UPS Load Calculation for Industrial Area Pumping Station PLC panel
Rev. 0
Al- Wefaq Control System
Sheet 2 PLC-5
Item Pt. no. Description Qty VA D.F Total Reference
1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H 2 7.5 1 15 Page 6
2 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE 4 0.77 1 3.08 Page 7
3 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY 2 20 1 40 Page 8
4 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 9
5 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 1 11 1 11 Page 10
6 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331 2 0.4 1 0.8 Page 11
7 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321 5 6.5 1 32.5 Page 12
8 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322 2 6.6 1 13.2 Page 13
9 6ES7197-1LA04 -0XA0 Y-Link for S7-400H SIMATIC S7-400H, Y-LINK 1 0 0 0 Page 14
10 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical 42 0.5 1 21 Page 25
14 FIT-201A/B Magnetic flow meters DN 500 2 15 1 30 Page 26
15 LSH-201A/B Level switch for hazarouds 2 2.5 1 5 Page 27
16 LIT-201A/B level indicator transmitter 2 23 1 46 Page 28
17 PIT-201A/B/C/D/E/F Pressure transmitter 6 0.4 1 2.4 Page 29
Summation 232.7
Auxiliary Rate 0
232.7
TOTAL IN VA
300
Page 1 of 43
Project: -
UPS Load Calculation Inlet Works panel
Rev. 0
Al- Wefaq Control System
Sheet 3,4 PLC-4
Item Pt. no. Description Qty VA D.F Total Reference
1 6ES7414-5HM06-0AB0 SIMATIC S7-400H, CPU 414-5H, CENTRAL UNIT 2 7.5 1 15 Page 6
2 6ES7960-1AA06-0XA0 SIMATIC S7-400H, SYNC SUBMODULE FOR 4 0.77 1 3.08 Page 7
3 6ES7407-0KA02-0AA0 SIMATIC S7-400, POWER SUPPLY PS407: 10A, WIDERANGE, 120/230V UC 2 20 1 40 Page 8
4 6GK5204-2BB10-2AA3 SCALANCE X204-2, MANAGED IE SWITCH 2 6.36 1 12.72 Page 9
5 6ES7153-2BA02-0XB0 SIMATIC DP, ET 200M INTERFACE IM 153-2 2 11 1 22 Page 10
6 6ES7331-1KF02-0AB0 SIMATIC S7-300, ANALOG INPUT SM 331,OPTICALLY ISOLATED, 8 AI, 13 BIT 2 0.4 1 0.8 Page 11
7 6ES7321-1BL00-0AA0 SIMATIC S7-300, DIGITAL INPUT SM 321,OPTICALLY ISOLATED 32DI 8 6.5 1 52 Page 12
8 6ES7322-1BL00-0AA0 SIMATIC S7-300, DIGITAL OUTPUT SM 322,OPTICALLY ISOLATED, 3 6.6 1 19.8 Page 13
9 46.52.9.024.0040 Relay 24VDC, 8A, 2 Pole,Lockable test button +mechanical indicator 74 0.5 1 37 Page 25
10 DLIT-301C Differential Level Indicator Transmitters 3 0.5 1 1.5 Page 30
11 AIT-401 Hydrocarbon Analyzer 1 0.6 1 0.6 Page 31
12 ASS-401 Auto Sampler 1 290 1 290 Page 32
13 FIT-401 FIT-401B Open Channel Ultrasonic level type flowmeter 2 23 1 46 Page 28
Summation 540.5
Auxiliary Rate 0
540.5
TOTAL IN VA
600
Page 2 of 43
Project: -
Summation 1367.6
Auxiliary Rate 0
1367.6
TOTAL IN VA
1400
Page 3 of 43
Project: -
120.356
TOTAL IN VA
200
Page 4 of 43
Project: -
Summation 2199.6
Auxiliary Rate 0
2199.6
TOTAL IN VA
2200
Page 5 of 43
6ES7414-5HM06-0AB0 Page 2
Power losses
Power loss, typ. 7.5 W
Backup battery
Battery operation
Backup current, typ. 180 μA ; Valid up to 40°C
Backup current, max. 1000 μA
Backup time, max. Dealt with in the module data manual with the
secondary conditions and the factors of influence
Feeding of external backup voltage to CPU 5 to 15 VDC
Feeding of external backup voltage to CPU 5 to 15 VDC
Memory
Work memory
integrated 4 Mbyte
integrated (for program) 2 Mbyte
integrated (for data) 2 Mbyte
expandable No
Load memory
expandable FEPROM Yes ; with Memory Card (FLASH)
expandable FEPROM, max. 64 Mbyte
integrated RAM, max. 512 kbyte
expandable RAM Yes
expandable RAM, max. 64 Mbyte
Backup
present Yes
with battery Yes ; all data
without battery No
CPU processing times
for bit operations, min. 18.75 ns
for word operations, min. 18.75 ns
for fixed point arithmetic, min. 18.75 ns
for floating point arithmetic, min. 37.5 ns
CPU-blocks
DB
Number, max. 6000 ; Number range: 1 - 16.000
Page 6 of 43
productdatablad 6ES7960-1AA06-0XA0
SIMATIC S7-400H,
SYNC SUBMODULE V6 FOR PATCH CABLES UP TO 10M
Input current
from CPU, max. 220 mA
Power losses
Power loss, typ. 0,77 W
Dimensions
Breedte 13 mm
Hoogte 14 mm
Diepte 58 mm
Weight
Weight, approx. 14 g
Status 6-jul-2013
Page 7 of 43
6ES7407-0KA02-0AA0 Page 2
Input current
Rated value at 110 V DC 1 A ; at 120 V DC
Rated value at 230 V DC 0.5 A
Rated value at 120 V AC 0.9 A
Rated value at 230 V AC 0.5 A
Inrush current, max. 63 A ; Full width at half maximum 1 ms
Output voltage
Rated value, 5 V DC Yes
Rated value, 24 V DC Yes
Output current
for backplane bus (5 V DC), max. 10 A ; no base load required
for backplane bus (24 V DC), max. 1 A ; idling-proof
Short-circuit protection Yes
Power
Power consumption, typ. 95 W
Power losses
Power loss, typ. 20 W
Backup battery
Backup battery
Backup battery (optional) Yes ; 2 x lithium AA; 3.6 V/2.3 Ah
Galvanic isolation
primary/secondary Yes
EMC
Compliance with line harmonic distortion limits
Observance of line harmonic distortion acc. to IEC Yes
61000-3-2, IEC 61000-3-3
Degree and class of protection
Protection class 1 ; with protective conductor
Standards, approvals, certificates
FM approval Yes ; Ta: 0 °C to 60 °C T4
Connection method
Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve,
external diameter 3 to 9 mm
Dimensions
Page 8 of 43
26
Attenuation / of fiber-optic cable transmission link / minimum 0 dB
necessary
Inputs/outputs
Operating voltage / of signaling contacts / at DC / rated value 24 V
• minimum 18 V
• maximum 32 V
Width 60 mm
Height 125 mm
Depth 124 mm
Type of mounting
Cascading in cases of star structuring Any (depending only on signal propagation time)
Product function
• CLI Yes
108 Page 9 of 43
6ES7153-2BA02-0XB0 Page 2
Page 10 of 43
60
6ES7331-1KF02-0AB0 Page 1
Input current
from backplane bus 5 V DC, max. 90 mA
Power losses
Power loss, typ. 0.4 W
Analog inputs
Number of analog inputs 8
Number of analog inputs for resistance 8
measurement
permissible input voltage for voltage input 30 V ; 12 V continuous, 30 V for max. 1 s
(destruction limit), max.
permissible input current for current input 40 mA
(destruction limit), max.
Input ranges
Voltage Yes
Current Yes
Thermocouple No
Page 11 of 43
73
6ES7321-1BL00-0AA0 Page 1
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 15 mA
Power losses
Power loss, typ. 6.5 W
Digital inputs
Number/binary inputs 32
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
up to 40 °C, max. 32
Page 12 of 43
6ES7322-1BL00-0AA0 Page 1
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 160 mA
from backplane bus 5 V DC, max. 110 mA
Power losses
Power loss, typ. 6.6 W
Digital outputs
Number/binary outputs 32
Limitation of inductive shutdown voltage to L+ (-53 V)
Lamp load, max. 5 W
Load resistance range
Page 13 of 43
Product data sheet 6ES7197-1LA04-0XA0
SIMATIC S7-400H,
Y-LINK FOR CONNECTING SINGLE-CHANNEL DP
SLAVES TO S7-400H BASED ON IM153-BA02 (NOT FIT
FOR PCS7 V6.1)
Dimensions
Width 40 mm
Height 125 mm
Depth 130 mm
Page 14 of 43
6ES7332-5HF00-0AB0 Page 1
Supply voltage
Load voltage L+
Rated value (DC) 24 V
Input current
from load voltage L+ (without load), max. 340 mA
from backplane bus 5 V DC, max. 100 mA
Power losses
Power loss, typ. 6 W
Analog outputs
Number of analog outputs 8
Voltage output, short-circuit protection Yes
Voltage output, short-circuit current, max. 25 mA
Current output, no-load voltage, max. 18 V
Output ranges, voltage
0 to 10 V Yes
Page 15 of 43
85
6ES7321-1BH02-0AA0 Page 1
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from backplane bus 5 V DC, max. 10 mA
Power losses
Power loss, typ. 3.5 W
Digital inputs
Number/binary inputs 16
Input characteristic curve acc. to IEC 61131, Type 1 Yes
Number of simultaneously controllable inputs
horizontal installation
up to 60 °C, max. 16
Page 16 of 43
6ES7322-1BH01-0AA0 Page 1
Supply voltage
Load voltage L+
Rated value (DC) 24 V
permissible range, lower limit (DC) 20.4 V
permissible range, upper limit (DC) 28.8 V
Input current
from load voltage L+ (without load), max. 80 mA
from backplane bus 5 V DC, max. 80 mA
Power losses
Power loss, typ. 4.9 W
Digital outputs
Number/binary outputs 16
Limitation of inductive shutdown voltage to L+ (-53 V)
Lamp load, max. 5 W
Load resistance range
Page 17 of 43
70-1
for backplane bus (24 V DC), max. 1 A ; idling-proof
Power
Power consumption, typ. 95 W
Power losses
Power loss, typ. 20 W
Battery
Backup battery
Backup battery
Galvanic isolation
primary/secondary Yes
Connection method
Connecting cables/cross sections 3 x 1.5 mm2, solid or stranded wire with end sleeve, external
diameter 3 to 9 mm
Dimensions
Width 50 mm
Height 290 mm
Depth 217 mm
Required slots 2
Weight
Weight, approx. 1200 g
Page 18 of 43
Product data sheet 6ES7412-3HJ14-0AB0
SIMATIC S7-400H,
CPU 412-3H CENTRAL UNIT FOR S7-400H AND S7-
400F/FH,
3 INTERFACES: 1 MPI/DP AND 2 FOR SYNC MODULES
768 KB MEMORY (256 KB DATA/512 KB CODE)
General information
Hardware product version 1
Engineering with
Programming package STEP7 V 5.3 SP2 or higher with HW update
Supply voltage
24 V DC No ; Power supply via system power supply
Input current
from backplane bus 5 V DC, typ. 1.2 A
Power losses
Power loss, typ. 5.5 W
Memory
Page 19 of 43
Product data sheet 6ES7960-1AA04-0XA0
SIMATIC S7-400H,
SYNC SUBMODULE V4 FOR PATCH CABLES UP TO 10M
Input current
from CPU, max. 210 mA
Power losses
Power loss, typ. 1.1 mW
Dimensions
Width 25 mm
Height 53 mm
Depth 140 mm
Weight
Weight, approx. 65 g
Page 20 of 43
6EP1333-3BA00 Page 3
Page 21 of 43
12
6ES7153-2BA02-0XB0 Page 2
Page 22 of 43
60
(6.)$% 3DJH
3URGXFWGDWDVKHHW (6.)$%
6,0$7,&6$1$/2*,138760
237,&$//<,62/$7('$,
%,75(62/87,21
8,5(6,67$1&(371,1,
/*1,37&.7<
0602'8/(83'$7(;3,1
,QSXWFXUUHQW
IURPEDFNSODQHEXV9'&PD[ bP$
3RZHUORVVHV
3RZHUORVVW\S b:
$QDORJLQSXWV
1XPEHURIDQDORJLQSXWV
1XPEHURIDQDORJLQSXWVIRUUHVLVWDQFH
PHDVXUHPHQW
SHUPLVVLEOHLQSXWYROWDJHIRUYROWDJHLQSXW b99FRQWLQXRXV9IRUPD[V
GHVWUXFWLRQOLPLWPD[
SHUPLVVLEOHLQSXWFXUUHQWIRUFXUUHQWLQSXW bP$
GHVWUXFWLRQOLPLWPD[
,QSXWUDQJHV
9ROWDJH <HV
&XUUHQW <HV
7KHUPRFRXSOH 1R
'DWH VXEMHFWWRPRGLILFDWLRQV
k&RS\ULJKW6LHPHQV$*
Page 23 of 43
73
• for glass FOC with 50/125 μm / at 3 dB/km / maximum 10 dB
Wavelength
Cable length
• 3 km
Inputs/outputs
Operating voltage / of signaling contacts / at DC / rated value 24 V
• rated value 24 V
• minimum 18.8 V
• maximum 28.8 V
• during operating 0 … 60 °C
Relative humidity
Page 24 of 43
46 Series - Miniature industrial relays 8 - 16 A
Features 46.52 46.61
1 & 2 Pole relay range
46.52 - 2 Pole 8 A
46.61 - 1 Pole 16 A
• Socket mount or direct connection via Faston
connectors
• AC coils & DC coils
• Available with: lockable test button,
mechanical indicator & LED indicator
• 8 mm, 6 kV (1.2/50 μs) isolation, coil-contacts
• Cadmium Free contacts
• 2 Pole CO, 8 A • 1 Pole CO, 16 A
• Plug-in/Solder terminals • Plug-in/Faston 187
46.52
29 12.4
32.8
20
46.61
Page 25 of 43 1
138
Proline Promag 50W, 53W
1
2
3
4
5
6
7
a b
A0003194
a Signal cable
b Coil current cable
1 Core
2 Core insulation
3 Core shield
4 Core jacket
5 Core reinforcement
6 Cable shield
7 Outer jacket
" Caution!
Grounding is by means of the ground terminals provided for the purpose inside the connection housing.
Ensure that the stripped and twisted lengths of cable shield to the ground terminal are as short as possible.
Power supply failure Lasting min. ½ cycle frequency: EEPROM saves measuring system data
• EEPROM or T-DAT (Promag 53 only) retain the measuring system data in the event of a power supply failure
• S-DAT: exchangeable data storage chip which stores the data of the sensor (nominal diameter, serial number,
calibration factor, zero point etc.)
10 Page 26 of 43 Endress+Hauser
Nivotester FTL 325 N
Power supply
Electrical connection Terminal blocks
The removable terminal blocks are separated into intrinsically safe connections (at top of the
instrument) and non-instrinsically safe connections (at bottom of the instrument). Also, the
terminal blocks have different colours to make them more easily recognisable. Blue for the
intrinsically safe section and grey for the non-intrinsically safe section. This difference helps to
ensure safe wiring.
DC version:
• Voltage ranges: 20...30 V AC / 20...60 V DC
• DC supply: max. 60 mA (1-channel)
• DC supply: max. 115 mA (3-channel)
• Permissible residual ripple within tolerance: Uss = max. 2 V
The Nivotester is equipped with reverse polarity protection.
Power consumption AC
1-channel: max. 1.75 W
3-channel: max. 2.75 W
DC
1-channel: max. 1.2 W (bei Umin 20 V)
3-channel: max. 2.25 W (bei Umin 20 V)
8 Page 27 of 43 Endress+Hauser
Prosonic S FMU90
Transmittable values • main value (level or flow, depending on the instrument version)
• distances
• counters
• temperatures
• average/difference/sum
• relay states
• rake control
• pump control
Addressing via dip switches at the instrument or via software (e.g. FieldCare)
Default address: 126 per software
Auxiliary energy
Supply voltage/ Instrument version Supply voltage Power consumption Current consumption
Power consumption/
Current consumption AC voltage
90 ... 253 VAC (50/60 Hz) max. 23 VA max. 100 mA at 230 VAC
(FMU90 - ****A****)
DC voltage
10,5 ... 32 VDC max. 14 W (typically 8 W) max. 580 mA at 24 VDC
(FMU90 - ****B****)
Galvanic isolation The following terminals are galvanically isolated from each other:
• auxiliary energy
• sensor inputs
• analogue output 1
• analogue output 2
• relay outputs
• bus connection (PROFIBUS DP)
Fuse • 2 A T /DC
• 400 mA T /AC
accesible in the terminal compartment
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
Current consumption • PROFIBUS PA: 11 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 16 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Residual ripple No influence on 4 to 20 mA signal up to r5 % residual ripple within the permitted voltage range [according to
HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
Endress+Hauser Page 29 of 43 19
Deltabar S
4 to 20 mA HART
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position
(delivery status): 11.5 to 45 V DC
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position:
10.5 to 45 V DC
PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 VDC
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Residual ripple Without influence on 4 to 20 mA signal up to r5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
18 Page 30 of 43 Endress+Hauser
x Power requirement 220 VAC
x Power consumption: 0.48 Watts
x Analog outputs: 4-20mA isolated
x Analog loop resistance: 500 Ohms, nominally @ 24V
x Alarms: Optional
x Certification: Available upon request
Mechanical
UV Lamp
x Materials: 316SS
x Max temperature rating: 315.5° C (600° F)
x Max pressure rating: 5000 psig
Mounting:
Area Class
Page 31 of 43
Liquistation CSF34
Power failure • Power supply via battery (optional): 2 x 12 V, 7.2 Ah, with additional charge controller
Performance characteristics
Sampling methods Vacuum pump / peristaltic pump:
• Event sampling
• Single and multiple samples
• Sampling table
Vacuum pump:
• In proportion to time
• In proportion to volume
Peristaltic pump:
• In proportion to time
• In proportion to volume
• In proportion to flow
Intake speed > 0.5 m/s (> 1.6 ft/s) for 13 mm (1/2") ID, in accordance with EN 25667, ISO 5667
> 0.6 m/s (> 1.9 ft/s) for 10 mm (3/8") ID, in accordance with Ö 5893 (Austrian standard); US EPA
22 Page 32 of 43 Endress+Hauser
Cerabar S
4 to 20 mA HART
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Test" position
(delivery status): 11.5 to 45 V DC
• Version for non-hazardous areas, jumper for 4 to 20 mA test signal in "Non-test" position:
10.5 to 45 V DC
PROFIBUS PA
• Version for non-hazardous areas: 9 to 32 V DC
FOUNDATION Fieldbus
• Version for non-hazardous areas: 9 to 32 V DC
Current consumption • PROFIBUS PA: 13 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
• FOUNDATION Fieldbus: 15 mA ± 1 mA, switch-on current corresponds to IEC 61158-2, Clause 21
Residual ripple Without influence on 4 to 20 mA signal up to r5 % residual ripple within the permitted voltage range
[according to HART hardware specification HCF_SPEC-54 (DIN IEC 60381-1)]
18 Page 33 of 43 Endress+Hauser
Page 34 of 43
Liquiline CM442
Performance characteristics
Response time Current outputs
t90 = max. 500 ms for an increase from 0 to 20 mA
10 Page 35 of 43 Endress+Hauser
Limit reed switch ZE 951 for DFM 165 - 350
bistable
Body Colour
• ABS • anthracite grey
> data sheet no.: 330207 - 2010/05/05 Page 36 of 43 All rights for technical modifications withheld 1
ASV Stübbe GmbH & Co. KG · Hollwieser Str. 5 · D-32602 Vlotho · Tel. +49(0)5733. 799-0 · Fax +49(0)5733. 799-5000 · contact@asv-stuebbe.de · www.asv-stuebbe.de
Current output to backplane bus (DC 5 V), max. 1600 mA ; Max. 5 V DC for SM and CM
Power losses
Power loss, typ. 12 W
Memory
Usable memory for user data 75 kbyte
Work memory
integrated 75 kbyte
expandable No
Load memory
integrated 4 Mbyte
Backup
present (maintenance-free)
CPU-blocks
Number of blocks (total) DBs, FCs, FBs, counters and timers. The maximum number of
addressable blocks ranges from 1 to 65535. There is no restriction,
the entire working memory can be used
OB
Number, max. Limited only by RAM for code
Flag
Number, max. 8 kbyte ; Size of bit memory address area
Address area
Process image
Inputs, adjustable 1 kbyte
Hardware configuration
Number of modules per system, max. 3 comm. modules, 1 signal board, 8 signal modules
Time of day
Clock
Hardware clock (real-time clock) Yes
Page 37 of 43
Product data sheet 6ES7221-1BH30-0XB0
Supply voltage
24 V DC Yes
Input current
from backplane bus 5 V DC, max. 130 mA
Digital inputs
from load voltage L+ (without load), max. 4 mA ; per channel
Output voltage
Power losses
Power loss, typ. 2.5 W
Digital inputs
Number/binary inputs 16
In groups of 4
Page 38 of 43
Product data sheet 6ES7222-1BH30-0XB0
SIMATIC S7-1200,
DIGITAL OUTPUT SM 1222, 16 DO, 24V DC,
TRANSISTOR 0.5A
Supply voltage
permissible range, lower limit (DC) 20.4 V
Input current
from backplane bus 5 V DC, max. 140 mA
Power losses
Power loss, typ. 2.5 W
Digital inputs
Number/binary inputs 0
Digital outputs
Number/binary outputs 16
In groups of 1
Output voltage
Page 39 of 43
Product data sheet 6ES7231-4HF30-0XB0
Supply voltage
24 V DC Yes
Input current
Current consumption, typ. 45 mA
Power losses
Power loss, typ. 1.5 W
Analog inputs
Number of analog inputs 8 ; Current or voltage differential inputs
permissible input voltage for voltage input (destruction limit), max. 35 V
permissible input current for voltage input (destruction limit), max. 40 mA
permissible input current for current input (destruction limit), max. 40 mA
Input ranges
Voltage Yes ; ±10 V, ±5 V, ±2.5 V
Current Yes ; 0 to 20 mA
Thermocouple No
Page 40 of 43
Alphanumeric keyboard Yes ; Onscreen keyboard
Touch operation
Design as touch screen Yes
Installation type/mounting
Mounting in portrait format possible Yes
Supply voltage
Type of supply voltage DC
Rated voltage/DC 24 V
Input current
Current consumption (rated value) 0.24 A
Power
Power consumption, typ. 6W
Processor
Processor type
X86 No
Memory
Flash Yes
RAM Yes
Type of output
Acoustics
Buzzer Yes
Speaker No
Time of day
Clock
Hardware clock (real-time clock) No
Battery-backed No
Synchronizable Yes
Interfaces
Number of RS 485 interfaces 0
Page 41 of 43
Product data sheet 6GK7242-5DX30-0XE0
Transmission rate
Transmission rate / at interface 1 / in accordance with PROFIBUS 9.6 kbit/s … 12 Mbit/s
Interfaces
Number of electrical connections
Supply voltage
Consumed current
Page 42 of 43
55 Series - General purpose relays 7 - 10 A
Features 55.32 55.33 55.34
Plug-in mount, general purpose
2, 3 & 4 Pole relays
55.32 - 2 Pole 10 A
55.33 - 3 Pole 10 A
55.34 - 4 Pole 7 A
• Lockable test button and mechanical flag
indicator as standard on 2 & 4 pole types
• AC coils & DC coils
• UL Listing (certain relay/socket combinations)
• Cadmium Free contacts (preferred version)
• 2 pole, 10 A • 3 pole, 10 A • 4 pole, 7 A
• Contact material options • Plug-in 94 series sockets • Plug-in 94 series sockets • Plug-in 94 series sockets
• 94 series sockets
• Coil EMC suppression
• Timer accessories 86 series
• European Patent
2 Page 43 of 43