Design thrust Block(Ø=90 ̊)

Design Pressure P = 800 kN/m2 (Provided by manufaturer)


Pipe Diameter(OD) = 0.2 m
Angle of bend Ø = 90 deg 1.57 rad
Cross sectional Area of pipe = 0.03
Thrust Force R = 35.51 kN
Length of the block (G) = 0.9
Height of block( E) = 0.7
Length of block (Fp) = 0.574 m
Length of Block (D) = 0.75 m
Height upto ground level (H) = 2.2 m
Weight of the concrete block Wt = 14.95 kN
Soil Unit Weight = 22 Kn/m3
Soil friction Angle = 30 deg 0.52 rad
Active Earth Pressure (ka) = 0.33
Passive Earth Pressure(kp) = 0.62

Normal Active Pressure = 17.57 kN/m


Tangitial Active Earth Pessure (Fa) = 10.14 kN/m

Determine Earth pressure coeffieceint for tangential active Pressure in the front of the Block(k ɣtanδɣ)
kɣtanδɣ = (Wt +Fa)/(1/2x ɣ xHxH)
0.47
Determine Earth pressure coeffieceint for tangential normal earth Pressure in the front of the Block(k ɣ)
kɣ = 2.85 obtained from figure "J"

Determine Anchor Resistence


Å = 134.16 kN/m

Determine Anchor Resistence


(L-0.1)/(H+h) = 0.22 m
(l ͤ-l)/(H+h) = 0.21 m
lͤ = 0.709 m
Determine Anchor Resistence Ratio
Aˢ /A ͤ = 0.85

Determine Load Capacity of Block Q


Q = 80.85 kN

Determine Factor of safety of Block


FS = 1.5
= Q/R
= 2.3
Pass
Minimum dimensions
OD(m) A(m)g B(m)f C(m)d D(m)e
>0.1 0.6 0.5 0.5 0.5
by manufaturer) 0.1 0.8 0.6 0.5 0.6
0.15 0.85 0.65 0.5 0.65
0.2 0.9 0.7 0.75 0.7
0.25 0.95 0.75 0.8 0.75

200mm
dia

the Block(k ɣtanδɣ)

ront of the Block(k ɣ)

h/H = 0.32