Вы находитесь на странице: 1из 46

BurnerTronic BT300

BT320...BT340

Parameter list
en

Original Operating Instructions .. 4200 1048 5600


Remote software........................... 4200 1017 5300
Fault list ......................................... 4200 1017 8500

09/2012 - Art. Nr. 4200 1018 1500A


Contents

1 VALIDITY OF THIS MANUAL . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2

2 PARAMETER LIST . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .3

2.1 System . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3

2.2 Maintenance . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4

2.3 Monitor output . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5

2.4 Power controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6

2.5 O2 controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11

2.6 CO controller. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 16

2.7 CO controller optimisation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 17

2.8 CO controller monitoring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 18

2.9 CO controller CO detection . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 19

2.10 CO controller edge signal . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 20

2.11 FAT (automatic combustion control unit) . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 21

2.12 Sequencer . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 26

2.13 Channel configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 28

2.14 Actuators . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 31

2.15 Ratio controller . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 33

2.16 Monitoring bands . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 38

2.17 LSB/fieldbus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 40

2.18 Feature parameters . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 43

09/2012 - Art. Nr. 4200 1018 1500A 1


1 Validity of this manual

1 Validity of this manual


This document is a supplement to the instruction manual for the BT300. It is valid only in
conjunction with the instruction manual for the respective device. The information in this
document relates to the latest software version. If you are using an older software version,
your device may not work exactly as described here.

09/2012 - Art. Nr. 4200 1018 1500A 2


2 Parameter list

2 Parameter list
2.1 System

No. Device Explanation Attributes


0001 BT300 ##Helligkeit der LCD Hintergrundbeleuchtung##
Group: 5
Min.: 0
Max.: 10
Default: 10
Write:0
Version:
0002 BT300 ##LCD Kontrast##
Group: 5
Min.: 0
Max.:25
Default: 10
Write:0
Version:
0003 BT300 ##Screensaver Modus des UI##
The screensaver is activated on expiry of the set time [min]. Group: 5
Min.: 0
Max.: 120
Default: 0
Write:0
Version:

3 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

2.2 Maintenance

No. Device Explanation Attributes


0010 BT300 ##Wartungsintervall [Tage]##
To extend maintenance interval, to extend maintenance period in days Group: 10
0: No check of maintenance interval Min.: 0
1: No additional time configured, only a warning message to be displayed. Max.: 65535
> 1: Additional time in days following expiry of maintenance time until a fault
is reported Default: 0
Write:2
Version:
0011 BT300 ##Zeit bis zur nächsten Brennerwartung [Tage]##
Maintenance time = number of days until next burner maintenance Group: 10
0: No check of maintenance time Min.: 0
> 0: Days until next burner maintenance Max.: 65535
Default: 0
Write: 2
Version:

09/2012 - Art. Nr. 4200 1018 1500A 4


2 Parameter list

2.3 Monitor output

No. Device Explanation Attributes


0024 BT300 ##Monitorausgang Kurvensatz 1 : 4mA entsprechen X Einheiten##
Lower value threshold of monitor output value for curve set 1 Group: 15
The value entered here is the value at which the monitor output should output 4 mA, Min.: 0
i.e. depending on the source selected for the monitor output signal, a lower range is Max.: 999
selected from which the monitor output is active. If the signal is below the selected
threshold, 4 mA continues to be output nevertheless, i.e. any change below the Default: 200
threshold is not displayed. Write: 2
With the BT300, the internal load is displayed by default. Version:
If the monitor output is configured for “internal load” (P 20 and P 21), configuration by
use of P 24, P 25, P28 and P 29 will not work. If the burner power output is to be
output as configured, the actual value of an actuator can be used as the source.
0025 BT300 ##Monitorausgang Kurvensatz 2 : 4mA entsprechen X Einheiten##
Lower value threshold of monitor output value for curve set 2 Group: 15
The value entered here is the value at which the monitor output should output 4 mA, Min.: 0
i.e. depending on the source selected for the monitor output signal, a lower range is Max.: 999
selected from which the monitor output is active. If the signal is below the selected
threshold, 4 mA continues to be output nevertheless, i.e. any change below the Default: 200
threshold is not displayed. Write:2
With the BT300, the internal load is displayed by default. Version:
If the monitor output is configured for “internal load” (P 20 and P 21), configuration by
use of P 24, P 25, P28 and P 29 will not work. If the burner power output is to be
output as configured, the actual value of an actuator can be used as the source.
0028 BT300 ##Monitorausgang Kurvensatz 1 : 20mA entsprechen X Einheiten##
Upper value threshold of monitor output value for curve set 1 Group: 15
The value entered here is the value at which the monitor output should output 20 mA. Min.: 0
If the value of the source signal is higher than the value set here, 20 mA will be output Max.: 999
nevertheless, i.e. any change in the source signal above the threshold specified is no
longer displayed. Default: 999
With the BT300, the internal load is displayed by default. Write: 2
If the monitor output is configured for “internal load” (P 20 and P 21), configuration by Version:
use of P 24, P 25, P28 and P 29 will not work. If the burner power output is to be
output as configured, the actual value of an actuator can be used as the source.
0029 BT300 ##Monitorausgang Kurvensatz 2 : 20mA entsprechen X Einheiten##
Upper value threshold of monitor output value for curve set 1 Group: 15
The value entered here is the value at which the monitor output should output 20 mA. Min.: 0
If the value of the source signal is higher than the value set here, 20 mA will be output Max.: 999
nevertheless, i.e. any change in the source signal above the threshold specified is no
longer displayed. Default: 999
With the BT300, the internal load is displayed by default. Write:2
If the monitor output is configured for “internal load” (P 20 and P 21), configuration by Version:
use of P 24, P 25, P28 and P 29 will not work. If the burner power output is to be
output as configured, the actual value of an actuator can be used as the source.

5 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

2.4 Power controller

No. Device Explanation Attributes


0040 BT300 ##Typ des Leistungsreglers.## ##0-AUS / 1-Konstantregler / 2-Witterungsgeführter-
Regler##
Approval pending Group: 20
Min.: 0
Max.: 3
Default: 0
Write:1
Version:
0041 BT300 ##2-stufiger Betrieb, 0=AUS,1=nur ÖL,2=nur GAS,3=ÖL+GAS##
Pending approval Group: 20
Min.: 0
Max.: 65535
Default: 0
Write:2
Version:
0043 BT300 ##Anfahrmaximaltemperatur##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 0
Write:0
Version:
0044 BT300 ##Anfahrleistung##
Pending approval Group: 25
Min.: 0
Max.: 999
Default: 0
Write:0
Version:
0045 BT300 ##Anfahrzeit##
Pending approval Group: 20
Min.: 0
Max.: 32767
Default: 0
Write:0
Version:

09/2012 - Art. Nr. 4200 1018 1500A 6


2 Parameter list

No. Device Explanation Attributes


0046 BT300 ##externe Leistungsgrenze##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 999
Write:0
Version:
0047 BT300 ##Softstopzeit -> Brennernachlauf##
Pending approval Group: 20
Min.: 0
Max.: 100
Default: 0
Write: 0
Version:
0048 BT300 ##Reglersollwert 1 minimum##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 90
Write: 0
Version:
0049 BT300 ##Reglersollwert 1 maximum##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 0
Write:0
Version:
0050 BT300 ##Reglersollwert 2 minimum##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 70
Write:0
Version:
0051 BT300 ##Reglersollwert 2 maximum##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 0
Write:0
Version:

7 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0052 BT300 ##Begrenzung des Sollwertes nach unten (Minimalwert)##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 0
Write:0
Version:
0053 BT300 ##Begrenzung des Sollwertes nach oben (Maximalwert)##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 999
Write:0
Version:
0054 BT300 ##Regelbereich unten (Einschaltpunkt)##
Pending approval Group: 20
Min.: 0
Max.: 65535
Default: 1
Write:0
Version:
0055 BT300 ##Regelbereich oben##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 10
Write:0
Version:
0056 BT300 ##Brenner Aus##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 15
Write:0
Version:
0057 BT300 ##P-Faktor des Reglers##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 30
Write:0
Version:

09/2012 - Art. Nr. 4200 1018 1500A 8


2 Parameter list

No. Device Explanation Attributes


0058 BT300 ##I-Faktor des Reglers##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 30
Write:0
Version:
0059 BT300 ##D-Faktor des Reglers##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 100
Write:0
Version:
0060 BT300 ##Nachstellzeit##
Pending approval Group: 20
Min.: 0
Max.: 60
Default: 5
Write:0
Version:
0061 BT300 ##Darstellung von Ist- und Sollwert bei Lastregler (0=digit, 1=°C, 2=bar, 3=mA)##
Pending approval Group: 20
Min.: 0
Max.: 5
Default: 1
Write:1
Version:
0062 BT300 ##4 mA entsprechen x Einheiten##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0063 BT300 ##20 mA entsprechen x Einheiten##
Pending approval Group: 20
Min.: 0
Max.: 999
Default: 160
Write:1
Version:

9 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0065 BT300 Setting that determines the input of the power controller to which the manually
specified load applies
Setting that determines the input of the power controller to which the manually Group: 20
specified load applies Min.: 3
0: Potentiometer Max.: 0
1: Three-point step (DPS)
2: 4-20 mA current loop Default: 2
3: 0-10 V voltage input Write:2
Version:
0066 BT300 ##Leistungsbegrenzung [Grad Celsius / 0,1bar]##
Limitation for parameters 48 - 49 Group: 20
Min.: 0
Max.: 999
Default: 0
Write: 2
Version:
0067 BT300 ##Reserviert für Leistungsregler##
Group: 20
Min.: 0
Max.: 0
Default: 0
Write: 1
Version:
0068 BT300 ##Reserviert für Leistungsregler##
Group: 20
Min.: 0
Max.: 0
Default: 0
Write: 1
Version:

09/2012 - Art. Nr. 4200 1018 1500A 10


2 Parameter list

2.5 O2 controller

No. Device Explanation Attributes


0100 BT300 ##O2-Reglertyp (0-kein O2-Regler/1-Standard/2-ohne Voreinst./3-nur Anzeige/8-
DeaktWert/9-LM-Wert##
Pending approval Group: 25
Min.: 0
Max.: 25
Default: 0
Write: 0
Version:
0101 BT300 ##O2-Regelung aktivieren ab Lastposition X (in Punkten)##
Pending approval Group: 25
Min.: 0
Max.: 999
Default: 0
Write: 0
Version:
0102 BT300 ##O2-Regelung deaktivieren ab Lastposition X (in Punkten)##
Pending approval Group: 25
Min.: 0
Max.: 999
Default: 999
Write:0
Version:
0103 BT300 ##Max. O2-Wert beim Vorlüften##
Pending approval Group: 25
Min.: 0
Max.: 250
Default: 240
Write: 2
Version:
0104 BT300 ##Min. O2-Wert beim Vorlüften##
Pending approval Group: 25
Min.: 0
Max.: 250
Default: 180
Write:2
Version:

11 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0105 BT300 ##Max. O2-Wert nach dem Zünden##
Pending approval Group: 25
Min.: 0
Max.: 250
Default: 140
Write:2
Version:
0107 BT300 ##Störabschaltung durch O2-Regler / CO-Regler zulassen (0-nein / 1-bei
Luftmangel)##
Pending approval Group: 25
Min.: 0
Max.: 1
Default: 0
Write: 2
Version:
0109 BT300 ##Totzeit der O2-Regelstrecke##
Pending approval Group: 25
Min.: 3
Max.: 40
Default: 15
Write: 0
Version:
0110 BT300 ##O2 : P-Faktor##
Pending approval Group: 25
Min.: 1
Max.: 50
Default: 5
Write:0
Version:
0111 BT300 ##Totzeitverkürzung der O2-Regelstrecke bei Vollast##
Pending approval Group: 25
Min.: 0
Max.: 5
Default: 3
Write:0
Version:
0113 BT300 ##O2-Regelung aktiv nach Zünden in sek.##
Pending approval Group: 25
Min.: 0
Max.: 9999
Default: 90
Write:1
Version:

09/2012 - Art. Nr. 4200 1018 1500A 12


2 Parameter list

No. Device Explanation Attributes


0118 BT300 ##min. Wert für Sondendynamiktest / 0=Sondendynamiktest abgeschaltet##
Pending approval Group: 25
Min.: 0
Max.: 20
Default: 2
Write:2
Version:
0120 BT300 Correction value output with O2 regulation deactivated. Fuel A
Pending approval Group: 25
Min.: 0
Max.: 1000
Default: 400
Write: 1
Version:
0121 BT300 ##Luftmangel Korrekturwert BrennstoffA##
Pending approval Group: 25
Min.: 0
Max.: 999
Default: 300
Write: 1
Version:
0123 BT300 Correction value output with O2 regulation deactivated. Fuel B
Pending approval Group: 25
Min.: 0
Max.: 1000
Default: 400
Write: 1
Version:
0124 BT300 ##Luftmangel Korrekturwert BrennstoffB##
Pending approval Group: 25
Min.: 0
Max.: 999
Default: 300
Write: 1
Version:
0128 BT300 ##oberes 1. ## ##Überwachungsband Brennstoff A in % vom Sollwert Grundlast##
Pending approval Group: 25
Min.: 0
Max.: 101
Default: 60
Write: 2
Version:

13 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0129 BT300 ##oberes 1. ## ##Überwachungsband Brennstoff A in % vom Sollwert Vollast##
Pending approval Group: 25
Min.: 0
Max.: 101
Default: 100
Write: 2
Version:
0130 BT300 ##oberes 1. ## ##Überwachungsband Brennstoff B in % vom Sollwert Grundlast##
Pending approval Group: 25
Min.: 0
Max.: 101
Default: 60
Write: 2
Version:
0131 BT300 ##oberes 1. ## ##Überwachungsband Brennstoff B in % vom Sollwert Vollast##
Pending approval Group: 25
Min.: 0
Max.: 101
Default: 100
Write: 2
Version:
0132 BT300 ##unteres 1.## ##Überwachungsband Brennstoff A in % vom Sollwert
Grundlast##
Pending approval Group: 25
Min.: 0
Max.: 100
Default: 40
Write: 2
Version:
0133 BT300 ##unteres 1.## ##Überwachungsband Brennstoff A in % vom Sollwert Vollast##
Pending approval Group: 25
Min.: 0
Max.: 100
Default: 50
Write: 2
Version:
0134 BT300 ##unteres 1.## ##Überwachungsband Brennstoff B in % vom Sollwert Grundlast##
Pending approval Group: 25
Min.: 0
Max.: 100
Default: 40
Write:2
Version:

09/2012 - Art. Nr. 4200 1018 1500A 14


2 Parameter list

No. Device Explanation Attributes


0135 BT300 ##unteres 1.## ##Überwachungsband Brennstoff B in % vom Sollwert Vollast##
Pending approval Group: 25
Min.: 0
Max.: 100
Default: 50
Write: 2
Version:
0136 BT300 ##unteres 2. ## ##Überwachungsband Brennstoff A in % vom Sollwert Grundlast##
Pending approval Group: 25
Min.: 0
Max.: 100
Default: 50
Write: 2
Version:
0137 BT300 ##unteres 2. ## ##Überwachungsband Brennstoff A in % vom Sollwert Vollast##
Pending approval Group: 25
Min.: 0
Max.: 100
Default: 70
Write: 2
Version:
0138 BT300 ##unteres 2. ## ##Überwachungsband Brennstoff B in % vom Sollwert Grundlast##
Pending approval Group: 25
Min.: 0
Max.: 100
Default: 50
Write:2
Version:
0139 BT300 ##unteres 2. ## ##Überwachungsband Brennstoff B in % vom Sollwert Vollast##
Pending approval Group: 25
Min.: 0
Max.: 100
Default: 70
Write:2
Version:

15 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

2.6 CO controller

No. Device Explanation Attributes


0200 BT300 ##CO-Reglertyp (0-aus, 1-nur bei Gas, 2-Kurvensatzspezifisch über
Parameter 201)##
Pending approval Group: 30
Min.: 0
Max.: 4
Default: 0
Write: 2
Version:
0202 BT300 ##Schwachlastwert: Unterhalb wird die CO-Regelung abgeschaltet##
Pending approval Group: 30
Min.: 0
Max.: 999
Default: 0
Write:0
Version:
0203 BT300 ##Grosslastwert: Oberhalb wird die CO-Regelung abgeschaltet##
Pending approval Group: 30
Min.: 0
Max.: 999
Default: 999
Write:0
Version:

09/2012 - Art. Nr. 4200 1018 1500A 16


2 Parameter list

2.7 CO controller optimisation

No. Device Explanation Attributes


0206 BT300 ##Max. Lastabstand zum Abbruch der statischen Optimierung##
Pending approval Group: 31
Min.: 0
Max.: 999
Default: 25
Write:2
Version:
0207 BT300 ##Pausenzeit bis zur folgenden Optimierung [Std]##
Pending approval Group: 31
Min.: 0
Max.: 254
Default: 8
Write: 2
Version:

17 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

2.8 CO controller monitoring

No. Device Explanation Attributes


0223 BT300 ##Anzahl der tolerierbaren Fehlversuche des CO-Sonden Dynamiktestes bei
Korrekturwert am Anschlag.##
Pending approval Group: 32
Min.: 0
Max.: 100
Default: 4
Write: 2
Version:
0224 BT300 ##Min. O2-Wert, bei Unterschreitung erfolgt Störabschaltung##
Pending approval Group: 32
Min.: 0
Max.: 250
Default: 0
Write: 2
Version:

09/2012 - Art. Nr. 4200 1018 1500A 18


2 Parameter list

2.9 CO controller CO detection

No. Device Explanation Attributes


0229 BT300 ##Luftanhebung: Startwert bei kommender CO-Erkennung##
Pending approval Group: 34
Min.: 0
Max.: 300
Default: 20
Write: 0
Version:
0232 BT300 ##CO-Kante: Luftanhebung bei Lastrichtungswechsel##
Pending approval Group: 34
Min.: 0
Max.: 400
Default: 30
Write: 1
Version:
0233 BT300 ##CO-Kante: Luftanhebung nach abgeschlossener Optimierung##
Pending approval Group: 34
Min.: 0
Max.: 400
Default: 20
Write: 1
Version:

19 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

2.10 CO controller edge signal

No. Device Explanation Attributes


0236 BT300 ##O2- Wert erzwingt Abschluss der Optimierung (Bedingung: Wert größer P 204)##
Pending approval Group: 35
Min.: 0
Max.: 100
Default: 0
Write: 2
Version:
0237 BT300 ##Maximaler O2-Wert zur Akzeptanz einer Optimierung##
Pending approval Group: 35
Min.: 0
Max.: 80
Default: 50
Write: 2
Version:

09/2012 - Art. Nr. 4200 1018 1500A 20


2 Parameter list

2.11 FAT (automatic combustion control unit)

No. Device Explanation Attributes


0300 BT300 ##Zwangsintermittierungszeit in Minuten (0=unendlich)##
Forced intermission time in minutes Group: 40
0 = the burner can run for endless time and no pause is incorporated Min.: 0
>0 = the burner is forced to pause after this time in minutes Max.: 1440
Default: 1430
Write: 2
Version:
0301 BT300 ##Automatischer Wiederanlauf (0=TRD, 1=AUS, 2=EN676)##
Configuration of automatic restart Group: 40
0 = automatic restart in accordance with TRD Min.: 0
1 = no automatic restart Max.: 10
2 = automatic restart in accordance with EN676 Default: 1
If P 301 ≠ 0 and P 328 > 0, and BT300 in malfunction mode, a change to parameters Write: 2
results immediately in a restart. Version:

0302 BT300 ##Start mit (1) bzw. ohne (0) Zündbrenner bei Öl, (2)=Öl mit Dauerzündflamme##
Ignition burner configuration for fuel oil Group: 40
0 = without ignition burner Min.: 0
1 = with ignition burner Max.: 4
2 = permanent ignition burner Default: 0
3 = with ignition burner - main flame detector does not detect ignition flame during Write: 2
ignition (process equal to 1) Version:
4 = with permanent ignition burner - main flame detector does not detect ignition flame
during ignition (process equal to 2)
0303 BT300 ##Start mit (1) bzw. ohne (0) Zündbrenner bei Gas, (2)=Gas mit Dauerzündflamme##
Ignition burner configuration for gas Group: 40
Values identical to P 302 Min.: 0
Max.: 4
Default: 0
Write: 2
Version:
0304 BT300 ##Programmüberwachungszeit in Sekunden##
This sets the program monitoring time for the integrated control unit. A fault is output if Group: 40
no ignition occurs within this time after "burner ON". No fault is output if the parameter Min.: 0
is set to 0.
Max.: 9999
Default: 600
Write: 2
Version:

21 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0305 BT300 ##1.Sicherheitszeit für Öl##
Fuel oil safety time 1 in seconds Group: 40
Enter the first safety time for fuel oil here. Take applicable standards into Min.: 1
consideration. Max.: 30
Default: 5
Write: 4
Version:
0306 BT300 ##2.Sicherheitszeit für Öl##
Fuel oil safety time 2 in seconds Group: 40
2nd safety time for fuel oil in seconds or safety time at start without ignition burner. Min.: 1
Set the second safety time for fuel oil here. Max.: 30
Observe applicable standards when you make your setting. Default: 5
If you are not using any ignition burner, this parameter includes the safety time. Write: 4
Version:
0307 BT300 ##1.Sicherheitszeit für Gas##
Gas safety time 1 in seconds Group: 40
1st safety time for gas in seconds (ignition safety time) Min.: 1
Take applicable standards into consideration. Max.: 30
Default: 3
Write: 4
Version:
0308 BT300 ##2.Sicherheitszeit für Gas##
Gas safety time 2 in seconds Group: 40
2nd safety time for gas in seconds or safety time at start without ignition burner. Min.: 1
Set the second safety time for gas here. Max.: 30
Observe applicable standards when you make your setting. Default: 3
If you are not using any ignition burner, this parameter includes the safety time Write: 4
Version:
0309 BT300 ##Vorzündzeit in Sekunden.##
Transformer time in seconds Group: 40
This time specifies the ignition transformer activation time (transformer pre-switch-on Min.: 2
time) and is determined here by the number of seconds that should elapse before the Max.: 40
ignition gas (or main gas) solenoid valve is opened.
Default: 3
With BT300, the fuel-oil pump is started at the same time. If the time is not long
enough for sufficient fuel-oil pressure to be generated in the system, this time should Write: 1
be extended. Version:
0310 BT300 ##Stabilisierungszeit##
Stabilisation time in seconds Group: 40
This parameter is used to set the stabilisation time. This parameter specifies how long Min.: 3
the ignition burner should burn between first and second safety time alone (without Max.: 30
activation of ignition transformer and with main gas valves still closed).
Default: 3
- Ignition
Write: 1
- Fuel change by ignition burner
Version:

09/2012 - Art. Nr. 4200 1018 1500A 22


2 Parameter list

No. Device Explanation Attributes


0311 BT300 ##Dichtheitskontrollzeit##
Leaktightness check time in seconds Group: 40
This sets the time for the leaktightness check. Default value 20 seconds.? Min.: 5
This parameter should be changed only if the volume of the leaktightness check Max.: 999
section and the switching hysteresis of the minimum gas pressure switch do not permit Default: 20
detection of the minimum leak amount required by the standard (see calculation
example in instruction manual). If the minimum leak amount is reliably detected even Write: 2
with a time shorter than 30 seconds, the value of the parameter can be reduced to Version:
save time.
0312 BT300 ##Dichtheitskontrolle vor dem Zünden (0-AUS / 1-AN)##
Leaktightness check before burner start Group: 40
0: not required Min.: 0
1: required Max.: 1
Default: 1
If P 312 > 0, then P 802 should be > 0. Write: 1
Version: 2.0
0313 BT300 ##Dichtekontrolle, Füllzeit Verlängerung [s] Hauptgas 1##
Time for filling the leaktightness check section in seconds Group: 40
The opening time of main gas 1 (2 s) for filling the leaktightness section can be Min.: 0
extended with this parameter. Max.: 3
0 = opening time of main gas 1 = 2 s Default: 0
1...= opening extension time [s] (total opening time = value in P 313 + 2 s)* Write: 4
Example: value in P 313 = 1 - total opening time = 3 s Version:
0315 BT300 ##Dichtheitskontrolle nach Abschalten (0-AUS / 1-AN)##
Leaktightness check after burner operation Group: 40
0: not required Min.: 0
1: required Max.: 1
Default: 0
If P 312 > 0, then P 802 must be > 0. Write: 1
Version: 2.0
0316 BT300 ##Vorlüftunterdrückung (0-aus / 1-aktiv / 2-automatisch / 3-autom.## ##Kurz)##
Pre-ventilation suppression Group: 40
0: no pre-ventilation suppression permitted Min.: 0
1: reserved (fault 107) Max.: 5
2: automatic pre-ventilation suppression permitted for all fuels and if burner inactive for Default: 0
less than 24 h Write: 1
3: automatic pre-ventilation suppression active for all fuels, but the flaps are fully Version:
opened and closed again once and if burner inactive for less than 24 h
4: automatic pre-ventilation suppression permitted for gas only and if burner inactive
for less than 24 h
5: automatic pre-ventilation suppression permitted for fuel oil only and if burner
inactive for less than 24 h

23 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0318 BT300 ##Vorlüftdauer in Sekunden##
This sets the pre-ventilation time of the burner. This setting is made by the person Group: 40
responsible for commissioning. However, the lower threshold is determined by P 317 Min.: 0
##"Mindestvorlüftdauer"##
Max.: 999
Default: 30
Write: 1
Version:
0319 BT300 ##Nachlüftzeit##
Post-ventilation time in seconds Group: 40
This setting determines how long BT300 ventilation should remain active after switch- Min.: 0
off. For this purpose, the air flaps are opened. With a parameter value of 0 and in the Max.: 999
event of a lockout, no post-ventilation takes place.
Default: 20
In post-ventilation mode, there is no monitoring of actuators. The actuators do not
open until the flame has gone out. However, the time does begin immediately with the Write: 1
closing of the solenoid valves. This after-flame time may need to be added to the Version:
desired post-ventilation time.
0320 BT300 ##Ölpumpe einschalten, 0=Standard, 1=zusammen mit dem Lüfter##
Timing of the fuel-oil pump, determines when the fuel-oil pump should be switched on Group: 40
0 = normal at ignition Min.: 0
1 = as early as entering Ready mode Max.: 1
Default: 0
Write: 2
Version:
0323 BT300 ##Irrelevanzzeit der Ölsicherheitskette beim Zünden auf Öl in Sekunden.##
Tolerance time/irrelevance time of fuel-oil safety chain at ignition running on fuel oil in Group: 40
0 to 10 seconds Min.: 0
Irrelevance time after ignition (longer tolerance) for fuel-oil safety chain. Max.: 10
This parameter makes it possible to extend the tolerance time for the fuel-oil safety Default: 1
chain during the ignition process in order to prevent lockouts caused by pressure
pulses when the main valves are opened. Write: 4
The value entered is in seconds. Version:
Default value 1.
The time begins with the opening of the main fuel valves.
After ignition has finished, this parameter has no effect.
0324 BT300 ##Irrelevanzzeit der Gassicherheitskette beim Zünden auf Gas in Sekunden.##
Tolerance time/irrelevance time of gas safety chain at ignition running on gas in 0 to 10 Group: 40
seconds Min.: 0
Irrelevance time during ignition (longer tolerance) for gas safety chain Max.: 10
This parameter makes it possible to extend the tolerance time for the gas safety chain Default: 1
during the ignition process in order to prevent lockouts caused by pressure pulses
when the main valves are opened. The value entered is in seconds. Default value 1. Write: 4
After ignition has finished, this parameter has no effect. Version:
The irrelevance time begins with the opening of gas valve 2 (2nd safety time) and
ends after the time entered here has elapsed.

09/2012 - Art. Nr. 4200 1018 1500A 24


2 Parameter list

No. Device Explanation Attributes


0325 BT300 ##Wartungsmodus (Steuergerät nur bis Stabilisierungszeit)##
0: maintenance mode OFF Group: 40
1: maintenance mode ON Min.: 0
This parameter makes it possible to set maintenance mode. Maintenance mode is Max.: 1
used for setting the ignition burner or the ignition flame detector. It allows 5 ignition Default: 0
attempts to be made in succession without the need for restarting with pre-ventilation
and leaktightness check each time. The control unit runs only until the stabilisation Write: 1
time. No main valves can be opened before this parameter is unset again. After the Version:
fifth ignition attempt, pre-ventilation and leaktightness check take place automatically.
However: In the event of a long reset, the counter for maintenance mode is
automatically reset. In other words, the next start-up is seen as the first, and pre-
ventilation and leaktightness check will take place. For this reason, it is preferable to
clear faults using a short reset (selector switch at ##"Status"##, channel 2 button up
first and then also channel 1 up).
Attention: the short reset is not possible for some faults.
0326 BT300 ##Nachbrennzeit (Flammsignal irrelevant) in Sekunden.##
The after-flame time determines the length of the waiting period after switch-off before Group: 40
a "flame OFF" check should begin. If this time is 0, no after-flame time is configured Min.: 0
and no "flame OFF" check is carried out
Max.: 180
Default: 10
Write: 1
Version:
0327 BT300 ##Verhalten des Zündtrafos in der Einschaltsequenz von Öl##
0: normal behaviour: the ignition transformer is activated at the time the fuel-oil pump Group: 40
is switched on Min.: 0
1: the ignition transformer is activated sooner at the time the ventilator is switched on Max.: 1
and is switched on once more after the flame has gone out (during post-ventilation)
Default: 0
Write: 2
Version:
0328 BT300 ##Automatischer Wiederanlauf bei Störung##
Delay period before automatic restart Group: 40
0 = no automatic restart Min.: 0
> 0 = delay period in seconds before automatic restart Max.: 30
Default: 5
If P 301 ≠ 0 and P 328 > 0, and BT300 in malfunction mode, a change to parameters Write: 2
results immediately in a restart. Version:

25 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

2.12 Sequencer

No. Device Explanation Attributes


0365 BT300 ##Grenze bis Vorlüften beendet werden kann Kanal 1##
Threshold for pre-ventilation (also post-ventilation) Group: 45
Here, you enter in digits how far the channel should open during pre-ventilation. If the Min.: 0
value is 999 (default), the channel opens as far as the stop. This parameter is for Max.: 999
adjusting pre-ventilation limits, e.g. in the case of air flaps, in order to achieve a
reduction in pre-ventilation time (provided air exchange is still possible during pre- Default: 999
ventilation). Write: 1
Version:
0366 BT300 ##Grenze bis Vorlüften beendet werden kann Kanal 2##
Threshold before pre-ventilation can be stopped, channel 2, in digits Group: 45
see P 365 Min.: 0
Max.: 999
Default: 999
Write: 1
Version:
0367 BT300 ##Grenze bis Vorlüften beendet werden kann Kanal 3##
Threshold before pre-ventilation can be stopped, channel 3, in digits Group: 45
see P 365 Min.: 0
Max.: 999
Default: 999
Write: 1
Version:
0368 BT300 ##Grenze bis Vorlüften beendet werden kann Kanal 4##
Threshold before pre-ventilation can be stopped, channel 4, in digits Group: 45
see P 365 Min.: 0
Special notes regarding channel 4: Max.: 999
Attention: With constant outputs, the target value is limited. It should be noted that Default: 999
the feedback range limits are entered manually. Write: 1
During automatic range limit determination, the feedback value for the limitation is, in Version:
the case of constant outputs, determined and stored in the device. It should be noted
here that the feedback reaches the limitation value during the period of automatic
range limit determination. The feedback is used for monitoring the pre-ventilation
position of the channel
Following activation of, or a change to, the pre-ventilation threshold of a constant
channel, you must carry out automatic range determination (see device
documentation).

09/2012 - Art. Nr. 4200 1018 1500A 26


2 Parameter list

No. Device Explanation Attributes


0373 BT300 ##Verzögerung Zünden nach Erkennung Zündstellung in Sekunden##
This enables you to specify how many seconds should elapse after detection of the Group: 45
ignition position by the ratio controller before ignition is authorised. Min.: 0
Max.: 999
Default: 0
Write: 2
Version:
0374 BT300 ##Verzögerungszeit für Grundlast bei sep.## ##Zündpunkt##
This enables you to set a delay period so that, after ignition, the ratio controller waits Group: 45
before it leaves the programmed, separate ignition point and goes to the basic load Min.: 0
point. This parameter has an effect only if a separate ignition point has been
configured. (P 803) Max.: 999
Default: 0
Write: 2
Version:
0375 BT300 ##Verzögerungszeit für Regelfreigabe##
Delay period for control authorisation in seconds. Group: 45
The burner remains at basic load during this time. Min.: 0
Max.: 999
Default: 0
Write: 2
Version:
0376 BT300 ##Klappenverzögerung nach Lüfter EIN in Sekunden##
Delay period in seconds for flaps after fan ON (only with FAT) Group: 45
Here, you can enter a time that delays the opening of the flaps after fan authorisation. Min.: 0
This has the effect of preventing an increase in the current draw of the fan motor in the Max.: 15
star/delta start phase.
Default: 5
This parameter also has an effect during permanent ventilation.
Write: 2
Version:
0377 BT300 ##Lastposition beim Abschalten (0=aktuelle Position / 1=Grundlast vor Abschalten)##
0: switch-off takes place at current load position Group: 45
1: basic load position adopted first before switch-off sequence is begun Min.: 0
Max.: 1
Default: 0
Write: 2
Version:

27 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

2.13 Channel configuration

No. Device Explanation Attributes


0400 BT300 ##Funktionsfestlegung Kanal 1##
This parameter is used to specify which type of actuator controls the respective output Group: 50
channel. In this way, you determine indirectly its behaviour during pre-ventilation, Min.: 0
during a band shift in the event of a power output change and during drift
compensation. In some cases, it may also determine special functions, e.g. if the Max.: 6
channel has been configured for recirculation or flue gas. Default: 3
Channel function Write: 2
0: OFF Version:
1: reserved (fault 107)
2: fuel
3: air flap
4: reserved (fault 107)
5: reserved (fault 107)
6: reserved (fault 107)
0401 BT300 ##Funktionsfestlegung Kanal 2##
see P 400 Group: 50
Min.: 0
Max.: 6
Default: 2
Write: 2
Version:
0402 BT300 ##Funktionsfestlegung Kanal 3##
see P 400 Group: 50
Min.: 0
Max.: 6
Default: 0
Write: 2
Version:
0403 BT300 ##Funktionsfestlegung Kanal 4##
see P 400 Group: 50
Min.: 0
Max.: 6
Default: 0
Write: 2
Version:
0405 BT300 ##Kanalfreischaltung für Kurvensatz 1##

09/2012 - Art. Nr. 4200 1018 1500A 28


2 Parameter list

Channel disable bits for each curve set. A set bit x means that the channel is used in Group: 50
curve set x Min.: 0
Here, you specify which channels are active for which curve set. By default, all Max.: 15
channels are active. With this function, it is possible to implement alternating channel
activity with fuel oil/gas (BT34x), for example. The selection is made by means of a bit Default: 15
pattern. Write: 2
Version:

1 = active
2 = inactive

29 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0406 BT300 ##Kanalfreischaltung für Kurvensatz 2##
By bit pattern, see P 405 Group: 50
Min.: 0
Max.: 15
Default: 15
Write: 2
Version:
0415 BT300 ##Brennstoff bleibt beim Vorlüften ZU##
Behaviour of fuel channels during pre-ventilation with operation on liquid gas Group: 50
0: normal operation Min.: 0
1: actuators configured for fuel remain closed during pre-ventilation Max.: 1
Fuel remains CLOSED during pre-ventilation? Default: 0
Switch (On/Off). Write: 2
If the parameter is set to 1, actuators configured for fuel remain closed during
pre-ventilation. If the BT300 is being used in a liquid gas system, the fuel actuator is Version:
not permitted to open during pre-ventilation. In this situation, this parameter must be
set to "On". Range limits must then be entered manually or range limit determination
must be disabled
(see P 650ff).

09/2012 - Art. Nr. 4200 1018 1500A 30


2 Parameter list

2.14 Actuators

No. Device Explanation Attributes


0453 BT300 ##Laufzeit in Pkt/Min. für stetigen Ausgang Kanal 4##
If the channel has been configured as a constant output, you can use this parameter to Group: 55
specify how quickly this output may undergo maximum change. However, the time Min.: 0
entered here is only a minimum run time. As a consequence of the ratio controller
routine, it may happen (e.g. with use of even slower flap drives on a different channel) Max.: 65535
that this time is significantly exceeded. The primary purpose of this parameter is to Default: 1500
effect an adaptation in the control of frequency converters. The value set here should
Write: 2
be consistent with the start-up time programmed on the frequency converter.
Version:
0455 BT300 ##Konfiguration des Stellgliedtyps Kanal 1##
Configuration of actuator type for each channel 1: Group: 55
1 = servomotors 0.8 Nm (665R5500...); 1.2 Nm (662R5001...) and 3 Nm (662R5003...) Min.: 1
2 = servomotors 10 Nm (662R5010...)
Max.: 2
Default: 1
Write: 2
Version:
0456 BT300 ##Konfiguration des Stellgliedtyps Kanal 2##
see P 455 Group: 55
Min.: 1
Max.: 2
Default: 1
Write: 2
Version:
0457 BT300 ##Konfiguration des Stellgliedtyps Kanal 3##
see P 455 Group: 55
Min.: 1
Max.: 2
Default: 1
Write: 2
Version:
0458 BT300 ##Position in der die angeschlossene Klappe geschlossen ist Kanal 1##
Position for each channel in which the connected flap is closed Group: 55
0 = closed at 12 o'clock position Min.: 0
1 = closed at 9 o'clock position for servomotors 1.2 Nm (662R5001...); 3 Nm
(662R5003...); 10 Nm (662R05010...) and 3 o'clock position for servomotors 0.8 Nm Max.: 1
(663R550...) Default: 0
Write: 2
Version:

31 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0459 BT300 ##Position in der die angeschlossene Klappe geschlossen ist Kanal 2##
see P 458 Group: 55
Min.: 0
Max.: 1
Default: 0
Write: 2
Version:
0460 BT300 ##Position in der die angeschlossene Klappe geschlossen ist Kanal 3##
see P 458 Group: 55
Min.: 0
Max.: 1
Default: 0
Write: 2
Version:
0461 BT300 ##Verhalten der Schrittmotor-Vertauscherkennung bei PowerOn##
1 = swap detection activated, Group: 55
run only after each cold start Min.: 0
2 = swap detection activated,
run after power supply voltage applied and after each cold start Max.: 1
Default: 0
Write: 2
Version:

09/2012 - Art. Nr. 4200 1018 1500A 32


2 Parameter list

2.15 Ratio controller

No. Device Explanation Attributes


0508 BT300 ##Bandverschiebung Kanal 1##
Band shift in the event of a load change Group: 60
This specifies in digits the band shift of the channel in the event of a change in power Min.: 0
output. The electronic ratio controller evaluates the directions in which the band shift Max.: 50
should take effect automatically based on the configuration of the respective actuator
(air up, fuel down). The band shift has an effect only if the load changes in the direction Default: 4
that represents an air advance for the channel (in case of load reduction, fuel advance; Write: 2
with load increase, air advance). The magnitude of the values to be entered here
Version:
depends on the effect of the actuator on the oxygen sensor.
0509 BT300 ##Bandverschiebung Kanal 2##
see P 508 Group: 5
Min.: 0
Max.: 50
Default: 4
Write: 2
Version:
0510 BT300 ##Bandverschiebung Kanal 3##
see P 508 Group: 60
Min.: 0
Max.: 50
Default: 4
Write: 2
Version:
0511 BT300 ##Bandverschiebung Kanal 4##
see P 508 Group: 60
Min.: 0
Max.: 50
Default: 4
Write: 2
Version:
0513 BT300 ##Laufzeit in Digit/Min. für DPS Lasteingang##
Run time factor for DPS load input Group: 60
This sets how quickly the signal of the external load should change when the load Min.: 0
value is input by DPS signal. With a DPS signal, the external load is formed by a Max.: 65535
counter, which counts up or down depending on contact state. In this way, the
parameter determines the speed of the counter. The setting is entered in digits per Default: 1000
minute. If the load input is not from DPS, the parameter must be set to 0. Write: 1
Version:

33 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0514 BT300 ##Mindestlaufzeit des Verbundes##
Limitation of adjustment speed of internal load with respect to load value specified. Group: 60
Minimum run time of load in seconds from ignition point to max load of the curve Min.: 10
Minimum run time of the ratio controller in seconds. This sets the minimum run time of Max.: 999
the ratio controller in seconds. This parameter is used to slow down the run-up time or
run-down time of the burner between weak load and full load. Default: 10
Write: 2
Version:
0515 BT300 ##Kanäle die zum Overshoot herangezogen werden##
This specifies which channels are used as the basis for calculating the overshoot. As Group: 60
the overshoot is fundamentally required with DPS outputs, but is not usually required Min.: 0
with constant outputs, you must not select constant channels. Actuators with curves
that are horizontal for some considerable length should also be excluded from the Max.: 15
overshoot. Default: 0
Write: 2
Version:
0516 BT300 ##Overshoot min. Wert##
This specifies the minimum value to be achieved by the actuator during the overshoot Group: 60
and is determined by the actual value. Each channel must have moved at least as far Min.: 0
as this value before the overshoot can be ended.
Overshoot is ended as soon as the overshoot termination condition is fulfilled for all Max.: 999
overshoot channels! Default: 0
Write: 2
Version:
0517 BT300 ##Overshoot max. Wert##
Overshoot max. value in digits relative to internal load. Group: 60
This specifies the maximum value that the internal load is permitted to achieve during Min.: 5
the overshoot and is determined by its actual value. As soon as this value is reached,
the overshoot is terminated. Max.: 250
Default: 5
Write: 2
Version:
0518 BT300 ##Wert der internen Last im Betriebsmodus AUS für Leistungsanzeige##
Value of load input in operating modes OFF and FAULT Group: 60
Value = 0: load follows external input value Min.: 0
Here, you can enter which value the ##"Interne Last"## output should output when the Max.: 999
BT300 is in "OFF" mode.
Default = 200, which corresponds to 4 mA. Default: 0
Write: 2
Version:

09/2012 - Art. Nr. 4200 1018 1500A 34


2 Parameter list

No. Device Explanation Attributes


0519 BT300 ##Totbanddefinition +/- diesem Wert wirkt keine Laständerung##
Load dead band: Group: 60
Low byte: load dead band if no load reversal Min.: 0
High byte: load dead band after load reversal
Max.: 65535
Load dead band for change without direction reversal = 5 digits
Default: 2565
Load dead band for change with direction reversal = 10 digits
Write: 1
This defines the dead band of the load input. Load changes that are within the range
entered here are ignored and do not cause an adjustment of the ratio controller. If the Version:
selected load dead band is too narrow, the ratio controller would run in a highly stop-
start manner because a control response would be initiated for even the smallest load
changes. Due to the additional routines, such as air advance in the event of power
output change and overshoot (approach of actuators from one side), this would result
in unnecessary stop-start behaviour. With a slightly fluctuating or disturbed load signal,
the actuators would be constantly moving. If the selected load dead band is too wide,
the power output demands of the load controller would not be followed through or the
change would occur in one step once the target value/actual value deviation became
even greater. This could result in the actual value of the control section (steam
pressure or flow temperature) fluctuating too much. The optimum value for this
parameter has to be determined on site. However, the parameter content should be
set below 3 digits only in exceptional circumstances so that, at a minimum, the signal
fluctuations on the load input do not lead to an adjustment of the ratio controller.
0525 BT300 ##Festlegung der Stufenanzahl für den stufigen Ölbetrieb (0=modulierender Betrieb /
1=Zwei Stufen / 2=Drei Stufen)##
0 = One stage = modulating operation Group: 60
1 = Two stages Min.: 0
2 = Three stages
Max.: 2
Default: 0
Write: 2
Version:
0526 BT300 ##Zeit in Sekunden, die der Regler mindestens benötigt um von einer Laststufe in die
nächste zu wechseln.##
Group: 60
Min.: 0
Max.: 999
Default: 10
Write: 2
Version:
0527 BT300 ##Stellung der Luftklappe an der das Ventil für die 2. ## ##Stufe eingeschaltet wird##
The value in this parameter determines the position of the air flap at which the 2nd Group: 60
fuel-oil valve is opened, i.e. the switch from stage 1 to stage 2 Min.: 0
Max.: 999
Default: 0
Write: 1
Version:

35 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0528 BT300 ##Stellung der Luftklappe an der das Ventil für die 2.## ##Stufe ausgeschaltet wird##
The value in this parameter determines the position of the air flap at which the 2nd Group: 60
fuel-oil valve is closed, i.e. the switch from stage 2 to stage 1 Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0529 BT300 ##Stellung der Luftklappe an der das Ventil für die 3.## ##Stufe eingeschaltet wird##
The value in this parameter determines the position of the air flap at which the Group: 60
3rd fuel-oil valve is opened, i.e. the switch from stage 2 to stage 3 Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0530 BT300 ##Stellung der Luftklappe an der das Ventil für die 3.## ##Stufe ausgeschaltet wird##
The value in this parameter determines the position of the air flap at which the 3rd fuel- Group: 60
oil valve is closed, i.e. the switch from stage 3 to stage 2 Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0531 BT300 ##Lastschwelle an der das Ventil für die 2.## ##Stufe eingeschaltet wird##
Load threshold for multistage load operation. Group: 60
The threshold defines the loads at which the switch to a different stage should Min.: 0
take place.
Max.: 999
Default: 0
Write: 1
Version:
0532 BT300 ##Lastschwelle an der das Ventil für die 2.## ##Stufe ausgeschaltet wird##
see P 531 Group: 60
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0533 BT300 ##Lastschwelle an der das Ventil für die 3.## ##Stufe eingeschaltet wird##
see P 531 Group: 60
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:

09/2012 - Art. Nr. 4200 1018 1500A 36


2 Parameter list

No. Device Explanation Attributes


0534 BT300 ##Lastschwelle an der das Ventil für die 3.## ##Stufe ausgeschaltet wird##
see P531 Group: 60
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:

37 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

2.16 Monitoring bands

No. Device Explanation Attributes


0600 BT300 Inoperative
v1.0 Group: 65
Maximum permissible deviation between expected position and feedback in 0.1° Min.: 0
from v2.0 Max.: 999
Inoperative
Default: 20
Write: 2
Version:
0604 BT300 ##Abschaltzeit für 1.Überwachungsband Kanal 4##
Monitoring band 1 tolerance time Group: 65
This sets the time for the first monitoring band. It must be just shorter than the Min.: 0
monitoring time of the dead band to enable a differentiated switch-off between Max.: 99
monitoring band and dead band. Thus for systems that comply with TRD regulations -
28 seconds. This time may be extended, e.g. for deviations in the case of safety- Default: 28
irrelevant actuators or special systems. Write: 4
Version:
0609 BT300 ##1.Überwachungsband negativ, Kanal 4 in digit##
Monitoring band 1 negative direction Group: 65
The negative monitoring band for the respective channel. The wider the monitoring Min.: 0
band, the more scope the ratio controller has for adjustment. The narrower the
monitoring band, the more often the ratio controller will be stopped during adjustment. Max.: 100
Outside the monitoring band, the actuator is controlled by a permanent signal. Within Default: 30
the monitoring band, movement is controlled by pulse signal towards the dead band.
Write: 2
Since constant channels have no dead band, the first monitoring band also acts as the
only switch-off threshold. With DPS, by contrast, the dead band is the decisive factor Version:
for switch-off tolerance.
0614 BT300 ##1.Überwachungsband positiv, Kanal 4##
Monitoring band 1 positive direction Group: 65
The wider the monitoring band, the more scope the ratio controller has for adjustment. Min.: 0
The narrower the monitoring band, the more often the ratio controller will be stopped Max.: 100
during adjustment. Outside the monitoring band, the actuator is controlled by a
permanent signal. Within the monitoring band, movement is controlled by pulse signal Default: 30
towards the dead band. Since constant channels have no dead band, the first Write: 2
monitoring band also acts as the only switch-off threshold. With DPS, by contrast, the
Version:
dead band is the decisive factor for switch-off tolerance.
0620 BT300 ##2.Überwachungsband negativ, Kanal 4##
Monitoring band 2 negative direction Group: 65
Second monitoring band in negative direction. This monitoring band is used for rapid Min.: 0
switch-off in the event of extreme control deviations. The setting should be suitably Max.: 100
generous. The parameterised value is added to the first monitoring band.
Default: 40
Write: 2
Version:

09/2012 - Art. Nr. 4200 1018 1500A 38


2 Parameter list

No. Device Explanation Attributes


0625 BT300 ##2.Überwachungsband positiv, Kanal 4##
Monitoring band 2 positive direction Group: 65
Second monitoring band in positive direction. This monitoring band is used for rapid Min.: 0
switch-off in the event of extreme control deviations. The setting should be suitably Max.: 100
generous. The parameterised value is added to the first monitoring band. In the event
of an "on-the-fly curve change", it must be ensured that the actuator is able to reach Default: 40
the second monitoring band within 30 seconds. Otherwise, the band must be widened Write: 2
accordingly.
Version:

39 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

2.17 LSB/fieldbus

No. Device Explanation Attributes


0750 BT300 ##LSB Familie (LAMTEC SYSTEM BUS##
Family to be used in LSB system environment Group: 80
0 = family 1 Min.: 0
1 = family 1 Max.: 4
2 = family 2
3 = family 3 Default: 1
4 = family 4 Write: 2
Note: Version:
Changes to this parameter do not come into effect until after a device reset
0751 BT300 ##LSB Konfiguration (LAMTEC SYSTEM BUS)##
unused Group: 80
Min.: 0
Max.: 65535
Default: 0
Write: 2
Version:
0752 BT300 ##LSB Gerätenummer (LAMTEC SYSTEM BUS)##
LAMTEC SYSTEM BUS group Group: 80
Min.: 0
Max.: 65535
Default: 1
Write: 2
Version:
0753 BT300 ##LSB Analogmodule konfigurieren##
Configuration of LSB analogue modules Group: 80
Min.: 0
Max.: 65535
Default: 255
Write: 2
Version:
0754 BT300 ##LSB Digitalmodule (Lastschwellen)##
unused Group: 80
Min.: 0
Max.: 65535
Default: 255
Write: 2
Version:

09/2012 - Art. Nr. 4200 1018 1500A 40


2 Parameter list

No. Device Explanation Attributes


0755 BT300 ##Buskarten Parameter Nr. 1##
Bus card parameters, only for externally connected devices. These are handed over to Group: 55
these devices only. They have no effect on BurnerTronic Min.: 0
See description of bus systems (default values for PROFIBUS) Max.: 999
Parameters for bus card (function depends on bus configuration. See separate bus Default: 0
documentation).
Write: 1
Version:
0756 BT300 ##Buskarten Parameter Nr. 2##
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 4
Write: 1
Version:
0757 BT300 ##Buskarten Parameter Nr. 3##
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0758 BT300 ##Buskarten Parameter Nr. 4##
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 100
Write: 1
Version:
0759 BT300 ##Buskarten Parameter Nr. 5##
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0760 BT300 ##Buskarten Parameter Nr. 6##
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:

41 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0761 BT300 ##Buskarten Parameter Nr. 7##
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0762 BT300 ##Buskarten Parameter Nr. 8##
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0763 BT300 ##Buskarten Parameter Nr. 9##
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:
0764 BT300 ##Buskarten Parameter Nr. 10##
see P 755 Group: 80
Min.: 0
Max.: 999
Default: 0
Write: 1
Version:

09/2012 - Art. Nr. 4200 1018 1500A 42


2 Parameter list

2.18 Feature parameters

No. Device Explanation Attributes


0800 BT300 ##Verwendung der integrierten Flammenwächter##
0: Main flame: ionisation detector Group: 85
Ignition flame: none Min.: 0
1: Main flame: ionisation detector
Ignition flame: UV tube Max.: 8
2: Main flame: ionisation detector Default: 0
Ignition flame: LDR photoresistor
Write: 2
3: Main flame: UV tube
Ignition flame: none Version:
4: Main flame: UV tube
Ignition flame: ionisation detector
5: Main flame: UV tube
Ignition flame: LDR photoresistor
6: Main flame: LDR photoresistor
Ignition flame: none
7: Main flame: LDR photoresistor
Ignition flame: ionisation detector
8: Main flame: LDR photoresistor
Ignition flame: UV tube
0801 BT300 ##Festlegung der Klemmenbelegung (0: Ölbetrieb - zweistufig oder modulierend / 1:
Ölbetrieb - dreistufig / 2: Gasbetrieb - modulierend / 3: Dual Fuel - Öl- und Gasbetrieb
- modulierend / 4: Dual Fuel - Ölbetrieb zwei-/dreistufig und Gasbetrieb
modulierend)##
Terminal assignment Group: 80
0: fuel-oil operation - two-stage/modulating Min.: 0
1: fuel-oil operation - three-stage (no ignition burner possible)
2: gas operation - modulating Max.: 65535
3: dual-fuel - fuel-oil and gas operation - modulating or 2-stage, ignition burner Default: 2
permitted (only BT340)
Write: 2
4: dual-fuel - fuel-oil operation up to three stages (without ignition burner) and
gas operation modulating (only BT340) Version:
0802 BT300 ##Dichtheitskontrolle ausführen##
Type of leaktightness check Group: 85
0: no leaktightness check Min.: 0
1: leaktightness check starts together with pre-ventilation
2: leaktightness check starts after pre-ventilation has finished Max.: 2
Determines whether or not the integrated leaktightness check in the device should be Default: 1
active (only has an effect if the device is also configured with active control unit). Write: 1
If P 802 ≠ 0 either P 312 should be ≠ 0 or P 315 should be ≠ 0. Version: 2.0
0808 BT300 ##Brennstoffauswahl (0: Brennstoff Öl / 1: Brennstoff Gas).## ##Wird nur
ausgewertet, wenn P 812 = 0 ist##
Fuel selection, evaluated only if P 812 = 0 Group: 85
0: fuel oil Min.: 0
1: gas
Max.: 1
Default: 1
Write: 2
Version:

43 09/2012 - Art. Nr. 4200 1018 1500A


2 Parameter list

No. Device Explanation Attributes


0809 BT300 ##Einstellung der Ausgabe an Klemme X24##
Setting of output at terminal X24 Group: 85
ATTENTION: the output at terminal X24 is not fail-safe and may therefore be used Min.: 0
only for display purposes.
0: output inoperative, i.e. always inactive Max.: 2
1: output displays a fault (terminal OFF: no fault, terminal ON: fault) Default: 1
2: output shows the currently selected fuel (terminal OFF: fuel oil, terminal ON: gas)
Write: 2
Version:
0811 BT300 ##Art des Drehzahlreglers (0: kein Drehzahlregler / 1…: Art des Sensors im
Drehzahlregler)##
0 = no speed controller Group: 85
1…: = type of sensor in speed controller Min.: 0
Max.: 5
Default: 0
Write: 1
Version:
0812 BT300 ##Festlegung der Quelle für die Bennstoffauswahl (0: Brennstoffauswahl über
Parameter 808 / 1: Brennstoffauswahl über Klemme am Leistungsregler-Modul)##
Determination of source for fuel selection Group: 85
0 = fuel selection via parameter 808 Min.: 0
1 = fuel selection via terminal on dual fuel module DFM
Max.: 2
Default: 0
Write: 2
Version:
0813 BT300 ##De-/Aktivierung und Schwellspannung zur Netzausfallerkennung##
Activation/deactivation and threshold voltage for power failure detection Group: 85
Bit 15 = fault message in the event of power failure >= 60 ms --> 0:off, 1:on Min.: 0
Bits 14 to 8 = unused
Bits 7 to 0 = threshold voltage (unit: 1 V RMS) Max.: 33023
Default: 32963
Write: 2
Version:

09/2012 - Art. Nr. 4200 1018 1500A 44


www.elco.net

Hotline
ELCO Austria GmbH
Aredstr.16-18 0810-400010
2544 Leobersdorf
ELCO Belgium nv/sa
Z.1 Researchpark 60 02-4631902
1731 Zellik
ELCOTHERM AG
Sarganserstrasse 100
0848 808 808
7324 Vilters
Switzerland
ELCO GmbH
Dreieichstr.10
0180-3526180
64546 Mörfelden-Walldorf
Germany
Elco Industry Italy
Corte degli Speziali 10/14 +39 0321 338600
28100 Novara
ELCO Burners B.V.
Amsterdamsestraatweg 27
035-6957350
1411 AW Naarden
Netherlands
OOO «Ariston Thermo RUS LLC»
Bolshaya Novodmitrovskaya
+7 495 783 0440
St.bld.14/1 office 626
127015 Moscow -Russia

Made in the EU. Non contractual document.