Electrical network protection

Sepam Series 80
Configuration

Sepam label: ................................................................ zone industrielle


Application type: ......................................................... S80
Configuration file: ....................................................... ZI SEPT 25 2019
Date of last modification: ........................................... 9/25/2019
Date printed: ................................................................ 9/25/2019

Customer: .................................................................... VUI


Project: ......................................................................... SEPAM S80
Switchboard: ............................................................... 5.5KV DIESEL
Cubicle: ........................................................................ ZONE INDUSTRIAL
Contents

1. GENERAL SETTINGS .......................................................................................................................................... 3


1.1. Hardware setup ....................................................................................................................................... 3
1.2. General characteristics ............................................................................................................................ 3
1.3. CT-VT sensors ........................................................................................................................................ 4
1.4. CT/VT circuit supervision ......................................................................................................................... 5
1.5. Predefined control logic ........................................................................................................................... 6
1.6. Logic input/output assignment ................................................................................................................. 6
2. SET PROTECTIONS ............................................................................................................................................ 7
2.1. Substation S80 ....................................................................................................................................... 7
2.2. Protection units on ................................................................................................................................... 8
2.3. Customized tripping curve ....................................................................................................................... 8
2.4. 50/51: Phase overcurrent ........................................................................................................................ 9
2.5. 50N/51N: Ground fault ............................................................................................................................. 10
2.6. 50BF: Breaker failure ............................................................................................................................... 10
2.7. 46: Negative sequence current / unbalance ............................................................................................. 10
2.8. 27D: Positive sequence undervoltage ..................................................................................................... 10
2.9. 27R: Remanent undervoltage .................................................................................................................. 11
2.10. 27: Undervoltage ................................................................................................................................... 11
2.11. 59: Overvoltage ..................................................................................................................................... 11
2.12. 59N: Neutral voltage displacement ........................................................................................................ 11
2.13. 47: Negative sequence overvoltage ....................................................................................................... 11
2.14. 81H: Overfrequency ............................................................................................................................... 12
2.15. 81L: Underfrequency ............................................................................................................................. 12
2.16. 79: Recloser .......................................................................................................................................... 12
3. LOGIPAM SETTINGS ........................................................................................................................................... 13
3.1. Logipam ................................................................................................................................................... 13
4. DEFINITION OF EQUATIONS .............................................................................................................................. 14
4.1. Logic equations ....................................................................................................................................... 14
5. SET CONTROL MATRIX ...................................................................................................................................... 15
5.1. Protection matrix ..................................................................................................................................... 15
5.2. Control logic output matrix ....................................................................................................................... 18
5.3. Logic input matrix .................................................................................................................................... 19
5.4. Logic equation output variable matrix ...................................................................................................... 20
5.5. GOOSE input matrix ................................................................................................................................ 21
6. SET FUNCTIONS ................................................................................................................................................. 22
6.1. Fault recording ........................................................................................................................................ 22
6.2. DLG ......................................................................................................................................................... 23
1. GENERAL SETTINGS

1.1. Hardware setup

Sepam label: ................................................................................................................................................................................... zone industrielle Application type: S80 Model: Integrated UMI
MES120 (14 input + 6 output module) n°1 ..................................................................................................................................... Present
MES120 (14 input + 6 output module) n°2 ..................................................................................................................................... Present
MES120 (14 input + 6 output module) n°3 ..................................................................................................................................... Absent
MSA141 (1 analog output module) ................................................................................................................................................ Absent
ACE 949/959/937 (communication network interface) n°1 ........................................................................................................... Present Communication protocol Modbus Sepam address 1
Speed 19200 Bauds Parity Even
Unsecured
COM2 module ................................................................................................................................................................................. Absent
ACE 850 (communication network interface) (Ethernet) .............................................................................................................. Absent
Memory Cartridge Type: ................................................................................................................................................................. MMS
MCS025 (Synchro-check module) ................................................................................................................................................. Absent

1.2. General characteristics

Description Setting Description Setting


Network frequency 50 Hz Sepam working language UKEng-IEC
Main/feeder ANSI M/Fdr Time synchronization mode None
Phase rotation direction a_b_c Control voltage monitoring (Vaux) On
Active setting group for all protection functions. Setting group A Rated Vaux 48 Vdc
Remote protection settings enabled No Low threshold alarm 80 % Vaux
Remote control with select before operate (SBO) No High threshold alarm 120 % Vaux
Demand Interval 5 min Cumulative breaking current alarm threshold 65535 (kA)²
Meter increment - Active energy 0.1 kWh
Meter increment - Reactive energy 0.1 kVARh
Temperatures C

Sepam label: zone industrielle 9/25/2019


Application type: S80 3 / 23
1.3. CT-VT sensors

Sepam label: zone industrielle 9/25/2019


Application type: S80 4 / 23
1.4. CT/VT circuit supervision

Sepam label: zone industrielle 9/25/2019


Application type: S80 5 / 23
1.5. Predefined control logic

Description Setting
Switchgear control Circuit breaker
Closing with synchro-check No
Closing request time 200 ms
Synchro confirmation time 0 ms
Zone selective interlocking Yes
Logic discrimination Acceleration No
Automatic transfer No
Voltage return time 3s
Normal Tie position Normally open
Unlock logic discrimination time 200 ms

1.6. Logic input/output assignment

Used Charact. Pulse Used Charact. Pulse Used Charact. Pulse


O1 Yes NO O101 Yes NO O201 Yes NO
O2 Yes NC O102 Yes NO O202 Yes NO
O3 Yes NO O103 Yes NO O203 Yes NO
O4 No O104 Yes NO O204 Yes NO
O5 Yes NC O105 No O205 No
O106 No O206 No

Logic input Neg Latch Logic input Neg Latch


I101 Breaker closed I201 ------- (Not used) -----------
I102 Breaker open I202 ------- (Not used) -----------
I103 External network sync I203 Other use
I104 Other use I204 ------- (Not used) -----------
I105 Open command I205 ------- (Not used) -----------
I106 Close command I206 ------- (Not used) -----------
I107 External trip 1 I207 ------- (Not used) -----------
I108 Other use I208 ------- (Not used) -----------
I109 SwitchA open I209 ------- (Not used) -----------
I110 Block remote control X I210 ------- (Not used) -----------
I111 ------- (Not used) ----------- I211 ------- (Not used) -----------
I112 ------- (Not used) ----------- I212 ------- (Not used) -----------
I113 ------- (Not used) ----------- I213 ------- (Not used) -----------
I114 ------- (Not used) ----------- I214 ------- (Not used) -----------

Sepam label: zone industrielle 9/25/2019


Application type: S80 6 / 23
2. SET PROTECTIONS

2.1. Substation S80

Sepam label: zone industrielle 9/25/2019


Application type: S80 7 / 23
2.2. Protection units on

On Latching Trip C.B.


50/51 - 1 X X X
50/51 - 2 X X X
50N/51N - 1 X X X
27 - 2 X
59 - 1 X
59 - 2 X

2.3. Customized tripping curve

1 2
I/Is 1.00 10.00
T(s) 1.00 1.00

Sepam label: zone industrielle 9/25/2019


Application type: S80 8 / 23
2.4. 50/51: Phase overcurrent

Measurement Settings
Unit Activity Latching Trip C.B. Confirmation Group
origin Tripping curve Threshold Delay Icc min. H2 Timer hold curve Timer hold
A Definite time 150 A 900 ms 6.3 kA Off Definite time 0 ms
1 On X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 400 A 100 ms 6.3 kA Off Definite time 0 ms
2 On X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
3 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
4 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms

Restraint H2 threshold : 17

A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms


5 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
6 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
7 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
A Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms
8 Off X X Ia,Ib,Ic No confirmation
B Definite time 1.26 kA 100 ms 6.3 kA Off Definite time 0 ms

Restraint H2 threshold : 17

Sepam label: zone industrielle 9/25/2019


Application type: S80 9 / 23
2.5. 50N/51N: Ground fault

Measurement Settings
Unit Activity Latching Trip C.B. Group
origin Tripping curve Threshold Delay Timer hold curve Timer hold H2 rest.
A Definite time 12 A 400 ms Definite time 0 ms
1 On X X Ir (Residual)
B Definite time 12 A 400 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
2 Off X X Ir sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
3 Off X X Ir sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
4 Off X X Ir sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
5 Off X X Ir sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
6 Off X X Ir sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
7 Off X X Ir sum
B Definite time 630 A 100 ms Definite time 0 ms
A Definite time 630 A 100 ms Definite time 0 ms
8 Off X X Ir sum
B Definite time 630 A 100 ms Definite time 0 ms

2.6. 50BF: Breaker failure

Settings
Unit Activity Latching Use closed
Is threshold Delay position of CB

1 Off X 200 A 200 ms

2.7. 46: Negative sequence current / unbalance

Settings
Unit Activity Latching Trip C.B. Trip C.B.
Tripping curve Threshold Delay
1 Off X X Ia,Ib,Ic Definite time 10 %IB 100 ms
2 Off X X Ia,Ib,Ic Definite time 10 %IB 100 ms

2.8. 27D: Positive sequence undervoltage

Settings
Unit Activity Latching Trip C.B. Measurement origin
Voltage threshold Delay
1 Off X Van,Vbn,Vcn / Vab,Vbc 30 %VLLp 100 ms
2 Off X Van,Vbn,Vcn / Vab,Vbc 30 %VLLp 100 ms

Sepam label: zone industrielle 9/25/2019


Application type: S80 10 / 23
2.9. 27R: Remanent undervoltage

Settings
Unit Activity Latching Measurement origin
Voltage threshold Delay
1 Off Van,Vbn,Vcn / Vab,Vbc 20 %VLLp 100 ms
2 Off Van,Vbn,Vcn / Vab,Vbc 20 %VLLp 100 ms

2.10. 27: Undervoltage

Settings
Unit Activity Latching Trip C.B. Measurement origin
Tripping curve mode Voltage threshold Delay
1 Off Van,Vbn,Vcn / Vab,Vbc Definite time Phase-to-phase 10 %VLLp 100 ms
2 On Van,Vbn,Vcn / Vab,Vbc Definite time Phase-to-phase 73 %VLLp 1s
3 Off Van,Vbn,Vcn / Vab,Vbc Definite time Phase-to-phase 10 %VLLp 100 ms
4 Off Van,Vbn,Vcn / Vab,Vbc Definite time Phase-to-phase 10 %VLLp 100 ms

2.11. 59: Overvoltage

Settings
Unit Activity Latching Trip C.B. Measurement origin
Mode Voltage threshold Delay
1 On Van,Vbn,Vcn / Vab,Vbc Phase-to-phase 107 %VLLp 5s
2 On Van,Vbn,Vcn / Vab,Vbc Phase-to-phase 110 %VLLp 500 ms
3 Off Van,Vbn,Vcn / Vab,Vbc Phase-to-phase 110 %VLLp 100 ms
4 Off Van,Vbn,Vcn / Vab,Vbc Phase-to-phase 110 %VLLp 100 ms

2.12. 59N: Neutral voltage displacement

Measurement Settings
Unit Activity Latching Trip C.B.
origin Tripping curve Voltage threshold Delay
1 Off Vr Definite time 10 %VLLp 100 ms
2 Off Vr Definite time 10 %VLLp 100 ms

2.13. 47: Negative sequence overvoltage

Settings
Unit Activity Latching Trip C.B. Measurement origin
Voltage threshold Delay
1 Off Van,Vbn,Vcn / Vab,Vbc 10 %VLLs 100 ms
2 Off Van,Vbn,Vcn / Vab,Vbc 10 %VLLs 100 ms

Sepam label: zone industrielle 9/25/2019


Application type: S80 11 / 23
2.14. 81H: Overfrequency

Settings
Unit Activity Latch Trip C.B. Measurement origin
fs threshold Delay Vs threshold
1 Off Van,Vbn,Vcn/Vab,Vbc 53 Hz 100 ms 20 %V
2 Off Van,Vbn,Vcn/Vab,Vbc 53 Hz 100 ms 20 %V

2.15. 81L: Underfrequency

Settings
Unit Activity Latch Trip C.B. Measurement origin df/dt
fs threshold Delay Vs threshold restraint

1 Off Van,Vbn,Vcn/Vab,Vbc 45 Hz 100 ms 20 %V No


2 Off Van,Vbn,Vcn/Vab,Vbc 45 Hz 100 ms 20 %V No
3 Off Van,Vbn,Vcn/Vab,Vbc 45 Hz 100 ms 20 %V No
4 Off Van,Vbn,Vcn/Vab,Vbc 45 Hz 100 ms 20 %V No

2.16. 79: Recloser

Activity ........................................ Off shot 1 shots 2,3,4


Number of reclosing shots ......... 1 50/51-1 Inactive Inactive
Additional dead time if CB not ready No 50/51-2 Inactive Inactive
Reclaim time ............................... 10 s 50/51-3 Inactive Inactive
Blocking time until 79 ready ...... 10 s 50/51-4 Inactive Inactive
Maximum additional dead time .. 10 s
50N/51N-1 Inactive Inactive
Dead time shot 1 ......................... 10 s
50N/51N-2 Inactive Inactive
Dead time shot 2 ......................... 10 s
50N/51N-3 Inactive Inactive
Dead time shot 3 ......................... 10 s
50N/51N-4 Inactive Inactive
Dead time shot 4 ......................... 10 s
V_TRIPCB Inactive Inactive

Sepam label: zone industrielle 9/25/2019


Application type: S80 12 / 23
3. LOGIPAM SETTINGS

3.1. Logipam

Activity ................ Off

Program file: .......


Program name: ...
Type of application:
Diagram version:
SFT2885 version:

Author: ................
Customer: ...........
Project: ...............
Switchboard: ......
Cubicle: ...............

Sepam label: zone industrielle 9/25/2019


Application type: S80 13 / 23
4. DEFINITION OF EQUATIONS

4.1. Logic equations

Sepam label: zone industrielle 9/25/2019


Application type: S80 14 / 23
5. SET CONTROL MATRIX

5.1. Protection matrix

O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106 O201 O202 O203 O204 O205 O206
50/51 - 1 X
50/51 - 2 X
50/51 - 3
50/51 - 4
50/51 - 5
50/51 - 6
50/51 - 7
50/51 - 8
50N/51N - 1 X
50N/51N - 2
50N/51N - 3
50N/51N - 4
50N/51N - 5
50N/51N - 6
50N/51N - 7
50N/51N - 8
50BF - 1
46 - 1
46 - 2
27D - 1
27D - 2
27R - 1 X
27R - 2 X
27 - 1 X
27 - 2 X
27 - 3
27 - 4
59 - 1 X
59 - 2 X
59 - 3
59 - 4
59N - 1
59N - 2
47 - 1
47 - 2
81H - 1 X
81H - 2 X
81L - 1 X

Sepam label: zone industrielle 9/25/2019


Application type: S80 15 / 23
O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106 O201 O202 O203 O204 O205 O206
81L - 2 X
81L - 3 X
81L - 4 X

Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 UK message US message Rec.
50/51 - 1 X X X
50/51 - 2 X X X
50/51 - 3 X
50/51 - 4 X
50/51 - 5 X
50/51 - 6 X
50/51 - 7 X
50/51 - 8 X
50N/51N - 1 X X X
50N/51N - 2 X X
50N/51N - 3 X
50N/51N - 4 X
50N/51N - 5 X
50N/51N - 6 X
50N/51N - 7 X
50N/51N - 8 X
50BF - 1
46 - 1 X
46 - 2 X
27D - 1 X
27D - 2 X
27R - 1
27R - 2
27 - 1 X
27 - 2 X X X
27 - 3 X
27 - 4 X
59 - 1 X X X
59 - 2 X X X
59 - 3 X
59 - 4 X
59N - 1 X
59N - 2 X

Sepam label: zone industrielle 9/25/2019


Application type: S80 16 / 23
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 UK message US message Rec.
47 - 1 X
47 - 2 X
81H - 1 X
81H - 2 X
81L - 1 X
81L - 2 X
81L - 3 X
81L - 4 X

Sepam label: zone industrielle 9/25/2019


Application type: S80 17 / 23
5.2. Control logic output matrix

O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106 O201 O202 O203 O204 O205 O206
Closing X
Tripping X X
Block closing X
Pick-up
Drop-out
Trip circuit fault X
Blocking send 1 X
TC/breaker position discrepancy
Breaker monitoring X
Reverse phase rotation X
Fault recording blocked
Recloser in service X
Low Vaux threshold
High Vaux threshold
Low battery fault
Cumulative breaking current monitoring
Rotation Discordance Command
Watchdog X

Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 UK message US message Rec.
Closing
Tripping X
Block closing
Pick-up X
Drop-out
Trip circuit fault
Blocking send 1
TC/breaker position discrepancy
Breaker monitoring
Reverse phase rotation
Fault recording blocked
Recloser in service
Low Vaux threshold
High Vaux threshold
Low battery fault
Cumulative breaking current monitoring
Rotation Discordance Command X
Watchdog

Sepam label: zone industrielle 9/25/2019


Application type: S80 18 / 23
5.3. Logic input matrix

O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106 O201 O202 O203 O204 O205 O206
I101 (Breaker closed)
I102 (Breaker open)
I103 (External network sync)
I104 (Other use)
I105 (Open command)
I106 (Close command)
I107 (External trip 1)
I108 (Other use)
I109 (Switch A open)
I110 (Block remot e cont rol)
I111 (------- (Not used) -----------)
I112 (--- ---- (Not used) - ---- ---- --)
I113 (--- ---- (Not used) - ---- ---- --)
I114 (--- ---- (Not used) - ---- ---- --)
I201 (------- (Not used) -----------)
I202 (------- (Not used) -----------)
I203 (Other use)
I204 (------- (Not used) -----------)
I205 (------- (Not used) -----------)
I206 (------- (Not used) -----------)
I207 (------- (Not used) -----------)
I208 (------- (Not used) -----------)
I209 (------- (Not used) -----------)
I210 (------- (Not used) -----------)
I211 (--- ---- (Not used) - ---- ---- --)
I212 (------- (Not used) -----------)
I213 (------- (Not used) -----------)
I214 (------- (Not used) -----------)

Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 UK message US message Rec.
I101 (Breaker closed) X
I102 (Breaker open) X
I103 (External network sync)
I104 (Other use)
I105 (Open command)
I106 (Close command)
I107 (External trip 1)
I108 (Other use)
I109 (Switch A open)
I110 (Block remot e cont rol)

Sepam label: zone industrielle 9/25/2019


Application type: S80 19 / 23
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 UK message US message Rec.
I111 (------- (Not used) -----------)
I112 (--- ---- (Not used) - ---- ---- --)
I113 (--- ---- (Not used) - ---- ---- --)
I114 (--- ---- (Not used) - ---- ---- --)
I201 (------- (Not used) -----------)
I202 (------- (Not used) -----------)
I203 (Other use)
I204 (------- (Not used) -----------)
I205 (------- (Not used) -----------)
I206 (------- (Not used) -----------)
I207 (------- (Not used) -----------)
I208 (------- (Not used) -----------)
I209 (------- (Not used) -----------)
I210 (------- (Not used) -----------)
I211 (--- ---- (Not used) - ---- ---- --)
I212 (------- (Not used) -----------)
I213 (------- (Not used) -----------)
I214 (------- (Not used) -----------)

5.4. Logic equation output variable matrix

O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106 O201 O202 O203 O204 O205 O206
V1
V2
V3
V4
V5
V6
V7
V8
V9
V10
V11
V12
V13
V14
V15
V16
V17
V18
V19
V20

Sepam label: zone industrielle 9/25/2019


Application type: S80 20 / 23
Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 UK message US message Rec.
V1
V2
V3
V4
V5
V6
V7
V8
V9
V10
V11
V12
V13
V14
V15
V16
V17
V18
V19
V20

5.5. GOOSE input matrix

O1 O2 O3 O4 O5 O101 O102 O103 O104 O105 O106 O201 O202 O203 O204 O205 O206

Led1 Led2 Led3 Led4 Led5 Led6 Led7 Led8 Led9 UK message US message Rec.

Sepam label: zone industrielle 9/25/2019


Application type: S80 21 / 23
6. SET FUNCTIONS

6.1. Fault recording

Description Setting
Activity On
Total recording time: 21 s
Memory used: 93 %
Number of recordings: 6
Duration of a recording: 3
Number of samples stored per cycle: 12
Number of pre-trigger cycles: 36

List of logic I/Os to record:


Logic
Pick-up ----- ----- ----- ----- ----- -----
----- ----- ----- ----- ----- ----- -----
----- -----
Base unit outputs
----- ----- O3 ----- O1
MES 120_1
I114 ----- ----- ----- I110 I109 I108
I107 I106 I105 I104 ----- I102 I101
----- ----- O104 O103 O102 O101
MES 120_2
----- ----- ----- ----- ----- ----- -----
----- ----- ----- ----- I203 ----- -----
----- ----- O204 O203 O202 O201

Sepam label: zone industrielle 9/25/2019


Application type: S80 22 / 23
6.2. DLG

Description Setting
Memory used: 100.0 %
Number of recordings: 1
Start/Stop Choice by SFT2841
Recording mode: Circular
Duration recordance: 100h:0m:0s
Sample interval: 0h:1m:0s

List of information to record:


Current
I1: primary current phase 1 (RMS) I2: primary current phase 2 (RMS) I3: primary current phase 3 (RMS) ----- ----- ----- -----
----- ----- ----- ----- ----- ----- -----
----- -----
Voltage
----- ----- ----- ----- ----- ----- V1: primary phase 1 to neutral voltage
V2: primary phase 2 to neutral voltage V3: primary phase 3 to neutral voltage ----- ----- ----- V0: primary residual voltage -----
----- ----- ----- Vi: primary negative sequence voltage ----- F: frequency -----
Energy
----- ----- ----- P: total active power ----- ----- -----
Q: total reactive power ----- ----- ----- S: total apparent power ----- -----
cosPhi: power factor ----- ----- ----- ----- ----- -----
----- -----
Others
-----
Network
----- ----- Ithd: current harmonic distortion Uthd: voltage harmonic distortion ----- ----- -----
----- ----- -----
Machine Operating Assistance
----- ----- ----- ----- ----- ----- -----
----- ----- ----- ----- ----- ----- -----
----- ----- ----- ----- ----- ----- -----
Switchgear Diagnosis Assistance
----- ----- ----- -----

Sepam label: zone industrielle 9/25/2019


Application type: S80 23 / 23