Академический Документы
Профессиональный Документы
Культура Документы
1 NEC CALCULATIONS
Continuously Loaded Conductors and its Proper Sizing
Sec. 220-10(b) Continuously and Non Continuous Loads
Where a feeder supplies continuously loads or any combination of continuous and noncontinuous load, the
rating of the overcurrent device shall not be less than the noncontinuous load plus 125% of the continuous loads.
n general, overcurrent protective devices will malfunction if subjected to more than 80% of their rating for continuous periods of time (note that 125% is simply the reciprocal of 80%),
The UL Electrical Construction Materials Directory (the "Green Book") contains the following rule under the product category "Circuit Breakers, M
"Circui Breakers, Molded Case, and Circuit Breakers Enclosures".
Unless otherwise marked, circuit breakers, should not loaded to exceed 80% of their current rating, where in normal operation the load
will continue for 3 hours or more.
A similar rule applies to fused switches.
Illustration Problem :
On a 120/240V system, there is 16,200VA of continuous load and 12,200VA continuous load. What is the minimum size of
overcurrent protective device and feeder conductors that could be used?
Abstract ; One of the most misunderstood issues in the specification of a UPS is sizing.
Five (5) steps procedure for determining the proper size of UPS.
Step 1 Make a list of all equipment to be protected (monitors, terminals, external data storage devices any other
crucial peripherals
Exception : You should not connect laser printers and copy machines.
Reasons : They draw enormously high inrush currents during normal operation.
Solution : Oversize the UPS and protect printers and copier machines with a good transient voltage surge suppressors
TVSS with a rating of 20A.
SIZING CALCULATION