PROJECT SAUNI YOJANA LINK-2 PACKAGE-6

TITLE FAULT CALCULATION FOR PUMP HOUSE


LARSEN & TOUBRO LIMITED
WATER & EFFLUENT TREATMENT IC DATE 18 January 2019

FAULT LEVEL CALCULATION AT 6.6 kV BUS LEVEL

Source fault details (Considered):


Source Transformer = 160 MVA
Impedence = 12.5 %
Source Fault MVA = 1280.0 MVA
Source Fault Current = 11.20 kA

Power Transformer parameters:


Primary Voltage = 66 kV
Secondary Voltage = 6.6 kV
Transformer Rating = 31 MVA
Transformer Impedance = 10 %

Conductor Parameters for 66 kV Transmission line:


Condutor type = ACSR Panther
Resistance per km = 0.1616 ohm/km
Reactance per km = 0.2272 ohm/km
Total Transmission line length = 14.50 km
Total Resistance = 2.34 ohm
Total Reactance = 3.29 ohm
Total Impedance = 4.04 ohm

Cable Parameters ( Transformer to 6.6 kV HT Panel)


Cable Size = 400 Sq.mm
No of Core = 3 Core
Resistance per km = 0.102 ohm/km
Reactance per km = 0.0829 ohm/km
No of Runs = 9 Runs
Total Cable Length = 0.08 km
Total Resistance = 0.00091 km
Total Reactance = 0.00074 km
Total Impedance = 0.00117 km

6.6 kV HT Motor Parameters


Motor Rating = 2200 kW
Quantity of Motor = 8 Nos
Motor Power factor = 0.98 p.f.
Motor kVA = 2244.90 kVA
Transient reactance = 0.2838 %

Base Value

MVAbase = 100 MVA


kVbase = 66 kV
2
Zbase = kV base
= MVAbase
= 43.56
Ibase = 1.5152
PROJECT SAUNI YOJANA LINK-2 PACKAGE-6

TITLE FAULT CALCULATION FOR PUMP HOUSE


LARSEN & TOUBRO LIMITED
WATER & EFFLUENT TREATMENT IC DATE 18 January 2019

FAULT LEVEL CALCULATION AT 6.6 kV BUS LEVEL

Source Impedance Calculation (p.u.)


Zsource = 0.0781 p.u.

Transformer Impedance Calculation (p.u.)


Ztrf = 0.32 p.u.

Motor Impedance Calculation (p.u.)


Zmotor = 12.642 p.u.

Ztm (Considering all motors) = 1.5803 p.u.

Transmission line Impedance Calculation (p.u.)


Ztrl = 0.093 p.u.

Cable Impedance Calculation (p.u.)


Zcable = 0.000027 p.u.

The equivalent impedance circuit as follows:

Zs = 12.642

Ztrl = 0.093

Zt Ztm = 1.5803 Zeq

Ztrf = 0.323

Zcable = 0.00003

Calculation of Zt (p.u.)
Zt (p.u.) = 0.4935 pu

Calculation of Zeq (p.u.)


Zeq (p.u.) = 0.3761 pu

Calculation of Fault Current (p.u.)


Ifault (p.u.) = 2.6590 pu

Calculation of Fault Current at Base KV


Fault current at 66 kV base = 2.3260 kA

Calculation of Actual Fault Current at 6.6 kV bus


Fault Current at 6.6 kV Bus = 23.26 kA

#
PROJECT SAUNI YOJANA LINK-2 PACKAGE-6

TITLE FAULT CALCULATION FOR PUMP HOUSE


LARSEN & TOUBRO LIMITED
WATER & EFFLUENT TREATMENT IC 18 January 2019
DATE

FAULT LEVEL CALCULATION AT 66 kV BUS LEVEL

Source fault details (Considered):


Source Fault Current = 11.20 kA
Source Fault MVA = 1280.0 MVA

Power Transformer Parameters :


Primary Voltage = 66 kV
Secondary Voltage = 6.6 kV
Transformer Rating = 31 MVA
Transformer Impedance = 10 %

Conductor Parameters for 66 kV Transmission line:


Condutor type = ACSR Panther
Resistance per km = 0.1616 ohm/km
Reactance per km = 0.2272 ohm/km
Total Transmission line length = 14.50 km
Total Resistance = 2.34 ohm
Total Reactance = 3.29 ohm
Total Impedance = 4.04 ohm

Cable Parameters ( Transformer to 6.6 kV HT Panel)


Cable Size = 400 Sq.mm
No of Core = 3 Core
Resistance per km = 0.1020 ohm/km
Reactance per km = 0.0829 ohm/km
No of Runs = 9 Runs
Total Cable length = 0.08 km
Total Resistance = 0.00091 km
Total Reactance = 0.00074 km
Total Impedance = 0.00117 km

6.6 kV HT Motor Parameters


Motor Rating = 2200 kW
Quantity of Motor = 8 Nos
Motor Power factor = 0.98 p.f.
Motor kVA = 2244.90 kVA
Transient reactance = 0.2838 %

Base Value

MVAbase = 100 MVA


kVbase = 66 kV
Zbase = kV2base
= MVAbase
= 43.56
Ibase = 1.5152 kA
PROJECT SAUNI YOJANA LINK-2 PACKAGE-6

TITLE FAULT CALCULATION FOR PUMP HOUSE


LARSEN & TOUBRO LIMITED
WATER & EFFLUENT TREATMENT IC 18 January 2019
DATE

FAULT LEVEL CALCULATION AT 66 kV BUS LEVEL

Source Impedance Calculation (p.u.)


Zsource = 0.0781 p.u.

Transformer Impedance Calculation (p.u.)


Ztrf = 0.32 p.u.

Motor Impedance Calculation (p.u.)


Zmotor = 12.642 p.u.

Ztm = 1.5803 p.u.

Transmission line Impedance Calculation (p.u.)


Ztrl = 0.093 p.u.

Cable Impedance Calculation (p.u.)


Zcable = 0.00003 p.u.

The equivalent impedance circuit as follows:

Zs = 0.0781 Ztrf = 0.323

Zt
Zcable = 0.00003 Zq Zeq

Ztrl = 0.093

Ztm = 1.5803

Calculation of Zt (p.u.)
Zt (p.u.) = 0.1709 pu

Calculation of Zq (p.u.)
Zq (p.u.) = 1.9029 pu

Calculation of Zeq (p.u.)


Zeq (p.u.) = 0.1568 pu

Calculation of Fault Current (p.u.)


Ifault (p.u.) = 6.3758 pu

Calculation of Fault Current at 66 KV


Fault current at 66 kV bus = 5.5773 kA