Вы находитесь на странице: 1из 7

DMV...

/11eco
Kompaktarmatur Compact unit Armature compacte Unica stuttura compatta
mit 2 Magnetventilen with 2 solenoid valves avec 2 electrovannes con 2 vavole elettro-
magnetiche

EN 161 Doppelmagnetventil
schnell öffnend, schnell schließend
Double solenoid valve
fast opening, fast closing
Electrovanne double
ouverture rapide, fermeture rapide
Valvola elettromagnetica doppia
apertura rapida, chiusura rapida

3 8 3

12

11

10

6
13

Sieb Strainer Tamis Reticella 1 4

Ventil V1 Valve V1 Clapet vanne V1 Otturatore V1 2

Anschlussflansch Flange Bride Flagia 3

9
Schließfeder V1 Closing spring V1 Ressort de Molla chiusura V1 4 5
fermeture V1
Gehäuse Housing Corps de vanne Corpo valvola 5 3

Anker V1 plunger V1 Induit V1 Indotto V1 6


2
Magnet V1 Solenoid V1 Bobine V1 Magnete V1 7

Elektroanschluss Electrical MB connecteur Morsettiera 8


connection 1

Ventil V2 Valve V2 Clapet vanne V2 Otturatore V2 9

Schließfeder V2 Closing Ressort de Molla chiusura V2 10


spring V2 fermeture V2
Anker V2 plunger V2 Induit V2 Indotto V2 11

Magnet V2 Solenoid V2 Bobine V2 Magnete V2 12

Zündgasflansch Ignition gas flange Bride de gaz Flangia gas 13


d’allumage d’accensione

MOP 500 mbar (50 kPa)


Rp 2 (DN 50), DN 65 - DN 125

Edition: 02/2010

Strictly confidential!
The company Karl Dungs GmbH & Co. KG is the exclusive holder of all rights, also
Karl Dungs GmbH & Co. KG
Siemensstrasse 6-10
Telefon +49 (0)7181-804-0
Telefax +49 (0)7181-804-166
www.dungs.com
in case of patent application. All rights reserved, including copy and circulation. D-73660 Urbach, Germany E-Mail info@dungs.com
Double solenoid valve
Rp 2 (DN 50)
DN 65 - DN 125
nominal diameters

DMV/11 eco
DMV-D/11 eco
DMV-DLE/11 eco

7.38

• Low power consumption

• Low weight

• Compact design

• High flow rates

• Max. operating pressure


500 mbar (50 kPa)

Technical description
The DUNGS double solenoid valve DMV Application
integrates two solenoid valves in one Double solenoid valves are used where two
compact fitting. single valves were mounted previously. In
connection with DUNGS gas regulators and
- Automatic shut-off valves as per DIN EN 161 additional components, a wide variety of
Class A Group 2. regulating tasks can be performed.
- Two A valves in one housing It does not contain any non-ferrous metals,
- Double seat valves suitable for gases of up to max. 0.1 vol.%
- High flow rates H2S, dry. Suitable for gases of families 1, 2,
- Max. operating pressure up to 0.5 bar 3 and other neutral gaseous media.
Printed in Germany • Edition 08.11 • Nr. 251 418

(50 kPa)
- Fast closing Approvals
- Fast opening EC type test approval as per EC Gas Ap-
(DMV/11 eco, DMV-D/11 eco) pliance Directive:
- Adjustable main volume (DMV-D/11 eco, DMV-…525-5125/11 eco CE-0085 AN 2801
DMV-DLE/11 eco) EC type test approval as per EC Pressure
- DC solenoid Equipment Directive:
- Low electric power consumption through DMV-…525-5125/11 eco CE0036
power switching Approvals in other important gas consum-
- Mountable closed position signal contact ing countries.
- Compact, light-weight
1…6
Specifications

Nominal diameters DN 65 80 100 125


Flange Connection flange as per DIN 2501 Part 1, to fit preweld flanges as per DIN 2633
(PN 16) DN 65 to DN 125, ISO 7005 - 1 (PN 16), ISO 7005 - 2 (PN 16)
Construction length as per DIN 3202 Part 1, row F1 for DN 65 to DN 125

Nominal diameters DMV 525/11 eco


Flange with pipe thread as Rp 2
per ISO 7-1

Max. operating pressure 500 mbar (50 kPa)

Solenoid valve V1 Automatic shut-off valve as per EN 161: Class A, Group 2

Solenoid valve V2 Automatic shut-off valve as per EN 161: Class A, Group 2

Closing time <1s

Opening time DMV.../11 eco, DMV-D…/11 eco: < 1 s

Main valve restrictor Adjustable (DMV-D.../11 eco, DMV-DLE.../11 eco)

Materials of gas conveying parts Housing: aluminium, steel, no non-ferrous metals


Seals at valve seat: NBR basis, suitable for gases as per G260/l
FKM basis, suitable for gases as per G260/l (Viton version)

Ambient temperature NBR: -15 °C to +60 °C


Viton: 0 °C to +60 °C

Installation position Solenoid vertically upright to lying horizontally

Dirt trap Sieve installed. To protect the complete gas train we recommend you to install
a suitable gas filter (refer to Datasheet 11.02)

Measuring gas connection G 1/4 DIN ISO 228 centrally upstream of V1 and downstream of V2 (not 525/11 eco)
G 1/8 DIN ISO 228 on both sides upstream of V1, between V1 and V2, downstream of V2

Ignition gas connection G 3/4 ignition gas flange as per ISO 228, possible on both sides between V1 and V2

Voltage/frequency 50 - 60 Hz, 230 V AC, -15% +10%, further voltages on request


Other preferred voltages: 110 V AC, 24 V DC

Rating / power consumption Version Starting power Holding power Break-away start- Holding
at 230 V AC, + 20°C approx. [W] approx. [W] ing current [A] current [A]
all indications are effective values
DMV 525/11 eco 2 x 65 2 x 16 2 x 0.32 2 x 0.11
DMV-... 5065/11 eco 2 x 65 2 x 16 2 x 0.32 2 x 0.11
DMV-... 5080/11 eco 2 x 95 2 x 20 2 x 0.54 2 x 0.20
DMV-... 5100/11 eco 2 x 125 2 x 25 2 x 0.54 2 x 0.20
DMV-... 5125/11 eco 2 x 125 2 x 25 2 x 0.54 2 x 0.20

Degree of protection / switch-on duration IP 54 / 100 %

Electrical connection Plug-in connection as per DIN EN 175301-803

Radio interference Degree of interference N

Closed position signal contact Type K01/1 (DIN tested), can be mounted on V1 and V2

2…6
Dimensions for DMV.../11 eco

d
c
b
e a
f

d Space requirement for replacing the solenoid


c
b
e a
f

Version Order pmax. Connec- Dimensions [mm] SolenoidSwit- Weight


No. [bar] tion a b c d e f No. ching [kg]
230VAC/ DN rate/h1)
NBR

DMV 525/11 eco 256 139 0.5 Rp 2 (DN 50) 162 88 179 275 125 97 1411/2P 60 7.2
DMV 5065/11 eco 256 293 0.5 DN 65 290 88 179 275 185 97 1411/2P 60 10.0
DMV 5080/11 eco 256 356 0.5 DN 80 310 104 246 370 200 109 1511/2P 60 16.3
DMV 5100/11 eco 249 774 0.5 DN 100 350 119 292 450 220 116 1611/2P 60 24.2
DMV 5125/11 eco 250 465 0.5 DN 125 400 142 329 500 255 125 1711/2P 60 31.7

DMV-D 525/11 eco 256 151 0.5 Rp 2 (DN 50) 162 88 179 275 125 97 1411/2P 60 7.2
DMV-D 5065/11 eco 256 296 0.5 DN 65 290 88 179 275 185 97 1411/2P 60 10.0
DMV-D 5080/11 eco 256 357 0.5 DN 80 310 104 246 370 200 109 1511/2P 60 16.3
DMV-D 5100/11 eco 253 459 0.5 DN 100 350 119 292 450 220 116 1611/2P 60 24.2
DMV-D 5125/11 eco 253 461 0.5 DN 125 400 142 329 500 255 125 1711/2P 60 31.7

DMV-DLE 525/11 eco 256 172 0.5 Rp 2 (DN 50) 162 88 179 275 125 97 1411/2PL 20 7.2
DMV-DLE 5065/11 eco 256 297 0.5 DN 65 290 88 179 275 185 97 1411/2PL 20 10.0
DMV-DLE 5080/11 eco 256 358 0.5 DN 80 310 104 265 370 200 109 1511/2PL 20 16.5
DMV-DLE 5100/11 eco 256 458 0.5 DN 100 350 119 346 450 220 116 1611/2PL 20 24.5
DMV-DLE 5125/11 eco 256 459 0.5 DN 125 400 142 387 500 255 125 1711/2PL 20 32.0
1)
Switching rate of DMV-DLE.../11 eco depends on opening time setting
Important: Always order, plug
connection and system ac-
3…6 cessories separately.
DMV/11 eco Two single stage solenoid valves, de-energised in absence of current, fast-opening, fast-clo-
sing.

DMV-D/11 eco Two single stage solenoid valves, de-energised in absence of current, fast-opening, fast-closing.
Manual limitation of gas flow is possible with main load adjustment (D) at valve 1 (V1).

DMV-DLE/11 eco Two single stage solenoid valves, de-energised in absence of current, slow-opening (L), fast-
closing. Adjustment of opening time (E) with fast stroke range at valve 2 (V2). Manual limitation
of gas flow is possible with main load adjustment (D) at valve 1 (V1).

Variants DMV/11 eco Rp 2 (DN 50) DMV/11 eco DN 65 - DN 125


Double solenoid valve DMV-…/11 eco
single stage operating mode

DMV ◆ ◆

DMV-D ◆ ◆

DMV-DLE ◆ ◆

Filter ◆ ◆

Gas pressure switch can be mounted:

on the flange ◆ (◆)

after the filter, before V1 ◆ ◆

between V1 and V2 ◆ ◆

after valve 2 ◆ ◆

valve V1, double seat ◆ ◆

valve V2, double seat ◆ ◆

Valves open separately ◆ ◆

Ignition gas flange G 3/4 ◆ ◆

◆ = standard
(◆) = on request
-- = not possible

4…6
Double solenoid valve modular system

Leakage gas valve

Ignition gas flange

External bypass valve

Internal bypass valve

pe,max. = 500 mbar

V1 V2

Min. gas pressure switch Max. gas pressure switch


Closed
position Closed position signal contact
signal
contact

Valve proving system

System accessories If a system accessory is


The double solenoid valve is prepared Compact pressure switch for mul- added, it may not be possible
for direct mounting of DUNGS system ac- tiple actuators GW…A5 to mount further devices.
cessories and additional equipment. Datasheet 5.02

Information on system accessories K01/1 closed position signal contact


to monitor closed position of valves
VPS 504 valve proving system Datasheet 12.01
Datasheet 8.10

Pressure limiter ÜB, NB...A2 for


multiple actuators
Datasheet 5.08

5…6
Double solenoid valve
Rp 2 (DN 50)
DN 65 - DN 125
nominal diameters

DMV/11 eco
DMV-D/11 eco
DMV-DLE/11 eco

Flow diagram DMV-DLE 525/11 eco


DMV-DLE 5065/11 eco
- 10 % V

co
)e

o
50

ec

ec
co
ec
(DN

5e

00

25
80

N1

N1
N6
p2

DN

1D

1D
1D
1R

/11

0/1

5/1
5/1
5/1

0
08

10

12
06
52

.. 5

.. 5

.. 5
.. 5
..

V-.

V-.

V-.
V-.

V-.
DM

DM

DM
DM

DM

Basis + 15° C, 1013 mbar, trocken


Based on + 15° C, 1013 mbar, dry
Base + 15° C, 1013 mbar, sec
Base + 15° C, 1013 mbar, secco

° [m3/h] Luft / Air / Aria dv = 1,00


Vn

° [m3/h] Erdgas / Natural gas / Gaz Naturel / Gas metano dv = 0,65


Vn

Dichte Luft Gas type Spec. Wgt. dv f


Spec. weight air [kg/m3]
poids spécifique de l'air
peso specifico aria Nat. gas 0.81 0.65 1.24
f= City gas 0.58 0.47 1.46
Dichte des verwendeten Gases LPG 2.08 1.67 0.77
Spec. weight of gas used Air 1.24 1.00 1.00
poids spécifique du gaz utilisé
peso specifico del gas utilizzato °
V = °
verwendetes Gas/gas used/ gaz utilisé/gas utilizzato
V Luft/air/air/aria x f

We reserve the right to make any changes in the interest of technical progress.

Head Offices and Factory Postal address


Karl Dungs GmbH & Co. KG Karl Dungs GmbH & Co. KG
Siemensstraße 6-10 Postfach 12 29
D-73660 Urbach, Germany D-73602 Schorndorf, Germany
Telephone +49 (0)7181-804-0 e-mail info@dungs.com
Fax +49 (0)7181-804-166 Internet www.dungs.com 6…6