LEGEND
START A = Lube oil temperature Engine inlet <20 oC
B = HT Cooling Water Temperature Engine Inlet < 20 oC
C = Lube Oil Temperature Engine Inlet >= 40 oC
D = HT Cooling Water Temperature Engine Inlet >= 60 oC
E = Lube Oil Temperature Engine Inlet >= 20 oC - < 40 oC
F = HT Cooling Water Temperature Engine Inlet >= 20 oC - < 60 oC
Indicating of : G = Operating Hour Engine 1 < Engine 2
- Position of selector switch H = Amount of starts Engine 1 < Engine 2
in SCADA side I = Operating Hour Engine 2 < Engine 1
- Position selector switch J = Amount of starts Engine 2 < Engine 1
at SaCos in Remote Position K = The calculated setpoint for each individual genset in CCP is higher
than 5% (minimum permissible power of the genset) of its nominal
value
L = AVR - Voltage Droop Mode
M = Not affected an active power limitation
N = Has reached Lube Oil Temperature >= 40
Alarm "ON" O = HT Cooling Water Temperature >= 60 Oc
In DCS and No 1. A P = The lowest actual active power
Engine 2. B Q = Operator select a genset which shall be switched to droop=0%
Controller R = Input of integer values according to the amount of engines
S = Engine Priority
Z =AVR - Volatge Droop Mode
Yes ---------------------------------------------------------------------------------------------
- Indicating engine ready to start OH = Operating Hour
AS = Amount of Starts
PW = Power Demand
Giving Speed setpoint is SP = Setpoint
similar with default = Engine Area
setting speed of engine = DCS Area
= Emergency (Engine Area)
No
Engine running
1.E No 1. C
2. F 2. D
Yes
SHUT DOWN
Cold Ramp Mode Warm Ramp Mode
Shutdown Trigger :
- PW < 5%
Engine Running - Emergency Condition
- Maintenance
No
Setpoint power output
engine
f = 50 Hz Setpoint until No
5% of Maximum
AVR controls on output engine
the rated voltage
value is similar
with setpoint Yes
Yes
Engine Stop
FINISH
Alternator CB “CLOSED”
Indicator :
- Position of selector switch
Yes
No Disconect from grid
PD < Max. Power
Output 1 Engine
Selection of Engine
Mode by Operator
Calculation
Setpoint (MW) Manual / By
Automatic No
Operator
Yes
- Not affected an active power limitation
- Has reached Lube Oil Temperature >= 40
No - HT Cooling Water Temperature >= 60 Oc
No K CB Opened - The lowest actual active power
Operator select a genset which shall be
switched to droop=0%
Yes No
Engine 1
- Engine 1 Iso Mode (X,Z) - Engine 2 Iso Mode (X,Z) - Engine 1 Iso Mode (X,Z) - Engine 2 Iso Mode (X,Z)
- Engine 2 Droop - Engine 1 Droop - Engine 2 Droop - Engine 1 Droop
Mode – Fixed Mode – Fixed Mode – Fixed Mode – Fixed
Calculation
Setpoint
Yes
No
Yes
Yes
Yes Time :
05.00 p.m - 10.00 p.m
No
Operator
Startup
Operator Operator
Floating Power
Mode Island Mode
(Isochronous Mode)
Giving signal to GCP :
- Giving signal to GCP : Speed Governor - “Droop Mode”
Speed Governor - “Droop Mode” (T) AVR - Power Factor Mode
AVR - Power Factor Mode (U) -Active Power Controller "Fixed" (W)
-Active Power Controller "Floating" (V) - Speed Governor Mode “Droop=0%” (X)
- AVR - Voltage Droop inhibit Mode (Y)
No OH Engine 1 No
OH Engine 1
OH Engine 1 No < 500 hours
< 500 hours
< 500 hours
Engine Running in No
limit condition
Finish