Вы находитесь на странице: 1из 15

Screening

Screening
 Semi-conductor screen
 Metallic screen / sheath

 Semi-conductor screen:
– Prevent electric field concentration
– Protection of insulation from electric
discharges

 Metallic screen:
– Nullify electric field outside cable

7/1/2016 Screening 2
Metallic Screen
 Nullify electric field outside cable:
– High voltage wires produce electric field around them which may affect
operation of surrounding electric equipment.
– HV cables may induce unwanted voltages in cables running in parallel.
– Affect operation of control cables
– A metallic screen can be considered as grounded Faraday’s cage.

 To prevent electric field concentration


– Protects outer jacket (outer sheath) from electric field discharges

 Draining the capacitive currents passing through the insulator


– Acts as second electrode of the capacitor formed by the cable

7/1/2016 Screening 3
Metallic Screen
 Circulation of currents induced by external magnetic fields
– Prevents screened control cables from effects of magnetic fields induced by
power cables in the vicinity.

 Draining the zero-sequence short-circuit currents


– In case of earth fault, acts as return path for part of zero-sequence currents.
– This determines size of metallic screen

 Prevent insulation from humidity


– Forms a radial barrier to prevent humidity from penetrating cable
– Presence of strong electric field and humidity together deteriorates insulation
by ‘watertreeing’.

7/1/2016 Screening 4
Types of metallic screen
 Extruded lead alloy sheath
 Waterproofing guaranteed
 High electrical resistance, therefore minimum energy loss
 Excellent corrosion resistance
Heavy and expensive
Lead is a toxic metal
Limited capacity to expel zero-sequence short-circuit currents.

 Concentric copper wire screen with aluminium tape


 Lightweight and cost effective design,
 High short-circuit capacity
Low resistance needs special screen connections (earthing at one point or
crossbonding) to limit circulating current losses.

7/1/2016 Screening 5
Types of metallic screen
 Aluminium screen
 Lightweight structure
 High short-circuit capacity
 Impervious to moisture
Low resistance needs special screen connections to limit circulating current
losses.
Higher Eddy Current losses than other screen types.

7/1/2016 Screening 6
Voltages induced on Metallic Screen
 When an alternating current runs through the conductor of a cable, a
voltage proportional to following is generated on metallic screen:
– the induction current
– the distance between phases
– the length of the line
 Under normal operating conditions, this voltage may reach several tens of
volts.
– Earthing of screen can prevent risk of electrocution
 In case of SC faults induced voltage can reach few kV.
– Practically it remains lower than a level harmful to outer jacket.
 In case of lightning overvoltages or switching overvoltages, induced
voltage may reach several tens of kV
– Sheath voltage limiters are used to limit this voltage to prevent damage to outer
jacket.

7/1/2016 Screening 7
Metallic Screen Earthing: Single Point Earthing
 Cable sheaths are solidly bonded and earthed at one point
 Applicable for short length cables (<500m)
 Voltage present between sheath and ground (should be limited below 25V)
 No closed sheath circuit and no sheath circulation current loss
Need sheath voltage limiter (SVL)

7/1/2016 Screening 8
Metallic Screen Earthing: Two Point Earthing
 Cable sheaths are solidly bonded and earthed at both points
 Applicable for longer length cables (up to 1km)
 No equipotential cable required
 No need of SVL
Circulation current present in sheath causing loss and heating
Reduces current carrying capacity of cable

7/1/2016 Screening 9
Metallic Screen Earthing: Cross Bonding
 Cable sheaths are solidly bonded and earthed at both ends
 Cable sheaths are cross-bonded at equal interval in multiple of three, at
cable joints.
 The phase sum of the induced voltages will be zero
 No circulating current when cable laying is symmetrical
Link box with SVL are needed at cross-bonding points

7/1/2016 Screening 10
Metallic Screen Earthing :Cross Bonding and
Transposition

 For unsymmetrical cable laying the induced phase voltages are not equal.
Therefore, the phase sum of the voltages are not zero despite cross
bonding.
 The cables are transposed at each joint position and the cable sheaths are
cross connected
 Sheaths are earthed at every third joint position.
 the phase sum of the induced voltage on sheaths over three sections is zero
 No circulating currents, no losses and heating
Link boxes with SVL are needed.

7/1/2016 Screening 11
Metallic Screen Earthing :Cross Bonding and
Transposition

7/1/2016 Screening 12
Calculation for induced voltage on sheath

 For Trefoil formation:


𝑆𝑆
𝐸𝐸 = 2ω𝐼𝐼 𝑙𝑙𝑙𝑙 × 10−4 (V/km)
𝑟𝑟
 For Flat formation:
2𝑆𝑆
𝐸𝐸𝐴𝐴 = 𝑗𝑗ω𝐼𝐼 𝑙𝑙𝑙𝑙 + 𝑗𝑗 3 ln 2 × 10−4 (V/km)
𝑟𝑟
𝑆𝑆
𝐸𝐸𝐵𝐵 = 𝑗𝑗2ω𝐼𝐼 𝑙𝑙𝑙𝑙 × 10−4 (V/km)
𝑟𝑟
2𝑆𝑆
𝐸𝐸𝐶𝐶 = 𝑗𝑗ω𝐼𝐼 𝑙𝑙𝑙𝑙 − 𝑗𝑗 3 ln 2 × 10−4 (V/km)
𝑟𝑟
Where,
E, EA, EB, EC : induced voltages on sheath. S : Center to center
ω : angular frequency (2πf) distance between cable
I : Current r : Mean radius of sheath

7/1/2016 Screening 13
Losses in screen
 Losses in screen occur due to:
– losses caused by circulating currents
– losses caused by eddy currents

 IEC 60287-1-1 defines calculation method for losses in screen as well as


armour.

7/1/2016 Screening 14
Thank You!

7/1/2016 Screening 15

Вам также может понравиться