Вы находитесь на странице: 1из 27

Steel Design Guide Series

Serviceability Design Considerations for

Low-Rise Buildings
Steel Design Guide Series

Serviceability Design
Considerations for
Low-Rise Buildings
Serviceability Design Considerations for Low-Rise Buildings
James M. Fisher
and
Michael A. West
Computerized Structural Design
Milwaukee, WI

A M E R I C A N I N S T I T U T E OF S T E E L C O N S T R U C T I O N
© 2003 by American Institute of Steel Construction, Inc. All rights reserved.
This publication or any part thereof must not be reproduced in any form without permission of the publisher.
Copyright  1990

by

American Institute of Steel Construction, Inc.

All rights reserved. This book or any part thereof


must not be reproduced in any form without the
written permission of the publisher.

The information presented in this publication has been prepared in accordance with rec-
ognized engineering principles and is for general information only. While it is believed
to be accurate, this information should not be used or relied upon for any specific appli-
cation without competent professional examination and verification of its accuracy,
suitablility, and applicability by a licensed professional engineer, designer, or architect.
The publication of the material contained herein is not intended as a representation
or warranty on the part of the American Institute of Steel Construction or of any other
person named herein, that this information is suitable for any general or particular use
or of freedom from infringement of any patent or patents. Anyone making use of this
information assumes all liability arising from such use.

Caution must be exercised when relying upon other specifications and codes developed
by other bodies and incorporated by reference herein since such material may be mod-
ified or amended from time to time subsequent to the printing of this edition. The
Institute bears no responsibility for such material other than to refer to it and incorporate
it by reference at the time of the initial publication of this edition.

Printed in the United States of America

Second Printing: October 2003

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
TABLE OF CONTENTS

INTRODUCTION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1 DESIGN CONSIDERATIONS RELATIVE TO


V I B R A T I O N S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 10
DESIGN CONSIDERATIONS RELATIVE TO Human Response to Vibration . . . . . . . . . . . . . . . . . . 10
ROOFING.................................. 2 Machines and Vibration . . . . . . . . . . . . . . . . . . . . . . . 11
Membrane Roofs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2 DESIGN CONSIDERATIONS RELATIVE TO
Metal Roofs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3 EQUIPMENT . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
Elevators.................................... 11
DESIGN CONSIDERATIONS RELATIVE TO Conveyors................................... 12
SKYLIGHTS . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Cranes . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Pendant O p e r a t e d . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
DESIGN CONSIDERATIONS RELATIVE TO Cab Operated . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
CLADDING . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4 Jib C r a n e s . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Foundation Supported Cladding for Crane Runways . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
Gravity Loads . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5 Mechanical Equipment . . . . . . . . . . . . . . . . . . . . . . . . 13
Frame Supported Cladding for Gravity Loads . . . . . 7 CONCLUSION . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
SUMMARY TABLES . . . . . . . . . . . . . . . . . . . . . . . . . . 14
DESIGN CONSIDERATIONS RELATIVE TO
INTERIOR PARTITIONS AND CEILINGS . . . . . 8 R E F E R E N C E S . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
PREFACE

This booklet was prepared under the direction of the Com-


mittee on Research of the American Institute of Steel Con-
struction, Inc. as part of a series of publications on special
topics related to fabricated structural steel. Its purpose is to
serve as a supplemental reference to the AISC Manual of
Steel Construction to assist practicing engineers engaged in
building design.
The design guidelines suggested by the authors that are out-
side the scope of the AISC Specifications or Code do not
represent an official position of the Institute and are not in-
tended to exclude other design methods and procedures. It
is recognized that the design of structures is within the scope
of expertise of a competent licensed structural engineer, ar-
chitect or other licensed professional for the application of
principles to a particular structure.
The sponsorship of this publication by the American Iron
and Steel Institute is gratefully acknowledged.

The information presented in this publication has been prepared in accordance with recognized engineer-
ing principles and is for general information only. While it is believed to be accurate, this information should
not be used or relied upon for any specific application without competent professional examination and verifi-
cation of its accuracy, suitability, and applicability by a licensed professional engineer, designer or archi-
tect. The publication of the material contained herein is not intended as a representation or warranty on
the part of the American Institute of Steel Construction, Inc. or the American Iron and Steel Institute, or
of any other person named herein, that this information is suitable for any general or particular use or of
freedom infringement of any patent or patents. Anyone making use of this information assumes all liability
arising from such use.

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
SERVICEABILITY DESIGN CONSIDERATIONS
FOR LOW-RISE BUILDINGS

INTRODUCTION or failures of any kind. In the real world (as the LRFD
The Metal Building Manufacturers' Association and the commentary points out) there is a finite, but very very small
American Institute of Steel Construction have jointly spon- probability that strength failure will occur. Because of the
sored this guide to develop a clearer understanding of serv- non-catastrophic nature of serviceability failures, a higher
iceability considerations for low-rise buildings. For the pur- probability of occurrence is allowed by current practice.
pose of this presentation, low-rise buildings are taken to have The foregoing is not to say that serviceability concerns are
the following characteristics: unimportant. In fact, the opposite is true. By having few codi-
fied standards, the designer is left to resolve these issues
(1) Function: general purpose structures for such uses as alone. Serviceability events which become serviceability
light manufacturing, crane buildings, warehousing, problems cost money to correct. In fact some aspects of serv-
offices, and other commercial and institutional iceability may be addressed by consideration of the trade-
buildings. off between high initial costs of a cautious design vs. the
(2) Proportions: repair costs associated with a more relaxed design. In this
(a) height: 60 feet tall or less. context one must remember that serviceability events are by
(b) stories: a maximum of five stories. definition not safety related so that a relaxed standard can
(c) aspect ratio: height to width less than or equal to be legitimate.
one. MBMA in its "Common Industry Practices" states that
it is up to the end customer or his agent to identify for the
Although serviceability issues have always been of con- metal building engineer any and all criteria so that the metal
cern, changes in codes and materials have added importance building can be designed to be "compatible with other ma-
3
to these matters. For example, in 1986 the AISC LRFD Spec- terials used on the construction project." This requirement
ification adopted the methodology of limit states design for implies that the end customer knows or could know these
steel structures.2 The Specification recognizes two categor- criteria. Nevertheless, it points out the requirement for the
ies of limit states: strength limit states and serviceability limit active involvement of the end customer in the design stage
states. Strength limit states control the safety of the struc- of a structure and the need for informed discussion of stan-
ture and must be met. Serviceability limit states define the dards and levels of building performance.
functional performance of the structure and should be met. The purpose of this document is to provide a foundation
The distinction between the two categories lies in the con- for that discussion, leading ultimately to a contractual agree-
sequences of exceeding the limit. The consequences of pass- ment between parties. The secondary purpose is to provide
ing a strength limit are buckling, instability, yielding, frac- a catalyst for discussion among engineers, builders, owners,
ture, etc. These consequences are the direct response of the fabricators and manufacturers for consensus on serviceability
structure or element to load. In general, serviceability is- criteria.
sues involve the response of people and objects to the be- Numerous serviceability design criteria exist, but they are
havior of the structure under load. For example, servicea- spread diversely through codes, journal articles, technical
bility involves "unacceptable elastic deformation and drifts" committee reports, manufacturers literature, office standards
and "unacceptable vibrations." and individual engineers. The goal of this paper is to gather
Whether or not a structure or element has passed a limit these criteria for a discussion on serviceability.
state is a matter of judgment. In the case of strength limits, The LRFD Specification lists five topics which relate to
the judgment is technical and the rules are laid down by build- serviceability concerns. They are:
ing codes. In the case of serviceability limits, the judgments
(1) Camber
are frequently non-technical. They involve the perceptions
(2) Expansion and Contraction
and expectations of building owners and building users. Serv-
(3) Deflections, Vibrations and Drift
iceability limits have in general not been codified in the past
(4) Connection Slip
in part because they concern the contractual relations with
(5) Corrosion
the owner rather than the protection of the public at large.
Because of the nature of serviceability limits, it is proper This guide is devoted almost exclusively to "Deflections,
that they remain outside the building codes. Vibrations and Drift." Camber may or may not be a solu-
In a perfect world the distinction between strength and tion to a serviceability issue, and the authors have attempted
serviceability would disappear. There would be no problems to identify appropriate and inappropriate situations in the

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
text. In most instances, the amount of total movement is of ing and analysis approach will be presented and discussed.
concern rather than the relative movement from the speci- Without these three elements (load, analysis approach, and
fied floor elevation, so that camber is not appropriate. There limit) a serviceability design criterion is useless.
are, however, situations where camber is definitely in order In the presentation which follows, criteria are stated for
such as in places where it is possible to sight down the under- given situations. An attempt has been made to document the
side of exposed framing. sources wherever possible. Many of the criteria are based
Expansion and contraction is discussed to a limited ex- upon the authors' own judgment and rules of thumb from
tent. The goal of this paper is to discuss those aspects of their own experience. Regardless of source, serviceability
primary and secondary steel framing behavior as they im- criteria are controversial and thus the authors hope that this
pact non-structural building components. For the types of compilation will be useful as a spearhead to the debate. It
low-rise commercial and light industrial projects which fall should be noted that for specific projects where the govern-
into the scope of this discussion, expansion and contraction ing codes mandate certain deflection limits, these code re-
in the limited context given above are rarely an issue. This quirements must be followed.
does not mean that the topic of expansion and contraction
is unimportant and, of course, the contrary is the case. DESIGN CONSIDERATIONS
Connection slip has not been addressed explicitly in this RELATIVE TO ROOFING
paper. However, it is the authors' intent that the various drift Serviceability as it relates to roofs in large measure relates
and deflection limits include the movements due to connec- to the structure's role in maintaining the integrity of the roof-
tion slip. Where the connection slip or especially the effect ing membrane and the drainage system. Ponding, while it
of accumulated connection slip in addition to flexural and/or relates both to the strength and stiffness of the roof struc-
axial deformations will produce movements in excess of the ture, is not a serviceability issue because a ponding problem
recommended guidelines, "slip-critical joints" should be con- is ultimately a strength problem (see AISC ASD para. K2
sidered. Slip-critical joints are also required in certain in- and commentary and AISC LRFD para. K2).6,10
stances which are enumerated in section 5 of the "Specifi- The concerns for the integrity of the roofing lie in three
cation for Structural Joints Using ASTM A325 or ASTM main areas: (1) in the field of the roof, (2) at the edges, and
A490 Bolts.5 It should be noted that joints made with snug- (3) at penetrations.
tight bolts in standard round holes will not generally result Two types of roofing will be discussed here: membrane
in serviceability problems for individual members or low- roofs and metal roofs on structure.
rise frames. Careful consideration must be given to all other
situations. Membrane Roofs
Corrosion, if left unattended, can lead to impairment of The field of a membrane roof must be isolated from the
structural capacity. Corrosion is also a serviceability concern differential thermal movement of membrane and structure.
as it relates to the performance of non-structural elements This is done by means of "area dividers" in the roof mem-
and must be addressed by good detailing practice and main- brane. The spacing of these joints depends on the type of
tenance. The primary concerns are the control or elimination roofing and climate conditions. They are generally spaced
of staining of architectural surfaces and prevention of rust at intervals of 150-200 feet. They will, in all likelihood, be
formation especially inside assemblies where it can induce spaced at intervals smaller than the building expansion
stresses due to the expansive nature of the oxidation process. joints.9
Again, the solutions are good detailing and maintenance. The integrity of the roofing field is effected by the under-
The serviceability design criteria discussed here will ad- lying structure. Factory Mutual in its Approval Guide gives
8,11
dress these topics: maximum spans for various deck types and gages. It con-
cedes that these limits may be exceeded by 10 percent due
(1) Roofing
to conditions along interior walls or the ends or sides of the
(2) Skylights
building and where column spacings in some bays may be
(3) Cladding
larger to accommodate occupancy. The overspans are not
(4) Interior Partitions and Ceilings
to be considered as initial design conditions. Where over-
(5) Vibrations
span conditions exist, mechanical attachment of the insula-
(6) Equipment
tion and additional side lap fasteners are required by Fac-
As stated above, these criteria for the most part limit rela- tory Mutual. Factory Mutual's acceptance criteria is based
tive and absolute deflection and, in the case of vibrations, on a deflection of span over 200 feet given a two span con-
place limits on the range of response and controls for the dition with a 300-lb. concentrated load at midspan.
14
physical characteristics for structures and elements. The Steel Deck Institute has slightly different criteria.
An essential element of these criteria will be that, in ad- They are: (1) a maximum deflection of span over 240 feet
dition to the limits discussed above, both a consistent load- for uniform design live load and (2) a limit of span over 240

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
feet with a 200-lb. concentrated load at midspan on a 1-ft Metal Roofs
0-in. wide section of deck. SDI also gives maximum recom- Metal roofs are of two types: Through Fastener Roofs (TFR)
mended spans for decks subjected to maintenance and con- and Standing Seam Roofs (SSR). Standing Seam Roofs for
struction loads. the purpose of this discussion include only those of the float-
Both of these standards recognize that the localized and ing type. Standing seam roofs without the floating feature
differential deflections induced by concentrated loads are in should be treated as Through Fastener Roofs.
general more important to the proper performance of the The field of a metal roof must, at times, be divided into
roof than the uniform load capacity. sections. In general, the limitations are as follows: For TFR
The Specification of the American Institute of Steel Con- the limit is on the direction parallel to the ribs and is roughly
struction recommends a minimum depth of roof purlins to 100 to 200 feet to control leakage at fasteners due to elonga-
13
"( /1000) times the span, except in the case of flat roofs." tion of the holes. Most metal building manufacturers rely
The Steel Joist Institute limits the maximum live load upon purlin roll to reduce slotting of the roof panels. Be-
deflection for roof joists and girders to span over 240 feet cause of their inherent greater stiffness, steel joists should
(para. 5.9, 104.10, and 1004.6).15,16,17 The National Roofing not be used with through fastener systems. The limitation
Contractors Association demands a limit on deflection "of on SSR is based on the "theoretical" maximum movement
roofs" to a maximum of span over 240 feet for total load.12 of the hold down clips. Depending on manufacturer it is in
As mentioned in the section on cladding which follows, the range of 150 to 200 feet.
the joint between wall and roof is a critical point. If there The strict control of vertical deflections for metal roofs
can be relative vertical and/or horizontal movement between is only limited near the (eave) ends and edges (rakes). In
wall and roof, the roofing edge detail must be able to ac- the field of the roof, the deflection of purlins can be limited
commodate this movement. If not, a roofing rupture will oc- to span over 150 feet for roof snow load. A maximum abso-
cur. This condition is of less concern where ballasted loose lute limit on deflection has not been specified since the roof-
laid membranes are used. On the other hand, it is a very ing experiences approximately the same curvature as deflec-
significant problem where conventional built-up roofing sys- tion limit increases with span. Setting a maximum absolute
tems are used. In built-up installations unless special isola- limit would control behavior relative to other objects within
tion joints are used, the movement tolerances are very small the building. This aspect is covered in the sections: Parti-
and deflection and movements must be treated on an abso- tions and Ceilings and Equipment. Along the gutters, it is
lute basis consistent with the details. essentail that there be positive drainage after the roof is
Details at penetrations for such items as soil stacks, elec- deflected under design load. Because the perimeter framing
trical conduit and roof drains must allow for vertical move- may be stiffer than the first interior purlin, a deflection check
ment of the roof structure independent of these items which should be made to prevent standing water between the eave
may be rigidly attached to other elements such as the floor and first interior purlin. In the case of side edges, the con-
below. cern is the same as in the case of membrane roofs and that
As for drainage, it is conventional in the roofing industry is that there could be separation in the flashing detail be-
to call for roof slopes on the order of inch per foot. tween wall and roof. This is a matter of limiting the vertical
These slopes are directed to drains by means of sloping the deflection to that tolerated by the detail.
structure, using tapered insulation, sloping fill or a combi- The concern for maintaining drainage on the overall roof
nation of the foregoing. Roof drains, gutters or scuppers are is largely eliminated by the relatively large pitches used for
located at the low points. The problem is that, from time metal roof buildings. They are on the order of inch per
to time, roof drainage points do not wind up at roof low foot for TFR and on the order of inch per foot for SSR.
points. However, it is essential that the deflection of purlins and
It has been suggested that roof drains be located at mid- rafters be checked to ensure positive drainage of the roof
span or mid-bay to take advantage of the low point created under load. This includes dead load and superimposed loads.
by deflection. This can easily be negated by camber (not re- It is recommended that the superimposed load be 50 per-
quested but supplied nonetheless) or upward deflection due cent of the roof snow load with a minimum of 5 psf. Roof
to patterned loading in continuous designs. snow loads are used as opposed to roof live loads, because
If on the other hand, drain points are located at columns, minimum specified live loads are a strength issue rather than
more control is possible. Within the limits of fabrication and a serviceability issue. For those structures without ceilings
erection tolerances, columns are known points of relative ele- or equipment hanging from the roof, this check for drain-
vation. To ensure proper drainage to a low point at a col- age is the only check which need be made.
umn, the maximum deflection in the zone around the col- Because the drainage for metal roofs is universally at the
umn must result in elevations which remain higher than the eaves into interior or exterior gutters or onto the ground,
drain. This is the criteria which must be used to set eleva- a discussion of the location of drainage points is not required.
tions of supports radiating from the low point. The concern for the proper detail of penetrations and

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
through roof pipes and conduits remains and the key is to spreading (or moving together) of supports. This movement
have details which isolate the pipes, etc., from the structure is to be measured along a line connecting the supports and
and roof. should be limited as follows:
DESIGN CONSIDERATIONS inch for alpha less than or equal to 25 degrees
RELATIVE TO SKYLIGHTS inch for alpha between 25 to 45 degrees
inch for alpha greater than or equal to 45 degrees
The design concerns appropriate to skylights are related to
those of cladding in that deflection must be controlled to where alpha is the angle between the line drawn between sup-
maintain consistency with the skylight design and to ensure ports and a line drawn from a support point through the ridge
air and watertight performance of the skylight. As always, of a gabled skylight or the crown of a vault or arch.
one could insist that the skylight manufacturer simply make The second case is control of relative support movement
his design conform to the building as designed, but as a prac- as deviations measured perpendicular to the line drawn be-
tical matter, it is more reasonable to match the limitations tween the support points. This limit is the support spacing
of standard design and detailing practices. over 240 feet with a maximum of inch. The appropriate
Skylights come in a variety of geometries such as planar, loading for both cases of relative movement is those loads
pyramidal, gabled, domed and vaulted. They are generally which will be applied after the skylight is glazed. See Fig-
supported by the roof structure. A key to their interaction ures accompanying the summary tables.
with the primary structure is whether or not they rely on The general issue of deflection prior to the setting of sky-
horizontal as well as vertical support for stability. This will lights is important and must be presented. The deflections
determine the loading of supports and indicate the nature of the support structure must be controlled to provide a rea-
of controls on support deflection. sonable base from which to assemble the skylight. To ac-
The primary reasons for controlling support point displace- complish this, the maximum deviation from true and level
ments for skylights are to: should be inch. Because the concern is the
condition at the time of setting the skylight, this can be
(1) control relative movement of adjacent rafters (warp-
controlled by a combination of stiffness and of camber as
ing of the glass plane).
required.
(2) control in plane racking of skylight frame.
Although not strictly a serviceability issue, one problem
(3) maintain integrity of joints, flashings and gutters.
in the interface between skylight and structure is gravity load
(4) preserve design constraints used in the design of the
thrusts at support points. It is possible to make stable struc-
skylight framing.
tures with and without gravity load thrusts. If the thrust loads
The control of support point movements can best be related are anticipated and accounted for in the structural design,
in reference to the plane(s) of glazing. The two directions there is no problem. If on the other hand, the structural en-
of movement of concern for skylight performance are (1) gineer has not provided for them and the skylight design has
movements normal to the plane(s) of glass and (2) move- counted on thrust resistance, there could be severe problems.
ments parallel to (in the) plane of glass. All vaults, pyramids, and three-hinged, arch-type structures
Movements in the plane of glass are racking-type move- exert lateral thrusts under gravity loading. The construction
ments. The relative displacement of parallel glazing supports documents must clearly spell out the provisions made for
must be limited to maintain gasket grip and prevent the light gravity load thrusts and whether or not the skylight supplier
from bottoming out in the glazing recesses. The limits for is allowed to choose structure types which require gravity
this movement are inch for gasketed mullions and inch load thrust resistance for stability or deflection control.
for flush glazing. The relevant loadings for this limit are those As always, attention to detail and coordination is critical.
which are applied after the skylight is glazed.
Movements normal to the plane of glass are more diffi- DESIGN CONSIDERATIONS
cult to describe. These movements are in two categories: (1) RELATIVE TO CLADDING
absolute movement of individual members; and (2) relative In current practice a line is drawn which separates the struc-
movement of adjacent members. tural and non-structural systems and components of a build-
First, the movement (deflection) of individual supporting ing. The foundations and super structure are structure and
beams and girders should be limited so as to control move- the curtain wall and roof are not. Despite this division what
ment of the skylight normal to the glass to span over 300 is produced in the field is a single unit, a building. It is this
feet with a maximum of 1 inch, where span is the span of unit which receives the ultimate scrutiny regarding its suc-
the supporting beam. The loading for this case would be cess or failure.
those loads occurring after the skylight is glazed. The primary means of controlling the interaction between
Secondly, the relative movement of adjacent supports must cladding and structure is isolation (divorcement in the words
be considered. There are two aspects of this. The first is of the AISC Specification). This is to prevent the inadvertent

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
loading of the cladding by movements in the primary and The concern for horizontal frame deflection varies depend-
secondary structure and is achieved by subdividing the clad- ing on whether the cladding lateral support is statically de-
ding with joints and by attaching the cladding to the struc- terminate or statically indeterminate. If the cladding has only
ture in a manner which is statically determinate. Using an a single tie back connection to the roof, lateral deflection
attachment which is statically indeterminate would require perpendicular to the plane of the cladding is of little con-
a compatibility analysis of both cladding and structure as a cern in the case of metal systems, of moderate concern for
composite structure. tilt-up concrete and full height precast systems, and of great
In addition to proper connections, the other key element concern in masonry systems. The limitation in metal sys-
is joint behavior. Joints are filled with sealants and gaskets. tems is the behavior of the joints at the building corners. The
Movements must be controlled so that these materials func- wall parallel to the direction of movement would not move
tion as intended in their design. The cladding for a building whereas the wall perpendicular to the movement would be
can be either sole source such as from a metal curtain wall dragged along by the frame deflection. The allowance for
manufacturer or be built up from a number of disparate ele- movement at corners is generally a function of the corner
ments such as masonry and window units. Each sort of clad- trim and its inherent flexibility. Thus, it can be seen why
ding has its unique concerns beyond those related to clad- metal clad buildings designed to a drift limit of height over
ding in general. 60 feet to height over 100 feet with 10-year wind loads have
The vertical support of cladding can be accomplished in performed successfully in the past. The case of tilt-up con-
three ways. For one and two story buildings, it is often feasi- crete and full height precast is of only moderate concern be-
ble to support the cladding on the foundation with the only cause the steel frame can drift and the simple span behavior
ties to the structure being those connections which are re- of the panels is preserved. Thus, drift limits in the range
quired for stability and for lateral forces. Secondly, systems of height over 100 feet are appropriate with 10-year wind
consisting of spandrel units or bay sized panels can be sup- loads. Ten-year recurrence interval winds are recommended
ported on the column lines. These connections would be ap- due to the non-catastrophic nature of serviceability issues
propriately detailed to maintain the statically determinate and the need to provide a standard consistent with day-to-
condition of support mentioned above. The third method of day behavior and average perceptions. Fifty-year winds are
support is for those systems of cladding which require sup- special events. In lieu of using the precision of a map with
port along the perimeter horizontal framing. 10-year wind speed isobars, the authors recommend using
The concerns for frame and cladding interaction escalate 75 percent of 50-year wind pressure as a reasonable (plus
as one moves through these three methods. or minus 5 percent) approximation of the 10-year wind pres-
sures. Again, the critical detail remains the corner. It should
Foundation Supported Cladding for Gravity Loads be noted that, in some cases, precast panel walls and tilt-up
In the first method, i.e., support along the foundation, the walls are buried in lieu of a foundation wall. In these cases,
limitations on frame behavior can be summarized as follows: drift must be limited to control cracking since these panels
For vertical deflections, since there is no connection be- are now rotationally restrained at their bases.
tween frame and cladding, the limits on vertical deflection The case of perimeter masonry walls requires a more
are (1) roof and floor beams must have deflections compati- detailed presentation. This is because of the unique nature
ble with the type of vertical slip connections detailed to later- of masonry, which has flexural stiffness with little flexural
ally support the cladding; (2) roof beams must have deflec- strength. For example, a 12-in. segment of 12-in. concrete
tions compatible with the perimeter termination of the block (face shell bedded) has a moment of inertia of 810
roofing membrane to cladding; (3) floor beams must have inches.4 It has a flexural capacity of 3.2 inch-kips (based
deflection compatible with the detailing between wall and upon an allowable stress of 23 psi.27 A 12-in. wide flange
floor finish; (4) floor and roof members must have deflec- section with a comparable moment of intertia (adjusted for
tion compatible with the detail of ceilings and cladding. Be- the difference in modulii of elasticity) can develop a mo-
cause this first method of vertical support is for relatively ment of 280 inch-kips. This wide variation in strength is,
short buildings, the shortening of columns would not be a of course, due to the wide variation in allowable bending
concern. However, it is possible that differential thermal ex- stresses, which in part is due to the ductile nature of steel
pansion would be a concern and this requires care in detail- and the brittle nature of masonry. One can enhance the flex-
ing the joint between interior partitions and the cladding, ural capacity of masonry with reinforcement. The 12-in. wall
which is to say that an isolation joint is required. in the example above can have its strength increased by a
Horizontal deflection of the frame and its effect on the factor of ten to fifteen times with reinforcement. In unrein-
cladding is of a more serious concern in this first method forced masonry, a crack at a critical cross section is a strength
of support. The two modes of movement are: (1) those per- failure. In reinforced masonry, a crack means the reinforce-
pendicular to the plane of cladding; and (2) those parallel ment is functioning, and thus cracking is only a serviceabil-
to the plane of cladding. ity concern. Thus, it can be seen that the increased strength

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
and ductility of reinforced masonry clearly makes it a su- predictable location, presumably at the floor line. The de-
perior choice over unreinforced masonry. tail itself requires careful consideration (see Figure 1). One
All of the foregoing is of concern to the designers of must also inform the owner of the anticipated behavior. It
masonry walls. Masonry design issues become of concern is recommended that the frame drift under the loads asso-
to the designers of steel building frames because masonry ciated with 10-year wind be controlled so as to limit crack
walls are in almost all cases supported by the steel frames width to inch, when a detail such as that of Figure 1 is
for lateral stability. used, and inch where no special detail is used. This
The design of masonry enclosing walls must take into ac- cracked base then becomes the first boundary condition in
count the nature and arrangements of supports. In general, the design of the masonry panel. The model for the panel
perimeter walls are supported along their bottom edges at the must show a hinged base rather than a fixed base. The fore-
foundation. They are additionally supported by some com- going limits are applicable to non-reinforced walls. Where
bination of girts, the roof edge, columns and wind columns. reinforcing is required for strength reasons, it is recom-
All of these elements with the exception of the foundation mended that the drift limit be changed to height over 200
are elements of the structural frame and will deflect under feet. A limit of height over 100 feet can be used if a hinge
load. What confronts the designers of the masonry is the prob- type base (see Figure 2) can be employed.
lem of yielding supports, which can produce results in the The remainder of the panel boundary elements are com-
actual structure which are dramatically different from design ponents of the structural frame. The goal here is to establish
models which are based on non-yielding supports. deflection limits compatible with the masonry. Having run
There are several solutions to this situation as it relates numerous finite element models of wall panels and support-
to the design of the masonry and the design of the steel. They ing framing, two conclusions have been reached. First, al-
are: most categorically, the change from a rigid support to a yield-
ing support can increase moment magnitudes by a factor of
(1) Make no allowance in the steel design and force the
two to three. Second, because of the great stiffness of the
design of the masonry to account for the deflecting
masonry panel itself, it is very difficult to provide reasona-
behavior of the steel.
bly sized support elements with sufficient stiffness to sig-
(2) Limit the deflection of the steel so that it is sufficiently
nificantly alter the distribution of panel shears and moments.
rigid as to nearly achieve the idealized state of non-
yielding supports.
(3) Provide some measure of deflection control in the steel
and design the masonry accordingly.
The first and second solutions are possible, but not practi-
cal. The first requires analysis beyond the scope of normal
building design, especially in that it requires a separate three-
dimensional analysis of the structure and the masonry act-
ing together. The second is nearly impossible in that it re-
quires nearly infinite amounts of steel to provide the near
infinite stiffness.
The third approach is a compromise between the two other
solutions. It involves setting reasonable limits for frame drift
and component deflections (girts, columns, etc.) and sec-
ondly, recognizing that the design of the masonry must con-
form to these deformations. The aspect of the masonry de-
sign which is at issue is the analysis to determine the
magnitude and distribution of shears and moments. The
model used to do this is that of a plate with one- or two-way
action having certain boundary conditions. It is these bound-
ary conditions which must be examined.
The first boundary condition to be examined is the base
of the wall. Although it may be a designer's goal that the
base of the wall not crack, the authors have concluded that
this is an unrealistic and unachievable goal due to the low
allowable bending stresses in masonry. A more realistic ap-
proach is to limit frame drift so as to control crack width
and to provide a detail to ensure that the crack occurs at a Figure 1. Masonry horizontal control joint.

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
Thus, it is the design of the masonry which is the critical there is less load on the girt. In the second approach a girt
element in this relation not the design of the steel. The model is eliminated. However, the wall and its connections to the
consisting of non-yielding supports and a fixed base is not columns must be strong enough to carry not only the wind
accurate. Fortunately, in practice, the increase in moments load on it but also the wind from the bottom span of wall
results in stresses in the range of ultimate bending stresses panel. The third approach requires the largest girt, but the
in the masonry and in the case of reinforced masonry there problem of masonry/wall panel differential deflection is
is the material ductility to mitigate the problem. What is eliminated. Additionally the girt/column connection provides
obvious is that controlling steel deflections is not the solu- the top of wall anchor, thus eliminating a connection between
tion. In order that support deflection not be totally neglected, masonry and building column. Each of these methods is
a limit of span over 240 feet with maximum absolute value workable. As always their success or failure depends on the
of inches is recommended for girts and columns sup- details.
porting masonry under a load associated with a 10-year The recommended limit for the girts supporting the wall
wind. panel above the masonry wainscot wall (as well as the all
One specialized case of masonry wall is that of the wain- metal panel wall) is span over 120 feet using 10-year wind
scot wall. The top of this masonry wall is usually six to loads. An absolute maximum deflection would depend upon
eight feet above the floor and the remainder of the wall is the girt supported equipment, if any, and the relative deflec-
metal panel. The junction between top of the masonry and tion between roof edge or wall base and first interior girt.
bottom of wall panel can be accomplished in three ways: As mentioned above, there is also a concern for movement
(1) isolation of masonry and panel; (2) attachment of the wall of the frame parallel to the cladding. There should be isola-
panel to an angle attached to the top of the masonry; and tion between wall and frame by means of sliding or yielding
(3) attachment of both the masonry and the panel to a girt. connections. Thus, the movement is only limited by the flex-
Each method has its unique concerns. ibility of the roofing wall joint and the floor wall joint. The
In the first case, the masonry and wall panel girt must be practical limitation will be joint behavior at the intersection
checked to limit relative deflection so that an air-tight and of parallel and perpendicular walls as noted earlier.
water-tight joint can be provided which will move but not
leak. This system has the advantage of a smaller girt since Frame Supported Cladding for Gravity Loads
The second method of support for cladding, i.e., connec-
tions to the beam/column intersections, is sometimes used
for buildings of two or more stories in height. In this case,
the frame carries both the vertical and horizontal forces from
the cladding, but the support points are limited to points along
the columns. In the idealized case, there are two support
points which carry vertical and lateral loads and two which
carry lateral loads only. These supports must be detailed to
slide or yield under horizontal forces in the plane of the panel
with the exception of one joint which is required for hori-
zontal shear stability.
One can see that the success or failure of this method de-
pends on the relative movement of the support points.
Vertical movement is the result of absolute and relative
column shortening (and lengthening). The consequences of
this is the performance of the panel perimeter caulk joints.
This movement should be kept in the range of inch, due
to 10-year wind load or 50 percent of design live load. The
other concern is racking of the bay. First, the racking must
be within the limit of movement of the connections, and sec-
ondly the racking must be within the limit of the movement
provided for between panels in adjacent stories. The junc-
tion of four panels where the sealant takes on a cross pat-
tern is a critical location.19 Relative movement between sto-
ries can introduce shearing forces in the intersection of the
horizontal and vertical sealants. While the limit on racking
is a function of connection design and joint detailing, one
Figure 2. Masonry horizontal control joint. can use a maximum interstory drift of story height over 500

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
feet using a 10-year wind load as a target limit with reason- cause the concern is for differential movement between floors
able assurance.19 and one may be able to assume some load on all floors (ex-
The third method of support, i.e., support along the span- cept the top and bottom stories). For these reasons, one may
drels, is the most complex and results in the most problems. consider using 50 percent of the design live load.
In this method, one has the concerns of the foregoing Walls which are continuously supported along a floor or
methods plust the issue of perimeter framing deflections as roof such as masonry walls or stud walls are supported in
well. Again there is the concern over determinate versus in- an indeterminate manner and require compatibility analysis
determinate attachment. The timing of loadings is also of or more commonly strict deflection limits to control dam-
concern. Deflections prior to setting of cladding are impor- age to the cladding.
tant since the fabrication of cladding may, in all likelihood, The limit on deflection given by the Brick Institute of
be done based on an idealized constant story elevations. Sec- America for lintels is maximum total load deflections of span
ondly, deflections during the setting of heavy cladding must over 600 feet but not more than 0.3 inches.29 The absolute
be considered. Lastly, deflections after the completion of limit governs for spans over 15 feet and is consistent with
cladding must be consistent with its detailing. typical joint details at ledges and window heads. BIA limits
It is inevitable that the cladding will not be in the plane lintel rotation to inch. The authors have taken this to mean
of the perimeter framing so one must also consider the ef- a tip from heel to toe of a single support angle which
fects of support deflections as a cantilever and/or the move- is approximately a rotation of 1 degree. ACI 531 also gives
ments created by rotation (torsion) of the parallel spandrel. limits for masonry beams and lintels as span over 360 feet
In the case of determinate attachment of cladding, the con- for total load and span over 600 feet for dead load only.28
cerns of perimeter beam deflection relate to the erection and Limitations for built-up insulation systems on studs are such
in-service performance of joints and details. that the limits given for the determinate systems would ap-
In the case of an indeterminate system, the concerns must ply to these as well.
also include a deflection limit which control stresses in the It should be noted that the foregoing limitations must be
cladding material. compared to deflections which include the effect of creep
In general, the vertical deflection of perimeter framing in those instances where it is appropriate, as in the case of
should be limited to span over 480 feet for total dead load, composite beams.
with an absolute limit of inch due to dead loads imposed
prior to setting the cladding and an absolute limit of in. DESIGN CONSIDERATIONS RELATIVE TO
dead load deflection after setting the cladding. INTERIOR PARTITIONS AND CEILINGS
The effect of setting heavy units sequentially down the The performance of exterior walls and roofs is generally
length of a perimeter framing element should be considered judged by their ability to not leak air or water. The perfor-
when the cladding weight exceeds 25 percent of the total dead mance of partitions and ceilings is largely aesthetic and re-
load on the beam. In this case, the deflection due to clad- lates to cracks and bows. Most finish materials are brittle
ding and initial dead load should be limited to span over 600 and thus have little tolerance for inadvertent loading due to
feet with an absolute limit of inch. deflections. The only notable exception to this is ceiling con-
The limits on vertical deflection after the completion of struction of metal grids and lay-in acoustical panels.
cladding must be consistent with the joints and details and One common criterion in the literature is the limitation
relate primarily to the relative deflections between floors. for floors and roofs supporting plaster ceilings that live load
For example, glass can pull out of the glazing stops which deflection not exceed span over 360 feet. This is found in
would be attached to the floor above. AISC ASD para. L3 and Steel Joist Institute para. 5.9, 104.10
Interlocking mullion expansion joints could disengage. and 1004.6. The SJI additionally applies the span over 360-ft
Windows in continuous slip heads could jam or disengage. limit to situations "where a structural concrete slab is sup-
Precast or stone panel vertical joints can open excessively ported. Also, the SJI limits live load deflection to span over
at the base and squeeze closed at their tops.24 To prevent 240 feet for all other cases.45,46,47 The Steel Deck Institute
these problems and others like them, one must limit live load limits deflection for composite slabs to span over 360 feet
deflection to span over 360 feet with a maximum of inch for superimposed loads.41
to inch depending on the details. Thoughtful considera- These limits produce deflected curvatures which are on
tion must be given to the magnitude of live load (that is load the border line of acceptable visual perceptibility. Other con-
after erection of cladding). It is the nature of live load spec- siderations may require stricter absolute limits on deflection.
ifications to err on the high side. Thus, the reasonably ex- For example, where drywall partitions meet drywall or plas-
pected live load in the perimeter zone of the building would ter ceilings, standard details allow for only inch to inch
generally be less than that specified. This is due to the rela- of movement. This is in general a stricter limit than span
tively low density of use of the floor space near the win- over 360 feet. An alternative to providing a stiffer structure
dows. One may also consider not using the full live load be- would be to support the drywall ceilings from ceiling framing

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
which is supported by the partitions rather than suspend the they deflect under successive applications of dead and live
ceiling from the structure above. This solution may only be load. One common example of this is beam deflection dur-
appropriate for relatively small rooms such as individual ing concreting operations and the possibility of complaints
offices. from finishing contractors over uneven floors. The Ameri-
Another alternative would be to enlarge the joint between can Concrete Institute in its committee report #117, "Stan-
wall and ceiling. This would require non-standard detailing dard Tolerances for Concrete Construction and Materials,"
and consequently a higher standard of care. Ceilings of metal states in para. 2.2.3.3 that "Tolerances for floors cast on
grids and acoustical panels are also of concern. Ceilings of metal decks or other easily deflected material shall not be
this type of construction generally have a high tolerance for less than the calculated deflection anticipated." For concrete
distortion due to the loose nature of their assembly. The one cast on temporary forms, the maximum allowable form
exception to this general characterization is the perimeter deflection in any bay is inch. This can be inferred from
detail. In standard installations this consists of a painted para. 2.1.2.1 which has to do with the deviation from ideal-
metal angle which is attached to the walls around the pe- ized location to the actual. This deviation can only be the
rimeter of the room. The metal ceiling grids bear on this result of misplaced forms and form deflection. ACI in para.
angle as do the perimeter row of ceiling panels. With this 2.2.3.2 says that "Class BX finish tolerances are generally
rigid perimeter, the remainder of the ceiling (on suspenders practical for floors over metal decking... if proper compen-
from the floor above) cannot deflect more than inch to sation has been made for deflection. The lack of planeness
inch without some distress. As in the case with plaster usual in the decking makes closer tolerances quite difficult."
and drywall ceilings, the alternative to controlling deflec- ACI 117 goes on to say "Class BX finish tolerances are gen-
tions in the structure above is to isolate the ceiling perime- erally suitable for Class 1, 2 and floors (residential, offices,
ter. This can be done, but it requires extra hangers and a hospitals, drives, floors, see ACI 302). The BX Surface Fin-
non-standard attachment of the perimeter trim. Addition- ish Tolerance is "Depression in floors between high points
ally, a flexible dust membrane may be needed. In buildings shall not be greater than inch below a 10-ft long straight
where the ceiling is used as a return air plenum, a detail must edge (note: This is span over 334.) ACI 117 in para. 2.1.5
be devised to maintain the effectiveness of this plenum. gives the maximum overthickness deviation for slabs less
The foregoing discussion is directed to downward deflec- than 12 inches thick as inch thick. These ACI Standards
tions of the framing supporting the ceiling from above. There are generally considered the "state of the art" and one should
is also a concern for floor deflections which draws the parti- not modify them without reasoned consideration.
tions downward relative to the ceiling. This situation is Apart from the deflection standards implied in the fore-
usually of lesser concern since the deflection magnitude is going, there are no published limits for the dead load deflec-
the net difference of the deflection of the two levels (except tion of floor beams.
in the top and bottom stories). Both the Steel Deck Institute and the American Society
Deflection of floors is also of concern as it relates to the of Civil Engineers in its "Specifications for the Design and
behavior of partitions. Since the floor supports the walls, the Construction of Composite Slabs" give limits for the deflec-
walls are of necessity forced to conform to the deflected con- tion of metal deck acting as a form. Both give a limit of span
tour of the floor both as the walls are erected and after the over 180 with a maximum of -in. deflection under the
walls are in place. In general, walls can be thought of as deep weight of wet concrete and the weight of the deck (SDI 3.5
40,41
beams or diaphragms. Thus, they have some ability to span and ASCE 2.1.2.2). SDI also limits the maximum
over places where the floor deflects downward beneath un- deflection for form decks to the same constraints. The limits
der the partition. The most vulnerable point in the wall is at on deflection under superimposed load on the composite sec-
the upper corners of door openings for two reasons. The first tion are given as span over 360 feet in SDI para. 5.4 (Com-
is longitudinal shrinkage of the wall itself and secondly be- posite). The ASCE document limits deflection for a range
cause of the discontinuity of the wall acting as a beam. The of span over 180 feet to span over 480 feet depending on
door head is the weak point in the overall wall and can crack conditions. This is presented in Table 2 in the ASCE docu-
as the wall attempts to follow its deflected support. ment which is an adoption of Table 9.5(b) in ACI 318-83.
Thus, as is frequently the case, the solution to structure It can be seen by comparison that the ASCE/SDI limits
partition interaction is effective control jointing. It is recom- are not as strict as those which can be inferred from ACI
mended that control joints be placed at the upper corners 117. Many successful projects have been constructed with-
of doorways and at intervals along walls that are not pierced out enforcing the strict standards of ACI 117. The success
by doors. The spacing of such joints is suggested to be 30 or failure of the concrete placement and finishing operation
feet or closer.34 Other references would restrict the aspect is dependent in large measure upon the skill of the concrete
ratio of the panel to 2:1 to 3:1.35 contractor and his ability to predict and compensate for
As in the case of spandrels supporting a curtain wall along deflections of the deck and supporting beams. To aid this
its length, the behavior of floors is sometimes a problem as process, the construction documents should be very clear as

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
to the finish tolerance and anticipated deflections. Camber- design live load (unless the code imposes a stricter standard).
ing of beams is sometimes helpful, however, it should be The comments in the roof section relating to partitions would
kept in mind that the deflection is the same only the starting also apply to floor deflection. These limits would also in-
elevation is different. clude creep deflection which can be significant in the long
There is also a concern for partition racking induced by term.
interstory drift. One published source gives drift indicies For lateral load: Story height over 500 feet for loads as-
(deflection over height) of 0.0025 (1/400) for "first distress" sociated with a 10-year wind for interstory drift using the
and 0.006 (1/167) for ultimate behavior for drywall on bare frame stiffness.
33
studs. As always, these limits are intended to be reasonable limits
Based on the foregoing discussion, the following deflec- in general. What is required is coordination between the
tion limits for both composite and non-composite beams and deflected structure and the non-structural components to en-
frame drift are recommended: sure that the limits are appropriate in the particular building
For dead load (roof): No limit except (1) as controlled by at hand.
ponding considerations, (2) as controlled by roofing perfor-
mance considerations and (3) as controlled by skylight per- DESIGN CONSIDERATIONS
formance. There is no limit as it relates to partitions and ceil- RELATIVE TO VIBRATIONS
ings since these materials are installed after the dead load Human response and the reaction of machines to vibrations
is in place. In the case of roofs which are concreted, the limits are also serviceability concerns. In general, human response
for floors would apply. to human or machine induced vibration takes a range from
For dead load (floor): Span over 360 feet with a maxi- no concern, through moderate objection and concern for the
mum of 1 in. This is to be the accumulated deflection in a building integrity to physical sickness and rejection of the
bay. This is greater than would be allowed by ACI tolerance structure. In the case of machinery the function of the de-
and requires that this deviation be adequately explained and vice can be impaired or destroyed. In general, the quality
accounted for in the plans and specifications. This deflec- of the output of the machine is the standard of success or
tion limit does not necessarily control ponding of wet con- failure, whereas for human response the criteria are largely
crete, which should be checked separately. The loading for subjective.
this deflection check is the weight of wet concrete, the As it regards the structural framework of a building, hu-
weight of steel deck and the weight of steel framing. For com- man response to vibrations can be limited to two categor-
posite floors, the deflection limits should be applied to the ies: (1) frame behavior in response to wind forces or earth-
instantaneous deflection plus one half of the expected creep quake forces; and (2) floor vibration. In the opinion of the
deflection. authors and other sources, frame behavior in response to
For live load (roof): Span over 360 feet where plaster ceil- lateral loads has not been a problem for the size and shape
ings are used and span over 240 feet otherwise. A maximum of buildings to which this document is limited. Low-rise
absolute value must also be employed which is consistent multi-story buildings are, in general, stiff enough so that wind
with the ceiling and partition details. This absolute limit induced vibrations are not a problem.57 This is, of course,
should be in the range of % inch to 1 inch. It should be noted not the case for high-rise buildings for which there is an abun-
that movable and demountable partitions have very specific dance of literature both theoretical and practical to which
tolerances required for them to function. These special limits reference can be made. Therefore, this discussion will be
are unique to each model and manufacturer and must be limited to floor vibrations.
strictly adhered to.
In many jurisdictions there is a distinction between live Human Response to Vibration
load and snow load. For the purpose of checking these deflec- Floor vibration and human response to it is of concern for
tion limits, it is recommended that one use 50 percent of the the buildings within the scope of this work (as well as for
minimum code specified live load or the 50-year roof snow high rise buildings). Although one must make an effort to find
load (including drifting), whichever produces the greater the appropriate documents, the problem is reasonably well
deflection. It should be noted that roof snow loads are used understood and there are recommended procedures to follow.
at full magnitude due to their probability of occurrence The design approach for consideration of human response
whereas minimum roof live loads are reduced due to their to floor vibration involves the following: (1) the natural fre-
transitory nature (rain, maintenance, etc.). In those juris- quency of the floor; (2) the initial amplitude; (3) the damp-
dictions where there is snow, but the roof load is expressed ing characteristics of the construction; and (4) a standard
as live load, the use of snow loads from model codes such of measure, which relates the previous three items.
as ANSI A58.1 is recommended. During the design phase, it is necessary to calculate the
For live load (floor): Span over 360 feet with a maximum natural frequency of the floor members by formulas involv-
absolute value of 1 inch across the bay with 50 percent of ing the acceleration due to gravity, the elastic modulus,

10

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
moment of inertia, supported weight and span of the ele- by other sources. The effects of such vibrations can be
ment or elements in question. In addition to the calculation mitigated in the following ways:
of natural frequency as required to use a standard of mea-
(1) The machine may be balanced or rebalanced.
sure, it is possible to make some categorical statements about
(2) The vibration source may be removed, relocated or
natural frequency. It is generally recommended that the
restricted. For example, crane runways should not be
natural frequency be different from the frequency of the ex-
attached to office areas in plants.
citing function, especially where resonance can be developed.
(3) Damping in the form of passive or active devices may
For floors, as an example, the frequency associated with
be added.
walking is one to four Hertz (cycles per second), whereas
(4) Isolation may be employed using soft springs or iso-
that associated with dancing is 5 Hz and it is rhythmic. These
lation pads.
frequencies should be avoided in the structure.
(5) The adjacent structure, floor, etc., may be tuned to
The calculation of initial amplitude usually involves the
a natural frequency substantially different from the
calculation of an instantaneous deflection due to a load con-
critical frequency. For example, the floor or its com-
sistent with the standard of comparison. This is generally
ponents should have a frequency which is either less
a load which simulates a "heel-drop" impact.
than one-half or greater than one and one-half times
An estimation of the damping as a percent of critical damp-
the fundamental frequency of the equipment.
ing is required, first, because the duration and nature of the
vibration are important to perception, and secondly, because Needless to say, the proper functioning of equipment is
this has been incorporated into the standard of comparison. critical in any operation. Thus, in the design of facilities such
Damping percentages in the absence of physical testing are as labs, medical or computer areas and manufacturing plants,
estimates and they are in the range of: vibration consideration is essential and the active participa-
tion of the owner and equipment suppliers is required to set
Bare floor: 3% (light slab and framing)
limits and provide performance data.
Finished floor: 6% (ceilings, ducts, flooring, furniture)
Finished floor: 13% (with partitions) DESIGN CONSIDERATIONS
Murray has recommended that there is no need to check RELATIVE TO EQUIPMENT
vibrations where damping is in the range of 8-10 percent.53 The assortment of equipment used in buildings is many and
A review of his commentary on this suggests that this would varied. This discussion will be limited to equipment which
usually apply to areas with fully developed partition layouts. is a permanent part of the building and will cover elevators,
This is consistent with general experience in that vibration conveyors, cranes and mechanical equipment.
critical areas are usually those of lightly loaded large open
spans. Elevators
The standard of measure for vibrations are plots of hu- Elevators are of two types: hydraulic and traction. Hydrau-
man response ("Not perceptible" through "Strongly percept- lic elevators are moved by a piston which is generally embed-
ible") in graph form of which the axes are Frequency (Hz ded in the earth below the elevator pit. Traction elevators
or CPS) and Displacement Amplitude.58 These plots are are moved by a system of motors, sheaves, cables and coun-
based on data collected by Reiher-Meister for steady state terweights. In both types the cars are kept in alignment by
vibrations and subsequently modified by Lenzen for single tee shaped tracks which run the height of the elevator shafts.
impact induced vibrations. Other plots have been made by Such tracks are also used to guide the counterweight in trac-
Wiss-Parmelee and examination has shown them to be con- tion elevators.
sistent with the modified Reiher-Meister plots which are Elevators impose few limits on deflection other than those
recommended for use in making judgment during design.58 previously mentioned in the sections on cladding and parti-
It should be noted that many floors which fall into the Dis- tions. A building drift limit of height over 500 feet calcu-
tinctly Perceptible range will perform adequately when they lated on the primary structure using 10-year winds will pro-
lie in the bottom half of the range, provided there is damp- vide adequate shaft alignment for the heights of buildings
ing on the order of at least 6 to 8 percent. discussed in this report. The vertical deflection limits given
For a full treatment of the foregoing, including the plot for floors in the partition section will provide adequate con-
of the modified Reiher-Meister scale, the cited references trol on the vertical location of sills. The only extraordinary
should be consulted. requirement is found in ANSI/ASME A17.1 rule 105.5 which
states, "The allowable deflections of machinery and sheave
Machines and Vibration beams and their immediate supports under static load shall
The behavior of machines in structures as it relates to vibra- not exceed 1/1666 of the span." The term "static load" re-
tion can be treated generally whether the machine is induc- fers to the accumulated live and dead loads tributary to the
ing the vibration or being acted upon by vibration induced beams in question including the unfactored elevator loads.

11

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
Although it would not be required by a strict reading of rule able movements during crane operation and it is recom-
105.5 the authors recommend that the span over 1666-ft limit mended that this be reviewed with the building owner at the
be used for the girders (if any) which support the beams. design stage.61
However, the limit need not be applied to the accumulated
deflection in the bay. Cab Operated
A drift limit for cab operated cranes is required so that the
Conveyors system will be perceived as safe by the operators. The limit
It is very difficult to give clear-cut serviceability guidelines for drift in the direction perpendicular to the runways is sug-
relative to the performance of conveyors due to their diverse gested to be height over 240 feet with a maximum of 2
configurations and the diverse nature of the materials con- inches.61 This displacement is to be measured at the eleva-
veyed. However, the following comments can be offered. tion of the runways. The appropriate loading is either the
The key to conveyor performance is the maintenance of crane lateral force or the lateral loads associated with a
its geometry especially in the area of switches and transfer 10-year wind on the bare frame. The crane lateral loads are
points. In general, the construction of conveying equipment those specified by the AISC Specification or the AISE Spec-
is flexible enough to absorb some distortion due to differen- ification as appropriate.
tial deflection of support points. Thus, the deflection limits The longitudinal displacement of crane runways is rarely
recommended in the sections on roofs and floors would be of concern when hot rolled shapes are used in the X-bracing.
appropriate for the design of roofs and floors supporting con- If, on the other hand, rigid frames are used, column bend-
veyors, i.e., span over 150 to 240 feet for roofs and span ing may result in an excessively limber structure. In the
over 360 feet for floors for live load including conveyor load. absence of any standard for this movement the authors pro-
As always, the conveyor supplier must account for support pose using the same limits as those proposed above for the
point deflection where sections are supported with an indeter- movements perpendicular to the runways. The loading for
minate arrangement of supports. this condition is the crane tractive forces. Consideration
There are three areas of special concern, however. First, must also be given to account for the longitudinal movement
because conveyors are rarely attached to all roof members, which is the result of column torsional rotations at brack-
there may be cases where the differential deflection places eted runway supports.
unexpected loads on the deck and deck fasteners which may Another category of movements are those which affect the
result in localized distress. Secondly, heavy conveyor loads lateral alignment of the runways. First, the lateral deflec-
may cause stress reversals in light and lightly loaded roofs, tions of the runways themselves should be limited to span
which must be accounted for in this design. Third, conveyors over 400 feet to avoid objectional visual lateral move-
can also cause local member distortions when they are not ments.65 The loading in this case is the lateral crane force.
properly connected to the framing. Because of the potential Secondly, one must control the relative lateral movements
for interface problems, it is essential that the conveyor sup- of support points to prevent the runways from moving apart
pliers criteria be discussed and incorporated into the design. or together. This will prevent the wheels from either drop-
ping between the rails or alternatively having the flanges bind
Cranes against the rails.
There are two categories of movement related to the opera- Loads affecting the inward or outward movement of sup-
tion of cranes. First, there are those building movements in- port points are those applied to the structure after the align-
duced by the crane operation which affect the performance ment of the rails. Inward movement is by and large the re-
of the building. The limits given in the previous sections are sult of crane loads, whereas the outward movements is caused
appropriate for the control of building movements induced by roof loads, chiefly high snow loads.
by crane operation. The second category of movements are The allowable amount of inward movement is controlled
those induced by other loads (perhaps in combination with by the arrangement and proportions of the wheel flange spac-
crane forces) which affect the performance of the cranes ing and should be coordinated with the crane supplier. The
themselves. This second area will be covered in this section. control of inward movements can be on the order of ½ inch
Three types of cranes will be discussed: pendant operated total.
traveling cranes, cab operated traveling cranes, and jib cranes. Outward column deflections at crane runway elevations
should be limited so that the total spread of the runways will
Pendant Operated not exceed one inch. The appropriate loading is snow load.
For pendant operated cranes, there are less strict require- It is suggested that the roof snow load be taken as zero in
ments. The controls related to other aspects of building per- areas where the 50-year snow is 13 psf or less. Fifty percent
formance will suffice. of the roof snow load should be taken in areas where the
However, it should be noted that buildings designed with roof snow load is between 13 psf and 31 psf and three-
a limit on drift of height over 100 feet will exhibit observ- quarters of the roof snow should be used where the roof

12

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
snow load is greater than 31 psf, when evaluating this piping, ductwork, exhaust hoods, coils, compressors, pumps,
differential movement. fans, condensers, tanks, transformers, switchgear, etc. This
equipment can be dispersed throughout the building, col-
Jib Cranes lected into mechanical rooms and/or located on the roof in
Jib cranes are in general attached to building columns. The the form of pre-engineered package units. The key feature
principal concern as it relates to deflections is that the drop of this equipment is that it represents real loads as opposed
of the outboard end of the jib cannot be so much as to pre- to code specified uniform loads which may or may not ever
vent the trolley from moving back towards the column with exist in their full intensity. Because of this, a degree of extra
reasonable effort. The limit of the drop of the outboard end attention should be applied to the control of deflections as
should be a maximum of the jib boom length over 225 feet. they relate to mechanical equipment.
One must keep in mind that this movement is the summa- This is especially true where the mechanical equipment
tion of the cantilever behavior of the jib itself plus the bend- loads are the predominant part of the total loads on a given
ing of the column due to the jib reaction. This second com- structure. What is of concern is excessive tilting and rack-
ponent may be significant when the jib is rotated so that it ing of equipment which could impair its function and
applies its loads to the weak axis of the column. differential deflection which could deform or break inter-
connecting piping or conduits. While the actual deflection
Crane Runways limits on each project should be carefully reviewed with the
Crane runways must also be controlled for vertical deflec- mechanical engineers and equipment suppliers, it can be
tions. Such deflections are usually calculated without an in- stated that buildings designed to the standard span over 150
crease for vertical impact. The deflection limits for various to 240 feet for roofs and span over 360 feet for live loads
crane types and classes are given below. have generally performed well.
Top running cranes:
CMAA Classes A, B and C . . . Span over 600 feet65
CMAA Class D . . . . . . . . . . . . . . . Span over 800 feet CONCLUSION
CMAA Classes E and F . . . . .Span over 1000 feet62 The criteria presented in each of the previous topic areas
Underhung and monorail cranes: are summarized in the tables which follow. Because of the
CMAA Classes A, B and C . . . . . Span over 450 feet limitations of this format and the consequent abbreviation,
Note: Underhung cranes with more severe duty cycles the reader is cautioned against using the summary tables
must be designed with extreme caution and are without reference to the full discussion in the text.
not recommended. As stated in the Introduction, the presentation of the
material in this guide should prompt discussion of this very
Mechanical Equipment important area of engineering practice. The authors hope that
Mechanical equipment for buildings generally consists of this goal is achieved.

13

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
SERVICEABILITY CONSIDERATIONS
ROOFING

ROOFING STRUCTURAL DEFORMATION RECOMMENDED LOADING


TYPE ELEMENT MAXIMUM
ROOFING HORIZONTAL
150' TO 200' THERMAL
EXPANSION JOINTS MOVEMENT

METAL DECK
VERTICAL DEFL. L/200 300# LOAD
(TWO SPAN)

METAL DECK VERTICAL DEFL. L/240 LL

METAL DECK VERTICAL DEFL. L/240 200# LOAD


MEMBRANE
ROOFS

MAINTENANCE &
METAL DECK - DECK SPAN †
CONSTRUCTION

PURLIN DEPTH
PURLINS VERTICAL DEFL. -
(Fy/1000) x SPAN

STEEL JOISTS VERTICAL DEFL. L/240 LL

JOIST GIRDERS VERTICAL DEFL. L/240 LL

"ROOFS" VERTICAL DEFL. L/240 DL + LL

1/8" TO 1/4" DRAINAGE


ROOFS SLOPE
PER FOOT

† - SEE SDI SPECIFICATIONS AND COMMENTARY


NOTES FOR STEEL ROOF DECK: SECTION 3.4

NOTE: THESE TABLES PRESENT INFORMATION TAKEN FROM THE TEXT AND PUT IN SUMMARY FORM. THE READER IS
CAUTIONED AGAINST USING THIS MATERIAL WITHOUT REFERENCE TO DISCUSSION PRESENTED IN THE TEXT.

14

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
SERVICEABILITY CONSIDERATIONS
ROOFING

ROOFING STRUCTURAL DEFORMATION RECOMMENDED LOADING


TYPE ELEMENT MAXIMUM
HORIZONTAL
EXPANSION JOINTS 100' TO 200' THERMAL
MOVEMENT

METAL ROOFS ROOF SLOPE 1/2" /FT. DRAINAGE

THROUGH
VERTICAL
FASTENER TYPE PURLIN
DEFLECTION
L/150 SNOW LOAD

VERTICAL POSITIVE DL + .5 x SNOW LOAD


PURLIN
DEFLECTION DRAINAGE DL + .5 PSF (MIN)

HORIZONTAL
EXPANSION JOINTS 150' TO 200' THERMAL
MOVEMENT

ROOF SLOPE 1/4" /FT. DRAINAGE


METAL ROOFS
STANDING SEAM VERTICAL
PURLIN L/150 SNOW LOAD
DEFLECTION

VERTICAL POSITIVE DL + .5 x SNOW LOAD


PURLIN
DEFLECTION DRAINAGE DL + .5 PSF (MIN)

NOTE: THESE TABLES PRESENT INFORMATION TAKEN FROM THE TEXT AND PUT IN SUMMARY FORM. THE READER IS
CAUTIONED AGAINST USING THIS MATERIAL WITHOUT REFERENCE TO DISCUSSION PRESENTED IN THE TEXT.

15

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
SERVICEABILITY CONSIDERATIONS
SKYLIGHT SUPPORTS

DEFORMATION CRITERIA LOADING

SKYLIGHT
FRAME RACKING

SKYLIGHT
FRAME RACKING

DEFLECTION
NORMAL TO GLAZING

NOTE: THESE TABLES PRESENT INFORMATION TAKEN FROM THE TEXT AND PUT IN SUMMARY FORM. THE READER IS
CAUTIONED AGAINST USING THIS MATERIAL WITHOUT REFERENCE TO DISCUSSION PRESENTED IN THE TEXT.

16

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
SERVICEABILITY CONSIDERATIONS
CLADDING
CLADDING CLADDING TYPE
SUPPORT AND DEFORMATION RECOMMENDED LOADING
TYPE SUPPORT ELEMENT MAXIMUM

METAL PANELS/ DRIFT PERPENDICULAR


H/60 TO H/100 10 YEAR WIND
BARE FRAME TO WALL

METAL PANELS/
HORIZONTAL DEAL L/120 10 YEAR WIND
GIRTS

METAL PANELS/
HORIZONTAL DEFL. L/120 10 YEAR WIND
WIND COLUMNS
FOUNDATION

PRECAST WALLS/ DRIFT PERPENDICULAR


H/100 10 YEAR WIND
BARE FRAME TO WALL

UNREINFORCED MASONRY DRIFT PERPENDICULAR 1/16" CRACK WIDTH *


10 YEAR WIND
WALLS/BARE FRAME TO WALL WALL BASE

REINFORCED MASONRY DRIFT PERPENDICULAR


H/200 † 10 YEAR WIND
WALLS/BARE FRAME TO WALL

MASONRY WALLS/
HORIZONTAL DEFL. L/240 1.5" 10 YEAR WIND
GIRT

MASONRY WALLS/
HORIZONTAL DEFL. L/240 1.5" 10 YEAR WIND
WIND COLUMNS

MASONRY WALLS/
VERTICAL DEFL. L/600 0.3" DL + LL
LINTEL

MASONRY WALLS/
ROTATION 1 deg. DL + LL
LINTEL

PRE-ASSEMBLED RELATIVE
COLUMNS

1/4" .5 x LL
UNITS/COLUMNS SHORTENING

PRE-ASSEMBLED
RACKING H/500 10 YR. WIND
UNITS/BARE FRAME

CURTAIN WALLS/
RACKING H/500 10 YR. WIND
BARE FRAME

CURTAIN WALLS/ DL
VERTICAL DEFL. 3/8"
SPANDREL (PRIOR TO CLADDING)
SPANDRELS

CURTAIN WALLS/
VERTICAL DEFL. L/480 5/8" TOTAL DL
SPANDREL

CURTAIN WALLS/ L/360


VERTICAL DEFL. .5 x LL
SPANDREL 1/4" TO 1/2" ‡
CURTAIN WALLS/ DL +
VERTICAL DEFL. L/600 3/8"
SPANDREL CLADDING WT. §

* - 1/8" WITH PROPER DETAILING


NOTES † - H/100 WITH PROPER DETAILING
‡ - DEPENDS ON WINDOW HEAD DETAILS
§ - WHEN CLADDING WT. > 25% OF TOTAL DEAD LOAD

NOTE: THESE TABLES PRESENT INFORMATION TAKEN FROM THE TEXT AND PUT IN SUMMARY FORM. THE READER IS
CAUTIONED AGAINST USING THIS MATERIAL WITHOUT REFERENCE TO DISCUSSION PRESENTED IN THE TEXT.

17

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
SERVICEABILITY CONSIDERATIONS
CEILINGS & PARTITIONS

FINISH STRUCTURAL DEFORMATION RECOMMENDED LOADING


TYPE ELEMENT MAXIMUM

VERTICAL L/360
ROOF MEMBER LL OR 50 YR. SNOW
DEFLECTION (PLASTERED CEILINGS)
CEILING

VERTICAL
ROOF MEMBER L/240 LL OR 50 YR. SNOW
DEFLECTION

VERTICAL
FLOOR BEAM/GIRDER L/360 1" DL
DEFLECTION

LATERAL
FRAME H/500 10 YR. WIND
DRIFT
PARTITION

VERTICAL
ROOF MEMBER 3/8" TO 1" † .5 X LL OR 50 YR. SNOW
DEFLECTION

VERTICAL
FLOOR BEAM/GIRDER L/360 3/8" TO 1" .5 x LL
DEFLECTION

NOTES † - DEPENDS ON PARTITION DETAILS

NOTE: THESE TABLES PRESENT INFORMATION TAKEN FROM THE TEXT AND PUT IN SUMMARY FORM. THE READER IS
CAUTIONED AGAINST USING THIS MATERIAL WITHOUT REFERENCE TO DISCUSSION PRESENTED IN THE TEXT.

18

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
SERVICEABILITY CONSIDERATIONS
EQUIPMENT

EQUIPMENT STRUCTURAL RECOMMENDED LOADING


DEFORMATION
TYPE ELEMENT MAXIMUM

RUNWAY TOTAL INWARD CRANE VERTICAL


1/2"
SUPPORTS MOVEMENT STATIC LOAD

RUNWAY TOTAL OUTWARD


TOP RUNNING

1" SNOW
SUPPORTS MOVEMENT
CRANES

RUNWAY HORIZONTAL
L/400 CRANE LATERAL
BEAM DEFLECTION

RUNWAY VERTICAL CMAA CLASS CRANE VERTICAL


L/600; A,B,C
BEAM DEFLECTION STATIC LOAD

RUNWAY VERTICAL CMAA CLASS CRANE VERTICAL


L/800;
BEAM DEFLECTION D STATIC LOAD

RUNWAY VERTICAL CMAA CLASS CRANE VERTICAL


L/1000;
BEAM DEFLECTION E,F STATIC LOAD

TOP RUNNING BARE DRIFT AT CRANE LATERAL OR


H/240 2"
CAB OPERATED FRAME RUNWAY ELEV. 10 YR. WIND

TOP RUNNING BARE DRIFT AT CRANE LATERAL OR


H/100
PENDANT OPERATED FRAME RUNWAY ELEV. 10 YR. WIND

RUNWAY VERTICAL CMAA CLASS


UNDERHUNG CRANE L/450; CRANE VERTICAL
BEAM DEFLECTION A,B,C

JIB CRANE BOOM VERTICAL L/225 CRANE VERTICAL


DEFLECTION

BARE
DRIFT H/500 10 YR. WIND
FRAME
ELEVATORS

SHEAVE VERTICAL
L/1666 DL + LL
BEAMS DEFLECTION

SHEAVE VERTICAL
L/1666 DL + LL
SUPPORT BEAMS DEFLECTION

NOTES † - SUM OF BOTH RUNWAYS

NOTE: THESE TABLES PRESENT INFORMATION TAKEN FROM THE TEXT AND PUT IN SUMMARY FORM. THE READER I
CAUTIONED AGAINST USING THIS MATERIAL WITHOUT REFERENCE TO DISCUSSION PRESENTED IN THE TEXT.

19

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
REFERENCES Cladding
18. Architectural Precast Concrete, Prestressed Concrete In-
Introduction
stitute, Chicago, 1973.
1. Galambos, T. V., P. L. Gould, M. K. Ravindra, H. Sur- 19. Bergmann, Roland, Structural Serviceability Aspects of
youtomo, and R. A. Crist, Structural Deflections: A Building Envelopes in Tall Buildings, Proceedings, Sym-
Literature and State of the Art Survey, Washington, posium/Workshop on Serviceability of Buildings, Na-
D.C.: U.S. Department of Commerce, National Bureau tional Research Council Canada, May 1988.
of Standards, 1973. 20. Building Code Requirements for Concrete Masonry
2. Load and Resistance Factor Design Specification for Structures and Commentary (ACI531), American Con-
Structural Steel Buildings and Commentary, AISC 1986. crete Institute, 1979.
3. Low Rise Building Systems Manual, MBMA 1986. 21. Ellingwood, Bruce, Serviceability Guidelines for Steel
4. Minimum Design Loads for Building and Other Struc- Structures, Proceedings, 1988 National Steel Construc-
tures, ANSI A58.1, American National Standards Insti- tion Conference, American Institute of Steel Construc-
tute, New York, 1982. tion, 1988.
5. Specification for Structural Joints Using ASTM A325 22. Freeman, S. A., Racking Tests of High Rise Partitions,
or A490 Bolts—Allowable Stress Design, American In- Journal of Structural Engineering, American Society of
stitute of Steel Construction, November 13, 1985. Civil Engineers, Vol. 103, No. 8, August 1977.
6. Specification for the Design, Fabrication and Erection 23. Galambos, Theodore V. and Bruce Ellingwood, Serv-
of Structural Steel Buildings with Commentary, Ameri- iceability Limit States: Deflection, Journal of Structural
can Institute of Steel Construction, 1989. Engineering, American Society of Civil Engineers, Vol.
7. Steel Structures for Buildings—Limit States Design, 112, No. 1, January 1986.
CAN3-S16.1-M78, Canadian Standards Association, 24. PCI Design Handbook: Precast and Prestressed, 3rd
reprinted, Handbook of Steel Construction, Canadian Edition, Prestressed Concrete Institute, Chicago, 1985.
Institute of Steel Construction, 3rd Edition, December 25. Recommended Practice for Engineered Brick Masonry,
1980. Brick Institute of America, 1978.
26. Simiu, E., M. J. Changery and J. J. Filliben, Extreme
Roofing
Wind Speeds at 129 Stations in the Contiguous United
8. Approval Guide, 1987—Equipment, Materials, Service States, U.S. Department of Commerce, National Bureau
for Conservation of Property, Factory Mutual Research of Standards, 1979.
Corporation, Factory Mutual System 1987. 27. Specification for the Design and Construction of Load
9. Expansion Joints in Buildings, Federal Construction Bearing Concrete Masonry, National Concrete Masonry
Council, Technical Report No. 65, National Academy Association, 1978.
of Sciences—National Research Council, Washington, 28. Specification for the Design, Fabrication and Erection
D.C . of Structural Steel for Buildings with Commentary,
10. Load and Resistance Factor Design Specification for American Institute of Steel Construction, 1978.
Steel Buildings and Commentary, American Institute of 29. Technical Notes on Brick Construction, Brick Institute
Steel Construction, Chicago, 1986. of America: Nos. 18, 18A and 18B "Differential Move-
11. Loss Prevention Data for Roofing Contractors, Factory ment," 1988; Nos. 28 and 28B: "Brick Veneer," 1987;
Mutual Research Corp., Factory Mutual System, vari- No. 31B: "Structural Steel Lintels," 1987.
ous dates. 30. Wind Drift of Steel-framed Buildings: State of the Art
12. N.R.C.A. Roofing and Waterproofing Manual, The, Na- Report, ASCE Task Force on Drift Control of Steel
tional Roofing Contractors Association, Chicago, 1981. Building Structures of the Committee on Design of Steel
13. Specification for the Design, Fabrication and Erection Building Structures, Journal of Structural Engineering,
of Structural Steel for Buildings with Commentary, American Society of Civil Engineers, Vol. 114, No. 9,
American Institute of Steel Construction, 1989. September 1988.
14. Specifications and Commentary for Steel Roof Deck,
Steel Deck Institute, 1987.
15. Standard Specifications for Joist Girders, Steel Joist In- Interior Partitions and Ceilings
stitute, 1990. 31. Building Code Requirements for Reinforced Concrete
16. Standard Specifications for Long Span Steel Joists, LH- (ACI 318-89), American Concrete Institute, 1989.
series and Deep Long Span Steel Joists, DLH—series, 32. Fisher, James M. and Donald R. Buettner, Applications
Steel Joist Institute, 1990. of Light-gage Steel in Composition Construction, Hand-
17. Standard Specifications for Open Web Steel Joists, book of Composite Construction Engineering, Van Nos-
K-series, Steel Joist Institute, 1990. trand Reinhold, 1979.

20

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
33. Freeman, S. A., Racking Tests of High Rise Partitions, iceability: Floor Vibrations, Journal of Structural En-
Journal of Structural Engineering, American Society of gineering, American Society of Civil Engineers, Vol.
Civil Engineers, Vol. 103, No. 8, August 1977. 110, No. 2, February 1984.
34. Gypsum Construction Handbook, 3rd Edition, United 51. Lenzen, Kenneth H., Vibration of Steel Joist—Concrete
States Gypsum Company, 1987. Slab Floors, Engineering Journal, American Institute
35. Nemestothy, E. and Gy. Visnovitz, Experimental Anal- of Steel Construction, July 1966.
ysis of the Deformability of Partition Walls and Brittle 52. Meriam, J. L., Statics and Dynamics, John Wiley and
Coverings, Proceedings, Symposium/Workshop on Serv- Sons, Inc., New York, 1967.
iceability of Buildings, National Research Council 53. Murray, Thomas M., Design to Prevent Floor Vibra-
Canada, May 1988. tions, Engineering Journal, American Institute of Steel
36. Ramsey, Charles G. and Harold R. Sleeper, Architec- Construction, Vol. 12, No. 3, 1975.
tural Graphic Standards, American Institute of Archi- 54. Murray, Thomas M. and William E. Hendrick, Floor
tects, John Wiley and Sons, 1970. Vibrations and Cantilevered Construction, Engineering
37. Ruddy, John L., Ponding of Concrete Deck Floors, En- Journal, American Institute of Steel Construction, Vol.
gineering Journal, American Institute of Steel Construc- 14, No. 3, 1977.
tion, Vol. 23, No. 3, 1986. 55. Rainer, J. H., Vibrations in Buildings, Canadian Build-
38. Sabnis, Gajanan and J. K. Sridhar, Fundamentals and ing Digest—Division of Buildings Research, National Re-
Overview of Composite Action in Structures, Handbook search Council Canada, May 1984.
of Composite Construction Engineering, Van Nostrand 56. Steffens, R. J., Structural Vibration and Damages, De-
Reinhold, 1979. partment of the Environment, Building Research Estab-
39. Salmon, Charles G. and James M. Fisher, Composite lishment, London, 1974.
Steel Concrete Construction, Handbook of Composite 57. Tallin, Andrew and Bruce Ellingwood, Serviceability
Construction Engineering, Van Nostrand Reinhold, 1979. Limit States: Wind Induced Vibrations, Journal of Struc-
40. Specification for the Design and Construction of Com- tural Engineering, American Society of Civil Enginer-
posite Slabs and Commentary on Specifications for the ing, Vol. 110, No. 10, 1984.
Design and Construction of Composite Slabs, Ameri- 58. Vibration of Steel Joist Floors, SJI Technical Digest,
can Society of Civil Engineers, 1984. No. 5, Steel Joist Institute, 1988.
41. Specifications and Commentary for Composite Steel
Floor Decks, Steel Deck Institute, 1987. Equipment
42. Specifications and Commentary for Non-composite 59. Elevators and Escalators, A17.1, American National
Steel Form Deck, Steel Deck Institute, 1987. Standards Institute, 1981.
43. Specifications and Commentary for Steel Roof Deck, 60. Fisher, James M. and Donald R. Buettner, Light and
Steel Deck Institute, 1987. Heavy Industrial Buildings, American Institute of Steel
44. Specifications for Structural Concrete for Buildings (ACI Construction, September 1979.
301-84) American Concrete Institute, 1984. 61. Fisher, James M., Industrial Buildings: Guidelines and
45. Standard Specifications for Joist Girders, Steel Joist In- Criteria, Engineering Journal, American Institute of
stitute, 1990. Steel Construction, Vol. 21, No. 3, 1984.
46. Standard Specifications for Long Span Steel Joists, LH- 62. Guide for the Design and Construction of Mill Build-
series and Deep Long Span Steel Joists, DLH-series, ings, AISE Technical Report No. 13, Association of Iron
Steel Joist Institute, 1990. and Steel Engineers, August 1979.
47. Standard Specifications for Open Web Steel Joists, 63. Load and Resistance Factor Design Specification for
K-series, Steel Joist Institute, 1990. Steel Buildings and Commentary, American Institute of
48. Standard Tolerances for Concrete Construction and Ma- Steel Construction, Chicago, 1986.
terials (ACI 117-81), American Concrete Institute, 1981. 64. Low Rise Building Systems Manual, Metal Building
Manufacturers Association, 1986.
Vibrations 65. Specifications for Electric Overhead Traveling Cranes,
49. Allen, D. E., and J. H. Rainer, Floor Vibration, Cana- Crane Manufacturers Association of America, 1987.
dian Building Digest—Division of Building Research, 66. Specification for the Design, Fabrication and Erection
National Research Council Canada, September 1975. of Structural Steel for Buildings with Commentary,
50. Ellingwood, Bruce, and Andrew Tallin, Structural Serv- American Institute of Steel Construction, 1989.

21

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.
DESIGN GUIDE SERIES
American Institute of Steel Construction, Inc.
One East Wacker Drive, Suite 3100
Chicago, Illinois 60601-2001

Pub. No. D 8 0 3 (5M194)

© 2003 by American Institute of Steel Construction, Inc. All rights reserved.


This publication or any part thereof must not be reproduced in any form without permission of the publisher.

Вам также может понравиться