Академический Документы
Профессиональный Документы
Культура Документы
NFS-320
Intelligent Addressable
Fire Alarm System
Intelligent Fire Alarm Control Panels
General
The NFS-320 intelligent Fire Alarm Control Panel is part of the
ONYX® Series of Fire Alarm Controls from NOTIFIER.
As a stand-alone small-to-medium system, or as a large net-
work, the ONYX Series of products meets virtually every appli-
cation requirement.
Designed with modularity and for ease of system planning, the
NFS-320 can be configured with just a few devices for small
building applications, or for a large campus or high-rise applica-
tion. Simply add additional peripheral equipment to suit the
application.
NOTE: Unless called out with a version-specific “R” or “E” at the
7112pho1.jpg
end of the part number, “NFS-320” refers to models NFS-320,
NFS-320R, and NFS-320E; similarly, “CPU-320” refers to models
CPU-320, and CPU-320E.
Features NFS-320
• Listed to UL Standard 864, 9th edition.
• One isolated intelligent Signaling Line Circuit (SLC) Style 4, 6
• Remote ACK/Signal Silence/System Reset/Drill via monitor
or 7.
modules.
• Up to 159 detectors (any mix of ion, photo, thermal, or multi-
• Automatic time control functions, with holiday exceptions.
sensor) and 159 modules (Addressable pull stations, nor-
mally open contact devices, two-wire smoke, notification, or • Surface Mount Technology (SMT) electronics.
relay). 318 devices maximum. • Extensive, built-in transient protection.
• Standard 80-character display. • Powerful Boolean logic equations.
• Network option — 103 nodes supported (AFP-200, AFP-300/
FLASHSCAN® INTELLIGENT FEATURES:
400, NFS-320, NFS-640, NFS2-640, AFP1010, AM2020,
NFS-3030, NFS2-3030, NCA/NCA-2 Network Annunciator, • Poll 318 devices in less than two seconds.
DVC-EM, NCS Network Control Station, or ONYXWorks™ • Activate up to 159 outputs in less than five seconds.
Network Control Station) using wire or fiber-optic connec- • Multicolor LEDs blink device address during Walk Test.
tions.
• Fully digital, high-precision protocol (U.S. Patent 5,539,389).
• 6.0 amp power supply with four Class A/B built-in Notification
• Manual sensitivity adjustment — nine levels.
Appliance Circuits (NAC). Selectable System Sensor, Whee-
lock, or Gentex strobe synchronization. • Pre-alarm ONYX intelligent sensing — nine levels.
• Built-in Alarm, Trouble, Security, and Supervisory relays. • Day/Night automatic sensitivity adjustment.
• VeriFire® Tools online or offline programming utility. Upload/ • Sensitivity windows:
Download, save, store, check, compare, and simulate panel – Ion – 0.5 to 2.5%/foot obscuration.
databases. Upgrade panel firmware. – Photo – 0.5 to 2.35%/foot obscuration.
• Autoprogramming and Walk Test reports. – Laser (VIEW®) – 0.02 to 2.0%/foot obscuration.
• Optional universal 318-point DACT. – Acclimate Plus™ – 0.5 to 4.0%/foot obscuration.
• 80-character remote annunciators (up to 32). – HARSH™ – 0.5 to 2.35%/foot obscuration.
• EIA-485 annunciators, including custom graphics. – IntelliQuad – 1.0 to 4.0%/foot obscuration.
• Printer interface (80-column and 40-column printers). • Drift compensation (U.S. Patent 5,764,142).
• History file with 800-event capacity in nonvolatile memory, • Degraded mode — in the unlikely event that the CPU-320
plus separate 200-event alarm-only file. microprocessor fails, FlashScan detectors revert to degraded
• Alarm Verification selection per point, with tally. operation and can activate the CPU-320 NAC circuits and
• Autoprogramming and Walk Test reports. alarm relay. Each of the four built-in panel circuits includes a
Disable/Enable switch for this feature.
• Presignal/Positive Alarm Sequence (PAS).
• Multi-detector algorithm involves nearby detectors in alarm
• Silence inhibit and Auto Silence timer options.
decision (U.S. Patent 5,627,515).
• March time / temporal / California two-stage coding / strobe
• Automatic detector sensitivity testing (NFPA-72 compliant).
synchronization.
• Maintenance alert (two levels).
• Field-programmable on panel or on PC, with VeriFire Tools
program check, compare, simulate. • Self-optimizing pre-alarm.
• Full QWERTY keypad.
• Battery charger supports 18 – 200 amp hour batteries
• Non-alarm points for lower priority functions.
Sample
System
Options
7112blok.wmf
6856tool.tif
TB7: NAC#3
LEDs 15, 16 LED3: Earth Fault
(general board
ground fault).
TB6: NAC#4
LEDs 17, 18 LED10: SLC Loop
TB1: AC Power Ground Fault.
Connection
(non-power-limited):
Hot, Neutral, and
Earth Ground.
TB5: Relays:
Supervisory,
Security
TB4: Alarm Relay, Trouble Relay. SW1, SW2, System switches, J7: KDM-R2 LED1: Power On (AC or battery)
Output relays; power-limited only if SW3, SW4: “No Keyboard Connection LED2: Signals Silenced
connected to a power-limited source. Disable-Enable Operation”: LED3: Point Disabled
switches for Backup SW5 Acknowledge
Alarm, NACs LED4: System Trouble
7112bord.wmf SW6 Silence LED5: Supervisory
1 – 4 respectively.
SW7 Reset LED6: Security
LED7: Pre-Alarm
LED8: Fire Alarm
Network Diagram
RPT-
WF
NCS or
ONYXWorks Block Diagram
RPT-
WF
NOTI•FIRE•NET
24
Sample Node Configurations PRN
NFS-320
NFS2-640
KEY:
PRN NFN Twisted-Pair Wire ACS
NFN Dual Fiber-Optic Link
Other Interfaces LCD-80 FDU-80
ACS
PRN
OPTIONAL NCS or ONYXWorks
Style 7
Connection
PRN
NCA-2
7112conf.wmf
ACS
System Capacity condensing) at 32°C ± 2°C (90°F ± 3°F). However, the useful
life of the system's standby batteries and the electronic compo-
• Intelligent Signaling Line Circuits ......................................... 1 nents may be adversely affected by extreme temperature ranges
• Intelligent detectors ......................................................... 159 and humidity. Therefore, it is recommended that this system and
• Addressable monitor/control modules .............................. 159 its peripherals be installed in an environment with a normal room
• Programmable internal hardware and output circuits .......... 4 temperature of 15 – 27°C/60 – 80°F.
• Programmable software zones ........................................... 99
• Special programming zones ............................................... 14 Agency Listings and Approvals
• LCD annunciators per CPU-320/-320E .............................. 32 The listings and approvals below apply to the basic NFS-320
• ACS annunciators control panel. In some cases, certain modules may not be listed
per CPU-320/-320E ........................ 32 addresses x 64 points by certain approval agencies, or listing may be in process. Con-
sult factory for latest listing status.
Specifications • UL Listed: file S635
• CSFM: 7170-0028:244; 7165-0028:243
• Primary input power, CPU-320 board: 120 VAC, 50/60 Hz,
3.0 A. CPU-320E board: 220/240 VAC, 50/60 Hz, 1.5 A. • FM Approved
• Total output 24 V power: 6.0 A in alarm. • MEA: 128-07-E , NYFD Certificate #6007
NOTE: The power supply has a total of 6.0 A of available power. • City of Chicago
This is shared by all internal circuits.
• Standard notification circuits (4): 1.5 A each. Standards
• Four-wire detector power: 1.25 A. The NFS-320 complies with the following UL Standards and
• Non-resettable regulated power outputs: 1.25 A each. NFPA 72 Fire Alarm Systems requirements:
• Battery charger range: 18 AH – 200 AH. Use separate cabi- – UL 864 (Fire).
net for batteries over 25 AH. – UL 1076 (Burglary).
• Optional high-capacity (25 – 120 AH) battery charger: CHG- – LOCAL (Automatic, Manual, Waterflow and Sprinkler
120 (see CHG-120 data sheet, DN-6040). Supervisory).
• Float rate: 27.6 V. – AUXILIARY (Automatic, Manual and Waterflow) (requires
TM-4).
Cabinet Specifications – REMOTE STATION (Automatic, Manual, Waterflow and
Sprinkler Supervisory) (requires TM-4).
NFS-320 cabinet dimensions: BACKBOX, OUTSIDE: 18.240"
(46.33 cm) height, 5.77" (14.656 cm) deep. WITH DOOR: – PROPRIETARY (Automatic, Manual, Waterflow and Sprin-
18.870" (47.93 cm) wide x 18.469" (46.911 cm) high x 5.817" kler Supervisory). Not applicable for FM.
(14.775 cm) deep. BACKBOX, INSIDE: 18.120" (46.025 cm) • CENTRAL STATION (Automatic, Manual, Waterflow and
inner width, 5.175" (13.145 cm) inner depth. Sprinkler Supervisory) (requires UDACT).
– EMERGENCY VOICE/ALARM.
Temperature and Humidity Ranges
This system meets NFPA requirements for operation at 0 –
49°C/32 – 120°F and at a relative humidity 93% ± 2% RH (non-