRG TEMP HIGH 85 DEGC DCS

BY EDN CEP-B MTR BRG TEMP - DE HIGH 80 DEGC DCS

BY EDN CEP-B MTR BRG TEMP - NDE HIGH 80 DEGC DCS

BY EDN CEP-B MTR WDG TEMP - 1 HIGH 110 DEGC DCS

BY EDN CEP-B MTR WDG TEMP - 2 HIGH 110 DEGC DCS

BY EDN CEP-B MTR WDG TEMP - 3 HIGH 110 DEGC DCS

BY EDN CEP-B MTR WDG TEMP - 4 HIGH 110 DEGC DCS

BY EDN CEP-B MTR WDG TEMP - 5 HIGH 110 DEGC DCS

BY EDN CEP-B MTR WDG TEMP - 6 HIGH 110 DEGC DCS

BY EDN CEP-B BRG VIB-HOZ HIGH 11 mm DCS

BY EDN CEP-B BRG VIB-VERT HIGH 11 mm DCS

67 CHEM DOZNG SYS TROUBL LFN10EH201 CHEM DOSING SYS TRBL --- DCS 00
CONTROL SCHEME FOR
BY EDN PHOS DOSING PUMP-A TRIPPED --- DCS
HP DOSING PUMPS
BY EDN PHOS DOSING PUMP-B TRIPPED --- DCS

BY EDN PHOS PREP TANK AGITATOR TRIPPED --- DCS

BY EDN PHOS MET TANK AGITATOR TRIPPED --- DCS

BY EDN PHOS PREP TANK LEVEL LOW TRUE --- DCS

BY EDN PHOS MET TANK LEVEL HIGH TRUE --- DCS

BY EDN PHOS MET TANK LEVELV.LOW TRUE --- DCS

BY EDN PHOS DOS PMP-A SUC DP HIGH TRUE --- DCS

BY EDN PHOS DOS PMP-B SUC DP HIGH TRUE --- DCS

BY EDN PHOS DPS LCP POWER SUPPLY FAILED --- DCS

BY EDN PHOS DOS PMP-A DISCH PR LOW TRUE --- DCS

BY EDN PHOS DOS PMP-B DISCH PR LOW TRUE --- DCS


CONTROL SCHEME FOR
BY EDN HYDZ DOSING DUPLEX STARINER CHOCKED --- DCS
LP DOSING PUMPS
BY EDN HYD PREP/ MTRG TANK-1 LVL LOW -- DCS

BY EDN HYD PREP/ MTRG TANK-1 LVL V. LOW -- DCS

BY EDN HYD PREP/ MTRG TANK-1 LVL HIGH -- DCS

BY EDN HYD PREP/ MTRG TANK-2 LVL LOW -- DCS

BY EDN HYD PREP/ MTRG TANK-2 LVL V. LOW -- DCS

BY EDN HYD PREP/ MTRG TANK-2 LVL HIGH -- DCS

14 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN HYDZ DOS PUMPS DISCH PR HIGH -- DCS

BY EDN HYDZ DOS PUMPS DISCH PR LOW -- DCS

BY EDN HYDZ DOS PUMP-A MCC DISTBD -- DCS

BY EDN HYDZ DOS PUMP-B MCC DISTBD -- DCS

BY EDN HYDZ TANK-1 STIRRER MCC DISTBD -- DCS

BY EDN HYDZ TANK-2 STIRRER MCC DISTBD -- DCS

BY EDN HYDZ DOSING PUMP-A TRIPPED --- DCS

BY EDN HYDZ DOSING PUMP-B TRIPPED --- DCS

BY EDN HYDZ PREP/ METRG TANK-1 STIRRER TRIPPED --- DCS

BY EDN HYDZ PREP/ METRG TANK-2 STIRRER TRIPPED --- DCS


CONTROL SCHEME FOR
BY EDN AMMONIA DOSING DUPLEX STARINER CHOCKED --- DCS
LP DOSING PUMPS
BY EDN AMMONIA PREP/ MTRG TANK-1 LVL LOW -- DCS

BY EDN AMMONIA PREP/ MTRG TANK-1 LVL V. LOW -- DCS

BY EDN AMMONIA PREP/ MTRG TANK-1 LVL HIGH -- DCS

BY EDN AMMONIA PREP/ MTRG TANK-2 LVL LOW -- DCS

BY EDN AMMONIA PREP/ MTRG TANK-2 LVL V. LOW -- DCS

BY EDN AMMONIA PREP/ MTRG TANK-2 LVL HIGH -- DCS

BY EDN AMMONIA DOS PUMPS DISCH HDR PR HIGH -- DCS

BY EDN AMMONIA DOS PUMPS DISCH HDR PR LOW -- DCS

BY EDN AMMONIA DOS PUMP-A MCC DISTBD -- DCS

BY EDN AMMONIA DOS PUMP-B MCC DISTBD -- DCS

BY EDN AMMONIA TANK-1 STIRRER MCC DISTBD -- DCS

BY EDN AMMONIA TANK-2 STIRRER MCC DISTBD -- DCS

BY EDN AMMONIA DOSING PUMP-A TRIPPED --- DCS

BY EDN AMMONIA DOSING PUMP-B TRIPPED --- DCS

BY EDN AMMONIA PREP/ METRG TANK-1 STIRRER TRIPPED --- DCS

BY EDN AMMONIA PREP/ METRG TANK-2 STIRRER TRIPPED --- DCS


CONTROL SCHEME FOR
BY EDN NaOH DOSING DUPLEX STARINER CHOCKED --- DCS
LP DOSING PUMPS
BY EDN NaOH MIXING/ STRG TANK LVL LOW -- DCS

BY EDN NaOH MIXING/ STRG TANK LVL V. LOW -- DCS

BY EDN NaOH MIXING/ STRG TANK LVL HIGH -- DCS

BY EDN NaOH DOS PUMPS DISCH HDR PR HIGH -- DCS

15 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN NaOH DOS PUMPS DISCH HDR PR LOW -- DCS

BY EDN NaOH DOS PUMP-A MCC DISTBD -- DCS

BY EDN NaOH DOS PUMP-B MCC DISTBD -- DCS

BY EDN NaOH MIXING/ STRG STIRRER MCC DISTBD -- DCS

BY EDN NaOH DOSING PUMP-A TRIPPED --- DCS

BY EDN NaOH DOSING PUMP-B TRIPPED --- DCS

BY EDN NaOH MIXING/ STRG STIRRER TRIPPED --- DCS

68 CW PMP-A TRIPPED BY EDN CW PUMP-A TRIPPED --- DCS CWP CONTROL SCHEME 00

BY EDN CWP-A PMP/ MTR BRG TEMP V.HIGH --- DCS

BY EDN CWP-A MTR WNDG TEMP V.HIGH --- DCS

BY EDN CWP-A BRG TEMP/WNDG TEMP/VIB V.HIGH --- DCS

BY EDN CWP-A MTR BRG VIB V.HIGH --- DCS

69 CW PMP-A SYS TROUBL BY EDN CWP-A SYS TRBL --- DCS CWP CONTROL SCHEME 00

BY EDN STANDBY CWP-A FAILED TO START TRUE --- DCS

BY EDN CW PUMP-A REVERSE ROTATION OPTD --- DCS

BY EDN CW PUMP-A STARTED & DISCH BFV 10DEG NOT OPEN --- DCS

BY EDN CW PUMP-A DISCH PR HIGH/LOW --- DCS

BY EDN CW PUMP-A TRIPPED & DISCH BFV FAILED TO CLOSE TRUE --- DCS

BY EDN CW FOREBAY LEVEL V.HIGH --- DCS

BY EDN CW FOREBAY LEVEL HIGH --- DCS

BY EDN CW FOREBAY LEVEL V.LOW --- DCS

BY EDN CW FOREBAY LEVEL LOW --- DCS

BY EDN ALL CWP's ON --- DCS

BY EDN ALL CWP's ON & DISCH HDR PR HIGH --- DCS

BY EDN ALL CWP's OFF --- DCS

BY EDN CWP's DISCH HDR PR LOW --- DCS

BY EDN CWP's DISCH HDR PR HIGH --- DCS

BY EDN CWP-A DISCH PR LOW --- DCS

BY EDN CWP-A DISCH PR HIGH --- DCS

BY EDN CWP-A MTR WNDG TEMP HIGH --- DCS

BY EDN CWP-A PMP/ MTR BRG TEMP HIGH --- DCS

BY EDN CWP-A THRUST BRG VIB HIGH --- DCS

16 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN CWP-A SUMP LEVEL LOW --- DCS

BY EDN CWP-A SUMP LEVEL V.LOW --- DCS

70 CW PMP-B TRIPPED BY EDN CW PUMP-B TRIPPED --- DCS CWP CONTROL SCHEME 00

BY EDN CWP-B MTR WNDG TEMP V.HIGH --- DCS

BY EDN CWP-B BRG TEMP/WNDG TEMP/VIB V.HIGH --- DCS

BY EDN CWP-B MTR BRG VIB V.HIGH --- DCS

BY EDN CWP-B PMP/ MTR BRG TEMP V.HIGH --- DCS

71 CW PMP-B SYS TROUBL BY EDN CWP-B SYS TRBL --- DCS CWP CONTROL SCHEME 00

BY EDN STANDBY CWP-B FAILED TO START TRUE --- DCS

BY EDN CW PUMP-B REVERSE ROTATION OPTD --- DCS

BY EDN CW PUMP-B STARTED & DISCH BFV 10DEG NOT OPEN --- DCS

BY EDN CW PUMP-B DISCH PR HIGH/LOW --- DCS

BY EDN CW PUMP-B TRIPPED & DISCH BFV FAILED TO CLOSE TRUE --- DCS

BY EDN CWP-B DISCH PR LOW --- DCS

BY EDN CWP-B DISCH PR HIGH --- DCS

BY EDN CWP-B MTR WNDG TEMP HIGH --- DCS

BY EDN CWP-B PMP/ MTR BRG TEMP HIGH --- DCS

BY EDN CWP-B THRUST BRG VIB HIGH --- DCS

BY EDN CWP-B SUMP LEVEL LOW --- DCS

BY EDN CWP-B SUMP LEVEL V.LOW --- DCS

72 CW PMP-C TRIPPED BY EDN CW PUMP-C TRIPPED --- DCS CWP CONTROL SCHEME 00

BY EDN CWP-C MTR WNDG TEMP V.HIGH --- DCS

BY EDN CWP-C PMP/ MTR BRG TEMP V.HIGH --- DCS

BY EDN CWP-C BRG TEMP/WNDG TEMP/VIB V.HIGH --- DCS

BY EDN CWP-C MTR BRG VIB V.HIGH --- DCS

73 CW PMP-C SYS TROUBL BY EDN CWP-C SYS TRBL --- DCS CWP CONTROL SCHEME 00

BY EDN STANDBY CWP-C FAILED TO START TRUE --- DCS

BY EDN CW PUMP-C REVERSE ROTATION OPTD --- DCS

BY EDN CW PUMP-C STARTED & DISCH BFV 10DEG NOT OPEN --- DCS

BY EDN CW PUMP-C DISCH PR HIGH/LOW --- DCS

BY EDN CW PUMP-C TRIPPED & DISCH BFV FAILED TO CLOSE TRUE --- DCS

BY EDN CWP-C DISCH PR LOW --- DCS

17 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN CWP-C DISCH PR HIGH --- DCS

BY EDN CWP-C MTR WNDG TEMP HIGH --- DCS

BY EDN CWP-C PMP/ MTR BRG TEMP HIGH --- DCS

BY EDN CWP-C THRUST BRG VIB HIGH --- DCS

BY EDN CWP-C SUMP LEVEL LOW --- DCS

BY EDN CWP-C SUMP LEVEL V.LOW --- DCS

74 SEAL AIR FAN SYS TROUBL BY EDN SEAL AIR FAN-A UNSUCCESSFUL START TRUE --- FSSS 00

BY EDN SEAL AIR FAN-B UNSUCCESSFUL START TRUE FSSS

BY EDN SEAL AIR HDR/ COLD AIR DUCT DP LOW>10 SEC LOW FSSS

BY EDN BOTH SEAL AIR FAN FAILED TO START & TRIPPED TRUE FSSS

75 APRDS SYS PARAMETERS ABNORMAL BY EDN HT AUX STM HDR TEMP LOW LOW < 12 ata DCS APRDS SCHEME

BY EDN HT AUX STM HDR TEMP HIGH HIGH >330 Deg C DCS

BY EDN HT AUX STM HDR TEMP V.HIGH V.HIGH >340 Deg C DCS

BY EDN LT AUX STM HDR TEMP LOW LOW <190 Deg C DCS

BY EDN LT AUX STM HDR TEMP HIGH HIGH >230 Deg C DCS

BY EDN HT AUX STM HDR TEMP V.HIGH V.HIGH >240 Deg C DCS

76 ACW SYSTEM TROUBLE BY EDN ACW SYSTEM TROUBLE --- DCS ACW PMP LOGIC 00

BY EDN ALL ACWPs ON --- DCS

BY EDN ALL ACWPs ON & DISCH HDR PR HIGH --- DCS

BY EDN ALL ACWPs OFF --- DCS

BY EDN ACWPs DISCH HDR PR LOW --- DCS

BY EDN ACWPs DISCH HDR PR HIGH --- DCS

BY EDN STANDBY ACWP-A FAILED TO START TRUE --- DCS

BY EDN ACWP-A REVERSE ROTATION OPTD --- DCS

BY EDN ACWP-A STARTED & DISCH BFV 10DEG NOT OPEN --- DCS

BY EDN ACWP-A TRIPPED & DISCH BFV FAILED TO CLOSE TRUE --- DCS

BY EDN ANY PMP RUNNING STANDBY NOT SELECTED DCS

BY EDN ACWP-A DISCH PR LOW --- DCS

BY EDN ACWP-A DISCH PR HIGH --- DCS

BY EDN ACWP-A MTR WNDG TEMP HIGH --- DCS

BY EDN ACWP-A PMP/ MTR BRG TEMP HIGH --- DCS

BY EDN ACWP-A THRUST BRG VIB HIGH --- DCS

18 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN ACWP-A SUMP LEVEL LOW --- DCS

BY EDN ACWP-A SUMP LEVEL V.LOW --- DCS

BY EDN STANDBY ACWP-B FAILED TO START TRUE --- DCS

BY EDN ACWP-B REVERSE ROTATION OPTD --- DCS

BY EDN ACWP-B STARTED & DISCH BFV 10DEG NOT OPEN --- DCS

BY EDN ACWP-B TRIPPED & DISCH BFV FAILED TO CLOSE TRUE --- DCS

BY EDN ACWP-B DISCH PR LOW --- DCS

BY EDN ACWP-B DISCH PR HIGH --- DCS

BY EDN ACWP-B MTR WNDG TEMP HIGH --- DCS

BY EDN ACWP-B PMP/ MTR BRG TEMP HIGH --- DCS

BY EDN ACWP-B THRUST BRG VIB HIGH --- DCS

BY EDN ACWP-B SUMP LEVEL LOW --- DCS

BY EDN ACWP-B SUMP LEVEL V.LOW --- DCS

BY EDN STANDBY ACWP-C FAILED TO START TRUE --- DCS

BY EDN ACWP-C REVERSE ROTATION OPTD --- DCS

BY EDN ACWP-C STARTED & DISCH BFV 10DEG NOT OPEN --- DCS

BY EDN ACWP-C TRIPPED & DISCH BFV FAILED TO CLOSE TRUE --- DCS

BY EDN ACWP-C DISCH PR LOW --- DCS

BY EDN ACWP-C DISCH PR HIGH --- DCS

BY EDN ACWP-C MTR WNDG TEMP HIGH --- DCS

BY EDN ACWP-C PMP/ MTR BRG TEMP HIGH --- DCS

BY EDN ACWP-C THRUST BRG VIB HIGH --- DCS

BY EDN ACWP-C SUMP LEVEL LOW --- DCS

BY EDN ACWP-C SUMP LEVEL V.LOW --- DCS

77 DMCW TG SYSTEM TROUBLE BY EDN DMCW TG SYSTEM TROUBLE --- DCS DMCW PMP LOGIC 00

BY EDN STANDBY DMCW PMP-A FAILED TO START TRUE --- DCS

BY EDN DMCW PMP-A DRIVE START PERM NOT AVLBL --- DCS

BY EDN DMCW PMP SUC HDR PR LOW --- DCS

BY EDN DMCW PMP SUC HDR PR V.LOW --- DCS

BY EDN DMCWP-A DISCH VLV FAILED TO OPEN TRUE --- DCS

BY EDN DMCWP-A DISCH VLV FAILED TO CLOSE TRUE --- DCS

BY EDN ALL DMCW PMPS OFF --- DCS

19 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN ANY RUNNING PMP STANDBY NOT SELECTED TRUE --- DCS

BY EDN DMCWP-A DISCH PR LOW --- DCS

BY EDN DMCWP-A DISCH PR HIGH --- DCS

BY EDN NORMAL MAKE-UP VLV FAILED TO OPEN TRUE --- DCS

BY EDN NORMAL MAKE-UP VLV FAILED TO CLOSE TRUE --- DCS


DMCW O/H TANK EMERGENCY MAK-UP VLV FAILED TO
BY EDN TRUE --- DCS
OPEN
DMCW O/H TANK EMERGENCY MAK-UP VLV FAILED TO
BY EDN TRUE --- DCS
CLOSE
BY EDN DP ACROSS PHE-A HIGH --- DCS

BY EDN DMCW PMP O/H TANK LVL LOW --- DCS

BY EDN DMCW PMP O/H TANK LVL V.LOW --- DCS

BY EDN DMCW PMP O/H TANK LVL HIGH --- DCS

BY EDN DMCW PMP O/H TANK LVL V.HIGH --- DCS

BY EDN DMCW PMP DISCH HDR PR LOW --- DCS

BY EDN DMCW PMP DISCH HDR PR HIGH --- DCS

BY EDN DMCWP-A MTR WNDG TEMP HIGH --- DCS

BY EDN DMCWP-A PMP/MTR BRG TEMP HIGH --- DCS

BY EDN DMCWP-A PMP/MTR BRG VIB HIGH --- DCS

BY EDN STANDBY DMCW PMP-B FAILED TO START TRUE --- DCS

BY EDN DMCW PMP-B DRIVE START PERM NOT AVLBL --- DCS

BY EDN DMCWP-B DISCH VLV FAILED TO OPEN TRUE --- DCS

BY EDN DMCWP-B DISCH VLV FAILED TO CLOSE TRUE --- DCS

BY EDN DMCWP-B DISCH PR LOW --- DCS

BY EDN DMCWP-B DISCH PR HIGH --- DCS

BY EDN NORMAL MAKE-UP VLV FAILED TO OPEN TRUE --- DCS

BY EDN NORMAL MAKE-UP VLV FAILED TO CLOSE TRUE --- DCS


DMCW O/H TANK EMERGENCY MAK-UP VLV FAILED TO
BY EDN TRUE --- DCS
OPEN
DMCW O/H TANK EMERGENCY MAK-UP VLV FAILED TO
BY EDN TRUE --- DCS
CLOSE
BY EDN DMCWP-B MTR WNDG TEMP HIGH --- DCS

BY EDN DMCWP-B PMP/MTR BRG TEMP HIGH --- DCS

BY EDN DMCWP-B PMP/MTR BRG VIB HIGH --- DCS

BY EDN STANDBY DMCW PMP-C FAILED TO START TRUE --- DCS

BY EDN DMCW PMP-C DRIVE START PERM NOT AVLBL --- DCS

20 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN DMCWP-C DISCH VLV FAILED TO OPEN TRUE --- DCS

BY EDN DMCWP-C DISCH VLV FAILED TO CLOSE TRUE --- DCS

BY EDN DMCWP-C DISCH PR LOW --- DCS

BY EDN DMCWP-C DISCH PR HIGH --- DCS

BY EDN NORMAL MAKE-UP VLV FAILED TO OPEN TRUE --- DCS

BY EDN NORMAL MAKE-UP VLV FAILED TO CLOSE TRUE --- DCS


DMCW O/H TANK EMERGENCY MAK-UP VLV FAILED TO
BY EDN TRUE --- DCS
OPEN
DMCW O/H TANK EMERGENCY MAK-UP VLV FAILED TO
BY EDN TRUE --- DCS
CLOSE
BY EDN DMCWP-C MTR WNDG TEMP HIGH --- DCS

BY EDN DMCWP-C PMP/MTR BRG TEMP HIGH --- DCS

BY EDN DMCWP-C PMP/MTR BRG VIB HIGH --- DCS

78 DMCW BP FOR SG SYSTEM TROUBLE BY EDN DMCW BP FOR SG AUX SYSTEM TROUBLE --- DCS DMCW PMP LOGIC 01A
BY EDN DMCWP-A BP-A FOR SG-AUX START PERM NOT AVLBL --- DCS

BY EDN STANDBY DMCWP-A BP-A FOR SG-AUX FAILED TO START TRUE --- DCS

BY EDN DMCWP-A BP-A FOR SG-AUX TRIPPED --- DCS


BY EDN BOTH DMCW BP FOR SG-AUX OFF --- DCS
BY EDN BOTH DMCW BP FOR SG-AUX ON --- DCS
BY EDN DMCW BP-A FOR SG-AUX DISCH PR LOW --- DCS
BY EDN DMCW BP-A FOR SG-AUX DISCH PR HIGH --- DCS
BY EDN DMCW BP FOR SG-AUX DISCH HDR PR LOW --- DCS
BY EDN DMCW BP FOR SG-AUX DISCH HDR PR HIGH --- DCS
BY EDN DMCW BP-A DISCH VLV FOR SG AUX FAILED TO OPEN TRUE --- DCS
BY EDN DMCW BP-A DISCH VLV FOR SG AUX FAILED TO CLOSE TRUE --- DCS
BY EDN DMCW BP SUC HDR PR FOR SG-AUX V.LOW --- DCS
BY EDN DMCW BP SUC HDR PR FOR SG-AUX LOW --- DCS
BY EDN DMCWP-A BSTR PMP-A FOR SG-AUX START PERM NOT AVLBL --- DCS

BY EDN STANDBY DMCWP-A BP-A FOR SG-AUX FAILED TO START TRUE --- DCS

BY EDN DMCWP-B BP-A FOR SG-AUX TRIPPED --- DCS


BY EDN DMCWP-C BP-A FOR SG-AUX START PERM NOT AVLBL --- DCS

BY EDN STANDBY DMCWP-C BP-A FOR SG-AUX FAILED TO START TRUE --- DCS
BY EDN DMCWP-C BP-A FOR SG-AUX TRIPPED --- DCS

79 ANY ACW PUMP TRIP BY EDN ANY ACWP TRIPPED --- DCS ACW PMP LOGIC 00

BY EDN ACWP-A TRIPPED --- DCS

BY EDN ACWP-A MTR WNDG TEMP V.HIGH --- DCS

BY EDN ACWP-A PMP/ MTR BRG TEMP V.HIGH --- DCS

BY EDN ACWP-A BRG TEMP/WNDG TEMP/VIB V.HIGH --- DCS

BY EDN ACWP-A MTR BRG VIB V.HIGH --- DCS

BY EDN ACWP-B TRIPPED DCS

21 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN ACWP-B MTR WNDG TEMP V.HIGH --- DCS

BY EDN ACWP-B PMP/ MTR BRG TEMP V.HIGH --- DCS

BY EDN ACWP-B BRG TEMP/WNDG TEMP/VIB V.HIGH --- DCS

BY EDN ACWP-B MTR BRG VIB V.HIGH --- DCS

BY EDN ACWP-C TRIPPED DCS

BY EDN ACWP-C MTR WNDG TEMP V.HIGH --- DCS

BY EDN ACWP-C PMP/ MTR BRG TEMP V.HIGH --- DCS

BY EDN ACWP-C BRG TEMP/WNDG TEMP/VIB V.HIGH --- DCS

BY EDN ACWP-C MTR BRG VIB V.HIGH --- DCS

80 ANY DMCW PUMP TRIP BY EDN ANY DMCWP TRIPPED --- DCS DMCW PMP LOGIC 00

BY EDN DMCWP-A TRIPPED --- DCS

BY EDN DMCWP-A MTR WNDG TEMP V.HIGH --- DCS

BY EDN DMCWP-A PMP/MTR BRG TEMP V.HIGH --- DCS

BY EDN DMCWP-A PMP/MTR BRG VIB V.HIGH --- DCS

BY EDN DMCW PMP DISCH HDR PR V.HIGH --- DCS

BY EDN DMCWP-B TRIPPED DCS

BY EDN DMCWP-B MTR WNDG TEMP V.HIGH --- DCS

BY EDN DMCWP-B PMP/MTR BRG TEMP V.HIGH --- DCS

BY EDN DMCWP-B PMP/MTR BRG VIB V.HIGH --- DCS

BY EDN DMCWP-C TRIPPED DCS

BY EDN DMCWP-C MTR WNDG TEMP V.HIGH --- DCS

BY EDN DMCWP-C PMP/MTR BRG TEMP V.HIGH --- DCS

BY EDN DMCWP-C PMP/MTR BRG VIB V.HIGH --- DCS

BY EDN DMCW BP-A FOR SG AUX TRIPPED DCS

BY EDN DMCW BP FOR SG-AUX DISCH HDR PR V.HIGH --- DCS

BY EDN DMCW BP-B FOR SG AUX TRIPPED DCS


ABSENT/NEGAT
81 EHC/TSC SYSTEM FAULT MAA00EC001_ZA18 TURB STRESS MARGIN . DCS 00
IVE
MYA01DU001_XT01 ELECRO-HYDR TURB CONTROLLER FAULT DCS

MYA01DU001_XT02 TURBINE STRESS INFLUENCE . OFF DCS

MYA01DU001_XT03 DN/DT MONITORING ACTIVE < 100 /MIN2 DCS

MYA01DU001_XT04 LIMIT PRESS ENGAGED ENGAGED DCS

MYA01DU001_XT05 PLUNGER COIL OFF OFF DCS

22 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

MYA01DU001_XT40 SPEED SLOPE VALUE LOW < 100/MIN2 DCS

MYA01EP001_XT05 TURBINE STRESS CAB FAULT DCS

82 FIRE PROTECTION OPERATED MAY00EY001_ZV01 FIRE PROTECTION 1 PUSHED DCS 00

MAY00EY001_ZV05 FIRE PROTECTION 2 PUSHED DCS

MAY00EY001_ZV14 FIRE PROT OIL TANK LEVEL LOW >900 MM DCS

MAY00EY001_XT01 FIRE PROTECTION OPRRATED DCS

83 GAS DRIER 1/2 TRIPPED MKG69EG001_ZV01 REF.GAS DRIER-1 TRIPPED DCS 00

MKG69EG001_ZV02 REF.GAS DRIER-2 TRIPPED DCS

84 GEN AUX SYS PARAM ABNORMAL MKQ00EE001_ZV02 BRG.EX.FAN 1 TRIPPED DCS 00

MKQ00EE001_ZV03 BRG.EX.FAN 2 TRIPPED DCS

MKY01EG004_ZV01 HOT GAS CLR A/B&C/D HIGH > 75 DEG.C DCS

BY EDN VACUUM BREAKER OPEN/ FAULT TRUE DCS 01A

BY EDN GENERATOR SEAL OIL PR LOW DCS 01A

BY EDN HOT AIR TEMPERATRE OF MAIN EXCITER HIGH / V.HIGH DCS 01A

85 GEN COLD GAS PARAM ABNORMAL MKY01EG003_ZV03 CLD GAS CLR A&B/C&D HIGH > 50 DEG.C DCS 00

MKY01EG003_ZV06 CLD GAS CLR A&B/C&D V.HIGH > 55 DEG.C DCS

MKY01EZ112_XK97 CLD GAS TEMP AFT CLR A&B DISCREN DCS

MKY01EZ113_XK97 CLD GAS TEMP AFT CLR C&D DISCREN DCS

BY EDN COLD GAS TEMP CONTROL VLV NOT IN AUTO TRUE DCS 01A
>105,.>100
86 STATOR WNDG/CORE TEMP HI MKY01EG002_ZV04 TEMP STATOR WINDING/CORE HIGH DCS 00
DEG.C
BY EDN STATOR WINDING FLOW LOW DCS 01A
<15,<2.8, >3.2
87 H2 PARAM CAS/MANIFOLD ABNORMAL MKY01EG007_ZV01 H 2 PR IN CASING/CYLIND ABNORMAL DCS 00
KG/CM
<95%,<90%H2
MKY01EG007_ZV02 H2 PURITY IN CASING LOW/V.LOW DCS
IN AI
88 LP BP SYSTEM ALARMS LBB01DP001_XT02 REHEATER SAFETY VLV OPEN DCS 00

MAX05EG001_ZV01 HPSU FAULTY FAULTY DCS

MAX05EG001_ZV03 BOTH CIRCULATION PUMPS(HPSU) ON DCS

MAX05EZ100_ZV01 HPSU EMERGENCY OFF DCS

MAY02EG001_ZV03 LP BY PASS 1TRIP RELEASED DCS

MAY02EG001_ZV04 LP BY PASS 2TRIP RELEASED RELEASED DCS

BY EDN LPBP CONDENSER PROT OPTD TRUE DCS 01A

89 LUB OIL/JACKING OIL SYSTEM FAULT MAV10EG001_ZV02 JACKING OIL PRESSURE VERY LOW <150 KG/CM2 DCS 00

MAA01EG001-ZV06 LUB OIL PRESSURE AFT FILTER LOW 1.2 KG/CM2 DCS

23 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

MAV10EG001_ZV03 RESERVE OIL PUMP ON DCS

MAV10EG001_ZV04 SWITCH OFF OIL PUMPS(AOP) OFF >7KG/CM2 DCS

MAV10EG001_ZV05 PRESSURE-OIL PRESS LOW <4.5 KG/CM2 DCS

MAV10EG001_ZV06 LUB OIL PRESSURE V.LOW <1.1K KG/CM2 DCS

MAV10EG001_ZV08 BOTH AC&DC EOP ON DCS

MAV10EG001_ZV09 LUB OIL FILTER CHOKED >0.9 KG/CM2 DCS

MAV24AP001_XG01 EMERGENCY OIL PUMP(DC) OVERLOADED DCS

MAV32AP001_XG01 JACKING OIL PMP(DC) OVERLOADED DCS

MAV35CP016_XG01 JACKING OIL FILTER CHOKED >4.2 KG/CM2 DCS

MAV42CT016A_XH01 OIL PUMP AFTER OIL COOLERS HIGH > 50 DEG.C DCS

MAV85CL015_XG01 LEAKAGE OIL TANK LEVEL HIGH HIGH > 50% DCS

MAX89CL015_XG01 WASTE OIL TANK LEVEL. HIGH >50% DCS


>850,>1200
MAY00EY001_ZV16 OIL TANK LEVEL LOW DCS
MM
BY EDN JOP TRIPPED TRUE DCS 01A

BY EDN DC SUPPLY TO EOP/JOP FAILED TRUE DCS 01A

90 TURBINE PROTECTION ALARMS MAY01EC101_ZA16 OVER SPEED TRIP DURING TEST > 3300RPM DCS 00

MAY01EZ000_XT02 GENERATOR PROTECTION OPERATED DCS


>VARIABLE,S
MAG01EZ100_ZK98 COND.PRESSUR ELEC(VPS) TRIP DCS
ETPOINT
DELP>0
MAG01EZ100_ZV06 COND.PRESSURE(VSP) HIGH DCS
KG/CM2
DETP>0KG/C
MAG01EZ100_ZV17 COND.PRESSURE(VSP) TRIP DCS
M2
MAY01DE001_XT01 LOAD SHEDDING RELAY OPERATED DCS

MAY01EZ001_XT01 EMERGENCY TURB TRIP CONTROL ROOM OPERATED DCS

MAY01EZ001_ZV06 AXIAL SHIFT TRIP >+1,<-1 MM DCS

MAY01EZ110 MFT TRIP DCS


>0.3 KG/CM2
MAY01EZ110ZV01 COND.PRESSURE ELEEC TRIP DCS
(ABS)
MAY10CG001C_XG01 OVER SPEED TRIP1 OPERATED >3300RPM DCS

MAA01EG001_ZV01 TURBINE TRIP GEAR OPERATED OPERATED TRIPPED DCS

MAA01EG001_ZV02 TURB TRIPPED ON LOW TRIP OIL PRESS TRIPPED <2 KG/CM2 DCS
>+.05,<-0.5
MAD12CY011_XH01 AXIAL SHIFT HIGH HIGH DCS
MM
>0.3
MAG01CG011E_XG51 CONDENSER PRESSUR MECH TRIP TRIP DCS
KG/CM2(ABS)
>VARIABLE,S
MAG01EZ100_XK95 COND PRESS ELEC(VSP) HIGH* HIGH DCS
ETPOIN
MAA00EC000_XT01 TURB TRIP FROM ATRS OPERATD DCS

24 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

MAA00EG001_ZV01 LP OUTER CAS REAR TEMP HIGH >90 DEG C DCS

MAA00EG001_ZV02 LP OUTER CASING REAR TEMP V.HIGH >110DEG.C DCS

MAA00EG001_ZV08 HYD COND PROT NOT IN OPER POSIT TRUE DCS


>+55, <-55
MAA00EG001_ZV28 DIFF TEMP HP CAS TOP BOTT HIGH DCS
DEG K
>+70,<-70 DEG
MAA00EG001_ZV29 DIFF TEMP HP CAS TOP BOTT VERY HIGH DCS
K
>+30,<-30 DEG
MAA00EG001_ZV30 DIFF TEMP IP CAS TOP BOTT HIGH DCS
K
>+45,<-45 DEG
MAA00EG001_ZV31 DIFF TEMP IP CAS TOP BOTT VERY HIGH DCS
K
MAA00EGOO1_ZV16 OPERATION WITHOUT LPBP STATION TRUE DCS

MAA01EGOO1_ZV03 MANUAL TURBINE TRIP OPERATED DCS

MAV10EG001_ZV01 OIL VAPOUR EXTRACTOR NOT ON DCS

MAV10EG001_ZV07 TURBINE GEARING NOT ON DCS

MKQ00EG001_ZV03 BOTH BRG EXHUST FAN ON /OFF DCS

MKY01EG001_ZV02 LEVEL SWITCHES MALFUNCTION DCS


>38, >50 DEG
MKY01EG010_ZV07 COOL WATER TMP BRF/AFT CLR HIGH DCS
.C
PGB33AA001_XN01 CONTROL VALVE NOT IN AUTO MODE DCS

91 SEAL OIL SYSTEM FAULT MKW00EG001_ZA01 DC SO PUMP ON ON DCS 00

MKW00EG001_ZV03 BOTH S.O.VAC.PUMPS ON/OFF TRUE DCS

MKW00EG001_ZV06 BOTH S.O..PUMPS ON/OFF TRUE DCS

MKW10EE001_ZV02 SEAL OIL PUMP-1 TRIPPED DCS

MKW10EE001_ZV03 SEAL OIL PUMP-2 TRIPPED DCS

MKW10EE003_ZV01 S.O VACUUM-1 PUMP TRIPPED DCS

MKW10EE003_ZV02 S.O VACUUM-2 PUMP TRIPPED DCS

MKW13AP001_ZV01 DC S.O PUMP TRIPPED DCS

MKY01EG007_ZV03 TMP H2/AIR-S SO DRAIN HIGH >70 DEG C DCS

MKY01EG007_ZV04 PR.IN SO.VAC.TANK HIGH >-0.4KG/CM2 DCS

MKY01EG008_ZA01 SO TEMP BFR CLR HIGH >50 DEG C DCS

MKY01EG008_ZA05 DP ACR SO FILTER HIGH >1.2 KG/CM2 DCS


<
MKY01EG008_ZV04 S.O.PUMPS ON &PR. LOW DCS
5.0,<8.5KG/CM
<0.9 , > 1.7
MKY01EG009_ZV09 SO DP TS/H2 OR ES/H2 SIDE LOW/HIGH DCS
KG/CM2
MKY01EG009_ZV10 SO DP PRES. TS/ES LOW <4.5 KG/CM2 DCS
>50, >55
MKY01EG010ZV03 S.O TEMP AFTER CLR HIGH/V.HIGH DCS
DEG.C
MKY01EZ117_XK97 S.O TEMP AFTER COOLER DISCREPENCY DCS

25 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

92 TG SLC NOT ON LCB00EE001_XA43 SLC COND PMPS NOT ON DCS 01M

MAC01EE001_XA43 SLC-LP WATER INJEC NOT ON DCS

MAL00EE001_XA43 SLC DRAINS NOT ON DCS

MAV23EE001_XA43 SLC AUX OIL PUMP NOT ON DCS

MAV24EE001_XA43 SLC EMERG OIL PUMP NOT ON DCS

MAV32EE001_XA43 SLC JACKING OIL PUMP NOT ON DCS

MAX51EE001_XA43 SLC EXTRACTION NRVS NOT ON DCS

MKQ00EE001_ZV01 SLC BRG.EX. FAN NOT ON DCS

MKW10EE001_ZV01 SLC SO PUMP NOT ON DCS


MODIFIED IN LINE WITH
93 MAIN STEAM TEMP HIGH/LOW MAA00EC001_ZA16 MAIN STEAM TEMP BEF ESV1/2 S/H LOW <15 DEG.C DCS 01M
CUSTOMER COMMENTS
MAA00EC001_ZA17 MAIN STEAM TEMP BEF LPBP S/H LOW <15 DEG.C DCS

MAA00EG001_ZV32 MAIN STEAM TEMP HIGH HIGH >551 DEG. C DCS

MAA00EG001_ZV33 HRH STEAM TEMP HIGH HIGH >551 DEG.C DCS

MAA50CT022_XH01 HPT EXHAUST STM TEMP HIGH >485 DEG.C DCS

MAY01EZ001_ZV05 HPT EXHAUST STM TEMP V.HIGH >510 DEG.C DCS

94 TG BRG METAL TEMP ABNOR TRIP MAA00EG001_ZV18 HPT FRONT BRG METAL TEMP HIGH >MAX DCS 00

MAA00EG001_ZV19 HPT REAR BRG METAL TEMP HIGH >MAX DCS

MAA00EG001_ZV20 HPT THRUST BRG METAL TEMP HIGH >MAX DCS

MAA00EG001_ZV21 IPT/LPT REAR BRG METAL TEMP HIGH >MAX DCS

MAA00EG001_ZV22 TURBINE BRG METAL TEMP HIGH HIGH DCS

MAY01EZ110_ ZA01 HPT FRONT BRG METAL TEMP VHIGH TRIP >130 DEG.C DCS

MAY01EZ110_ZA02 HPT REAR BRG METAL TEMP V.HIGH TRIP >130 DEG.C DCS

MAY01EZ110_ZA03 HPT THRUST BRG METAL TEMP V.HIGH TRIP >130 DEG.C DCS

MAY01EZ110_ZA04 IPT REAR BRG METAL TEMP V.HIGH TRIP >130 DEG.C DCS

MAY01EZ110ZA05 LPT REAR BRG METAL TEMP V.HIGH TRIP >130 DEG.C DCS

MAY01EZ110ZV06 TURBINE BRG METAL TEMP V.HIGH TRIP >130 DEG.C DCS

MKY01EG006_ZV04 GEN/S.RING BRG FRNT/REAR METAL TMP HIGH >90 DEG,C DCS

MKY01EG006_ZV08 GEN/S.RING BRG FRNT/REAR MRTAL TMP V.HIGH >130 DEG.C DCS

MKY01EZ114_XK97 GEN.BEARING METAL TS DISCREPANCY DCS

MKY01EZ115_XK97 GEN.BEARING METAL ES DISCREPANCY DCS

MKY01EZ116_XK97 SLIP RING BEARING TEMP DISCREPANCY DCS

95 TG BRG/SHAFT VIB/SHAFT EXP. ABNORMAL MAA.00EG001_ZV09 TURB BRG VIBRATION HIGH HIGH >84 DCS 00

26 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

MAA.00EG001_ZV10 TURB BRG VIBRATION VERY HIGH >106 DCS

MA.A00EG001_ZV11 TURB SHAFT VIBRATION HIGH >200 DCS

M.AA00EG001_ZV12 TURB SHAFT VIBRATION V.HIGH >320 DCS

MAA00EG001_ZV13 SHAFT EXPANSION HIGH >+30,>-3mm DCS

MAAA00EG001_ZV23 IP+LP ROTOR EXPANSION HIGH +36,<-3.0mm DCS


+3.5,<-
MAA00EG001_ZV25 HP/IP DIFF EXP. HIGH DCS
5.0,>6.5mm
MAA00EG001_ZV09 GEN/SLIP RING BRG VIBRATION HIGH >84MU DCS

MAA00EG001_ZV10 GEN/SLIP RING BRG VIBRATION V.HIGH >106 DCS

MAA00EG001_ZV11 GEN/SLIP RING SHAFT VIBRATION HIGH >200 DCS

MAA00EG001_ZV12 GEN/SLIP RING SHAFT VIBRATION V.HIGH >320 DCS

MAA01EG001_XT01 SHAFT ECCENTRICITY ABNORMAL >400 DCS

96 TG SYSTEM FAULT MAA00EG001_ZV15 HP/IP TRIMM DEVICE FAULT DCS 00

MAA00EG001_ZV17 OPER.WITH OUT LPBP STATION FAULT DCS

MAD00DU001_XT05 VIBR &EXPN MEARSMENT FAULT DCS

MAL00EG001_ZV01 DRAINS FAULT FAULT DCS

MAM20CT001A_XH01 HPT INTEL U-RING FAILURE FAILURE >355 DEGC DCS

MAW01DP001_XT05 GLND STM PRESS CNTRL FAULT DCS

MAY00EY001_ZV02 FIRE PROT CHAN 1 FAULT DCS

MAY00EY001_ZV06 FIRE PROT CHAN 2 FAULT DCS

MAY00EY001_ZV15 FIRE PROT OIL TANK LEVEL FAULT DCS

MAY01DE001_XT05 LOAD SHEDDING RELAY 24V FAULT DCS

MAY01EZ110_XT05 220 V ELECT TURBINE TRIP FAULT DCS

MKY01EG008_ZV06 DC SO PUMP ABNORMAL DCS

MKY01EG011_ZA01 220V DC TO CXW01A N.AVAILABLE DCS

MKY01EG011_ZA02 24V DC TO CXW01B N.AVAILABLE DCS

MKY01EZ110_ZV01 GEN MECH PROT(CH 1) TRIPPED DCS

MKY01EZ110_ZV02 GEN MECH PROT(CH 2) TRIPPED DCS

97 SH/RH/DRUM METAL TEMP ABNORMAL HAD10CT001 TEMP. (METAL) AT DRUM - L HIGH DCS ANALOG I/O LIST 00

HAD10CT002 TEMP. (METAL) AT DRUM - L HIGH DCS

HAD10CT003 TEMP. (METAL) AT DRUM -MIDDLE HIGH DCS

HAD10CT004 TEMP. (METAL) AT DRUM -MIDDLE HIGH DCS

HAD10CT005 TEMP. (METAL) AT DRUM - R HIGH DCS

27 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

HAD10CT006 TEMP. (METAL) AT DRUM - R HIGH DCS

HAH20CT001 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT002 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT003 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT004 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT005 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT006 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT007 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT008 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT009 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT010 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT011 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT012 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT013 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT014 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT015 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT016 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT017 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT018 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT019 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT020 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT021 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT022 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH20CT023 TEMP.(METAL) AT LTSH TUBE -L HIGH 467 Deg C DCS

HAH35CT001 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT002 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT003 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT004 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT005 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT006 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT007 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT008 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

28 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

HAH35CT009 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT010 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT011 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT012 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT013 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT014 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT015 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT016 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT017 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT018 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT019 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT020 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT021 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT022 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT023 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT024 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT025 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT026 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT027 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT028 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT029 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT030 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT031 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT032 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT033 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT034 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT035 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT036 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT037 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT038 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT039 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT040 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

29 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

HAH35CT041 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT042 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT043 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT044 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT045 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH35CT046 TEMP. (METAL) AT PSH TUBES HIGH 551 Deg c DCS

HAH50CT001 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT002 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT003 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT004 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT005 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT006 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT007 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT008 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT009 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT010 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT011 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT012 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT013 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT014 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT015 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT016 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT017 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT018 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT019 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT020 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAH50CT021 TEMP. (METAL) AT FSH TUBES HIGH 579 Deg c DCS

HAJ20CT001 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT002 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT003 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT004 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT005 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

30 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

HAJ20CT006 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT007 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT008 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT009 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT010 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT011 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT012 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT013 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT014 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT015 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT016 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT017 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT018 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT019 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT020 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT021 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT022 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT023 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT024 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT025 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

HAJ20CT026 TEMP.(METAL) AT RH TUBES HIGH 605 Deg C DCS

EAF01CL001 COAL BUNKER-A LEVEL LOW/HIGH DCS

EAF02CL001 COAL BUNKER-B LEVEL LOW/HIGH DCS

EAF03CL001 COAL BUNKER-C LEVEL LOW/HIGH DCS

EAF04CL001 COAL BUNKER-D LEVEL LOW/HIGH DCS

EAF05CL001 COAL BUNKER-E LEVEL LOW/HIGH DCS

EAF06CL001 COAL BUNKER-F LEVEL LOW/HIGH DCS

98 AIR FLOW < 30% / O2 LOW BY EDN AIR/COAL RATIO NOT OK DCS DESCRIPTION MODIFIED 01M

BY EDN OXYGEN LOW DCS

99 MILL BOWL DP HIGH BY EDN MILL-A TO BOWL DP HIGH FSSS 00

BY EDN MILL-B TO BOWL DP HIGH FSSS

BY EDN MILL-C TO BOWL DP HIGH FSSS

31 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN MILL-D TO BOWL DP HIGH FSSS

BY EDN MILL-E TO BOWL DP HIGH FSSS

BY EDN MILL-F TO BOWL DP HIGH FSSS

100 MILL OUTLET TEMP HIGH BY EDN MILL-A OUTLET TEMPERATURE HIGH 110 Deg C FSSS 00

BY EDN MILL-B OUTLET TEMPERATURE HIGH 110 Deg C FSSS

BY EDN MILL-C OUTLET TEMPERATURE HIGH 110 Deg C FSSS

BY EDN MILL-D OUTLET TEMPERATURE HIGH 110 Deg C FSSS

BY EDN MILL-E OUTLET TEMPERATURE HIGH 110 Deg C FSSS

BY EDN MILL-F OUTLET TEMPERATURE HIGH 110 Deg C FSSS

101 MILL NO COAL FLOW BY EDN MILL-A NO COAL FLOW TRUE -- FSSS 00

BY EDN MILL-B NO COAL FLOW TRUE -- FSSS

BY EDN MILL-C NO COAL FLOW TRUE -- FSSS

BY EDN MILL-D NO COAL FLOW TRUE -- FSSS

BY EDN MILL-E NO COAL FLOW TRUE -- FSSS

BY EDN MILL-F NO COAL FLOW TRUE -- FSSS

102 MILL OFF HAG/CAG OPEN BY EDN MILL-A OFF&HAG N CLSD/CAD>5% OPN TRUE -- FSSS 00

BY EDN MILL-B OFF&HAG N CLSD/CAD>5% OPN TRUE -- FSSS

BY EDN MILL-C OFF&HAG N CLSD/CAD>5% OPN TRUE -- FSSS

BY EDN MILL-D OFF&HAG N CLSD/CAD>5% OPN TRUE -- FSSS

BY EDN MILL-E OFF&HAG N CLSD/CAD>5% OPN TRUE -- FSSS

BY EDN MILL-F OFF&HAG N CLSD/CAD>5% OPN TRUE -- FSSS

103 PA HDR PRESS LOW/V.LOW BY EDN ANY PA FAN ON & PA HDR PRESSURE >5 SEC LOW FSSS 00

BY EDN ANY PA FAN ON & PA HEADER PRESSURE V.LOW FSSS

BY EDN ANY PA FAN ON & LOSS OF PRIMARY AIR TRUE FSSS

BY EDN ALL PA/FD FANS OFF & ANY PULV ON TRUE FSSS

104 PURGE INTERRUPT BY EDN STAGE-I PURGE INTERRUPTED TRUE -- FSSS 00

BY EDN PURGE READY NOT AVAILABLE TRUE -- FSSS

BY EDN STAGE-II PURGE INTERRUPTED TRUE -- FSSS

105 SCAN FAN TRBL BY EDN 24VDC OUT/FDFs OFF & SCNR DMPR NOT OPEN -- FSSS 00

BY EDN ANY SCANNER FAULT TRUE -- FSSS

BY EDN BOTH SCAN FANS OFF & NO MFT TRUE -- FSSS

BY EDN LOSS OF UNIT CRITICAL POWER +24V DC TRUE -- FSSS

32 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN SCAN FAN-A FAILED TO START/ TRIPPED TRUE -- FSSS

BY EDN SCAN FAN-B FAILED TO START/ TRIPPED TRUE -- FSSS

BY EDN BOTH SCAN FAN FAILED TO START/ TRIPPED TRUE -- FSSS

106 UNIT FLAME FAILURE BY EDN UNIT FLAME FAILURE TRIP TRIP -- FSSS 00

107 HFO/LFO PRESS LOW BY EDN HFO PMP ON & DISCH HDR PR LOW FOCP 00

BY EDN LDO PMP ON & DISCH HDR PR LOW FOCP

108 HFO/LFO PUMP TRIPPED BY EDN HFO PUMP-A TRIPPED -- FOCP 00

BY EDN HFO PUMP-B TRIPPED -- FOCP COMMON FOR BOILERS 1&2

BY EDN HFO PUMP-C TRIPPED -- FOCP

BY EDN LFO PUMP-A TRIPPED -- FOCP

BY EDN LFO PUMP-B TRIPPED -- FOCP COMMON FOR BOILERS 1&2

BY EDN LFO PUMP-C TRIPPED -- FOCP

109 ANY MILL AIR FLOW LOW BY EDN MILL-A AIR FLOW LOW DCS 00

BY EDN MILL-B AIR FLOW LOW DCS

BY EDN MILL-C AIR FLOW LOW DCS

BY EDN MILL-D AIR FLOW LOW DCS

BY EDN MILL-E AIR FLOW LOW DCS

BY EDN MILL-F AIR FLOW LOW DCS

110 ANY MILL LUB OIL SYS TRBL BY EDN MILL-A SUMP OIL LVL LOW > 10mm CL SG PKG 00

BY EDN MILL-A LUB OIL TEMP HIGH > 80°C SG PKG

BY EDN MILL-A LUB OIL PRESS LOW < 3.5 BAR SG PKG

BY EDN MILL-A LO DISCH FILT DP HIGH > 1.5 BAR SG PKG

BY EDN MILL-B SUMP OIL LVL LOW > 10mm CL SG PKG

BY EDN MILL-B LUB OIL TEMP HIGH > 80°C SG PKG

BY EDN MILL-B LUB OIL PRESS LOW < 3.5 BAR SG PKG

BY EDN MILL-B LO DISCH FILT DP HIGH > 1.5 BAR SG PKG

BY EDN MILL-C SUMP OIL LVL LOW > 10mm CL SG PKG

BY EDN MILL-C LUB OIL TEMP HIGH > 80°C SG PKG

BY EDN MILL-C LUB OIL PRESS LOW < 3.5 BAR SG PKG

BY EDN MILL-C LO DISCH FILT DP HIGH > 1.5 BAR SG PKG

BY EDN MILL-D SUMP OIL LVL LOW > 10mm CL SG PKG

BY EDN MILL-D LUB OIL TEMP HIGH > 80°C SG PKG

33 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN MILL-D LUB OIL PRESS LOW < 3.5 BAR SG PKG

BY EDN MILL-D LO DISCH FILT DP HIGH > 1.5 BAR SG PKG

BY EDN MILL-E SUMP OIL LVL LOW > 10mm CL SG PKG

BY EDN MILL-E LUB OIL TEMP HIGH > 80°C SG PKG

BY EDN MILL-E LUB OIL PRESS LOW < 3.5 BAR SG PKG

BY EDN MILL-E LO DISCH FILT DP HIGH > 1.5 BAR SG PKG

BY EDN MILL-F SUMP OIL LVL LOW > 10mm CL SG PKG

BY EDN MILL-F LUB OIL TEMP HIGH > 80°C SG PKG

BY EDN MILL-F LUB OIL PRESS LOW < 3.5 BAR SG PKG

BY EDN MILL-F LO DISCH FILT DP HIGH > 1.5 BAR SG PKG

111 PULV. CONTROL SYSTEM TRBL BY EDN PULV. TRIP TRUE FSSS 00

BY EDN PULV. IGNITION PERMIT NOT AVAILBL TRUE FSSS

BY EDN AUTO PULV. UNSUCCESSFUL START TRUE FSSS

BY EDN PULV. UNSUCCESSFUL SHUTDOWN TRUE FSSS

BY EDN PULV. BOWL DP HIGH FSSS

BY EDN PULV. OFF & HAG NOT CLOSED OR CAD> 5% OPEN TRUE FSSS

BY EDN PULV. O/L TEMP LOW FROM DDCMIS TRUE FSSS

BY EDN PULV. O/L TEMP HIGH FSSS

112 HP BP SYSTEM TRBL BY EDN HPBP-1 DOWNSTREAM TEMP HIGH >350 DEG C DCS 00

BY EDN HPBP-2 DOWNSTREAM TEMP HIGH >350 DEG C DCS

BY EDN HPBP VLV BP-1 VALVE MALFUNCTIONING TRUE DCS

BY EDN HPBP VLV BP-1 DURING STARTUP STUCK DCS

BY EDN HPBP VLV BP-2 VALVE MALFUNCTIONING TRUE DCS

BY EDN HPBP VLV BP-2 DURING STARTUP STUCK DCS

BY EDN HPBP-1 DOWNSTREAM TEMP V.HIGH >370 DEG C DCS

BY EDN HPBP-2 DOWNSTREAM TEMP V.HIGH >370 DEG C DCS

BY EDN HPBP CONTROL PR DEVIATION V.HIGH DCS 01A

BY EDN GCB OFF & HP/LP BYPASS VLV LESS THAN 10% TRUE DCS 01A
SEQ CONTROL SCHEME
113 COLTCS SYSTEM TRBL PAH10EH201 COLTCS SYSTEM GROUP FAULT ALARM DCS 00
FOR COLTCS
BY EDN COLTCS-A EMG. BACKWASH SEQ ON DCS

BY EDN COLTCS-A BALL RECIRCULATING PMP MTR TRIPPED DCS

BY EDN COLTCS-A BALL SCREEN ACT FAIL TO OPEN DCS

34 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN COLTCS-A BALL SCREEN ACT FAIL TO CLOSE DCS

BY EDN COLTCS-A OVERSIZE BALL COUNT SHORT DCS

BY EDN COLTCS-A TOTAL BALL COUNT SHORT DCS

BY EDN COLTCS-A BACKWASH SEQUENECE FAILURE DCS

BY EDN COLTCS-A BALL SEPARATOR DP HIGH DCS

BY EDN COLTCS-A BALL SEPARATOR DP V.HIGH DCS

BY EDN COLTCS-A DP TRANSMITTER FAILED DCS

BY EDN COLTCS-A BACKWASH SEQ ON DCS

BY EDN COLTCS-B EMG. BACKWASH SEQ ON DCS

BY EDN COLTCS-B BALL RECIRCULATING PMP MTR TRIPPED DCS

BY EDN COLTCS-B BALL SCREEN ACT FAIL TO OPEN DCS

BY EDN COLTCS-B BALL SCREEN ACT FAIL TO CLOSE DCS

BY EDN COLTCS-B OVERSIZE BALL COUNT SHORT DCS

BY EDN COLTCS-B TOTAL BALL COUNT SHORT DCS

BY EDN COLTCS-B BACKWASH SEQUENECE FAILURE DCS

BY EDN COLTCS-B BALL SEPARATOR DP HIGH DCS

BY EDN COLTCS-B BALL SEPARATOR DP V.HIGH DCS

BY EDN COLTCS-B DP TRANSMITTER FAILED DCS

BY EDN COLTCS-B BACKWASH SEQ ON DCS


SEQ CONTROL SCHEME
114 SCS SYSTEM TRBL PCA10EH201 SCS SYSTEM TROUBLE TRUE DCS 00
FOR SCS
BY EDN SCS-A DP V.HIGH DCS

BY EDN SCS-A DP HIGH DCS

BY EDN SCS-A FLUSHING START COMMAND FROM DPT TRUE DCS

BY EDN SCS-A SYSTEM AUTO STOP DCS

BY EDN SCS-A RUN TIME FAILURE DCS

BY EDN SCS-A MCC DISTBD DCS

BY EDN SCS-A DEBRIS DISCH VLV FAILED TO OPEN TRUE DCS

BY EDN SCS-A DEBRIS DISCH VLV FAILED TO CLOSE TRUE DCS

BY EDN SCS-B SYSTEM TROUBLE TRUE DCS

BY EDN SCS-B DP V.HIGH DCS

BY EDN SCS-B DP HIGH DCS

BY EDN SCS-B FLUSHING START COMMAND FROM DPT TRUE DCS

35 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

BY EDN SCS-B SYSTEM AUTO STOP DCS

BY EDN SCS-B RUN TIME FAILURE DCS

BY EDN SCS-B MCC DISTBD DCS

BY EDN SCS-B DEBRIS DISCH VLV FAILED TO OPEN TRUE DCS

BY EDN SCS-B DEBRIS DISCH VLV FAILED TO CLOSE TRUE DCS

115 MS TEMP SH O/L TRBL BY EDN MS TEMP AT SH O/L TRBL DCS ACS 00

BY EDN MS TEMP AT SH O/L-L LOW DCS

BY EDN MS TEMP AT SH O/L-L HIGH DCS

BY EDN MS TEMP AT SH O/L-R LOW DCS

BY EDN MS TEMP AT SH O/L-R HIGH DCS

116 HRH STM TEMP RH O/L TRBL BY EDN HRH STM TEMP AT RH O/L TRBL DCS ACS 00

BY EDN HRH STM TEMP AT RH O/L-L LOW DCS

BY EDN HRH STM TEMP AT RH O/L-R HIGH DCS

117 GR FAN-A/B TRIPPED BY EDN GR FAN-A TRIPPED --- DCS ANALOG I/O LIST 00

BY EDN GR FAN-B TRIPPED --- DCS

118 GR FAN-A/B VIB/ BRG/WDG TEMP HIGH BY EDN GR FAN-A WDG TEMP HIGH T+5 DEGC DCS ANALOG I/O LIST 00

BY EDN GR FAN-A MTR BRG TEMP HIGH 85 DEGC DCS

BY EDN GR FAN-A BRG TEMP HIGH 77 DEGC DCS

BY EDN GR FAN-A BRG VIB HIGH 6.3 mm/s DCS

BY EDN GR FAN-B WDG TEMP HIGH T+5 DEGC DCS

BY EDN GR FAN-B MTR BRG TEMP HIGH 85 DEGC DCS

BY EDN GR FAN-B BRG TEMP HIGH 77 DEGC DCS

BY EDN GR FAN-B BRG VIB HIGH 6.3 mm/s DCS

119 VACCUM LOW BY EDN VACCUM LOW TRUE DCS 01A

120 DRUM LVL HIGH/ LOW BY EDN DRUM LVL HIGH/ LOW TRUE DCS 01A

121 CEP DISCH PRESS LOW BY EDN CEP DISCH PR LOW TRUE DCS 01A

122 AIR MOTOR ON BY EDN AIR MOTOR ON TRUE DCS 01A

123 EMER DRUM DRN VLV OPEN BY EDN EMER DRUM DRAIN VLV OPEN TRUE DCS 01A

124 BFP-A SUC PR LOW BY EDN BFP-A SUC PR LOW TRUE DCS 01A

125 BFP-A SUC FLOW LOW & RC VLV NOT OPEN BY EDN BFP-A SUC FLOW LOW & RC VLV NOT OPEN TRUE DCS 01A

126 BFP-B SUC PR LOW BY EDN BFP-B SUC PR LOW TRUE DCS 01A

127 BFP-B SUC FLOW LOW & RC VLV NOT OPEN BY EDN BFP-B SUC FLOW LOW & RC VLV NOT OPEN TRUE DCS 01A

36 OF [37]
ALARM SCHEDULE
PROJECT: 4X270 MW BHADRADRI TPS
DRG. NO. PE-DG-411-145-I202; REV01

128 BFP-C SUC PR LOW BY EDN BFP-C SUC PR LOW TRUE DCS 01A

129 BFP-B SUC FLOW LOW & RC VLV NOT OPEN BY EDN BFP-C SUC FLOW LOW & RC VLV NOT OPEN TRUE DCS 01A

130 VACCUM PMP-1 TRIP BY EDN VACCUM PMP-1 TRIP TRUE DCS 01A

131 VACCUM PMP-2 TRIP BY EDN VACCUM PMP-2 TRIP TRUE DCS 01A

132 SEAL OIL/H2 DP HIGH BY EDN SEAL OIL/ H2 DP HIGH TRUE DCS 01A

133 IA/SA PRESSURE LOW BY EDN IA/SA PRESSURE LOW TRUE DCS 01A

134 CAS SYSTEM TROUBLE BY EDN CAS SYSTEM TROUBLE LOW TRUE DCS 01A

135 TSC TROUBLE BY EDN TSC TROUBLE TRUE DCS 01A

136 HOTWELL MU PMP DISCH HDR PR LOW BY EDN HOTWELL MU PMP DISCH HDR PR LOW DCS 01A

137 CST TANK LVL ABNORMAL BY EDN CST TANK LVL ABNORMAL DCS 01A

138 AIR/COAL RATIO NOT OK/ O2% LOW BY EDN AIR/COAL RATIO NOT OK/ O2% LOW TRUE DCS 01A

139 FURNACE TEMP TROUBLE BY EDN FURNACE TEMP TROUBLE DCS 01A

140 STEAM PARAM FOR TG ABNORMAL BY EDN STEAM PARAM FOR TG ABNORMAL DCS 01A

141 TURBINE TRIP BY EDN TURBINE TRIP DCS 01A