SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
CONDUCTORS, BARE
1. 1
BARE CONDUCTORS TYPE ACAR/ACSR/ACSR-AW/AAAC Applicable Standards: 10-TMSS-01
Bahra Advance Cable Manufacture Co. ACAR, ACSR, ACSR/AW and AAAC Type tests on all PQ Letter
Ltd type of conductors Based on S&SD letters # 15-01562-1-30504401
Saudi Arabia performed (October dated 18th March 2015 & #
03-09, 2015) at 15-04785-1-30504401 dated 18th November,
Po Box 5989 Jeddah 21432 , Saudi Kinectrics 2015, it is pre-qualified with the following
Arabia Laboratory Toronto conditions:
Canada,
Contact Person - Mr. Loai Taha Al-Bar, Report No. WARRANTY:
Sale Manager K-419714-RC-0001- Ten (10) years extended warranty/guarantee in
Phone - +966-2-591-1115 R01 & . respect of defects due to design, manufacture,
Email ID - Loai.albar@bahra-cable.com K-419714-RC-0002- installation & workmanship from the date of the
R01 Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award
Kinectrics Report # and from the date of first delivery in case of
K-419605-RC-0001- direct material supply order .This was confirmed
R00 & in writing by the manufacturer through their letter
K-419605-RC-0002- # (BCC/SEC/LAB/GSM/MZ) dt: December 9, 2015.
R00
Previously Bahra Cable Co.
Kinectrics Report #
K-419714-RC-0001-
R01 &
K-419714-RC-0002-
R01
1. 1 Page 1 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
JEDDAH CABLE CO. ACAR, ACSR, ACSR/AW and AAAC Type Tests for PQ Letter
Saudi Arabia Conductors type Based on S&SD Letter No. 16-09867-30504401
ACSR, ACSR/AW, dated 7 Dec 2016 , JEDDAH CABLE Co. Jeddah
Plant -jeddah AAAC, ACAR were -K.S.A is Pre-qualified with following condition.
performed in
Po Box 31248 , Jeddah 21497 Jeddah , KINECTRIC WARRANTY:
Saudi Arabia International Inc. Ten (10) years extended warranty from the date
Laboratory – of PAC of the first turnkey project in case of
jeddah CANADA , contract award or date of first delivery in case of
KINECTRICS Report# direct material supply order.
Contact Person - Mr. Mohammad Said K-419635-RC-0001-
Minkara R01,
Phone - +966-126360770 K-419635-RC-0002-
Email ID - R01,
sayoubi@cables.energya.com , K-419635-RC-0003-
msminkara@cables.energya.com R01,
Website - K-419635-RC-0004-
http://www.cables.energya.com R01,
JCC-EP-PQ-0102-14
-34.
MIDAL CABLE , ACAR, ACSR, ACSR/AW and AAAC Type test conducted PQ Letter
Saudi Arabia from 25.08.2015 to Based on S&SD letter # 15-09640-030504401
04.09.2015 at dated November 24, 2015, it is pre-qualified with
Plant -Al Khobar different the following conditions:
laboratories in
P.O. Box 2312 Al Khobar 31952 Saudi Germany Viz SAG, WARRANTY:
Arabia ISP Institues, State Ten (10) years extended warranty from the date
Material testing of PAC of the first turnkey project in case of
Contact Person - Mr.Ammar Al Khuzaei institute ,FGH etc. contract award or date of first delivery in case of
General Manager Marketing & Sales , (Test Report # direct material supply order as
Mr. Mahadi Hussain 2015-049A, confirmed through Letter # Nil dated 19.10.2014.
Phone - +966-13-8988989 2015-049C &
+966-509994288 2015-049D)
Email ID - midalksa@midalcable.com
Hussain@midalcable.com
Website - http://www.midalcale.com
1. 1 Page 2 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
MIDAL CABLE LTD. ACAR, ACSR, ACSR/AW and AAAC Tests performed at:
BAHRAIN Manufacturer’s Lab.
(2014/2013/2010)
Plant -Bahrain Report #:
AAAC/P-1634-C/14/
Midal Cable Ltd. Bahrain Po Box 5939 01
Manama, Bahrain, Bldg. 744 Road 5128 AAAC/P-1196-C/13/
Block 951 Askar Road Bahrain. 08
Manama , Bahrain ACSR/P-890-C/10/0
4
Contact Person - Mr. Ammar Al Khuzaei ACSR/P-1087-C/11/2
Phone - +973-17832832 7
Email ID - ammar@midalcable.com ACSR/AW/P-696C/0
Website - http://www.midalcable.com/ 8/29
ACSR/AW/P-814C-A
/09/03
ACAR/P-1000-C/11/
23
STERLITE ACAR, ACSR, ACSR/AW and AAAC Tests performed at: PQ Letter
INDIA Based on TS&SD Letter #
FGH, Germany 10-F001691/01-03032301 dated 19/06/2010, it is
S. No. 99/P, Madhuban Dam Road, (Dec., 2009) pre-qualified with the following condition:
Rakholi Silvassa 396230 - India
Report # H1005, WARRANTY:
Contact Person - Mr. Vivek Ananad H10006, H10007 Ten (10) years extended warranty/guarantee in
Phone - +91-97-6555-3878 and H10008 respect of defects due to design, manufacture,
Email ID - vivek.anand@sterlite.com installation & workmanship from the date of
Website - Provisional Acceptance Certificate (PAC) of the
http://www.sterlitetechnologies.com turnkey project in case of contract award or date
of delivery in case of direct material supply order.
1. 1 Page 3 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
ALFANAR ELECTRICAL SYSTEMS ACAR, ACSR, ACSR/AW and AAAC Type Tests PQ Letter
Saudi Arabia performed for ACSR Based on S&SD letter# 13-02020-01-30504401
Conductor dated July 30, 2013, it is pre-qualified with the
Plant -3Rd Industrial Area, Al Kharaj at:Kinectrics - following: conditions.
Road, Riyadh Saudi Arabia Canada dated 11th
Feb 2013, Report #
Po Box 301 , Riyadh 11411 , North Righ K419415-RC-0001-R CONDITION:
Road Between Exit 5 & 6 Riyadh , 01 The first batch of AAAC, ACSR/AW & ACAR type
Saudi Arabia conductors shall be type tested at an
independent testing laboratory in the presence of
Contact Person - Mr. Ahmed Al Afifi (03) SEC/National Grid SA repreentatives and one
Phone - +966-500857946 approved third party inspector and all cost
Email ID - ahmed.al-afifi@alfanar.com pertaining to tests shall be borne by the
manufacturer.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmd by the manufacturer
through their letter #C-PRQ-2013-02 dated June
17, 2013.
Website - http://www.southwire.com/
Website -
http://www.alcoa.com/usa/en/home.as
p
1. 1 Page 4 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
APAR INDUSTRIES LTD. Imdad Support & ACAR, ACSR, ACSR/AW and AAAC Tests Performed for PQ Letter
INDIA technical AAAC Conductor Based on TS&SD Letter # 10-01566-2-03032300
PO Box 56451 Riyadh (Stress Strain, dated 14/06/2010, it is pre-qualified with the
Plant -Nalagarh Plant, Silvassa Plant 11554 Breaking Strength, following conditions:
Phone - 011-4657556 x UTS and
Nalagarh Plant: 222,311 Longitudinal CONDITION:
Khasra No. 467, Hadbast No. 101, Email – Smoothness) at The first batch of ACSR, ACSR/AW & ACAR type
Muuza Beer Plassi Tec. Nalagarh P.O Imd1adtech@gmail.com VEIKI-VNL, conductors shall be type tested at an
Manjhauli (Jagatkhana) District Solan Budapest – Hungary independent testing laboratory in the presence of
(H.P) 174 101 India in Jan., 2014) (03) SEC/National Grid SA repreentatives and one
Tel: 0091-01795-200384 Report # 7765/VNL approved third party inspector and all cost
E-mail: agv@apar.com pertaining to tests shall be borne by the
manufacturer, as confirmed by the manufacturer
through letter # AIL/BRD/PQ/SEC/19, dt: 22nd
SILVASSA Plant: May, 2010.
Survey No. 148/1 Kudacha, Silvassa,
Rakholi Road, Silvassa (U.T.OFD & NH) WARRANTY:
-396230 INDIA Ten (10) years warranty from the date of PAC of
Tel: 0091-260-2630193-194 the turnkey project in case of contract award or
Fax, 0091-260-2630916 date of delivery in case of direct material supply
E-mail: ashwin@apar.com order. This has been confirmed in writing by the
manufacturer; through letter # AIL/BRD/
SEC/PQ/19 dated 22nd May 2010.
1. 1 Page 5 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
RIYADH CABLES ACAR, ACSR, ACSR/AW and AAAC Tests performed at:
Saudi Arabia KSU Laboratory,
Riyadh K.S.A (July
P.O. Box 26862- Riyadh, 11496 Riyadh 2014)
, Saudi Arabia Report #
2014-OHL-2-ACSR/
Contact Person - Dr. Nabiah Al-Saati AW
,Technical Executive Director
Email ID - technical@riyadh-cables.com
Website -
http://www.riyadh-cables.com/
Jeddah
Total = 12
CONDUCTORS, BARE
1. 2
GUY WIRE STRAND, GALVANIZED (GROUNDING) Applicable Standards: 10-TMSS-02
SOUTHWIRE
United States
Website - http://www.southwire.com/
1. 2 Page 6 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TREFILEUROPE
FRANCE
Website -
http://www.mittalsteel.com/Facilities/Eu
rope/Mittal+Steel+Gandrange/Trefileuro
pe/
JOSLYN
United States
Website -
http://www.joslynhivoltage.com/
Total = 4
CONDUCTORS, BARE
1. 3
OVERHEAD GROUND WIRE (OGW) Applicable Standards: 10-TMSS-03
Plant -Bahrain
SOUTHWIRE
United States
Website - http://www.southwire.com/
1. 3 Page 7 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TREFILEUROPE
FRANCE
Website -
http://www.mittalsteel.com/Facilities/Eu
rope/Mittal+Steel+Gandrange/Trefileuro
pe/
ALCOA
United States
Website -
http://www.alcoa.com/usa/en/home.as
p
1. 3 Page 8 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
ECN CG SA
SPAIN
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
RIYADH CABLES
Saudi Arabia
1. 3 Page 9 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
SAUDI CABLE
Saudi Arabia
Jeddah
Total = 9
CONDUCTORS, BARE
1. 4
OPTICAL FIBER GROUND WIRE (OPGW) Applicable Standards: 10-TMSS-04
Website - http://www.afltele.com/
AFL TELECOMMUNICATIONS GMBH Type test report for Previously Draka Comteq Germany GmbH & KG.
GERMANY OPGW ASLH-D(S)
BB 96 SMF No WARRANTY:
Monchengladbach , Germany AL4/A20SA Ten (10) years extended warranty/guarantee in
161/21-20,0 respect of defects due to design, manufacture,
Type test report for installation & workmanship from the date of
OPGW type Provisional Acceptance Certificate (PAC) of the
ASLH-D(S)bb first turnkey project in case of contract award or
48SMF (AL4/A20SA date of first delivery in case of direct material
163/20-20,0) supply order.
(Equivalent to Wolf
with 48 Fiber).
1. 4 Page 10 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
JIANGSU ZHONGTIAN TECHNOLOGY OPGW, 70kN 13.3mm, 48 Fibers Tests performed at: PQ Letter
CO.LTD (ZTT) Kinectrics Canada Based on TS&SD Letter # 10-01654-03032301
CHINA (July, 2011) Report # dated June 05, 2010 and S&SD Letter
K-419311-RC0001-R 12-05204-1-30504401 dated February 04, 2013,
Chinanantong, China 00 it is prequalified with the following condition:
WARRANTY:
Tests performed at: Ten (10) years extended warranty/guarantee in
OPGW, 120kN, 17.3mm, 48 Fibers Kinectrics Canada respect of defects due to design, manufacture,
(July, 2011) Report # installation & workmanship from the date of
K-419311-RC0002-R Provisional Acceptance Certificate (PAC) of the
00 first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order.
Tests performed at:
Kinectrics Canada
Report #
OPGW, 15.3mm (70kN) & 18.4mm K-419653-RC-0002-
(120kN), 96 Fibers R00 (June 11,2015)
& Report #
K-419653-RC-0003-
OPGW, 18.5mm (77kN) 48 Fibers R00 (June 11,2015).
(OPGW -48B1-185 [77.7 ; 253.9])
Tests performed at:
Kinectrics Canada
Report #
K-419653-RC-0001-
R00 (May 04,2015).
1. 4 Page 11 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
PHILLIPS FITEL
CANADA
Website - http://www.phillipsfitel.com
1. 4 Page 12 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
PRYSMIAN TELECOM Zamil Group Holding co, 6715 120 kN/24 kA 48 core, Tests performed at: PREVIOUSLY "PIRELLI"
SPAIN Commercial Div 6716 70 kN/13 kA 48 core Kinectrics Canada
www.zamilcd.com.sa Report #
Plant -Vilanova I La Geltru/Spain Phone - K-419533-RC-0002-
966-0-504-320-776 8609 120 kN/24 kA 96 core, R01 (May, 2014)
Ctra. C-15,Km, 2-P.I. Masia D’En Notari Email - 8610 70 kN/13 kA 96 core Report #
08800 Vilanova I La Geltru ( Spain) khaleds@zamilcd.com.s K-419530-RC-0001-
a 8146 77.8kN/18 kA 48 core (94P64Dz) R00 (Jan, 2013)
Contact Person - Mr. Toni Nieto
Phone - +34608749306
Email ID -
Antonio.nieto@prysmiangroup.com
Website -
http://www.prysmiangroup.com
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
FUJIKURA
JAPAN
Website - http://www.ffcpg.com.my/
DRAKA NK
FINLAND
Website - http://www.draka.com/
PIRELLI
ITALY
1. 4 Page 13 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire OPGW-120kN, 36 Fibers, 17.9mm Tests performed at: PQ Letter
SOUTH KOREA Co.,Ltd. Branch Al-Tube type Kinectrics Canada, Based on TS&SD letter# 09-F00730/03-03032301
P. O. box 300201,Riyadh KERI & Taihan (2011) dated 24th August 2009, it is prequalified with the
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais (New) following condition:
Of Korea Building, 6th Floor Office 96C 14.9mm (New)
No. 613 - Taihan Electric 96C 18.5mm Taihan Electric Wire WARRANTY:
180, Simin-Daero, Dongan-Gu, Wire Co.,Ltd. Branch Co. Ltd - Korea has Ten (10) years extended warranty/guarantee in
Anyangsi, Gyeonggi-Do, Korea Korea, Phone - 966) 114190227 successfully respect of defects due to design, manufacture,
Republic Of Email - completed the type installation & workmanship from the date of
jsnam@taihan.com tests of Fiber Optical Provisional Acceptance Certificate (PAC) of the
Contact Person - Mr. JAI-HO SHIM Ground Wire first turnkey project in case of contract award or
Phone - +82) 2 316 9378 (OPGW) in date of first delivery in case of direct material
Email ID - jhshim@taihan.com independent supply order , as confirmed by the manufacturer
Website - http:// laboratory through their letter no.nil, dt: 30/03/2008.
http://www.taihan.com/eng1/customer/ (KINECTRICS,
s 015.asp Canada) report # (New)
K-419657-RC-0001- PQ letter:
R00 during March Based on S&SD letter # 17-08663-30504401
16, 2015 & dated December 18, 2017, Taihan Electric Wire
RC-0002-R00 during Co. Ltd - Korea is pre-qualified for Fiber Optical
March 17,2015 in Ground Wire (OPGW) as conforming to latest
the presence of National Grid SA specification # 10-TMSS-04
SEC/National Grid
SA Engineers. WARRANTY:
• Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation and workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
vide letter # TENA171206-01, dated December
06, 2017.
BRUGG TELECOM AG
SWITZERLAND
Website - http://www.brugg.com/
1. 4 Page 14 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
CORNING CABLES
United Kingdom
Website -
http://www.corningcablesystems.com/
Total = 13
CONDUCTORS, BARE
1. 5
BARE, COPPER-CLAD STEEL GROUNDING CONDUCTOR AND GROUND ROD Applicable Standards: 10-TMSS-05
COMSCOPE BIMETALS
United States
Website - http://www.fmsudafix.com/
Website -
http://www.jiwoong.co.kr/main
eng.html
1. 5 Page 15 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Copperweld Bimettalics LLC Mishan Holding Group Previously LTV Copperweld, name has been
United States P.O. Box 6295, Dammam changed based on Copperweld Bimettalics letter
31442, KSA # Nil dated January 03,2018.
Plant -Fayetteville, Tennessee
Tennessee
1. 5 Page 16 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Nottingham WARRANTY:
Ten (10) years Extended Warranty as confirmed
Contact Person - Mark Rimmington, through Letter No. ANW/NG SA/ SEC / EW/ L01 /
Director 2016 dated 27/10/2016 shall be applicable for all
Phone - +44(0)1159271721 supplies to the Company by A. N. Wallis & Co.
Email ID - info@an-wallis.com Ltd. – UK
Website - www.an-wallis.com
Total = 7
CONDUCTORS, BARE
1. 6
HEAT-RESISTANT ALUMINUM ALLOY BARE CONDUCTORS FOR OVERHEAD LINE Applicable Standards: 10-TMSS-06
1. 6 Page 17 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
J-POWER SYSTEM CORP, Middle East Regional GAP Type & INAVR Type Conductors: Test performed at: PQ Letter
JAPAN Office GTACSR, GZTACSR and Toyoura Works Based on TS&SD letter# 09-00649-1-03032301
Mr. Amjad Abdelaziz ZTACIR/AS, XTACIR/AS (JECTEC) Nov./Dec. dated 28 March 2009 and S&SD letter no.
Plant -JAPAN-Hitachi ,General Manager 2014, Oct. 2009, 15-00017-1-30504401 dated 8th Feb 2015 it is
Amja.aziz@jpower.co.jp Jan. 2013, Mar. pre-qualified for Heat Resistant Conductors
3-13-16 Mita- Minato-Ku, Tokyo 2004, & Sep 2007 subject to the following conditions:
108-0073 , Japan
Report # WARRANTY:
Phone - +61-3-5232-4709 JTR12AY091245, Ten (10) years extended warranty in respect of
Email ID - amjad.aziz@jpowers.co.jp JTR12AY-13092, the defects due to design, manufacturing &
Website - JTR12-AY044167,JT workmanship from the date of the Provisional
http://www.jpowers.co.jp/english/inde R12-AY07980, Acceptance Certificate (PAC) of the first turnkey
x.html JTR12-AY07092, project (in case of contract award) and from the
JTR12-AY12107,JTR date of first delivery in case of direct material
12-AY09913 & supply order shall be provided as confirmed by
JTR12-Ay141633 the manufacturer through their letters #
#JLX80-15-0013 dated 5th Feb 2015 and
Type Tests JLX80-15-0022 dated March 02nd, 2015.
performed from 27th
Nov to 5th Dec 2014
at:
Japan Electric Cable
technology
Center(JECTEC) Lab
Shizuoka, Japan.
Report#
IR-2014-5001-40261
-001
Total = 3
1. 6 Page 18 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
CONDUCTOR, INSULATED
2. 1
POWER CABLE, XLPE, CU OR AL, 1-CORE, 69 kV Applicable Standards: 11-TMSS-01
SAUDI CABLE
Saudi Arabia
Jeddah
2. 1 Page 19 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://www.alcatel.fr/
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
DEMIRER KABLO
TURKEY
Website - ?http://
http://www.masskablo.com/about us
co?mpany.asp?md=
2. 1 Page 20 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
Website - http://www.draka.com/
Website - http://www.ffcpg.com.my
Email ID - lang=en
Website -
http://www.mkm-?mediline.de/index.ph
p/edv-und-software-?entwicklung/mkm
-computer-network-?ungarn?lang=en?
Website - http://
http://www.suedkabel.de/index e.htm
2. 1 Page 21 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
JEDDAH CABLE CO. XLPE Cable Type tested in 2010 Based on S&SD letter# 16-06823-30504401
Saudi Arabia 1x1200mm² Report # TDT dated August 14, 2016, the manufacturer is
1002-10 prequalified for XLPE Insulated Power Cable as
Plant -jeddah , 69 kV confirming to SEC specification # 11-TMSS-01,
Rev.0, with the following condition:
Po Box 31248 , Jeddah 21497 Jeddah ,
Saudi Arabia • Ten (10) years extended warranty for XLPE
Power Cable from the date of PAC of the turnkey
jeddah project in case of contract award and date of
delivery in case of direct material supply order,
Contact Person - Mr. Mohammad Said as confirmed by the manufacturer through letter
Minkara #NIL dated August 14, 2016.
Phone - +966-126360770
Email ID -
sayoubi@cables.energya.com ,
msminkara@cables.energya.com
Website -
http://www.cables.energya.com
Total = 13
CONDUCTOR, INSULATED
2. 2
POWER CABLE, XLPE INSULATED, COPPER CONDUCTOR, SINGLE CORE, 110 TO 132 kV Applicable Standards: 11-TMSS-02
2. 2 Page 22 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
LS PREVIOUSLY LG;
SOUTH KOREA
Website - http://www.lscable.com/
2. 2 Page 23 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
RIYADH CABLES 110 TO 132kV, Tests performed at: Based on S&SD letter # 16-04560-30504401
Saudi Arabia 1x2500mm2 KEMA dated June 12, 2016, the manufacturer is
Netherlands (Jan. prequalified for XLPE cable 132KV,as
P.O. Box 26862- Riyadh, 11496 Riyadh 2014) conforming to National Grid SA specification #
, Saudi Arabia Report # TIC 11-TMSS-02, Rev.01.
1489-13
Contact Person - Dr. Nabiah Al-Saati
,Technical Executive Director Type /Special tests
Email ID - technical@riyadh-cables.com were successfully
Website - conducted along
http://www.riyadh-cables.com/ with following cable
accessories from
Brugg Cables at
KINECTRIC –
Canada. Report No:
K-423363
RC-0000-R0 & SGS
Inspection report #
01.14189 Rev.0 &
KEMA Tests on Joint
Outer Protection –
Extract of Report TIC
1012-14:
I. Porcelain Insulated
Outdoor Sealing End
from Brugg Cables -
Type # TE 1.170-01
II. SF6 Gas Insulated
Sealing End from
Brugg Cables - Type
#
TF 1.170-12
III. Insulating Joint
from Brugg Cables -
Type # MPAP
1.145-33
2. 2 Page 24 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire Tests performed at:
SOUTH KOREA Co.,Ltd. KEMA
P. O. box 300201,Riyadh Netherlands (Mar
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais 1995, Dec
Of Korea Building, 6th Floor Office 2009 & June 2013)
No. 613 -
180, Simin-Daero, Dongan-Gu, Phone - 966) 114190227
Anyangsi, Gyeonggi-Do, Korea Korea, Email -
Republic Of jsnam@taihan.com
BRUGG Mass Power contracting 110 kV to 132 kV. Tests performed at: NAM. GIS termination, Transformer Termination,
SWITZERLAND Co. KEMA Outdoor termination, Cross bonding & Straight
Contact Person:Mr. Syed Netherlands Through Joints - XLPE Cables 16 Models of XLPE
5201 Brugg Switzerland,28 Ch5201 Ali Report # TDT cable
Brugg Switzerland, 0506818743 ,Phone - 3148-10 (2011)
0506818743 70851907-TDT-09-6
Contact Person - Mr. Pierre Londorf Email - 9942A
Phone - +41-56-460-3637 s.ali@mass-group.net (2009) & TIC
Email ID - londorf.pierre@brugg.com 1012-14(2014
Website - http://www.brugg.com/
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
DAINICHI-NIPPON CABLES
(MITSUBISHI)
JAPAN
2. 2 Page 25 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - ?http://
http://www.masskablo.com/about us
co?mpany.asp?md=
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
DRAKA NK
FINLAND
Website - http://www.draka.com/
Website - http://
http://www.suedkabel.de/index e.htm
FUJIKURA
JAPAN
Website - http://www.ffcpg.com.my/
2. 2 Page 26 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
JEDDAH CABLE CO. 1x1200mm2 All models type Based on TS&SD Letter #10-02784-01-03032301
Saudi Arabia (110kV & 132kV) tested at: dated October 10,2014 and S&SD Letter
KEMA Netherlands #14-04876-01-30504401 dated july 16 2014. It is
Plant -jeddah 1x2000mm2 (2010, prequalified for 132 kV , 1x2500mm2
(115kV & 132kV) 2012, 2013 & 2014) CU/XLPE/CWS/LAT/HDPE Power Cable as
Po Box 31248 , Jeddah 21497 Jeddah , Report # TIC confirming to N ational Grid Specification #
Saudi Arabia 1x2500mm2 132kV 1065-12, TIC 11-TMSS-02 Rev.1 with the following condition
1002-13, TDT
jeddah 1001-10, TIC Ten ( 10) years extended wararanty for XLPE
1072-12, TIC Power cable from the date of PAC of the turnkey
Contact Person - Mr. Mohammad Said 1013-14 project in case of contract award or date of
Minkara delivery in case of direct material supply order.
Phone - +966-126360770 This was confirmed in writing by Jeddah cable.
Email ID - Co. through letter #nil dated 26th June 2006.
sayoubi@cables.energya.com ,
msminkara@cables.energya.com
Website -
http://www.cables.energya.com
2. 2 Page 27 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
JEDDAH CABLE CO. 1x1200mm2 (132kV) HV Optimized Type test performed Based on S&SD letter # 18-02714-01-30504401
Saudi Arabia Design in DNV-GL (KEMA) – dated July 16, 2018 Jeddah Cable Co , Rabigh,
Netherland testing Saudi Arabia is pre-qualified for 132kV,
Plant -RABIGH Laboratory Report # 1x1200mm2 CU/XLPE/CWS/LAT/HDPE Cables HV
1113-18 Optimized Design as conforming to National Grid
Exit 294, Rabigh Industrial area, Rabibh SA specification # 11-TMSS-02, Rev.02 with the
K.S.A following conditions:
Total = 16
CONDUCTOR, INSULATED
2. 3
POWER CABLE, XLPE INSULATED, COPPER CONDUCTOR, SINGLE CORE, 230 kV Applicable Standards: 11-TMSS-02
2. 3 Page 28 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
2. 3 Page 29 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire Tests performed at: WARRANTY:
SOUTH KOREA Co.,Ltd. KEMA Ten (10) years extended warranty/guarantee in
P. O. box 300201,Riyadh Netherlands respect of defects due to design, manufacture,
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais installation & workmanship from the date of
Of Korea Building, 6th Floor Office Provisional Acceptance Certificate (PAC) of the
No. 613 - first turnkey project in case of contract award or
180, Simin-Daero, Dongan-Gu, Phone - 966) 114190227 date of first delivery in case of direct material
Anyangsi, Gyeonggi-Do, Korea Korea, Email - supply order.
Republic Of jsnam@taihan.com
BRUGG CONDITION:
SWITZERLAND All type/design and routine/sample tests shall be
conducted at SEC approved independent
Contact Person - Mr. Pierre Londorf laboratory in presence of representative of 3rd
Phone - +41-56-460-3637 party inspection agency & three engineers of
Email ID - londorf.pierre@brugg.com SEC for first contract.
Website - http://www.brugg.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order.
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
DAINICHI-NIPPON CABLES
(MITSUBISHI)
JAPAN
2. 3 Page 30 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
DEMIRER KABLO
TURKEY
Website - ?http://
http://www.masskablo.com/about us
co?mpany.asp?md=
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
Website - http://
http://www.suedkabel.de/index e.htm
FUJIKURA
JAPAN
Website - http://www.ffcpg.com.my/
2. 3 Page 31 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
JEDDAH CABLE CO. 1x2500mm2 CU/XLPE, 230kV Type test performed PQ Letter
Saudi Arabia in DNV-GL (KEMA) – Based on S&SD letter # 18-03331-02-30504401
Netherland testing dated September 18, 2018 Jeddah Cable Co ,
Plant -RABIGH laboratory, report # Rabigh, Saudi Arabia is pre-qualified for 230kV,
1377-16 1x2500mm2 CU/XLPE Cables as conforming to
Exit 294, Rabigh Industrial area, Rabibh Prequalification Test National Grid SA specification # 11-TMSS-02
K.S.A performed in
DNV-GL (KEMA) – Warranty
RABIGH Netherland testing Ten (10) years extended warranty/guaranty
laboratory, report # from the date of (PAC) of the Turnkey project (In
Contact Person - Mr. Mohammad Said - 1404-18 case of contract award) and from the date of
Mr. SAMER AYOUBI delivery for the direct material supply order. The
Phone - 012 636 0770 guarantee/warranty shall be applicable from first
Email ID - project and shall cover all the cost of materials
msminkara@cables.energya.com - and labor as per warranty/guarantee of materials
sayoubi@cables.energya.com and workmanship and subsequently reduced
Contact Person Email ID - yearly in case of future project award. This was
msminkara@cables.energya.com - confirmed in writing by Jeddah cable. Co. through
sayoubi@cables.energya.com their letter # nil dated # nil.
Website - www.cables.energya.com
Total = 11
CONDUCTOR, INSULATED
2. 4
POWER CABLE, XLPE INSULATED, COPPER CONDUCTOR, SINGLE CORE 380 kV Applicable Standards: 11-TMSS-02
ILJIN ELECTRIC CO. LTD. 380kV XLPE Cable 1x2500mm² Based on S&SD letter# 16-2299-02-30504401
SOUTH KOREA CU/XLPE/LEAD/HDPE dated May 02, 2016, it is prequalified for380kV
XLPE Cable 1x2500mm² CU/XLPE/LEAD/HDPE as
Plant -Hongseong, South Korea conforming to National Grid SA Material
Specification 11-TMSS-02, Rev 01 with the
905-17, Mannyeon-ro, Hwaseong-si, following conditions:
Gyeonggi, KOREA
• Ten (10) years extended warranty from the
Contact Person - Mr. Jeong Kyung Woo date of PAC of the turnkey project in case of
, Mr. Jaeho Kim contract award and date of delivery in case of
Phone - +82-2-707-9161 direct material supply order, as confirmed by the
Contact Person Email ID - manufacturer through letter # ILJHC-160412 A
jkwoo@iljin.co.kr , jaeho.kim@iljin.co.kr dated 12/04/2016.
Website - http://www.iljinelectric.co.kr
2. 4 Page 32 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire 1x2500mm2 Tests performed at: PQ Letter
SOUTH KOREA Co.,Ltd. CWS Type, KEMA Based on S&SD letter # 14-08139-01-30504401
P. O. box 300201,Riyadh 380 kV with the following drawing Netherlands (Jan. dated: January 07, 2015, the manufacturer is
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais numbers: 2014 to prequalified to supply 380kV 1x2500mm2 CWS
Of Korea Building, 6th Floor Office May, 2014) Type power cables:
No. 613 - - Power cable: Report # TIC
180, Simin-Daero, Dongan-Gu, Phone - 966) 114190227 TXCCD-3802500-130501. 3094-14 WARRANTY:
Anyangsi, Gyeonggi-Do, Korea Korea, Email - Ten (10) years extended warranty in respect of
Republic Of jsnam@taihan.com the defects due to design, manufacturing,
installation and workmanship from the date of the
Contact Person - Mr. JAI-HO SHIM Provisional Acceptance Certificate (PAC) of the
Phone - +82) 2 316 9378 first turnkey project (in case of contract award)
Email ID - jhshim@taihan.com or from the date of first delivery in case of direct
Website - http:// material supply order shall be provided as
http://www.taihan.com/eng1/customer/ confirmed by the manufacturer through their
s 015.asp letter # Nil dated September 02, 2014.
2. 4 Page 33 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
BRUGG CONDITION:
SWITZERLAND All type/design and routine/sample tests shall be
conducted at SEC approved independent
5201 Brugg Switzerland,28 Ch5201 laboratory in presence of representative of 3rd
Brugg Switzerland, party inspection agency & three engineers of
SEC for first contract.
Contact Person - Mr. Pierre Londorf
Phone - +41-56-460-3637 WARRANTY:
Email ID - londorf.pierre@brugg.com Ten (10) years extended warranty/guarantee in
Website - http://www.brugg.com/ respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order.
2. 4 Page 34 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
DAINICHI-NIPPON CABLES
(MITSUBISHI)
JAPAN
Website - ?http://
http://www.masskablo.com/about us
co?mpany.asp?md=
VISCAS FUJIKURA
JAPAN
Website - http://
http://www.viscas.com/e contact.html
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
Website - http://
http://www.suedkabel.de/index e.htm
2. 4 Page 35 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
JEDDAH CABLE CO. 1x2500mm2 CU/XLPE, 380kV Type test performed PQ Letter
Saudi Arabia in DNV-GL (KEMA) –
Netherland testing Based on S&SD letter # 18-03331-02-30504401
Plant -RABIGH laboratory, report # dated September 18, 2018 Jeddah Cable Co ,
1184-16 Rabigh, Saudi Arabia is pre-qualified for 380kV,
Exit 294, Rabigh Industrial area, Rabibh Prequalification Test 1x2500mm2 CU/XLPE Cables as conforming to
K.S.A performed in National Grid SA specification # 11-TMSS-02
DNV-GL (KEMA) –
RABIGH Netherland testing Warranty
laboratory, report #
Contact Person - Mr. Mohammad Said - 1406-18 Ten (10) years extended warranty/guaranty
Mr. SAMER AYOUBI from the date of (PAC) of the Turnkey project (In
Phone - 012 636 0770 case of contract award) and from the date of
Email ID - delivery for the direct material supply order. The
msminkara@cables.energya.com - guarantee/warranty shall be applicable from first
sayoubi@cables.energya.com project and shall cover all the cost of materials
Contact Person Email ID - and labor as per warranty/guarantee of materials
msminkara@cables.energya.com - and workmanship and subsequently reduced
sayoubi@cables.energya.com yearly in case of future project award. This was
Website - www.cables.energya.com confirmed in writing by Jeddah cable. Co. through
their letter # nil dated # nil.
Total = 12
CONDUCTOR, INSULATED
2. 5
POWER CABLE, LPOF, CU, 1-CORE, CABLE –110 kV TO 132 kV Applicable Standards: 11-TMSS-03
Website - http://
http://www.swcc.co.jp/eng/index.htm
Website - http://www.alcatel.fr/
2. 5 Page 36 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://
http://www.transcanadawireandcable.
com
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire Rating - 132kV KEMA, Netherlands Including Joints & Terminations
SOUTH KOREA Co.,Ltd. July 2000
P. O. box 300201,Riyadh
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais
Of Korea Building, 6th Floor Office
No. 613 -
180, Simin-Daero, Dongan-Gu, Phone - 966) 114190227
Anyangsi, Gyeonggi-Do, Korea Korea, Email -
Republic Of jsnam@taihan.com
Website - http://
http://www.bruggcables.com/index/ind
ex.cfm?page=home&sprache=de
Website -
http://www.nexans.com/eservice/Navi
gate.nxnavigationRef=
-10&CZ=Corporate
2. 5 Page 37 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
Website - http://
http://www.daetwyler.net/e/index.htm
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
Website - http://www.ffcpg.com.my/
2. 5 Page 38 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
LS CABLES PREVIOUSLY LG
SOUTH KOREA
Including Joints & Terminations
Plant -Gumi/Korea
Total = 15
CONDUCTOR, INSULATED
2. 6
POWER CABLE, LPOF, CU, 1-CORE, 230 kV Applicable Standards: 11-TMSS-03
Website - http://www.alcatel.fr/
Website - http://
http://www.transcanadawireandcable.
com
2. 6 Page 39 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire Feb. 2006 Including Joints & Terminations.
SOUTH KOREA Co.,Ltd.
P. O. box 300201,Riyadh CONDITION:
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais All type/design and routine/sample tests shall be
Of Korea Building, 6th Floor Office conducted at SEC approved independent
No. 613 - laboratory in presence of representative of 3rd
180, Simin-Daero, Dongan-Gu, Phone - 966) 114190227 party inspection agency & three engineers of
Anyangsi, Gyeonggi-Do, Korea Korea, Email - SEC for first contract.
Republic Of jsnam@taihan.com
WARRANTY:
Contact Person - Mr. JAI-HO SHIM Ten (10) years extended warranty/guarantee in
Phone - +82) 2 316 9378 respect of defects due to design, manufacture,
Email ID - jhshim@taihan.com installation & workmanship from the date of
Website - http:// Provisional Acceptance Certificate (PAC) of the
http://www.taihan.com/eng1/customer/ first turnkey project in case of contract award or
s 015.asp date of first delivery in case of direct material
supply order.
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
2. 6 Page 40 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://www.ffcpg.com.my/
Total = 9
CONDUCTOR, INSULATED
2. 7
POWER CABLE, LPOF, CU, 1-CORE,380 kV Applicable Standards: 11-TMSS-03
Website -
http://www.hitachi-?cable.co.jp/en/inde
x.html
Website -
http://www.mitsubishi-cable.co.jp/inde
x e.html
Website - http://
http://www.swcc.co.jp/eng/index.htm
2. 7 Page 41 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://www.alcatel.fr/
Website - http://
http://www.transcanadawireandcable.
com
2. 7 Page 42 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire Including Joints & Terminations.
SOUTH KOREA Co.,Ltd.
P. O. box 300201,Riyadh CONDITION:
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais All type/design and routine/sample tests shall be
Of Korea Building, 6th Floor Office conducted at SEC approved independent
No. 613 - laboratory in presence of representative of 3rd
180, Simin-Daero, Dongan-Gu, Phone - 966) 114190227 party inspection agency & three engineers of
Anyangsi, Gyeonggi-Do, Korea Korea, Email - SEC for first contract.
Republic Of jsnam@taihan.com
WARRANTY:
Contact Person - Mr. JAI-HO SHIM Ten (10) years extended warranty/guarantee in
Phone - +82) 2 316 9378 respect of defects due to design, manufacture,
Email ID - jhshim@taihan.com installation & workmanship from the date of
Website - http:// Provisional Acceptance Certificate (PAC) of the
http://www.taihan.com/eng1/customer/ first turnkey project in case of contract award or
s 015.asp date of first delivery in case of direct material
supply order.
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
2. 7 Page 43 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://www.ffcpg.com.my/
LS CABLES PREVIOUSLY LG
SOUTH KOREA
Including Joints & Terminations.
Plant -Gumi/Korea
WARRANTY:
13 F Ls Tower ,127, Ls-Ro, Ten (10) years extended warranty/guarantee in
Dongan-Gu, Anyang-Si, Gyeonggi-Do, respect of defects due to design, manufacture,
Korea installation & workmanship from the date of PAC
of the First turnkey project in case of contract
Contact Person - Jiyup Baik award or date of the First delivery in case of
Phone - +82-544697602 directmaterial supply order.
Email ID - nayuppie@lscns.com
Website - http://www.lscns.com
Total = 16
CONDUCTOR, INSULATED
2. 8
MEDIUM VOLTAGE POWER CABLE -XLPE –13.8 kV Applicable Standards: 11-TMSS-04
Website - http://www.ducab.ae
2. 8 Page 44 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
2. 8 Page 45 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
SAUDI CABLE
Saudi Arabia
Jeddah
Website -
http://www.omancables.com/
LS PREVIOUSLY LG
SOUTH KOREA Including Joints & Terminations
Website - http://www.lscable.com/
2. 8 Page 46 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire KEMA, Netherlands Including Joints & Terminations
SOUTH KOREA Co.,Ltd. (Nov. 2007)
P. O. box 300201,Riyadh
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais
Of Korea Building, 6th Floor Office
No. 613 -
180, Simin-Daero, Dongan-Gu, Phone - 966) 114190227
Anyangsi, Gyeonggi-Do, Korea Korea, Email -
Republic Of jsnam@taihan.com
2. 8 Page 47 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Plant -jeddah
jeddah
Bahra Advance Cable Manufacture Co. (XLPE) MV Power Cable with a size MV Power Cable Based on S&SD Letter # 16-07712-1-30504401
Ltd bigger than 630 mm² with a size bigger dated October 04, 2016, it is pre-qualified for
Saudi Arabia than 630 mm² to be Insulated Conductor Cable as conforming to
supplied to National Grid SA Specification # 11-TMSS-04,
Po Box 5989 Jeddah 21432 , Saudi SEC/National Grid Rev.1 with the following conditions:
Arabia SA shall fully type
tested at an •Ten (10) years extended warranty from the date
Contact Person - Mr. Loai Taha Al-Bar, accredited of PAC of the first turnkey project (in case of
Sale Manager laboratory in the contract award) or date of first delivery (in case
Phone - +966-2-591-1115 presence of National of direct material supply order), as confirmed
Email ID - Loai.albar@bahra-cable.com Grid SA through BAHRA CABLES Co. –JEDDAH, KSA
Engineers & third letter # nil dated September 06, 2016.
party inspector.
. Previously Bahra Cable Co.
2. 8 Page 48 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
2. 8 Page 49 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Gaon Cables CO., LTD. Abdulaziz M. AlSuwaiket MV Power Cable up to 1000 mm² Type Tests PQ letter:
SOUTH KOREA (AlSuwaiket) conducted in KEMA Based on S&SD letter # 18-01986-030504401
AlSuwaiket during 01 to 09 dated May 24, 2018 for Gaon Cables. Gunpo,
Plant -Gunpo +966-13-857-1155 March 2018 Korea is pre-qualified for Medium Voltage Power
abdulaziz@alsuwaiket.c Report no 01 14440 Cables as conforming to latest National Grid SA
120, LS-ro 45beon-gil, Gunpo-si, om A (by SGS) specification # 11-TMSS-04, with the following
Gyeonggi-do, 15841, Republic of Korea conditions:
Total = 12
CONDUCTOR, INSULATED
2. 9
MEDIUM VOLTAGE POWER CABLE - XLPE , 33 & 34.5 kV Applicable Standards: 11-TMSS-04
2. 9 Page 50 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Note:
MV Power Cable beyond cable size of 630 mm2
to be supplied to National Grid SA shall be fully
type tested at an accredited laboratory in the
presence of National Grid SA Engineers & third
party inspector.
Website - http://www.ducab.ae
2. 9 Page 51 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
SAUDI CABLE
Saudi Arabia
Jeddah
Website -
http://www.omancables.com/
2. 9 Page 52 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://www.lscable.com/
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire Tests performed at: Including Joints & Terminations
SOUTH KOREA Co.,Ltd. Branch KEMA,
P. O. box 300201,Riyadh Netherlands
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais (Dec. 1986)
Of Korea Building, 6th Floor Office
No. 613 -
180, Simin-Daero, Dongan-Gu, Phone - 966) 114190227
Anyangsi, Gyeonggi-Do, Korea Korea, Email -
Republic Of jsnam@taihan.com
Website - http://
http://www.swcc.co.jp/eng/index.htm
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
2. 9 Page 53 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
DEMIRER KABLO
TURKEY
Website - ?http://
http://www.masskablo.com/about us
co?mpany.asp?md=
Website - http://www.ffcpg.com.my
Email ID - lang=en
Website -
http://www.mkm-?mediline.de/index.ph
p/edv-und-software-?entwicklung/mkm
-computer-network-?ungarn?lang=en?
Bahra Advance Cable Manufacture Co. (XLPE) MV Power Cable with a size MV Power Cable Based on S&SD Letter # 16-07712-1-30504401
Ltd bigger than 630 mm² with a size bigger dated October 04, 2016, it is pre-qualified for
Saudi Arabia than 630 mm² to be Insulated Conductor Cable as conforming to
supplied to National Grid SA Specification #11-TMSS-04,
Po Box 5989 Jeddah 21432 , Saudi SEC/National Grid Rev.1 with the following conditions:
Arabia SA shall fully type
tested at an •Ten (10) years extended warranty from the date
Contact Person - Mr. Loai Taha Al-Bar, accredited of PAC of the first turnkey project (in case of
Sale Manager laboratory in the contract award) or date of first delivery (in case
Phone - +966-2-591-1115 presence of National of direct material supply order), as confirmed
Email ID - Loai.albar@bahra-cable.com Grid SA Engineers & through BAHRA CABLES Co. –JEDDAH, KSA
third party inspector. letter # nil dated September 06, 2016
2. 9 Page 54 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Plant -jeddah
jeddah
2. 9 Page 55 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Gaon Cables CO., LTD. Abdulaziz M. AlSuwaiket MV Power Cable up to 1000 mm² Type Tests PQ letter:
SOUTH KOREA (AlSuwaiket) conducted in KEMA Based on S&SD letter # 18-01986-030504401
(AlSuwaiket) during 01 to 09 dated May 24, 2018 for Gaon Cables. Gunpo,
Plant -Gunpo +966-13-857-1155 March 2018 Korea is pre-qualified for Medium Voltage Power
abdulaziz@alsuwaiket.c Report no 01 14440 Cables as conforming to latest National Grid SA
120, LS-ro 45beon-gil, Gunpo-si, om A (by SGS) specification # 11-TMSS-04, with the following
Gyeonggi-do, 15841, Republic of Korea conditions:
Total = 18
CONDUCTOR, INSULATED
2. 10
Distributed Temperature Sensing (DTS) System for U/G Power Cable Applicable Standards: 11-TMSS-06
2. 10 Page 56 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Yokogawa Electric Corporation Yokogawa Saudi Arabia DTSX200 and DTSX3000 Yokogawa Electric PQ Letter
JAPAN Company, Saudi Corporation, Japan Based on S&SD letter # 17-02871-5-30504401
Arabia-Dhahran has successfully dated April 19,2017 , Yokogawa Electric
Plant -Japan Ibn Rushd Street, completed type tests Corporation, Japan is pre-qualified for Distributed
Dhahran Techno-Valley - on Distributed Temperature Sensing System (Type: DTSX200
Yokogawa Manufacturing Corporation Dhahran, P.O.Box 3368, Temperature and DTSX3000) as conforming to National Grid
Koufu Factory 155, Takamurocho, Al-Khobar 31952, Sensors (DTS) Type SA specification # 11-TMSS-06, with the
Kofu-City, Yamanashin 400-8558- Kingdom of Saudi Arabia DTSX200 and following conditions:
Japan +966 (13) 331 9600 DTSX3000 in
Hazem.Hassan@sa.yok presence of three WARRANTY:
Kofu ogawa.com SEC/National Grid Ten (10) years extended warranty in respect of
SA Engineers and defects due to design, manufacturing and
Contact Person - Mr. Teichi Matsumoto third party inspector workmanship from the date of PAC of the first
& Mr. Hazem A. Hassan at Independent turnkey project (in case of contract award) or
Phone - +81-55-243-0480 testing laboratory UL from the date of first delivery (in case of direct
Email ID - – Japan on 30 May material supply order), as confirmed, through
Hazem.Hassan@sa.yokogawa.com 2016 & Yokogawa their Letter No. SSD-PDZZ21-G15-25-3 dated
Contact Person Email ID - Electric Corporation 20/01/2016.
Hazem.Hassan@sa.yokogawa.com Laboratory- Japan
Website - WWW.yokogawa.co.jp during 26 to 27 May
2016.
Total = 2
CONDUCTOR, INSULATED
2. 11
DTS System Integration, Assembly and Factory Acceptance Testing (FAT) Applicable Standards:
2. 11 Page 57 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
WARRANTY
Ten (10) years extended warranty in respect of
defects due to design, manufacturing and
workmanship from the date of PAC of the first
turnkey project (in case of contract award) or
from the date of first delivery (in case of direct
material supply order), as confirmed, through
their Letter No. NIL dated 13/10/2016.
Total = 1
CONDUCTOR, INSULATED
2. 12
POWER AND/OR CONTROL CABLES COPPER OR ALUMINUM CONDUCTOR 600/1000V Applicable Standards: 11-TMSS-10
RATING
2. 12 Page 58 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
2. 12 Page 59 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
SAUDI CABLE
Saudi Arabia
Jeddah
Website -
http://www.mesccables.com/
2. 12 Page 60 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
thru letter #nil, dt: 21/08/2010.
BELDEN
United States
Website - http://www.belden.com/
2. 12 Page 61 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
MIDDLE EAST SPECIALIZED CABLE CO. Previously JORDAN NEW CABLE COMPANY-
MESC, JORDAN-
JORDAN AMMAN [The name has been changed based on
S&SD/P&SFD letter # 14-01869-30504401 dated
Jordan March 24, 2014].
TEKAB CO. LTD. LV Power & Control Cables upto 630 TEKAB Certificate # PQ letter:
United Arab Emirates mm² Size with Copper Conductor ( TCL/TTC-1810300 Based on S&SD letter# 13-07588-30504401
except clause 4.3.5c for corrugated dated 16.10.2018 dated December 11, 2013 & S&SD letter#
Sharjah , United Arab Emirates armors) for LV Power Cable 18-4055-01-30504401 dated November 04, 2018,
KEMA TEST REPORT it is pre-qualified for Power and/or Control Cable
Website - http://www.tekab.com/ # 1633-17 dated Copper 600/1000 Volts for All LV power & control
22.01.2018 for LV cables upto 630 mm² size
Power Cable
KEMA TEST REPORT WARRANTY:
# 3188-17 dated Ten (10) years extended warranty/guarantee in
25.06.2018 for LV respect of defects due to design, manufacture,
Control Cable installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
thru letter #0580/SO/13, dt: Nov 17, 2013
2. 12 Page 62 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Bahra Advance Cable Manufacture Co. Low Voltage Cables (1X630mm2 & KEMA –Netherland PQ Letter
Ltd 4x300 mm2 CU/XLPE/PVC-FR 1KV) & during 18th to 25th Based on S&SD letter # 15-01562-1-30504401
Saudi Arabia April 2014 & dated March 18 2015 nd S&SD letter #
KINECTRICS-Canada 16-00558-1-30504401 dated February 15 2016,
Po Box 5989 Jeddah 21432 , Saudi during 18th to 24th the manufacturer is prequalified for LV power
Arabia Aug 2014 Report cables with the following condition:
No.TIC 1018-14 for
Contact Person - Mr. Loai Taha Al-Bar, multi-core power WARRANTY:
Sale Manager cable, TIC 1019-14 Ten (10) years extended warranty/guarantee in
Phone - +966-2-591-1115 for single-core respect of defects due to design, manufacture,
Email ID - Loai.albar@bahra-cable.com power cable installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order as confirmed by the manufacturer
through their letter # (BCC/AQ/GSM/MZ dated
August 20,2011) for LV cables and letter # ( 1005
/ BH / 2016 dated 14/02/2016) for control cable.
Plant -jeddah
jeddah
2. 12 Page 63 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Gaon Cables CO., LTD. Abdulaziz M. AlSuwaiket LV Power and/or Control Cable up to Type Tests PQ letter:
SOUTH KOREA (AlSuwaiket) 630 mm² conducted in KEMA Based on S&SD letter # 18-01986-030504401
(AlSuwaiket) during 01 to 09 dated May 24, 2018 for Gaon Cables. Gunpo,
Plant -Gunpo +966-13-857-1155 March 2018 Korea is pre-qualified for Low Voltage Power &
abdulaziz@alsuwaiket.c Report no 01 14440 Control Cables as conforming to latest National
120, LS-ro 45beon-gil, Gunpo-si, om B (by SGS) Grid SA specification # 11-TMSS-10, with the
Gyeonggi-do, 15841, Republic of Korea Report no 01 14440 following conditions:
C (by SGS)
Contact Person - 1.SeongJun Kim WARRANTY:
(GAON CABLE CO., LTD.) Ten (10) years extended warranty/guarantee in
Phone - +82-2-6921-3880 respect of defects due to design, manufacture,
Email ID - kimsj1@gaoncable.com installation and workmanship from the date of
Contact Person Email ID - Provisional Acceptance Certificate (PAC) of the
kimsj1@gaoncable.com first turnkey project in case of contract award or
Website - www.gaoncable.com date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
vide letter # Nil, dated April 12, 2016.
Total = 14
2. 12 Page 64 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
CONDUCTOR, INSULATED
2. 13
SHIELDED INSTRUMENTATION CABLE Applicable Standards: 11-TMSS-11
Website -
http://www.mesccables.com/
BELDEN
United States
Website - http://www.belden.com/
2. 13 Page 65 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
TEKAB CO. LTD. Instrumentation Cables without Metallic KEMA TEST REPORT PQ letter:
United Arab Emirates Sheath # 3187-17 dated Based on S&SD letter# 18-4055-01-30504401
25.06.2018 for LV dated November 04, 2018, it is pre-qualified for
Sharjah , United Arab Emirates Instrumentation instrumentation Cables without Metallic Sheath
Cables
Website - http://www.tekab.com/ WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
ALPHA
United States
Website - http://www.alpha.com/
AT & T
United States
Website - http://www.att.com/
Total = 6
CONDUCTOR, INSULATED
2. 14
EARTHING AND BONDING CABLE Applicable Standards: 11-TMSS-12
2. 14 Page 66 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
RIYADH CABLES
Saudi Arabia
SAUDI CABLE
Saudi Arabia
Jeddah
2. 14 Page 67 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://www.ffcpg.com.my/
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
LS CABLES PREVIOUSLY LG
SOUTH KOREA
Plant -Gumi/Korea
2. 14 Page 68 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Bahra Advance Cable Manufacture Co. i. Coaxial Bonding Cable 600/1000V Type test report #TIC PQ Letter
Ltd & 1800/3000V up to 500mm2 1019-14 conducted Based on S&SD letter # 17-00912-1-30504401
Saudi Arabia ii. Single Core Bonding Cable in KEMA-Netherland. dated February 16, 2017, BAHRA ADVANCE
600/1000V & 1800/3000V up to 500 CABLE MANUFACTURE Co. Ltd –JEDDAH, KSA is
Po Box 5989 Jeddah 21432 , Saudi mm2 pre-qualified for the proposed Coaxial Bonding
Arabia iii. Earthing Cable 600/1000V & and Earthing Cable as conforming to National
1800/3000V up to 500 mm2 Grid SA specification # 11-TMSS-12 rev.0, with
Contact Person - Mr. Loai Taha Al-Bar, the following conditions:
Sale Manager
Phone - +966-2-591-1115 WARRANTY:
Email ID - Loai.albar@bahra-cable.com Ten (10) years extended warranty from the date
of PAC of the first turnkey project (in case of
contract award) or date of first delivery (in case
of direct material supply order), as confirmed,
through their letter # Nil, dated October 25, 2016
shall be applicable for all proposing Coaxial,
Bonding Earthing Cable to be supplied to
SEC/National Grid SA.
2. 14 Page 69 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
PIRELLI
GERMANY
Berlin , Germany
Website - http://
http://www.pirelli.com/splash/index.htm
l
Total = 9
CONDUCTOR FITTINGS
3. 1
LINE HARDWARE Applicable Standards: 12-TMSS-01
HUBBELL POWER SYSTEMS, INC. Previously A B CHANCE [The name has been
United States changed based on S&SD/P&SFD letter#
14-010193-30504401 dated January 06, 2015
Plant -Columbia , United States and based on Hubbell Power System Grid Letter
# Nil dated December 18, 2014]
ALCOA
United States
Website -
http://www.alcoa.com/usa/en/home.as
p
JOSLYN
United States
Website -
http://www.joslynhivoltage.com/
Website - http://www.iselfa.it/
3. 1 Page 70 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
SA RA ENERGY, CONSTRUCTION, Line Hardware up to 380kV & Tests performed at: Based on S&SD letter# 14-09052-01-30504401
TRADE AND INDUSTRY CO. INC. Twin Spacer Dampers up to 132kV Veiki-VNL Lab. dated 11th December 2014 ,TS&SD fax #
TURKEY Budapest, Hungary 09-00087-03032301 dated 11/01/2009
(Corona/RIV, Power pre-Qualified for Line Hardware up to 380kV and
Plant -Polatli (Ankara) & Adana Arc & Tensile Twin Space Damper up to 132kV with the
(Aadna), Turkey Strength with following conditions:
4-bundle ACAR &
2-bundle ACSR/AW
Conductors WARRANTY:
(Dec. 2012 & April, Ten (10) years extended warranty/guarantee in
2013) respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order
CAROBENI
ITALY
3. 1 Page 71 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
DALEKOVOD PROIZVODNJA Innovative Systems Line Hardware up to Tests performed at: PQ Letter
CROATIA (isys) 380 kV Koncar Based on TS&SD fax # 10-01179-03032301
PO Box 60606 Riyadh Croatia, EGU Czech dated April 20, 2010, this manufacturer is
Croatia, Europe, Vukomericka 9, 10410 11555,KSA Republic, pre-qualified for Line Hardware except Spacer
Velika Gorica Zagreb , Croatia/Hrvatska Phone - ZKU, KERI & Bazet Dampers with the following conditions:
+966-11-460-8161 HV
Contact Person - Mr. Davor Maljkovic, Email - kamal@isys.sa Laboratories WARRANTY:
B.Sc. M.E. Ten (10) years extended warranty/guarantee in
Phone - +385 1 62 29 900 respect of defects due to design, manufacture,
Email ID - installation & workmanship from the date of
davor.maljkovic@dalekovod.hr Provisional Acceptance Certificate (PAC) of the
Website - first turnkey project in case of contract award or
http://www.dalekovod-proizvodnja.co date of first delivery in case of direct material
m , http://www.dalekovod.hr supply order.
3. 1 Page 72 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
3. 1 Page 73 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
MOSDORFER GMBH
AUSTRIA
NUOVA ELETTROMECCANICA SUD Dopa Co. for Trading and - Line Hardware upto 380kV Some of tests PQ Letter
S.P.A, industry - Spacer Damper type (Twin) with mutually ageed Based on S&SD letter # 15-06603-030504401
ITALY Al Nuzha District Riyadh, drawing # 8.40.N2.888 Rev.05 between National dated August 13, 2015 it is pre-qualified for
Saudi Arabia P.O Box - Spacer Damper type (Quad) with Grid SA & NES were Hardware Fittings, as conforming to National Grid
Zona Industriale - 89052 Campo 87017 Code No. 11462 drawing # 8.40.N4.864 Rev.05 conducted during SA specification12-TMSS-01 with the following
Calabro (Rc) - Italy Mr. Abdullah Alabdullah plant survey visit conditions:
Deputy General Manager from 8th to 11th
Phone - +39 0965.792.111 (6 line) - Email/ June, 2015. NOTE:
Telefax +39 0965.792.222 alabullah@dopacompany Each new design of Line Hardware & Fittings
Email ID - info@nesspa.it .com which has not been tested before, shall be type
Website - http://www.nesspa.it (+966) 11 2694609 , Type tests were tested per latest revision of 12-TMSS-01.
Mobile:(+966) 50 conducted on
4449933 spacer dampers WARRANTY:
(Nut Cracker type) Ten (10) years Extended Warranty from the date
at NES Factory Italy of PAC of the first turnkey project in case of
and Demont contract award or date of first delivery in case of
Laboratory, Italy direct material supply order shall be applicable for
from 24th July to the Line Hardware to be supplied to SEC/National
28th July, 2016 with Grid SA, as confirmed through letter # Rome,
Test Report No. TR dated 14.11.2014.
SPAT 16/024, dt:
July, 2016
3. 1 Page 74 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Werkstrasse 7
6102 Malters
Schweiz
3. 1 Page 75 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
PREFORMED LINE PRODUCTS (PLP) M/s Al Abdulkarim - AGS Suspension Clamp & Spacer Type tests PQ Letter
United Kingdom Holding Co. Riyadh Damper(Twin/Quad) up to 380 kV performed during Based on S&SD letter # 15-09419-1-30504401
Riyadh KSA - Spacer Dampers type (Quad) with plant survey visit dated November 18, 2015, it is pre-qualified for
East Portway, Andover, Hampshire drawing # SDNCU 8044527V Rev. E from 08th to 11th AGS Suspension Clamp & Spacer Damper
Sp10 3Lh England September 2015 at (Twin/Quad) up to 380KV as conforming to
pip@preformed-gb.com Preformed Line National Grid SA specification # 12-TMSS-01.
Product Lab
Contact Person - Mr. Mohamed Atif and Hampshire, England WARRANTY:
Mr. Stephen (Report Ten (10) years extended warranty from the date
Email ID - alahmama@naizak.com, #TR(GB)No:3060) , of PAC of the first turnkey project in case of
ttaljaard@preformed-gb.com # TR- 3061 Rev.2) & contract award or date of first delivery in case of
alshihzm@akh.com.sa 8730/VNL. direct material supply order.
Website - http://www.preformed.com
Type tests were
conducted on
spacer dampers
(Nut Cracker type)
at PLP (GB) Ltd. ,
ANDOVER UK, from
31 Oct 2016,to 1st
Nov 2016.with test
report No. TR(GB)
No. 3314-E dated
1st Nov 2016 ,TR
(GB) No. 3312-E
dated 31 Oct 2016
and TR(GB) No.
3313-E dated 31 Oct
2016.
SICAMEX
FRANCE
Website - http://
http://www.sicame.com/HTML
FR/filiales sicamex.htm
3. 1 Page 76 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
INDUSTRIAS ARRUTI
SPAIN
Website -
http://www.grupoarruti.com/empresa.a
sp
Total = 17
CONDUCTOR FITTINGS
3. 2
COMPRESSION TYPE CONNECTORS FOR OVERHEAD TRANSMISSION LINES Applicable Standards: 12-TMSS-02
ALCOA
United States
Website -
http://www.alcoa.com/usa/en/home.as
p
Website - http://www.iselfa.it/
3. 2 Page 77 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
MOSDORFER
AUSTRIA
3. 2 Page 78 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://www.smci-fc.fr/
CAROBENI
ITALY
3. 2 Page 79 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
3. 2 Page 80 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
NUOVA ELETTROMECCANICA SUD Dopa Co. for Trading and Overhead Line Compression type PQ Letter
S.P.A, industry connectors Based on S&SD letter # 15-06603-030504401
ITALY Al Nuzha District Riyadh, dated August 13, 2015 it is pre-qualified for
Saudi Arabia P.O Box Overhead line compression type Connectors, as
Zona Industriale - 89052 Campo 87017 Code No. 11462 conforming to National Grid SA specifications #
Calabro (Rc) - Italy Mr. Abdullah Alabdullah 12-TMSS-02
Deputy General Manager
Phone - +39 0965.792.111 (6 line) - Email/ Note:
Telefax +39 0965.792.222 alabullah@dopacompany Each new design of Overhead Line Compression
Email ID - info@nesspa.it .com type Connectors which has not been tested,
Website - http://www.nesspa.it (+966) 11 2694609 shall be type tested as
,Mobile:(+966) 50 per latest revision of 12-TMSS-02.
4449933
WARRANTY:
Ten (10) years Extended Warranty from the date
of PAC of the first turnkey project in case of
contract award or date of first delivery in case of
direct material supply order shall be applicable for
the Compression type Connectors, to be supplied
to SEC/National Grid SA as confirmed through
letter # Nil dated 14.11.2014.
Werkstrasse 7
6102 Malters
Schweiz
3. 2 Page 81 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
SICAMEX
FRANCE
Website - http://
http://www.sicame.com/HTML
FR/filiales sicamex.htm
BURNDY
United States
Website -
http://portal.fciconnect.com/portal/page/
portal/FcicntPublic/BurndyWeldMenu
ELASTIMOLD
United States
Website -
http://www-public.tnb.com/ps/util/index
.cgia=elastimold
HOMAC
United States
Website - http://www.homac.com/
INDUSTRIAS ARRUTI
SPAIN
Website -
http://www.grupoarruti.com/empresa.a
sp
Total = 17
CONDUCTOR FITTINGS
3. 3
OBSTRUCTION MARKERS AND WARNING LIGHTS Applicable Standards: 12-TMSS-03
3. 3 Page 82 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Website - http://www.smci-fc.fr/
Website -
http://www.bpsarabia.com.sa/
OBSTA
FRANCE
Website - http://www.obsta.com
P&R TECHNOLOGIES
United States
Website - http://www.pr-tech.com/
Website - http://www.pfisterer.com/
Website -
http://www.tanawiremarker.com/
DERVAUX
FRANCE
Website -
http://www.dervaux-distribution.fr/
Total = 8
3. 3 Page 83 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
CONDUCTOR FITTINGS
3. 4
Splice & Termination Kits for Power Cable up to 132 KV Applicable Standards: 12-TMSS-10
3. 4 Page 84 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Taihan Electric Wire Co. 1.GIS Termination (Dry Type Plugin): PQ Letter:
Saudi Arabia Model Name : GPPS-145-L Based on S&SD letter # 18-04569-01-30504401
Drawing # : EBG-132-PPS01 dated December 11, 2018, Taihan Electric Wire
Plant -Riyadh Co. – Saudi Arabia, Riyadh is pre-qualified for
2.GIS Termination (Fluid Filled) : 132kV Cable Splice & Termination Kits as
Riyadh, Kingdom of Saudi Arabia Model Name : GMFS-145-O conforming to National Grid SA specification #
P.O. Box 519- Riyadh 11383 Size : 200-1600 mm2 12-TMSS-10, with the following condition:
Drawing # : EBG-132-S02 Rev: A
Contact Person - Mr. Seung IL, Kim Conditions:
(General Manager) 3.GIS Termination (Fluid Filled) : Fresh Type/Special tests as per SEC/National
Phone - +966 593 836 444; Model Name : GMFS-145-O Grid SA Standards/Specifications shall be
Email ID - sikim@taihan.com; Size : 1600 ~ 2500 mm² conducted on the proposed 132kV Cable Splice &
Website - www.sauditaihan.com Drawing # : EBG-132-S03 Rev: A Termination as per 12-TMSS-10 Rev.01 in an
independent testing laboratory in the presence of
4.Transformer Termination (Fluid Filled) three (3) SEC/National Grid SA Engineers & one
: (1) SEC/National Grid SA approved Independent
Model Name : OMFS-145-O Inspection Agency (IIA) Inspector. All costs of
Size : 200 ~ 1600 mm² which shall be borne by the manufacturer. This
Drawing # : EBO-132-S02 Rev. A was confirmed in writing by the manufacturer
through their letter # Nil dated Nil
5.Transformer Termination (Fluid Filled)
: Warranty:
Model Name : OMFS-145-O Ten (10) years extended warranty/guaranty
Size : 1600 ~ 2500 mm² from the date of (PAC) of the Turnkey project (In
Drawing # : EBO-132-S03 Rev. A case of contract award) and from the date of
delivery for the direct material supply order. The
6.Outdoor Termination: guarantee/warranty shall be applicable from first
Model Name : AMPS-145-66 project and shall cover all the cost of materials
Size : 200 ~ 2500 mm² and labor as per warranty/guarantee of materials
Drawing # : EBA-P132-S01 Rev. A and workmanship and subsequently reduced
yearly in case of future project award. This was
7.Insulation Joint: confirmed in writing by Taihan Electric Wire Co.,
Model Name : SMI-145-CS Riyadh, Saudi Arabia through their letter #
Size : 200 ~ 2500 mm² STL-091/17/K dated # August 28, 2017.
Drawing # : PMJ-132-IJC-CS Rev. A
3. 4 Page 85 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
PFISTERER Kontaktsysteme GmbH M/s CEPCO Civil & 132KV HV Connex Plug in Dry Type PFISTERER PQ letter:
GERMANY Electrical Projects termination size 6 (including socket) Kontaktsysteme Based on S&SD letter # 17-07474-2-30504401
Contracting Co. with drawing # 866999999A1.3 Rev GmbH-Germany dated November 01, 2017, PFISTERER
Plant -GERMANY P.O Box 8234, Jeddah .01 successfully Kontaktsysteme GmbH-Germany is pre-qualified
21482, KSA conducted type for 132KV Plug-in Dry Type GIS termination
Rosenstrasse 44 73650 Winterbach +966 26634331 tests on 132KV HV conforming to latest National Grid SA
m.yamout@cepco-sa.co Connex 6 GIS Plug in specification # 12-TMSS-10, with the following
Winterbach m Dry Type termination conditions :
(including socket) in
Contact Person - Mr. Andre Goessler, independent test WARRANTY:
Sales Manager & Mr.Stephane wope, laboratory Ten (10) years extended warranty/guarantee in
Technical Advisor (KEMA-Netherland respect of defects due to design, manufacture,
Phone - +49718170050 with report # TIC installation and workmanship from the date of
Email ID - 1072-12) in the Provisional Acceptance Certificate (PAC) of the
Andre.Goessler@pfisterer.de, presence of first turnkey project in case of contract award or
Stephane.Wope@pfisterer.com SEC/National Grid date of first delivery in case of direct material
Website - www.Pfisterer.de SA Engineers & supply order, as confirmed by the manufacturer
Third Party inspector vide letter # Nil, dated October 24, 2016.
ABB
SWITZERLAND
3. 4 Page 86 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
2. Transformer Termination :
3. Outdoor Termination:
3. 4 Page 87 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
3. 4 Page 88 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
3. Outdoor Termination:
Model Name : EHFV123
Rating: 123kV
5. GIS Termination:
Model Name : EHSDV 123/145/170
Size : 1600-2500 mm2
Drawing # : 0.360.06.0a
Rev: 0
Rating: 123kV
6. Outdoor Termination:
Model Name : EHFV 123/145/170
Size : Up to 2500 mm²
Drawing # : 0.36.72.13A
Rev: 2
Rating: 123kV
8. Transformer Termination:
Model Name : EHTV 123/145/170
Size : 185-1400 mm2
Drawing # : 0.360.85.0a
3. 4 Page 89 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Rev: 5
Rating: 123kV
DAINICHI-NIPPON CABLES
(MITSUBISHI)
JAPAN
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
DRAKA NK
FINLAND
Website - http://www.draka.com/
PIRELLI
GERMANY
Berlin , Germany
Website - http://
http://www.pirelli.com/splash/index.htm
l
3. 4 Page 90 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
3. Transformer Termination:
Model Name : SOA 1.145
Rating: 145kV
9. Transformer Termination
(Fluid-Filled):
Model Name : STY1.145
Rating: 145kV
3. 4 Page 91 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
Drawing # OTSF31005
Rating: 145kV
NKT (COLOGNE PLANT)NKT CABLES METS Riyadh 1. Outdoor Termination: Type test witnessed PQ Letter
GROUP Mr. Won Koo Kown Model Name : FEV 170-P during 03rd-7th Based on S&SD letter # 15-05202-01-30504401
GERMANY General Manager Size : Up to 2500 mm² November 2014 & 8 dated
,wkkwon@mets.com.sa Drawing # : 3. 7 5056-04 August,2014 and 14 September 15, 2015, it is pre-qualified as per
Düsseldorfer Strasse 400 Chempark nelson@mets.com.sa Rev: 1 July 2015. KEMA 12-TMSS-10.
51061 Cologne Germany Rating: 170kV Nederland
Test Report WARRANTY:
Phone - +49-0-221-6-760 2. GIS Termination: No1211-15 Ten (10) Extended Warranty/Guarantee for the
Email ID - info@nktcables.com , Model Name : SEV 170 proposed 132 kV cables accessories shall be
saud.khalid@nktcable.com Size : Up to 2500 mm² provided in respect of the defectsdue to design,
Website - http://www.nktcable.com Drawing # : 3. 7 0264-01 manufacturing, installation and workmanship from
Rev: 1 the date of Provisional Acceptance Certificate
Rating: 170kV (PAC) of the project (in case of contract award)
and from the date of delivery for the direct
3. Transformer Termination: material supply order as confirmed through the
Model Name : TEV 170 manufacturer letter # nil dated June 04, 2013.
Size : Up to 2500 mm²
Drawing # : 3. 7 0263-01
Rev: 1
Rating: 170kV
Drawing # : 3. 7 8122-01
Rating: 145kV
3. 4 Page 92 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
4. GIS Termination:
Model Name : ESG 145-V
Size : Up to 2500 mm²
Drawing # : PRO2225
Rev: 5
Rating: 145kV
5. GIS Termination:
Model Name : ESG145-V
Size : Up to 2000 mm²
Drawing # : PRO2236Rev: 6
Rating: 145kV
6. GIS Termination:
Model Name : ESG 170-V
Size : Up to 2000 mm²
Drawing # : PR02227
Rev: 5
Rating: 170kV
7. Transformer Termination:
Model Name : ESU-123-V
Size : Up to 2500 mm²
Rating: 123 kV
3. 4 Page 93 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
8. Transformer Termination:
Model Name : ESU-145-V
Size : Up to 2500 mm²
Rating: 145 kV
3. 4 Page 94 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
3. 4 Page 95 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
3. 4 Page 96 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
RAYCHEM, GERMANY / TE
CONNECTIVITY
GERMANY
Website - http://www.raychem.com/
3. 4 Page 97 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
BRUGG CABLE Mass Power Contracting 1. GIS Termination : Tests performed at:
SWITZERLAND Company KEMA, Netherlands
Building 6429, a. Model Name: TFD1.170-11 (Plugin (2006/2014)
Website - Sybawyah Street Dry Type)
http://www.bruggcables.com/index/ind Aldana District, Dammam Drawing # : S1767-4
ex.cfmsprache=en 32437-3928 Size : Up to 2500 mm²
Saudi Arabia Rating : 170 kV
+966 53 901 4014 Remarks : Shall be considered officially
s.ali@mass–group.net qualified after performing the required
type test
2. Transformer Termination :
3. 4 Page 98 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
3. Outdoor Termination:
3. 4 Page 99 of 606
SER. MATERIAL/ MANUFACTURER NAME, NAME OF AUTHORIZED LOCAL TYPE/MODEL AND RATING TYPE TESTS REMARKS/OBSERVATIONS (NGSA
EQUIPMENT PREQUALIFIED PLANT, REPRESENTATIVE DETAILS (DATE,TEST APPROVAL LETTER,EXTENDED
DESCRIPTION LOCATION,CITY/COUNTRY AND /VENDOR (IF ANY) LABORATORY, WARRANTY)
COMPLETE ADDRESS P.O.B., STREET ADDRESS, LOCATION AND
#, WEBSITE, TELEPHONE & E-MAIL NAME,TELEPHONE, REPORT NUMBER)
ETC. AND NAME OF AUTHORIZED
6. Transition Joint:
DAITWEILER
United Kingdom
Website - http://www.duttweiler.de/
Website - http://www.ffcpg.com.my/
4. GIS Termination:
Model Name : CVC-GWO-110-BD
Size : Up to 2500 mm²
Rev: A
Rating: 123kV
5. GIS Termination:
Model Name : CVC-GWO-132-BD
Rating: 145kV
6. Outdoor Termination:
Model Name : AMP-145
Rating: 145kV
7. Outdoor Termination:
Model Name : CVC-APS-1322000A-BD
Rating: 145kV
8. Outdoor Termination:
Model Name : CVC-APS-1322410A-BD
Size : Up to 2500 mm²
Rev: A
Rating: 145kV
Rating: 145kV
Total = 20
CONDUCTOR FITTINGS
3. 5
Splice & Termination Kits for Power Cable up to 230 KV Applicable Standards: 12-TMSS-10
ABB AG
GERMANY
Website - http://
http://www.suedkabel.de/index e.htm
BRUGG CONDITION:
SWITZERLAND All type/design and routine/sample tests shall be
conducted at SEC approved independent
Contact Person - Mr. Pierre Londorf laboratory in presence of representative of 3rd
Phone - +41-56-460-3637 party inspection agency & three engineers of
Email ID - londorf.pierre@brugg.com SEC for first contract.
Website - http://www.brugg.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order.
DAINICHI-NIPPON CABLES
(MITSUBISHI)
JAPAN
FUJIKURA
JAPAN
Website - http://www.ffcpg.com.my/
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
Berlin , Germany
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire 230 kV Tests performed at: WARRANTY:
SOUTH KOREA Co.,Ltd. Branch KEMA Ten (10) years extended warranty/guarantee in
P. O. box 300201,Riyadh Netherlands respect of defects due to design, manufacture,
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais installation & workmanship from the date of
Of Korea Building, 6th Floor Office Provisional Acceptance Certificate (PAC) of the
No. 613 - Taihan Electric first turnkey project in case of contract award or
180, Simin-Daero, Dongan-Gu, Wire Co.,Ltd. Branch date of first delivery in case of direct material
Anyangsi, Gyeonggi-Do, Korea Korea, Phone - 966) 114190227 supply order.
Republic Of Email -
jsnam@taihan.com
Contact Person - Mr. JAI-HO SHIM
Phone - +82) 2 316 9378
Email ID - jhshim@taihan.com
Website - http://
http://www.taihan.com/eng1/customer/
s 015.asp
Total = 10
CONDUCTOR FITTINGS
3. 6
Splice & Termination Kits for Power Cable up to 380 KV Applicable Standards: 12-TMSS-10
Website - http://
http://www.suedkabel.de/index e.htm
BRUGG CONDITION:
SWITZERLAND All type/design and routine/sample tests shall be
conducted at SEC approved independent
5201 Brugg Switzerland,28 Ch5201 laboratory in presence of representative of 3rd
Brugg Switzerland, party inspection agency & three engineers of
SEC for first contract.
Contact Person - Mr. Pierre Londorf
Phone - +41-56-460-3637 WARRANTY:
Email ID - londorf.pierre@brugg.com Ten (10) years warranty in respect of defects
Website - http://www.brugg.com/ extended warranty/guarantee in respect of
defects due to design, manufacture, installation &
workmanship from the date of Provisional
Acceptance Certificate (PAC) of the first turnkey
project in case of contract award or date of first
delivery in case of direct material supply order.
DAINICHI-NIPPON CABLES
(MITSUBISHI)
JAPAN
VISCAS FUJIKURA
JAPAN
Website - http://
http://www.viscas.com/e contact.html
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
PIRELLI
GERMANY
Berlin , Germany
Website - http://
http://www.pirelli.com/splash/index.htm
l
LS CABLES & SYSTEMS LTD. 380 kV cable Tests performed at PREVIOUSLY LG;
SOUTH KOREA 1. Outdoor Termination KEMA
1x2500 mm2, CU/XLPE/LEAD/PE Netherlands (Aug, PQ Letter
Contact Person - Mr. H.S.JO (General a. Model Name: UEMA40Q004, 2014 to Based on S&SD letter # 15-3193-30504401 dated
Manager) Mr. Young Min Seo b. Model Name: UMEMA40Q004 from Dec, 2014) May 03, 2015, the manufacturer is prequalified to
Email ID - symsky@iscns.com PPC insulators (Germany). Test Report Nos. supply the Power Cables & Accessories with the
Website - http://www.lscable.com/ ? 1066-14 & TIC specified designations only:
2. Transformer Termination 1564-14
a. Model Name: WC-114022 with WARRANTY:
Drawing # WC-114022 rev. 00 Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
3. GIS Termination (Dry Type) installation & workmanship from the date of
a. Model Name: UEPG40Q001 with Provisional Acceptance Certificate (PAC) of the
Drawing # UEPG40Q001 rev. 00 first turnkey project in case of contract award or
date of first delivery in case of direct material
4. Cross Bonding Joint supply order.
a. Model Name: UEMK40Q002 with
Drawing # UEMK40Q002 rev. 00
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire 380 kV Tests performed at: PQ Letter
SOUTH KOREA Co.,Ltd. Branch 1x2500mm2 KEMA Based on S&SD letter # 14-08139-01-30504401
P. O. box 300201,Riyadh Netherlands (Jan. dt: January 07, 2015, the manufacturer is
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais 1. Outdoor Termination 2014 to prequalified to supply power cables &
Of Korea Building, 6th Floor Office a. Model Name: May, 2014) accessories with the specified designations only:
No. 613 - Taihan Electric CVC-APS-3804605N-BD rev. A Report # TIC
180, Simin-Daero, Dongan-Gu, Wire Co.,Ltd. Branch 3094-14 WARRANTY:
Anyangsi, Gyeonggi-Do, Korea Korea, Phone - 966) 114190227 2. GIS termination (Fluid-Filled ) Ten (10) years extended warranty in respect of
Republic Of Email - a. Model Name: CVC-GWO-380-BD rev. the defects due to design, manufacturing,
jsnam@taihan.com A installation and workmanship from the date of the
Contact Person - Mr. JAI-HO SHIM Provisional Acceptance Certificate (PAC) of the
Phone - +82) 2 316 9378 3. GIS termination (Dry Type) first turnkey project (in case of contract award)
Email ID - jhshim@taihan.com a. Model Name: CVC-GWBS-380-BD or from the date of first delivery in case of direct
Website - http:// rev. A material supply order shall be provided as
http://www.taihan.com/eng1/customer/ confirmed by the manufacturer through their
s 015.asp 4. Transformer Termination letter # Nil dated September 02, 2014.
a. Model Name: CVC-OWO-380-BD
with Drawing # WD-433884 rev. 01
Total = 11
CONDUCTOR FITTINGS
3. 7
LINK BOXES FOR GROUNDING OF U/G POWER CABLE Applicable Standards: 12-TMSS-11
AARTCO UP TO 230KV.
Saudi Arabia
Website - http://www.aartco.com.sa/
AL SHAHRANI EST.
Saudi Arabia
Website - http://www.alshahranig.com
EM ELEKTRIK MALZERMELERI Gulf Trade Link Est. Type tests were PQ Letter
YUKLENIM SAN.TIC. A.S. PO Box 20362 Riyadh conducted in KEMA Based on S&SD letter # 15-07259-2-30504401 dt:
TURKEY 11455 Netherland in Sept17, 2015, the manufacturer is prequalified to
Mr. Ahmed Qazi presence of supply Link box, Up to 132kV with Stainless Steel
(Itosb)No:25 34959 Tepeören-Tuzla Commercial Manager SEC/National Grid Material as conforming to National Grid SA
Istanbul / Turkey ahmed@gradelink.com SA Engineers during specification # 12-TMSS-11
1st to 5th June
Phone - +90 216 593 37 15 & 2015.This Test was WARRANTY:
19(Pbx),Fax: +90 216 593 37 21 repeated on this link Ten (10) years extended warranty in respect of
Email ID - info@emelec.com.str box during 30th the defects due to design, manufacturing,
June and 1st July installation and workmanship from the date of the
2015 in DNV-GL . Provisional Acceptance Certificate (PAC) of the
Type Test Report No. project (in case of contract award) and from the
1206-15 VI, 1207-15 date of delivery in case of direct material supply
VI, 1208-15 VI, order shall be provided as confirmed by the
1209-15 VI manufacturer through their extended warranty
letter attached with the letter #EM-011-/031 dated
January 25, 2012.
STEINER
GERMANY
Website -
http://www.steiner-binoculars.com/ind
ex.html
LS CABLES PREVIOUSLY LG
SOUTH KOREA
Plant -Gumi/Korea
DEMIRER KABLO
TURKEY
Website - ?http://
http://www.masskablo.com/about us
co?mpany.asp?md=
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
PIRELLI
GERMANY
Berlin , Germany
Website - http://
http://www.pirelli.com/splash/index.htm
l
Website - http://www.ffcpg.com.my/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
Total = 13
INSULATORS
4. 1
INSULATORS, STATION POST TYPE, PORCELAIN, INDOOR/OUTDOOR, 69 KV THROUGH 380 Applicable Standards: 15-TMSS-01
KV
LAPP INSULATORS REDWITZ GMBH
GERMANY
Website - http://www.lappusa.com/
Website - http://www.wsi.com/
Rating: 380kV
Models: 7.035478, 7.035471
Total = 6
INSULATORS
4. 2
INSULATORS, PORCELAIN SUSPENSION TYPE UP TO 380kV Applicable Standards: 15-TMSS-02
NGK INSULATORS LTD Mitsubishi Corporation Porcelain Fog type Disc Insulator Tests performed:
JAPAN 5h Floor tower A4, Models: May 25-June 01,
Granada Business park 132 kV 111KN 2011, March 01-13,
Plant -Aichi Japan, Exit 9 CA-825MW 2007, and March
Phone - CA-825EZ, 20-22, 2007
Contact Person - Mr. H. Nakane & Mr. Y +966-11-511-7516
Ogawa Email: hashim.a.ibrahim@ 132 kV 160KN Report # 110023T,
Email ID - n111ex@ngk.co.jp & mitsubishicorp.com CA-839MX 110024T,
ogawa@ngk.co.jp CA-839EX,
Website - http://www.ngk.com/ 070011T, 070012T,
380 kV 160 KN 120025T,
CA833MZ
CA833EX, 080027T, 080030T,
080031T
380 kV 210 KN
CA845MY 110021T, 110022T,
CA-845 EZ,
380 kV,160 KN
CA-635MZ
CA-635EZ
CA-635EW
380 kV,210 KN
CA640MY, CA640EY
Total = 1
INSULATORS
4. 3
INSULATORS, GLASS, SUSPENSION TYPE TYPE UP TO 380kV Applicable Standards: 15-TMSS-02
VERESCENCE La Graja SL Innovative Systems Toughened Glass (Aero form/Fog) Tests performed at: PQ Letter
SPAIN (isys) 120kN, 160KN, and 210kN EGU & ZKU labs Based on S&SD letter# 13-07206-01-30504401
PO Box 60606 riyadh Models: (Czech republic). dated November 09, 2013, it is pre-qualified for
Sgd La Granja Vidrieria, S. L. Paseo Del 11555 KSA E-120DZ-146 (March 4-15, 2013) Glass insulators with the following condition:
Pocillo S/N 40100 B Granja De San Phone - E-160GDZ-146
Ildefonso (Segovia) Spain Segovia , +966-11-460-8161 E-210GDZ-170 Report # 9886/A/13, WARRANTY:
Spain Email - kamal@isys.sa E-120PPZ-146 9886/B/12, Ten (10) years extended warranty/guarantee in
E-160PZ-156 9886/D/13, and respect of defects due to design, manufacture,
Contact Person - Mr. Elias Py Rodriguez E-210PZ-170 13/044 installation & workmanship from the date of
Phone - +(+34) 917707516 E-120DZ-127 Provisional Acceptance Certificate (PAC) of the
Email ID - insulators@sgdgroup. corn first turnkey project in case of contract award or
Website - date of first delivery in case of direct material
http://www.sgdinsulators.com supply order, as confirmed by the manufacturer
thru letter #nil, dt: Nov 08, 2012.
Total = 2
INSULATORS
4. 4
INSULATORS, PORCELAIN HORIZONTAL LINE POST TYPE Applicable Standards: 15-TMSS-03
Total = 3
INSULATORS
4. 5
INSULATORS, PORCELAIN, LONG ROD TYPE UP TO 380 kV Applicable Standards: 15-TMSS-04
Zapel SA Innovative Systems 132kV Long Rod Porcelain Insulators Type test performed PQ Letter:
Poland (ISys) 160KN at KEMA Laboratory Based on S&SD letter # 17-04625-01-030504401
P.O.Box 60606, Riyadh Dwg. # 032Z-15 & 033Z-15 Prague dated June 07,2017, Zapel SA Poland is
Plant -Poland 11555 120KN Report# 5024-17 & pre-qualified for 132kV Long Rod Porcelain
Dwg. # 158Z-15 & 159Z-15 5025-17 dated Insulators as conforming to National Grid SA
Zapel SA Techniczna 1 36-40, local Contact Person: 10-03-17 specification # 15-TMSS-04, with the following
Boguchwala, Poland Mr. Kamal Al Muhanna Drawing # 032Z-15 conditions:
Mobil# +966 -505491067 & 033Z-15
Contact Person - Mr. Wojciech Sztaba +966 (11) 4608160, +966 WARRANTY:
Phone - +48178720100 (11) 4608161 Type test performed • Ten (10) years extended warranty from the
Email ID - zapel@zapel.com.pl kamal@isys.sa at EGU HV date of PAC of the first turnkey project (in case
Contact Person Email ID - laboratory Praha of contract award) or date of first delivery (in
Wojciech.Sztaba@zapel.com.pl dated 10.03.2017 case of direct material supply order), as
Website - confirmed, through their Letter No. NIL dated
http://www.zapel.com.pl/en/products/i Report #10573/A/17 30/05/2016 shall be applicable for the equipment
nsulators/ Report #10573/B/17 to be supplied to SEC/National Grid SA.
Report #10573/C/17
Report #10573/D/17
Report #10576/A/17
Report #10576/B/17
Drawing #
032Z-15
033Z-15
159Z-15
158Z-15
032Z-15
033Z-15
132kV, 120 KN
CA45501A
CA45503A
CA45514A
CA45516A
CA45502A
CA45504A
CA45515A
CA45517A
LAPP INSULATORS GMBH • Rating : 160kN Tests performed at: Based on S&SD letter # 18-01028-30504401
GERMANY Material / Drawing Numbers: dated February 27, 2018, Type/Model Rating for
7.012395.00.07.00 / 101.708.00.05; EGU HV LAPP Insulators Germany is updated.
Plant -Bahnhofstrasse 5, 95632 7.012397.00.07.00 / 101.710.00.05; (2009/2010/2011/20
Wunsiedel Germany 7.012724.00.07.00 / 101.740.00.05; 13)
7.012700.01.07.00 / 101.713.01.05; Report #
Contact Person - Mr. i.A. Thomas 7.012725.00.07.00 / 101.741.00.05 01/09, 02/09, 46/13,
Zembsch 41/13, 75a/09,
Phone - +49 (0) 92 32 / 50 15 5 • Rating : 210kN 9763/11, 40/13,
Email ID - Material / Drawing Numbers: 42/11, 21/10,
tzembsch@lappinsulators.com 7.012396.00.07.00 / 101.709.00.05 10129/A/14 dated
Website - July, 2014,
http://www.lappinsulators.com • Rating : 330kN 10614/A/17
Material / Drawing Numbers: (18-02-17),
7.012719.01.07.00 / 101.735.01.05; 10702/B/17
7.012398.00.07.00 / 101.711.00.05; (13-07-17)
7.012716.01.07.00 / 101.731.01.05;
7.012754.01.07.00 / 101.771.01.05 Type tests
performed in
Lapp Germany lab.
(2009-2013)
Lapp Test Report
Nos.01/09, 02/09,
46/13,41/13,
75a/09, 9763/11,
40/13,42/11, 21/10,
40/13, 15/17
(24-01-17),
KEMA DNV-GL:
5275-18 (26-10-18)
Total = 5
INSULATORS
4. 6
INSULATORS, COMPOSITE, HORIZONTAL LINE POST, SUSPENSION AND TENSION TYPE (UP Applicable Standards: 15-TMSS-05
TO 230 KV)
LAPP INSULATORS GMBH MODULAR DESIGN Type tests Prequalified for MODULAR TYPE DESIGN
GERMANY 115 kV 120/160 kN conducted at LAPP insulators
Germany lab
Plant -Bahnhofstrasse 5, 95632 Model:
Wunsiedel Germany 14K3349 & 50 Test Report No.
28/13 & 29/13
Contact Person - Mr. i.A. Thomas 230 kV
Zembsch 120/160 kN
Phone - +49 (0) 92 32 / 50 15 5
Email ID - Model:
tzembsch@lappinsulators.com 7.09538 & 39
Website -
http://www.lappinsulators.com
E.B. REBOSIO S.R.L MOLDED DESIGN Prequalified for MOLDED TYPE DESIGN insulators
ITALY up to 132 kV
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order.
-------------
PQ Letter
Based on S&SD letter# 18-03367-02-30504401
dated October 29, 2018 M/s E.B. Rebosio S.r.l,
Italy (previously prequalified up to 132kV) is
prequalified for Composite Suspension and
Tension Insulators up to 230kV as conforming to
National Grid Saudi Arabia Material Specification
15-TMSS-05, Rev.02 with the following condition:
Type Test:
The first project of 230kV Composite Insulators,
per 15-TMSS-05, to be supplied to SEC/National
Grid SA shall be type, special and routine tested
in presence of three (3) SEC/National Grid SA
and one (1) SEC/National Grid SA approved IIA
Inspector as confirmed through Manufacturer
Letter # Nil dated September 13, 2018. All cost of
which shall be borne by E.B. Rebosio S.r.l, Italy.
Warranty
Ten (10) years extended warranty from the date
of PAC of the turnkey project for 230kV in case
of contract award or date of delivery in case of
direct material supply order, as confirmed by the
manufacturer through letter # Nil dated
September 04, 2018.
FCI (FURUKAWA COMPOSITE LSR DESIGN Prequalified for LSR TYPE DESIGN insulators
INSULATORS LTD)
HUNGARY
Budapest , Hungary
Website - http://www.fcifurukawa.hu
MACLEAN POWER SYSTEM MODULAR DESIGN Prequalified for MODULAR TYPE DESIGN
United States insulators
NGK LOCKE INC. Mitsubishi Corporation MOLDED DESIGN Tests performed: Prequalified for MOLDED TYPE DESIGN insulators
United States 5h Floor tower A4, 111 kN,160 kN (2011 & 2012)
Granada Business park Report # 120014T
Virginia Beach, Va, Usa Exit 9
Phone -
Contact Person - Mr. H. Enomoto +966-11-511-7516
Email ID - enomoto@ngk-polymer.com Email -
Website - http://www.ngk-locke.com/ hashim.a.ibrahim@mitsu
bishicorp.com
PFISTERER SEFAG AG MOLDED DESIGN Tests performed: Prequalified for MOLDED TYPE DESIGN insulators
SWITZERLAND (2013)
120 kN/160 kN (110 kV) PQ Letter
Plant -Malters, Switzerland Based on TS&SD letter# 10-02374-03032301
Drawing #: dated August 18, 2010It is pre-qualified for
Werkstrasse 7, 6102 Malters, 138206-393A Composite Suspension & Tension insulators up to
Switzerland 138206-667A 380 kV, Composite Line Post insulators up to 132
kV with the following conditions:
Email ID - info.uk@pfisterer.com
Website - http://www.sefag.ch WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order
XIANGYANG GUOWANG COMPOSITE Molded Design Prequalifed for MOLDED TYPE DESIGN insulators
INSULATORS CO. up to 132 kV only.
CHINA
WARRANTY:
Plant -Xiangyang city, China. Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
No.10, Dengman Road, High & New installation & workmanship from the date of
Tech Park, Industry District, Xiangyang, Provisional Acceptance Certificate (PAC) of the
Hubei 441057, P.R China first turnkey project in case of contract award or
date of first delivery in case of direct material
Contact Person - Mr. Wang Xin supply order shall be given for the proposed 132
Phone - Tel: 0086-710-3262531,Fax: kV composite insulators
0086-710-3250621
The warranty/ guarantee shall be applicable from
first project and shall cover all the cost of
materials and labor as per warranty / guarantee
of materials and subsequently reduced yearly in
case of future project award. This was agreed
through the manufacturer letter # GCR-06-02
dated 2015-07-08.
Note:
Previously “XIANGFAN GUOWANG”, the name
has been changed to “Xiangyang Guowang
Composite Insulators Co. Ltd.” based on the
manufacturer letter # RI/PQ/
XYGW/TT132/2015/008 dt: August 09, 2015 and
the supporting documents approved by the
concerned authorities in China.
Total = 7
INSULATORS
4. 7
INSULATORS, COMPOSITE, HORIZONTAL LINE POST, SUSPENSION AND TENSION TYPE (UP Applicable Standards: 15-TMSS-05
TO 380 KV)
LAPP INSULATORS GMBH MODULAR DESIGN Prequalified for modular type design insulators
GERMANY Rating: Tests Performed: CONDITION:
160 kN-380 kV Type tests Any new type of Insulators (other than the types
Plant -Bahnhofstrasse 5, 95632 conducted at LAPP already tested) offered by Lapp, Germany shall
Wunsiedel Germany Model – Germany lab, EGU & be Type Tested in presence of three (3) SEC
Rodurflex CS160SB30/79 ZKU Engineers and one (1) Approved Independent
Contact Person - Mr. i.A. Thomas (195/163)4900 Agency Inspector.
Zembsch 7.095670.80.01.00/ Lapp Germany Test
Phone - +49 (0) 92 32 / 50 15 5 7.095670.80.22.00 Report No. 29/13, dt: WARRANTY:
Email ID - 09/04/2013 Ten (10) years extended warranty/guarantee in
tzembsch@lappinsulators.com respect of defects due to design, manufacture,
Website - EGU Test Report installation & workmanship from the date of
http://www.lappinsulators.com No.9898/A/13 from Provisional Acceptance Certificate (PAC) of the
03/04/2013 to first turnkey project in case of contract award or
08/04/2013. date of first delivery in case of direct material
supply order
ZKU Test Report No.
13-059, dated:
05/04/2013
Type Test:
The first project of 380kV Composite Insulators,
per 15-TMSS-05, to be supplied to SEC/National
Grid SA shall be type, special and routine tested
in presence of three (3) SEC/National Grid SA
and one (1) SEC/National Grid SA approved IIA
Inspector as confirmed through Manufacturer
Letter # Nil dated September 13, 2018. All cost of
which shall be borne by E.B. Rebosio S.r.l, Italy
Warranty
Ten (10) years extended warranty/guarantee
from the date of (PAC) of the Turnkey project (In
case of contract award) and from the date of
delivery for the direct material supply order. The
guarantee/warranty shall be applicable from first
project and shall cover all the cost of materials
and labor as per warranty/guarantee of materials
and workmanship and subsequently reduced
yearly in case of future project award. This was
confirmed in writing by E.B.REBOSIO S.r.L, Italy
through their letter # nil dated # September 04,
2018.
MACLEAN POWER SYSTEM Yousif Al Hobays Office MODULAR DESIGN Type tests Prequalified for MODULAR TYPE DESIGN
United States for Trading Service conducted at EGU, insulators
PO Box 301134 Riyadh Model: ZKU,Klokar &
Plant -7801 Park Place Road 11372 Saudi Arabia Cat./Drawing S678192 VG03 KFUPM WARRANTY:
Email:yhobayb@gmail.co Ten (10) years extended warranty/guarantee in
York, South Carolina m EGU Test Report respect of defects due to design, manufacture,
29745, USA No.9447/08 dt: installation & workmanship from the date of
18/11/2008. Provisional Acceptance Certificate (PAC) of the
Contact Person - Mr. Ms. Anabel first turnkey project in case of contract award or
Gdriozola EGU Test Report date of first delivery in case of direct material
Contact Person Email ID - No.9449/08 dt: supply order, as confirmed by the manufacturer
addriozola@macleanfogg.com 16-17/12/2008 through their letter no.RI/MCLN/SEC/AS, dt: 5th
Website - http:// April, 2007.
http://www.macleanpower.com/ ZKU Test Report No.
08-109, dt:
21/10/2008)
NGK LOCKE INC. Mitsubishi Corporation MOLDED DESIGN Tests performed: Prequlified for MOLDED TYPE DESIGN insulators
United States 5h Floor tower A4, July 01-05, 2008,
Granada Business park 380 kV,178 kN July 25-27, 2011 and PQ Letter
Virginia Beach, Va, Usa Exit 9 April 20-27, 2005 Based on TS&SD letter #
Phone - 402-SL1370-SK-95 10-F02356/02-03032301 dated 22/11/2010, it is
Contact Person - Mr. H. Enomoto +966-11-511-7516 Report # pre-qualified for 380 kV Composite Insulators:
Email ID - enomoto@ngk-polymer.com Email:hashim.a.ibrahim@ 380 kV,222 kN 080022T (For 380
Website - http://www.ngk-locke.com/ mitsubishicorp.com Models: kV, 178 kN WARRANTY:
Insulators) Ten (10) years extended warranty/guarantee in
50B-SL1370-SK-95 110036T & 050028T respect of defects due to design, manufacture,
50B-SL1370-SK-59 (For 380kV, 222kN installation & workmanship from the date of PAC
502-SL1770-SK-95 Insulators) of the turnkey project in case of contract award
502-SE1570-SK-15 or date of delivery in case of direct material
230 kV,160 kN 120014T, supply order.
36B-SS1140-SK-08 PO3031T,
230 kV,111 kN 030058T,
251-SL970-3J-09 TN-NCI-98143
TN-NCI-2000009 R1
132 kV, 160 kN
36B-SS620-SK-0A
132 kV 111 kN
25A-SL540-SJ-0A
115 kV,160 kN
36B-SL510-SK-0A
115 kV,111 kN
25A-SL440-SJ-0A
PFISTERER SEFAG AG Tests performed Prequlified for MOLDED TYPE DESIGN insulators
SWITZERLAND
MOLDED DESIGN PQ Letter
Plant -Malters, Switzerland Based on TS&SD letter# 10-02374-03032301
160 kN-380 kV dated August 18, 2010It is pre-qualified for
Werkstrasse 7, 6102 Malters, Composite Suspension & Tension insulators up to
Switzerland Drawing #: 380 kV, Composite Line Post insulators up to 132
138206-588BC kV with the following conditions:
Email ID - info.uk@pfisterer.com
Website - http://www.sefag.ch 160kN (380kV) WARRANTY:
Ten (10) years extended warranty/guarantee in
Drawing #: respect of defects due to design, manufacture,
138206-588BC installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order.
Total = 5
INSULATORS
4. 8
RTV SILICON RUBBER INSULATOR COATING Applicable Standards: 15-TMSS-07
Total = 2
AL-SALAM INSDUTRIES AND TRADING Only one trial 110/132kV transmission line project
EST./ADVANCE TECHNOLOGIES. only (short line)
Saudi Arabia
AL BABTAIN POWER&TELECOM CO
Saudi Arabia
AL ZAMIL STEEL
Saudi Arabia
WARRANTY
Ten (10) years Extended Guarantee / Warranty
from the date of PAC of first Project (in case of
contract award) or from the date of delivery for
the direct material supply order,as confirmed
through their Letter # Nil dated 04/01/2015.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
through their letter no. AS/2009/0704/001, dt: 7th
April, 2009..
Email ID - aic@aicsteel.com.
Website - http://www.aicsteel.com/
ENERGYA STEEL SOLUTION (HESHAM latticed steel Based on S&SD letter # 15-10909-02-30504401
HELAL EL SEWEDY & PARTNERS FOR structures up to 380 kV dated February 10, 2016 , TS&SD letter#
STEEL INDUSTRIES CO.) 09-2179/07-03032301 dated November 11, 2009,
Saudi Arabia approval of Executive Directive for TS&SD letter#
09-02179/06-03032301 dated November 11, 2009
Rabigh – Yanbu High Way Exit 927 & based on S&SD letter# 13-01978/01-30504401
Industrial Zone Aramco Road dated June 10, 2013, it is pre-qualified for
Contact Person - Mr. Ahmed Khan , Mr. - Substation Steel Structures up to 380 kV
Rayan A. Taj
Phone - +966-5609678655 Tel: +966 - Transmission Towers for projects up to 380
500150706 ,Fax: +966 500576159 kV(Except design)
Email ID - info@energyasteel.com
Contact Person Email ID - and
ahmed.khan@energyaksa.com, - Communication Towers for Transmission
Rayan.Taj@energyasteel.com Sector
,Rayan.Taj@energyaKSA.com
with the following condition:
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order
This was confirmed, through their Letter # nil
dated October 14, 2014.
GEYARD FOR COMMERCE AND IMPORT Prequalified for Substation Steel Structures only
CO.
Saudi Arabia
HIDADA
Saudi Arabia
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order.
Chennai , India
Website -
http://www.larsentoubro.com/
Total = 16
AL BABTAIN POWER&TELECOM CO
Saudi Arabia
HIDADA
Saudi Arabia
PETIT JEAN
FRANCE
Website - http://www.petitjean.fr/uk/ec
gm.php
SUMMIT MANUFACTURING
United States
Pa , United States
Website - http://www.summitmc.com/
TECHNOPALI
ITALY
Website - http://www.technopali.co.uk
VALMONT
United States
Website - http://www.valmont.com/
Total = 7
Website -
http://www.amiantit.com/en/default.php
Total = 2
POWER AND TELECOMMUNICATION Cable Clamps for Power Cables up to CPRI ( Central PQ Letter:
EQUIPMENTS FACTORY (P.T.E. CO.) 380 kV Power Research Based on S&SD letter # 18-04057-01-30504401
(CEPCO) Institute ) Report # dated November 11, 2018, Power Transmission
Saudi Arabia CPRIBLRHPL1819T0 and Telecommunication Equipment Factory Co. -
104 dated 16.7.2018 (P.T.E. ..Co.), Jeddah, Saudi Arabia is
Jeddah Industrial City : P.O Box 8234 and Report # pre-qualified for Cable Clamps up to 380kV as
Jeddah 21482 CPRIBLRMEDMISC18 conforming to National Grid SA specification #
19T0014 dated 23-TMSS-04, with the following condition:
Contact Person - Eng. Mohammad 13.7.2018 for Flat
Saleem Mir (General Manager) Clamps Warranty:
Phone - Tel: +966 1260 95165: Cell Ph: Ten (10) years extended warranty/guaranty
+966 595 3323 74 CPRI ( Central from the date of (PAC) of the Turnkey project (In
Email ID - sales-pte@cepco-sa.com; Power Research case of contract award) and from the date of
azmat@cepco-sa.com; Institute ) Report # delivery for the direct material supply order. The
sales@pte-sa.com; CPRIBLRHPL1819T0 guarantee/warranty shall be applicable from first
inquiry@pte-sa.com 107 dated 16.7.2018 project and shall cover all the cost of materials
Website - www.pte-sa.com and Report # and labor as per warranty/guarantee of materials
CPRIBLRMEDMISC18 and workmanship and subsequently reduced
19T0014c dated yearly in case of future project award. This was
13.7.2018 for Trefoil confirmed in writing by Power Transmission and
Clamps Telecommunication Equipment Factory Co. -
(P.T.E. ..Co.), Jeddah, Saudi Arabia through their
SGS Inspection letter # PTE/PQ/Clamps/2016/L-097R1 dated #
Report # August 13, 2018.
BRD/GHV/34/2018
Total = 1
Email ID - aic@aicsteel.com.
Website - http://www.aicsteel.com/
3M
United States
Website - http://solutions.3m.com/en
US/
AB WIRE
SWEDEN
Website - http://www.moorlink.com/
ABAHSAIN-COPE
Saudi Arabia
Website -
http://www.abahsain.net/Abcope.htm
AL-AMAL CO. Type / Model: FOR LADDERS & Type Tests FOR LADDERS & ACCESSORIES
Saudi Arabia ACCESSORIES conducted in King
Saud University on WARRANTY:
Riyadh, Saudi Arabia 14th July, 2008 Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order as confirmed by the manufacturer
vide their letter no. IMD-CR-955, dt: October 29th,
2007.
AL-MISBAH HOUSE FOR STEEL Type / Model: Metallic Cable Tray PQ Letter
WORKS Systems Based on TS&SD letter 09-00509/1-03032301
Saudi Arabia dated 16th. March 2009 for Metallic Cable Tray
Rating: Systems.
Riyadh , Saudi Arabia
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
EFCOR
United States
WARRANTY:
Eight (8) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order as confirmed by the manufacturer
through their letter no.nil, dt: 2nd Aug, 2008.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
thru letter #nil, dt: 2nd Dec, 2012.
HIDADA
Saudi Arabia
Website - http://www.hidada.com.sa/
Website -
http://mecss.com.sa/contact.html
O-Z GEDNEY
United States
Website - http://www.o-zgedney.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
thru letter #NIL, DT: 15th Jan, 2013.
TOLARTOIS
FRANCE
Website -
http://www.tole-perforee.com
WESCOSA
Saudi Arabia
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by Al-Ashouri
Industries through letter # 2010/4-03/0003 dated
01/08/2010.
Ba’amer Electric Factory Galvanized Carbon Steel Cable Trays Type Test PQ letter:
Saudi Arabia and Ladders Report/Inspection Based on S&SD letter # 18-01054/01-030504401
Certificate # dated April 24, 2018, for Ba`Amer Electric
Plant -Jeddah, 2nd Industrial City R/013/SA/RYD/18 Factory Jeddah, KSA is pre-qualified for Cable
dated 10.2.2018 Support Systems (Cable Trays, Cable Ladders,
P.O. Box 30066 Jeddah 21477 conducted at Cable Trunking, Strut Metal Framing Etc.) as
Al-Hoty Calibration conforming to latest National Grid SA
Jeddah Services Khobar specification # 24-TMSS-01, Rev.01 with the
KSA following conditions:
Contact Person - Engr. Mohammad
Al-Shareef WARRANTY:
Phone - 012 6610 260 - 012 608 1999 Ten (10) years extended warranty/guarantee in
Email ID - sales2@baamerelectric.com respect of defects due to design, manufacture,
Contact Person Email ID - installation and workmanship from the date of
mohammad@baamerelectric.com Provisional Acceptance Certificate (PAC) of the
Website - www.baamerelectric.com first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
vide letter # Nil, dated April 05, 2018.
Total = 20
S&C
United States
Website - http://www.sandc.com/
ALPHA NIDAU
SWITZERLAND
CONDITION:
All type/special and routine tests for Disconnect
Switches 420kV, 4000A (S3CD, S3CDT &
S3CD2T) only and Standalone Grounding
Switches (STB) 420kV, 63kA only shall be
conducted at in an Independent testing laboratory
on one switch before supplied to SEC system in
the presence of three (3) SEC/National Grid SA
engineers & one (1) National Grid SA approved
independent inspection agency Inspector, all the
related costs for witnessing the tests will be
borne by the manufacturer. This was confirmed
by Alstom Grid S. p .A, ITALY through their letter
# 323/11/C/RP.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
thru letter #136/11/CO/RP.
EFACEC
PORTUGAL
Website - http://www.hapam.nl/
MG/EGIC
FRANCE
SIEMENS
GERMANY
Website - http://
http://www.siemens.de/Pages/EntryPa
geRedirect.aspx
Website -
http://www.southernstates.com/
AREVA
FRANCE
Plant -France
Website - http://www.areva.com/
ABB ( T& D)
United States
Website - http://www.abb.us/
Total = 12
SUBSTATION PANELS
9. 1
RELAY & CONTROL PANEL Applicable Standards: 31-TMSS-01
Ingenious Network FZC Power Flow Contracting NGSA-RCP-16001-B / Up to 132KV Ingenious Network PQ Letter
United Arab Emirates Siteen Street, Al-Malaz, FZC- Sharjah, UAE Based on S&SD letter # 17-00160-1-30504401
Dsitrict P.O Box 325917, successfully dated January 19, 2017, Ingenious Network FZC-
Plant -Saif Free Zone, Sharjah, UAE Riyadh-11371, KSA completed type Sharjah, UAE is pre-qualified for Relay & Control
+966 11 4734876 Panels up to 132kV as conforming to National
Q3-047 Sharjah Airport International Rami.azzam@powerflo Grid SA specification # 31-TMSS-01, with the
Free Zone (SAIF Zone) Al Dhaid Road, w-sa.com following conditions:
P.O Box 120110, Sharjah, United Arab
Emirates WARRANTY:
Ten (10) years extended warranty from the date
Sharjah of PAC of the first project (in case of contract
award) or date of first delivery (in case of direct
Contact Person - Mr. Tabish M. Ismail, material supply order), as confirmed, through
Sales & Marketing their Letter No. PQN-SEC-15001-RCP-6A dated
Phone - +971 6 5579471 June 6,2015 shall be applicable for all Relay &
Email ID - Control Panels to be supplied to SEC/National Grid
ahmed.bader@ingenious-network.com SA.
Contact Person Email ID -
tabish.i@ingenious-network.com
Website -
www.ingenious-network.com
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
AREVA
United Kingdom
Website - http://www.areva.com/
ABB S.R.O (RFF) ABB Automation Co. Ltd. Type tested in PQ Lettter
CZECH REPUBLIC PO Box.414 Riyadh Independent Lab Based on S&SD letter# 15-09012-1-30504401
11383 EZU Parague, Czech dated November 05, 2015, it is pre-qualified for
Stetkova 1638/18,140 00 Praha 4Czech republic/EVPU Nova Relay & Control Panels as conforming to National
Republic-Trutnov Dubnica, Slovakia on Grid SA specification # 31-TMSS-01, with the
5th to 15th may following condition:
Contact Person - Mr. Essam 2015
Bashraheel & Mr Aref Al-Arrak Report#08.220.985. WARRANTY
Email ID - Ten (10) year Extended Warranty as confirmed
Essam.bashraheel@sa.abb.com through
&Aref.alarrak@sa.abb.com their Letter No. 14-05231-01-30504401 dated
November 10,
2014 shall be applicable for all supplies by ABB
s.r.o (RFF), Trutnov-Czech Republic.
Website -
http://www.kerrcruickshank.com/
KONCAR ELEKTRICNI UREDAJI D.D Nesma Telecom& Rating - upto 380 kv PQ Lettter
CROATIA Technology Co. Ltd. Based on S&SD letter# 14-1456-03-30504401
Jeddah Asfan Road dated April 15, 2014, it is pre-qualified for Relay &
Plant -Zagreb/Croatia - Hrvatska inside azzam compound Control Panel up to 380 kV as conforming to
Tel:012-2727637,Phone - National Grid SA specification # 31-TMSS-01,
Končar-Električni Uređaji D.D. Prisoje 0500000582 with the following condition:
29A, 21232, Dicmo, Hr Email - WARRANTY
nesmaelectric@nesma.c Ten (10) years extended warranty/guarantee in
Contact Person - Mr. Ljubomir Zubčić, om respect of defects due to design, manufacture,
Phone - +385 21 778 512; +385 91 374 installation & workmanship from the date of
2009 Provisional Acceptance Certificate (PAC) of the
Email ID - Email first turnkey project in case of contract award or
:ljubomir.zubcic@koncareu.hr date of first delivery in case of direct material
Website - Web: supply order.
http://www.koncareu.hr
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
thru letter #META/12/AM, dt: Mar 23, 2011.
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer through
their letter no.nil, dt: 18th July, 2008.
REYROLLE LTD.
United Kingdom
Website -
http://www.reyrolle-protection.com/
Grenoble France
TIEPCO
Saudi Arabia
ABB SWITZERLAND LTD ABB Automation Co. Ltd. Type tested in PQ Lettter
SWITZERLAND PO Box.414 Riyadh Independent Lab Based on S&SD letter# 15-09013-1-30504401
11383 EZU Parague, Czech dated November 05, 2015, it is pre-qualified for
Contact Person - Mr. Essam Republic /EVPU Relay & Control Panels, as conforming to National
Bashraheel & Mr Aref Al-Arrak Nova Dubnica, Grid SA specification # 31-TMSS-01 with the
Email ID - Aref.alarrak@sa.abb.com, Slovakia on 5th to following condition:
Essam.bashraheel@sa.abb.com 15th may 2015
WARRANTY
Report#08.220.986. Ten (10) years Extended Warranty as confirmed
through
their Letter #14-05230-01-30504401 NIL dated
4th November 2014 shall be applicable for all
supplies made by ABB Switzerland Ltd -
Switzerland.
ACRASTYLE
United Kingdom
Website - http://www.acrastyle.co.uk/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
thru letter #NIL, DT: 03/10/2013.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
thru letter #nil, dt: 16th june, 2010.
Total = 29
SUBSTATION PANELS
9. 2
AUXILIARY AC/DC PANELS Applicable Standards: 31-TMSS-02
Website - http://www.alojaimi.com/Our
Companies/Introduction - Mohammed
Al-Oja/introduction - mohammed
al-oja.html
Website -
http://www.atco.com.sa/en/manufactu
ring east west factory.asp
Website - http://www.hawaepbf.com
CONDITION:
All type, special, routine and sample tests as per
SEC specifications/standards shall be carried out
on the first batch of each type of Auxiliary
AC&DC Panels to be supplied to SEC in case of
securing an order in the presence of three (3)
SEC engineers & one (1) approved independent
inspection agency Inspector in an independent
testing laboratory. All the related costs for
witnessing the tests will be borne by the
manufacturer. This was confirmed by
WESCOSA-Dammam through letter # Nil dated
18/05/2010.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by
WESCOSA-Dammam through letter # Nil dated
30/08/2010.
META SWITCHGEAR COMPANY Rating: The tests have been Previously MEMF-ETA Switchgear Manufacturing
Saudi Arabia ACDB 230/400 Vac, upto 3200 A, 75 conducted at CPRI, Company, Riyadh, Saudi Arabia [The name has
kA, 1 sec. India, witnessed by been changed based on S&SD letter #
P. O. Box 61891, Riyadh 11575, Saudi UL & SGS Engineers 14-02218-01-30504401 dated March 23, 2014].
Arabia,Near 2Nd New Industrial, 2Nd DCDB 800 A, 25 kA, 1sec. and certificates and
Phase Riyadh 11575, Saudi Arabia test reports are PQ Letter:
(Branch Of Memf Electrical Industries issued by UL. SGS S&SD letter # 14-02218-01-30504401 dated
Co.) inspection report March 23, 2014 & TS&SD letter
CHN/VCS/014/2014 #11-F03210/01-03032301 dated 29/11/2011
dated 24/01/2014 pre-qualified for AC&DC Panels.
for ACDB & DCDB
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by MEMF-ETA
Switchgear Manufacturing Company through
letter # META/11/13/AM, dated 21st Feb, 2011.
MUSAID SWITCHGEAR,
Saudi Arabia
REMAL
Saudi Arabia
Website - http://www.remal.com/
SIEMENS
Saudi Arabia
Plant -Jeddah
Website - http://www.siemens.com.sa
Total = 13
SUBSTATION PANELS
9. 3
TERMINAL BLOCKS Applicable Standards: 31-TMSS-06
Cabur PQ Letter:
ITALY • Based on S&SD letter # 17-0071-030504401
dated January 09,2017, Cabur, Altare- Italy is
Plant -Altare- Italy pre-qualified for Terminal Blocks as conforming to
National Grid SA specification # 31-TMSS-06,
Contact Person - JAL International, Mr. with the following conditions:
Muhammad Sajjad Manzoor
Contact Person Email ID - WARRANTY:
sajjad.manzoor@jalinternational.com.sa • Ten (10) years extended warranty in respect of
the defects due to design, manufacturing,
installation and workmanship from the date of the
Provisional Acceptance Certificate (PAC) of the
first project (in case of contract award) and from
the date of first delivery in case of direct material
supply order shall be provided as confirmed by
the manufacturer through their letter No. NIL
dated 18/12/2015.
Website -
http://www.abb.com/cawp/seitp202/c1
256c290031524bc1256a2900291e39.a
spx
PHOENIX
GERMANY
Website -
http://www.phoenixcontact.com/termin
al-blocks/26840.htm
WEIDMULLER
GERMANY
Website - http://www.weidmuller.com/
Total = 8
SWITCHGEAR
10. 1
METAL – ENCLOSED AIR INSULATED SWITCHGEAR 11 KV THROUGH 34.5 KV Applicable Standards: 32-TMSS-01
TYPE/MODEL: NES-H
FORCED COOLED
Rating:
13.8kV, 4000A @ 40°C, 60Hz,
Incomer (1000×2793x1880mm),
VCB-LVB-17M-40D/301E2H,
Interrupter-10403
Incomer (CT upper & lower side of CB): Circuit breaker up to 24kV, 4000A, 40kA from
(1000x2200/2595x1400/1780mm), ABB-SACE-Italy (ITABB).
Bus Section
(1000x2200/2595x1400mm) &,
Bus riser (800x2200/2595x1400mm):
3003 @ 40°C, 60Hz, 25kA (3s)/65kAp.
1600A SWGR:
1600A Incomer
(800x2200/2595x1400mm) ; Bus
Section (800x2200/2595x1400mm, Bus
Riser (650x2200/2595x1400mm: 1607A
@ 40°C, 60Hz, 25kA(3s)/65kAp
CIRCUIT BREAKERS:
Incomer, Bus Section: VD4 17.31-25
(vacuum interrupter VG6), ABB Italy
(embedded pole)
FORCED COOLED
Rating:
TYPE/MODEL:
UniGear ZS1 13.8kV SWGR with CT
upper & lower side of CB.
Incomer (1000×2595x1780mm),
VCB-VD4 1731-25,Vacuum
Interrupter-VG6
OLD VERSION:
Rating: 13.8kV
SIEMENS
United States
Website -
http://www.usa.siemens.com/entry/en/
VA TECH
FRANCE
Plant -France
Website - http://www.vatech-hydro.at
WESCOSA
Saudi Arabia
Plant -Germany
Website -
http://www.alibaba.com/member/smilja
nmusic/contactinfo.html
Website - http://www.areva.com/
CIRCUIT BREAKERS:
Incomer, Bus Section: VD4 17.31-25
(vacuum interrupter VG6), ABB Italy
(embedded pole)
EARTHING SWITCH:
UMR, ELEKTROBUDOWA SA, Poland
LSIS METS Middle East Solution Power V17 & CB type LVB17 Type test were PQ Letter:
KOREA, Republic of Technical Services 13.8 kV successfully S&SD letter# 15-03781-2-30504401 dated June
Contact Person:Mr. conducted in KERI 04, 2015,for for MV Switchgear Type “ Solution
Plant -Republic Of Cheongju, Korea Abdul Majeed Atiyyah Incomer, Bus Section and Bus Riser Korea during 16th Power V17” & CB type “ LVB17” rated for 13.8
Vice President & Mr. ratings June to 17th July kV.
Ls Tower, 127 Ls-Ro Dongan-Gu Won Koo Kwon General (W-950xD-2000xH-2620 mm); 3000A 2014 in Presence of
Anyang-Si Syeonnggi-Do 431-848 Manager , P.O. Box: @ 40°C, 60Hz, 25kAp Approved IIA WARRANTY:
Korea 4323 Riyadh - 11491 (3s) / 65kAp, natural cooled. Inspector. Ten (10) years extended warranty/guarantee will
Kingdom of Saudi Arabia. Type Test Report be applicable for all 13.8 kV Medium Voltage
Contact Person - Mr Je Woo Lee Power Tel: +966 1 2424923,Fax: Outgoing feeder & Capacitor feeder #2014TC00634 Switchgear type Solution Power V17 to be
Grid Business Group & +966 1 2424924 (630 A / 1250A) - supplied to SEC/National Grid SA as confirmed
Mr.Kui-Joong,Yun General Manager PQ wkkwon@mets.com.sa , (W-750xD-2000xH-2620 mm); 1250A through LSIS Letter #013/LSIS-PQ/2015 dated
Dept Powr Grid Business Group aatiyyah@mets.com.sa @ 40°C, 60 Hz, 25kA 26th May 2015.
Phone - +82-2-2034-4541 , (3s) / 65kAp, natural cooled.
82-2-2034-4918 • Circuit Breaker:
Email ID - jwleea@lsis.com Incomer & Bus section: LSIS, Korea –
,kjoongy@lsis.com Type
(LVB-17M-40D/30-1E2H, Interrupter:
LV10403, Opr. Mech:
Motor-spring, LVB Pro-MEC)
Outgoing feeder: LSIS, Korea-Type
(LVB-17M-25D/12-1E2H,
Interrupter: LV10252, Opr. Mech:
Motor-spring, LVB Pro-MEC)
Capacitor feeder: LSIS, Korea-Type
(LVB-17M-25D/12-1E2H-DB,
Interrupter: LV12503, Opr. Mech:
Motor-spring, LVB Pro-MEC), Capacitor
Bank back to back
switching current-630A.
• Earthing switch Type SEH/MH31SM &
SEH/MH31M.
• CT: ABB, Czech (CT located in upper
& lower side of CB for
I/C, O/G, B/S).
• VT: ABB, Czech
KONCAR ELECTRICAL EQUIPMENT 33kV SWGR LIMITED TO DTA ONLY; FOR CTA
(KONCAR), SPLIT Type / Model: BVK-s-38 PREQUALIFICATION UNDER PROGRESS
CROATIA
Rating: 33kV,
Plant -Split/Croatia – Hrvatska
CIRCUIT BREAKER:
Koncar Elektricni Uredaji D.D Prisoje
29A, 21232 Dicmo Hr CT & VT:
Rating:
CIRCUIT BREAKER
S&C
United States
Website - http://www.sandc.com/
OLD VERSION:
Type / Model: F400G
CIRCUIT BREAKER
SF1 & SF2
13.8kV SWGR:
Rating:
13.8kV, 2500A @ 55°C, 60Hz,
CIRCUIT BREAKERS:
2500 (3150A) Incomer, Bus Section:
LF3 -3150@ 40°C, 60Hz) Interrupter
SF6
FORCED COOLED
Rating:
13.8kV, 3600A @ 40°C, 60Hz,
25kA(3s)/65kAp, IP4X, FORCED
COOLED, CT lower side of CB.
Website -
http://www.toshiba.co.jp/index j3.htm
HITACHI LTD 33kV SWGR: Originally JAPAN AE POWER SYSTEM CORP and
JAPAN subsequent change affected as per HITACHI
Type/Model: letter # XAE-VR-121213, dated 13-12-2012 and
Plant -Tokyo, Japan FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
Rating:
Akihabara Daibiru Building, 18-13,
Soto-Kanda 1-Chome, Chiyoda-Ku, 13.8kV
Tokyo, 101-8608, Japan
Type/Model:
Contact Person - Mr. Masaharu Tsumori
Phone - +81-3-4564-4741
Email ID -
masaharu.tsumori.gx@hitachi.com
Website - http://www.hitachi.com
EFACEC ENERGIA MAQUINAS E Bandariyah International 33kV Switchgear: 33kV SWGR: PQ letter:
EQUIPAMENTOS ELECTRICOS, S.A Co. Ltd, SWGR type: QBN7 & CB type DIVAC KEMA- Dielectric Based on S&SD letter # 17-07121/02-030504101
PORTUGAL CONTACT PERSON:Raid Incomer, Bus Section and Bus Riser tests, temperature dated October 24, 2017 EFACEC Portugal is
Shabsough or Rejith Rating; 2500A @ 40°C, 60Hz, rise test, Short time pre-qualified for 13.8kV Switchgear Type
Plant -Porto/Portugal Rami , 3rd Floor Building 25kAp(3s) / 65kAp, natural cooled - and Peak withstand NORMACEL & CB type DIVAC as conforming to
3 Mutlaq complex, P.O. Dimension (W-1300xD-2768xH-2858 current test, CB latest National Grid SA specification #
Parque Empresarial Da Arroteia 4296, Al Khobar-31952, mm). making & breaking 32-TMSS-01.
(Poente), Apartado 1018 4468-952 S. KSA Outgoing feeder (630 & 1250A) & test, Capacitor bank
Mameda De Infesta- Portugal Phone: 966-555010864 Capacitor feeder (1250A) @ 40°C, 60 switching current, PQ letter:
& Phone: Hz, 25kA(3s) / 65kAp- natural cooled. ES SC making Based on S&SD letter # 17-07122/02-030504101
Contact Person - Mr. Abílio Rodrigues: : 966-553712308 Dimension (W-1000xD-2768xH-2858 performance dated October 10, 2017, EFACEC Portugal is
+351 968331386;+351 229562300, Mr. rshabsough@bandariya mm) CESI: Temperature pre-qualified for 33KV Switchgear Type QBN7 &
Filipe Vila Real: +351 939236215; +351 h.com Or rise test, Arcing due CB type DIVAC as conforming to latest National
229562300 rrami@bandariyah.com Circuit Breaker: to internal fault, Grid SA specification # 32-TMSS-01
Email ID - Metal Clad Switchgears: : Incomer & Bus section: 2500A @ 40°C, EFACEC: Mechanical
abiliorodrigues@efacec.com; 60Hz, 25kAp(3s) / 65kAp, EFACEC, endurance test of
en@efacec.com & Power Portugal –Type CB DIVAC 3625G, CB & ES.
Transformers: Interrupter-(VG6), Opr. Mech: Spring
:filipe.vilareal@efacec.com; charged - CDV2M 13.8kV SWGR:
en@efacec.com Outgoing feeder: 630A @ 40°C, 60Hz, KEMA- Dielectric
Website - 25kAp(3s) / 65kAp; EFACEC, Portugal – tests, temperature
http://www.efacec.pt/en/switchgear/ Type CB DIVAC 3625B, Interrupter- rise test, Short time
& (VG6), Opr. Mech: Spring charged - and Peak withstand
http://www.efacec.pt/en/transformers/ CDV2M current test, CB
Outgoing feeder: 1250A @ 40°C, 60Hz, making & breaking
25kAp(3s) / 65kAp; EFACEC, Portugal – test, Capacitor bank
Type CB DIVAC 3625D, Interrupter- switching current,
(VG6), Opr. Mech: Spring charged - ES SC making
CDV2M performance
Capacitor feeder: 1250A@ 40°C, 60Hz, CESI: Temperature
25kAp(3s) / 65kAp; EFACEC, Portugal – rise test, Arcing due
Type CB DIVAC 3625D-K, Interrupter- to internal fault,
(VG6-K), Opr. Mech: Spring charged - EFACEC: Mechanical
CDV2M, Capacitor switching current: endurance test of
500A CB & ES.
Earthing switch: EFACEC, Portugal –
Type Qbn7, 25kA (3s)/65kAp.
CT: ALCE Turkey or ABB Czech
Republic lower side of CB of O/G & I/C,
Upper side CB for B/S & B/R .
VT: ALCE Turkey or ABB Czech
Republic
13.8kV Switchgear:
SWGR type: Normacel & CB type
DIVAC
Incomer, Bus Section and Bus Riser
Rating; 3150A @ 40°C, 60Hz,
25kAp(3s) / 65kAp, natural cooled &
3600A/ 4000A @ 40°C, 60Hz,
25kAp(3s) / 65kAp with forced
cooling- Dimensions; Incomer
(W-1000xD-1566xH-2619 mm), Bus
tie (W-1000xD-1666xH-2619 mm) &
Bus riser
(W-1000xD-1566/1666xH-2619 mm).
Outgoing feeder (630 & 1250A) &
Capacitor feeder (1250A) @ 40°C, 60
Hz, 25kA(3s) / 65kAp- natural cooled.
Dimension (W- 750xD-1566xH-2619
mm)
Circuit Breaker:
Incomer & Bus section: 3150@ 40°C,
60Hz, 25kAp(3s) / 65kAp, EFACEC,
Portugal –Type CB DIVAC 1725H,
Interrupter-(VG7), Opr. Mech: Spring
charged - CDV2M
Outgoing feeder: 630A @ 40°C, 60Hz,
25kAp(3s) / 65kAp; EFACEC, Portugal –
Type CB DIVAC 1725B , Interrupter-
(VG4-S), Opr. Mech: Spring charged –
CDV1M
Outgoing feeder: 1250A @ 40°C, 60Hz,
25kAp(3s) / 65kAp; EFACEC, Portugal –
Type CB DIVAC 1725D, Interrupter-
(VG4-S), Opr. Mech: Spring charged –
CDV1M
Capacitor feeder: 1250A@ 40°C, 60Hz,
25kAp(3s) / 65kAp; EFACEC, Portugal –
Type CB DIVAC 1725D-K, Interrupter-
(VG6), Opr. Mech: Spring charged -
CDV2M, Capacitor switching current:
630 A
SIEMENS Siemens Ltd. 13.8 kV AIS: Type/Model: NXAIR, Type Tests PQ letter:
TURKEY P.O. Box 4621, Jeddah 3600A conducted at IPH Based on S&SD letter # 17-04571-02-30504401
21412, K.SA. CESI-Berlin and dated June 22, 2017, SIEMENS -Turkey is
Plant -Turkey 02 661 8972 For Incomer: KEMA & PEHLA pre-qualified for 13.8KV Switchgear Type NXAIR
Aslam.jameel@siemens. 13.8kV, 3008A, @40 °C, 60Hz, as conforming to latest National Grid SA
Gebze Organize Sanayi Bolgesi, 1000. com 25kA(3s)/65kAp, AFLR with Natural specification # 32-TMSS-01, with the following
Cd. No. 1004, 41480-Gebze, Kocaeli, cooling, Dimensions (2500H X 1000W X conditions:
Turkey 2250D), CT Upper & Lower of CB
13.8kV, 3600A @40 °C, 60Hz, 25kA Warranty :
Gebze, Kocaeli (3s)/65kAp, AFLR with Forced cooling • Ten (10) years extended warranty/guarantee in
(4-fans), Dimensions (2500H X 1000W respect of defects due to design, manufacture,
Contact Person - Mr. Ediz Gizlier X 2250D), CT Upper & Lower of CB installation & workmanship from the date of
Phone - +90 (262) 676 2000 Circuit Breaker: 3AE1666-7, 13.8kV, Provisional Acceptance Certificate (PAC) of the
Email ID - ediz.gizlier@siemens.com 3150A, @40 °C, 60Hz , 25kA first turnkey project in case of contract award or
Contact Person Email ID - (3s)/65kAp, Vacuum Interrupter: date of delivery in case of direct material supply
ediz.gizlier@siemens.com VS17040, Opr. Mechanism: SION order, as confirmed in writing by the
Website - www.siemens.com.tr 3AE1666 manufacturer through their letter #
Earthing Switch: Siemens, Turkey, AEL-E/PQ/NXAIR/02/2013 dated July 25, 2014.
Type: 174-3138.3
CT & VT: ALCE, Turkey/Pfiffner, Turkey
For Bus Section:13.8kV, 3008A, @40 °
C, 60Hz, 25kA(3s)/65kAp, AFLR with
Natural cooling, Dimensions (2500H X
1000W X 2250D), CT Upper & Lower
of CB
13.8kV, 3600A @40 °C, 60Hz, 25kA
(3s)/65kAp, AFLR with Forced cooling
(4-fans), Dimensions (2500H X 1000W
X 2250D), CT Upper & Lower of CB
Circuit Breaker: 3AE1666-7, 13.8kV,
3150A, @40 °C, 60Hz , 25kA
(3s)/65kAp, Vacuum Interrupter:
VS17040, Opr. Mechanism: SION
3AE1666
CT & VT: ALCE, Turkey/Pfiffner, Turkey
For Bus Riser:
13.8kV, 3008A, @40 °C, 60Hz,
25kA(3s)/65kAp, AFLR with Natural
cooling, Dimensions (2300H X 1000W X
1750D)
13.8kV, 3600A @40 °C, 60Hz, 25kA
(3s)/65kAp, AFLR with Natural
ABB ( T& D)
United States
Website - http://www.abb.us/
Total = 21
SWITCHGEAR
10. 2
SF6 GAS INSULATED SWITCHGEAR 110kV to 132kV Applicable Standards: 32-TMSS-02
Hitachi Power Systems Indonesia Walid Jufalli Corporation GIS: CFTA-145, 145kV, 3150A @40 ºC, 145kV GIS Type PQ letter:
(HPSI) (WJCO) 60HZ, 40kA (1s)/104kAp. CFTA with CB, Based on S&SD letter # 17-03689-03-30504401
Indonesia P.O Box#1380, Jeddah DS/ES & cable dated May 18, 2017, it is pre-qualified for 145kV
21493, Kingdom of Saudi Circuit Breaker: compartment has GIS Type CFTA with CB CFPTB-40LB, FAR3 as
Plant -Indonesia Arabia. CFPTB-120-40LB-FAR3, 145kV, 3150A successfully conforming to National Grid SA with specification
Mr. Yuichi Wakabayashi, @40 ºC, 60HZ, 40kA (1s)/104kAp with completed the type # 32-TMSS-02 with the following conditions:
EJIP Industrial Park Plot 8E, Cikarang +966 (12) 2637600 & spring charge operating mechanism tests in laboratories;
Selatan, Bekasi, 17750 Indonesia +966 500338276 type: “FA”. KERI – Korea during WARRANTY:
yuichi.wakabayashi@hit 25 July to 10 August •Ten (10) years extended Guarantee/warranty
Contact Person - Mr. Hendrawan, achi-td.com Busbar DS: CFL-EEA, 145kV, 3150A 2016 & Hitachi from the date of PAC of the project (in case of
Phone - Phone: +62-21-8970350, @40 ºC, 60HZ, 40kA (1s)/104kAp with Laboratory- Japan contract award) or date of delivery (in case of
Mobile: +62 815 11536388 operating mechanism type “CA”. during 14 November direct material supply order), as confirmed to
Email ID - to 17 December SEC/National Grid SA, through their Letter No #
hendrawan@hitachipowersystems.co.i Line DS: CFL-EEA, 145kV, 3150A @40 2016 HPSI-BD/02/VIII/2014 R3 dated March 22, 2017.
d& ºC, 60HZ, 40kA (1s)/104kAp with
yoshikazu.hirotani@hitachipowersyste operating mechanism type “CA”.
ms.co.id
Contact Person Email ID - Mr. MS: CFL-EEA, 145kV, 60HZ, 40kA
Hendrawan, (1s)/104kAp with operating mechanism
Website - type “CA”.
http://www.hitachi.com/products/powe
r/TandD/location/index.html HSES: CFGM-FA, 145kV, 60HZ, 40kA
(1s)/104kAp with operating mechanism
type “MSG” Spring charged.
ABB AG NEW VERSION (TYPE ELK-04C ) NEW VERSION NEW VERSION (TYPE ELK-04C )
GERMANY Equipment designations & Ratings: (TYPE ELK-04C ) PQ letter:
a) GIS: ELK-04C, 145kV, 3150A @40 ABB, AG Germany Based on S&SD letter # 18-01225-2-30504401
Mannheim, Germany , Brown Boveri ºC, 60HZ, 40kA (3s)/108kAp. has successfully dated April 01, 2018, for ABB, AG Germany is
Street 30, 63457 Hannau, Germany completed type tests pre-qualified for 145 kV GIS Type ELK-04C as
b) Circuit Breaker: SD04 on 145kV GIS Type conforming to latest National Grid SA
Contact Person - Mr. Josef Hanson (2GHV010550M0001), 145kV, 3150A ELK-04C at specification # 32-TMSS-02, with the following
Email ID - josef.hanson@de.abb.com @40 ºC, 60HZ, 40kA (3s)/108kAp with Independent testing condition:
Website - http:// spring charge operating mechanism laboratories KEMA –
http://www.abb.de/cawp/deabb200/ea type: “MSD1 ((2GHV003600)” Netherland & PEHLA WARRANTY:
b4f33d72c264bec1256fb90037eeaa.as CB Capability: Inductive: YES, – Switzerland Ten (10) years extended warranty from the date
px Capacitor Bank: NO of PAC of the project (in case of contract award)
or date of delivery (in case of direct material
c) Busbar DS: TX04 supply order), as confirmed to SEC/National Grid
(2GHV010550M0001), 145kV, 3150A SA, through their Letter No #
@40 ºC, 60HZ, 40kA (3s)/108kAp with PGHV-180115/GIS-1, dated March 02, 2018.
operating mechanism type “DHS
(1HC0070676)”.
OLD VERSION (TYPE ELK-04 )
d) Line DS: TX04 PQ Letter: TS&SD letter # 11-00455-5-03032301
(2GHV010550M0001), 145kV, 3150A dated April 04, 2011, for new version 145kV GIS
@40 ºC, 60HZ, 40kA (3s)/108kAp with type ELK-04.
operating mechanism type “DHS
(1HC0070676)”. WARRANTY
Ten (10) years extended warranty/guarantee in
e) Maintenance ES: EM04 respect of defects due to design, manufacture,
(2GHV002340), 145kV, 60HZ, 40kA installation & workmanship from the date of
(3s)/108kAp with operating mechanism Provisional Acceptance Certificate (PAC) of the
type “DHS (1HC0070676)”. first turnkey project in case of contract award or
date of first delivery in case of direct material
f) High Speed Earthing Switch: EB04 supply order , as confirmed by the manufacturer
(2GHV006000), 145kV, 60HZ, 40kA through letter no. PTPH/GVS-Nb, 10, dt: 14th May
(3s)/108kAp with operating mechanism 2010.
type “EB04/2GHV006000)” Spring
charged. OLD VERSION
PQ Letter: DM # 011/63000/KB/168, dated
g) CT: CN04 (2GHV010550M0001) 18-08-1422 (H) prequalified GIS type ELK-04
CB Capability:
Inductive load switching: YES
Capacitor bank back to back Switching:
YES
DS type: ELK-DE0-3POS,
OLD VERSION:
Type/ Model: ELK-04
HYOSUNG HEAVY INDUSTRIES 145 kV GIS Type test was LATEST VERSION:
CORPORATION (HICO) LATEST VERSION conducted at Based on S&SD letter # 15-07077-01-30504401
SOUTH KOREA Type HSG-144D independent testing dated September 07, 2015, it is pre-qualified for
40kA, 2500A/ 3150 A labs like CESI- 145kV GIS Type
Plant -Republic of Changwon, Korea Italy,KERI – Korea, HSG-144D, 40 kA, 2500A/3150A
CB type HCSP-144D/ MELCO-Japan,
Eric Rhie, 450, Gongdeok-Dong, Opr. Mechanism HMSP-500 (spring HYOSUNG For latest WARRANTY
Mapo-Gu, Seoul , Korea charged); version Ten (10) years Extended Guarantee / Warranty
Tel:82-707-6180 from the date of PAC of the Project (in case of
CB Capability for: contract award) or from the date of delivery for
Contact Person - Mr. Eric Rhie Sale Inductive current switching: YES the direct material supply order. This is applicable
Manager & Mr. Joey W. J Kyung Capacitor bank back to back switching: from first project and subsequently reduced
Marketing Manager YES yearly in case of future project. This was
Email ID - inseock@hyosung.com confirmed, through their Letter No.SB/TDS/AK/
Contact Person Email ID - Busbar DS type 120 930/2100A dated 01/04/2013.
inseock@hyosung.com , MDMO-144D/ Opr. Mech: HM3P-710;
tsing@hyosung.com Line DS type
Website - MDMO-144C / Opr. Mech. HM3P-710;
http://www.hyosung.co.kr/eng/index.js MES type MEMO-144C
p?, www.hyosung.com / Opr. Mech. HM3P-710; HES type
MEMS-144C / Opr. Mech.
HMMS-500 (Spring charged), Cable
compartment
type-HSG-144D
KONCAR HIGH VOLTAGE 145kV GIS GIS & ADAPTORS ONLY TO DTA.
SWITCHGEAR INC, Type/ Model: K8D.6
CROATIA PQ Letter: As per existing
Rating: 132kV
Plant -Zagreb/Croatia-Hrvatska
CB Capability:
Borongajska Cesta 81C 10000 Zagreb Inductive load switching: NO
Capacitor bank back to back Switching:
Contact Person - Mr. Toni Delić NO
Phone - +385 (0)99 2475 663, +385
(0)1 235 4606
Email ID - toni.delic@koncar-eva.hr
Website - http://www.koncareu.hr
CT: JK
NEW VERSION
Type/Model: 8DN8-II
Rating: 145kV
CB Capability:
Inductive load switching: NO
Capacitor bank back to back Switching:
NO
Rating: 145kV
CB Capability:
Inductive load switching: NO
Capacitor bank back to back Switching:
NO
DS type: 8DN8
ES type: 8DN8
FUJI ELECTRIC CO. 145kV GIS Originally JAPAN AE POWER SYSTEM CORP and
JAPAN subsequent change affected as per HITACHI
OLD VERSION letter # XAE-VR-121213, dated 13-12-2012 and
Type/ Model: SDA5 (SDA514), 145kV FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
CB Capability:
Inductive load switching: NO
Capacitor bank back to back Switching:
NO
• Old version:
145kV GIS type HEXABOLIC-TH7
CB type
DTH7 Hydraulic mechanism
ES type ST TH7.
DS type 8DN8
ES type 8DN8.
TOSHIBA CORPORATION, T&D 145kV GIS Type Tested at ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN Toshiba lab during DURING APRIL 2005.
NEW VERSION 25th March to 12th 2005.
Website - April 204 & 18th to
http://www.toshiba.co.jp/index j3.htm GIS Type 20th Aug 2014 and NEW VERSION
G3A-b with CB type GSPK-145FPW / repeated internal arc
Opr. Mechanism tests in KEMA PQ Lettter
GSPK-145FW (spring charged); Netherland during Based on S&SD letter # 15-09018-2-30504401
CB Capability for: 8th to 10th April dated November 10, 2015, it is pre-qualified for
Inductive current switching: YES 2015 & 10th to 12th 145kV GIS Type
Capacitor bank back to back switching: June 2015. G3A-b, as conforming to National Grid SA
YES Report Nos. specification # 32-TMSS-02,
2238-15,30-07,29-0
Busbar DS type DAM-145W2 / 7,27-07, WARRANTY
Opr. Mech: DAM; Line DS type Ten (10) years Extended Guarantee / Warranty
DBM-145W2 / Opr. Mech. DBM; from the date of PAC of first Project (in case of
MES type EBM-145W2 / Opr. Mech. contract award) or from the date of first delivery
EBM; for the direct material supply order. This was
HES type confirmed, through their Letter No. TSB/TDS/AK/
EAP-145W2 / Opr. Mech. EAP (Spring 120930/2100A dated 01/04/2013.
charged)
OLD VERSION
Type/ Model:
Rating: 145kV
CB type: GSPK-145AP
CB Capability:
Inductive load switching: NO
Capacitor bank back to back Switching:
NO
HITACHI LTD 145kV GIS Originally JAPAN AE POWER SYSTEM CORP and
JAPAN NEW VERSION: subsequent change affected as per HITACHI
Type/ Model: CFTA letter # XAE-VR-121213, dated 13-12-2012 and
Plant -Tokyo, Japan FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
Rating: 145kV,
Akihabara Daibiru Building, 18-13, NEW VERSION:
Soto-Kanda 1-Chome, Chiyoda-Ku, CB type: CFPT-120-40L, FAR3 Motor PQ Letter:
Tokyo, 101-8608, Japan spring mechanism MD # 011/63000/KB/169, dated 18-08-1422 (H),
pre-qualified GIS type CFTA.
Contact Person - Mr. Masaharu Tsumori CB Capability:
Phone - +81-3-4564-4741 Inductive load switching: NO
Email ID - Capacitor bank back to back Switching:
masaharu.tsumori.gx@hitachi.com NO
Website - http://www.hitachi.com
DS type: CFL-120
ES type: CFL-120
OLD VERSION
Type/ Model: CFT
Rating: 145kV
DS type: SFL-EA
Hyundai Electric & Energy Systems Co. 145kV GIS 145kV GIS 145kV GIS
Ltd LATEST VERSION LATEST VERSION LATEST VERSION
SOUTH KOREA Type/Model: 145SP-3 Type/Model: Type/Model: 145SP-3
145SP-3
Plant -Ulsan Rating: 145kV, 2000A/3150A@40 ºC, PQ letter:
60HZ, 40kA (3s)/104kAp. Type Test performed Based on S&SD letter MPQ #11424110 dated
1000, Bangeojinsunhwan-doro, in KERI, Korea # October 01, 2018, Hyundai Electric & Energy
Dong-gu, Ulsan, South Korea, CB type: 145SP-K3, 145kV, 2018TC00434 Systems Co. Ltd., Korea is pre-qualified for 145
2000A/3150A@40 ºC, 60HZ, 40kA (2018), kV GIS type 145SP-3 as conforming to latest
Ulsan (3s)/104kAp, Operating mechanism: 2018TC00439 National Grid SA specification # 32-TMSS-02,
145M-MSCB(Spring charged) . (2018), with the following conditions:
Contact Person - Mr. Young Jun Bae CB Capability: Inductive load switching: 2018TC00441
(Regional General Manager) , Mr. Lee YES, Capacitor bank back to back (2018), WARRANTY:
Chung Hee (Vice President (Power Switching: YES. 2018TC00442 Ten (10) years extended warranty/guarantee
Infrastructure Sales & Marketing – II)) (2018), from the date of (PAC) of the Turnkey project (In
Phone - +966-11-293-2026, DS type: BDS type: 145SP-BD3 & LDS 2018TC00448 case of contract award) and from the date of
+82-31-8006-6837 type: 145SP-LD3 - 2000A/3150A@40 (2018), delivery for the direct material supply order. The
Contact Person Email ID - ºC, 60HZ, 40kA (3s) /104kAp, 2018TC00449 guarantee/warranty shall be applicable from first
peterbae@hyundai-electric.com , Operating mechanism: 145M-M3P. (2018), project and shall cover all the cost of materials
kolch@hyundai-electric.com 2018TC00450 and labor as per warranty/guarantee of materials
Website - MES type: 145SP-ME3, 40kA (3s) (2018), and workmanship and subsequently reduced
http://www.hyundai-elec.com /104kAp, Operating mechanism: 2018TC00455 yearly in case of future project award. This was
145M-M3P. (2018), confirmed in writing by Hyundai Electric & Energy
2018TC00456 Systems Co. Ltd., Korea through their letter #
HES type: 145SP-HE3, 40kA(3s) (2018), S370-1703-LSH1 dated # March 29, 2017.
/104kAp, Operating mechanism: 2018TC00458
145M-MSES (spring charged). (2018),
2018TC00459
(2018), NEW VERSION
145kV GIS 2018TC00510 Type/Model: 145SP-1
NEW VERSION (2018),
Type/ Model: 145SP-1 2018TC00511 PQ Letter:
(2018), TS&SD # 04-0692-030320, dated 15-03-2004,
Rating: 145KV, 2500A @40°C, 2017TC00070 pre-qualified GIS type 145SP-1
60Hz,40kA (3s)/ 104kAp (2017),
2016TC00558
CB type: 145SP-K1, Motor spring (2016), KEMA # Previously Hyundai Heavy Industries Co. Ltd [The
mechanism 2515-15 (2015). name has been changed based on P&SFD letter
#17-04234/01-030504401 dated May 24, 2017].
CB Capability:
Inductive load switching: YES
Capacitor bank back to back Switching:
NO
BDS type: 145SP-3PS1
LDS type: 145SP-3PS2
MES type: 145-3PS2
HES type: 145SP-LES2
OLD VERSION:
Type/ Model: 145SP
Rating: 145kV
CB Capability:
Inductive load switching: NO
Capacitor bank back to back Switching:
NO
DS type: 145SP-DS
MES: Type 145SP-ES
HES type: 145SP-LES
MITSUBISHI ELECTRIC CORPORATION Yuji KOBAYASHI / 145kV GIS Type Test performed PQ letter:
JAPAN General Manager LATEST VERSION in Based on S&SD letter #18-03818-030504401
Power Transmission & Type/Model: 100-GMKD-1 KERI, Korea # dated October 30, 2018, Mitsubishi Electric,
Plant -T&D Systems Center, Amagasaki Distribution Division, Rating 145kV, 3150A@40 ºC, 2017TC00557, dated Japan is pre-qualified for 145 kV GIS type
City, Japan MITSUBISHI ELECTRIC 60Hz,40kA (3s)/ 104kAp 15-17/03/2017, 100-GMKD-1 as conforming to latest National Grid
SAUDI, LTD. P.O. box: CB type: 120-SFMT-40CJ, 145kV, KERI, Korea # SA specification # 32-TMSS-02, with the
Mitsubishi Electric Corporation, Tdsc, 2391, Riyadh 11451 3150A@40 ºC, 60HZ, 40kA 2017TC00559, dated following conditions:
Marketing Department, 8-1-1 +966 11 477 7947 (3s)/104kAp. Operating mechanism: 08-09/03/2017,
Tsukaguchi-Honmachi, Amagasaki City, (Ext.260) / +966 55 547 BM-J4 (spring motor charged) KERI, Korea # WARRANTY:
Hyogo, 661-8661, Japan 5316 CB Capability: 2017TC00085, dated Ten (10) years extended warranty/guarantee
Kobayashi.Yuji@fc.mels Inductive load switching: YES 20/03-16 to from the date of (PAC) of the Turnkey project (In
Contact Person - Mr. Yohei Okada a.com.sa Capacitor bank back to back Switching: 26-07-17, case of contract award) and from the date of
Phone - +81-6-6497-8288 YES KERI, Korea # delivery for the direct material supply order. The
Email ID - BDS /LDS type: 120-GRD, 3150A@40 2017TC00468, dated guarantee/warranty shall be applicable from first
Okada.Yohei@dw.MitsubishiElectric.co. ºC, 60HZ, 40kA (3s) /104kAp, 21-03-2017, project and shall cover all the cost of materials
jp Operating mechanism: MDE and labor as per warranty/guarantee of materials
Website - MES type: 120GRED, 40kA (3s) KEMA, Netherland # and workmanship and subsequently reduced
http://global.mitsubishielectric.com/ /104kAp , Operating mechanism: MDE 2049-18, dated 1-23 yearly in case of future project award. This was
HES type: 120-GRE-A, 40kA(3s) Feb to 09-14 March confirmed in writing by Mitsubishi Electric, Japan
/104kAp Operating mechanism: MBE 2018, through their letter # Nil dated July 08, 2018.
(spring motor charged) KEMA, Netherland #
Cable compartment: H60F392, 2050-18, dated 28
3150A@40 ºC, 60HZ, 40kA (3s) Feb to 02 March
/104kAp 2018, -ORIGINALLY TMT&D CORP. & DISSOLVED
KEMA, Netherland # DURING APRIL 2005.
2051-18, dated 1-23
145kV GIS Feb to 09-05 March
NEW VERSION 2018,
Type/Model: 100GMKD
Mitsubishi, Japan #
Rating 145kV, 60Hz,40kA (xs)/ 104kAp HKT-29504, dated
CB type: 120-SFMT-40CJ 23-24/01/2017,
CB Capability: Mitsubishi, Japan #
Inductive load switching: YES HKT-29474, dated
Capacitor bank back to back Switching: 10/11/2017,
NO Mitsubishi, Japan #
DS type: 120GRD/GLD HKT-29530, dated
MES type: 120GRED/GRE 04-08/08/2017,
HES type: 120 GRED/GRE-A Mitsubishi, Japan #
HKT-29472, dated
OLD VERSION: 26-30/09/2016,
Type/Model: 120GMKM Mitsubishi, Japan #
HKT-29475, dated
Rating: 145kV 15-30/09/2016,
CB type: 120-SFMT-40, Pneumatic Mitsubishi, Japan #
mechanism HKT-29470, dated
DS type 120-GR-20, 120-GL-20 24/08-13/09/2016,
MES type: 120-GRE, 120-GREC Mitsubishi, Japan #
HES type: 120-GREA HKT-29478, dated
07-08/11/2016,
OLD VERSION: Mitsubishi, Japan #
Type/ Model: 100GMKD HKT-28699, dated
Nil,
Rating:145kV, Mitsubishi, Japan #
CB type: 120-SFMT-40CE, Motor spring HKT29397, dated
mechanism 13-01-2015,
DS type: 120GLD Mitsubishi, Japan #
HES type: 120-GREA HKT29398, dated
13-01-2015,
Mitsubishi, Japan #
HKT29397, dated
13-01-2015,
Mitsubishi, Japan #
HKT-28699-A, dated
13-01-2015,
Mitsubishi, Japan #
HKT-29346, dated
08-06-2013,
Mitsubishi, Japan #
HKT-29365, dated
5-08- 2013,
Mitsubishi, japan #
HKT-29510-A, dated
20-24 June, 2013
ILJIN ELECTRIC CO. LTD. GIS Type test completed Based on S&SD letter# 16-2020-01-030504401
SOUTH KOREA dated 31.03.2016 it is pre-qualified for 145kV GIS
145kV GIS type IJS1440-60, type IJS1440-60, 40kA(3s), 3150A as conforming
Plant -Hongseong, South Korea 40kA(3s), 3150A to National Grid SA specification # 32-TMSS-02,
with the following conditions:
905-17, Mannyeon-ro, Hwaseong-si, CB type IJC1440-60, Opr. Mech: • Ten (10) years Extended Guarantee / Warranty
Gyeonggi, KOREA IJCM1440-60 (Motor Spring) from the date of PAC of first Project (in case of
contract award) or from the date of delivery for
Contact Person - Mr. Jeong Kyung Woo • CB Capability for: the direct material supply order. This was
, Mr. Jaeho Kim Induced current switching: YES confirmed by the manufacturer through their
Phone - +82-2-707-9161 Capacitor Bank back to back switching: Letter # ILJHK20160217W dated 17.02.2016
Contact Person Email ID - YES
jkwoo@iljin.co.kr , jaeho.kim@iljin.co.kr
Website - http://www.iljinelectric.co.kr Busbar DS type:IJBDE1440-60
(Opr. Mech: IJBDEM1440-60)
GE GRID GMBH GIS Type test completed Based on S&SD letter# 13-4433-01-30504401,
SWITZERLAND 145kV GIS type F35 with dated 16 January 2013, it is pre-qualified for
rated current, 3150A @40°C, 60Hz, 145kV GIS type F35 with rated current, 3150A
Plant -. @40°C, 60Hz, against specification #
CB type- F35-CB4 / Opr. 32-TMSS-02, Rev.1 with the following condition:
Oberentfelden Switzerland Mech: FK3-2 (spring charged),
CB Capability for: 1. Eight (8) years extended warranty from the
Inductive load switching: YES date of PAC of the first turnkey project (in case
of contract award) or from the date of first
Capacitor bank back to back Switching: delivery of direct material supply order. This was
YES confirmed through manufacturer lletter ref:
Q1F35_210409 dated 21 April 2009.
Line & Busbar DS-F35-DES-4/
Opr. Mech: ME1-3, Old Version:
145kV GIS type B65 with CB type B65-
MES-F35-DES-4/ Opr. Mech: ME1-3, Previously " Areva T &D AG,
SWITZERLAND-Oberentfelden ", the name has
HES-F35-EFZ/Opr. Mech:MF-3 (spring been changed to ALSTOM Grid AG,
charged), Oberentfelden, Switzerland, based on ALSTOM
Grid Letter # Nil dated July 11, 2012.
CT-F35-CT4, Previously " ALSTOM Grid AG Switzerland,
Oberentfelden ", the name has been changed to "
OLD GE Grid Switzerland GmbH,Oberentfelden ".
based on GE Grid letter # Nil dated June 01, 2016.
145kV GIS type B65
DS type B65-DS
ES type B65-ES
Total = 15
SWITCHGEAR
10. 3
SF6 GAS INSULATED SWITCHGEAR 230 KV Applicable Standards: 32-TMSS-02
CB Capability:
Inductive load switching: xx
Capacitor bank back to back Switching:
No
CT Type: ELK-CN14/300
(1HC0071250M0040)
OLD VERSION
Type/ Model: ELK-1
Rating: 245kV
CB Type: ELK SP2-1.
FUJI ELECTRIC CO. 245kV GIS Originally JAPAN AE POWER SYSTEM CORP and
JAPAN subsequent change affected as per HITACHI
Type/Model: letter # XAE-VR-121213, dated 13-12-2012 and
FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
CB:
CB Capability:
Inductive load switching: xx
Capacitor bank back to back Switching:
xx
Website -
http://www.toshiba.co.jp/index j3.htm
HITACHI LTD 245kV GIS Originally JAPAN AE POWER SYSTEM CORP and
JAPAN subsequent change affected as per HITACHI
Type / Model: MFPT MFPTB-300-63L letter # XAE-VR-121213, dated 13-12-2012 and
Plant -Tokyo, Japan FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
Rating: 245kV
Akihabara Daibiru Building, 18-13,
Soto-Kanda 1-Chome, Chiyoda-Ku, CB type: MFPTB-300-63LA,
Tokyo, 101-8608, Japan HAR/MFTB-300-563L
MITSUBISHI ELECTRIC CORPORATION 245kV GIS ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN DURING APRIL 2005.
Type / Model: 200GPS
Plant -T&D Systems Center, Amagasaki
City, Japan Rating: 245kV
Total = 8
SWITCHGEAR
10. 4
SF6 GAS INSULATED SWITCHGEAR & HYBRID SF6 GAS INSULATED SWITCHGEAR, 380 KV Applicable Standards: 32-TMSS-02
GE Grid Solution SAS (GE & Alstom GIS Type test completed Previously "AREVA T&D– FRANCE-(AIX-LES
Joint Venture) BAINS) ", the name has been changed to
FRANCE 420kV GIS type T155 FOR NEW TYPE: ALSTOM Grid SAS-France based on ALSTOM
GE Grid Solution Grid-France letter # Nil, dated December 07,
Plant -Aix-Les Bains, France CB type T155, FB2T (Hydraulic SAS (GE & Alstom 2012,
Mech.) Joint Venture) – and again the name has been changed to GE Grid
GE Grid Solution SAS (GE & Alstom France has Solution SAS (GE & Alstom Joint Venture)-France
Joint Venture), 1, Rue Paul Doumer FOR NEW TYPE: successfully based on their letter # Nil, dated October 13,
73100 Aix-Les-Bains (France) GIS: T155-420kV (Mono), 3150A @ completed type tests 2016.
40°C , 60Hz , 63kA(1Sec) on 420kV GIS Type
Aix-Les Bains Circuit breaker: T155-CB3, 3150A@40 T155- 420KV FOR NEW TYPE:
ºC, 60HZ, 63kA (1s), Operating (Mono) at PQ letter:
Contact Person - Mr. Zinedine RABAH mechanism:FK3-6 Independent testing Based on S&SD letter # 18-01638-01-30504401
Phone - +33(0) 4 79 88 79 80 + 971 4 BDS/LDS: T155-DS3, 3150A@40 ºC, laboratories; CREDA dated April 17, 2018, for GE Grid Solution SAS
4299 651 60HZ, 63kA (1s), Operating - France, KEMA – (GE & Alstom Joint Venture) – France is
mechanism: ME2-2 Netherland & CESI – pre-qualified for GIS Type T155- 420kV (Mono)
MES: T155-ES3, Operating mechanism: Italy. as conforming to latest National Grid SA
ME2-2 specification # 32-TMSS-02
HES: T155-EF3, Operating mechanism:
ME2-2 (spring charged) WARRANTY:
Cable compartment: T155, , 3150A@40 •Ten (10) years extended warranty/guarantee
ºC, 60HZ from the date of Provisional Acceptance
Current transformer: T155-CT3 Certificate (PAC) of the first turnkey project in
Bus duct: T155-420kV: 3150A@55 ºC, case of contract award or date of first delivery in
60HZ, 63kA (1s) case of direct material supply order, as
confirmed to SEC/National Grid SA, through their
letter # BHT14032017, dated March 14, 2017.
MES: ELK-TK3/420,
Operating Mechanism-ELK-BAC
CT : ELK-CN3
Rating: 420kV
CB Capability:
Inductive load switching: xx
Capacitor bank back to back Switching:
xx
DS: 8QD1
OLD VERSION:
Type/ Model: GID CB type GSR
400R2B/GSRK, DOUBLE BREAK,
Hydraulic mechanism
Rating: 420kV
HITACHI LTD 420kV GIS Originally JAPAN AE POWER SYSTEM CORP and
JAPAN subsequent change affected as per HITACHI
Type/ Model: IFT letter # XAE-VR-121213, dated 13-12-2012 and
Plant -Tokyo, Japan FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
Rating: 420kV, 3150A @40°C, 60Hz
Akihabara Daibiru Building, 18-13,
Soto-Kanda 1-Chome, Chiyoda-Ku, CB: Double break
Tokyo, 101-8608, Japan
CB Capability:
Contact Person - Mr. Masaharu Tsumori Inductive load switching:xx
Phone - +81-3-4564-4741 Capacitor bank back to back
Email ID - Switching:xx
masaharu.tsumori.gx@hitachi.com
Website - http://www.hitachi.com
2007TC00603/09-04
DS: BDS type 550DRM2/2016, LDS -2007, KEMA #
type-550 DRM1/2016, 4000A@55 ºC, 56-07/ 23 Feb-4 May Old version:
60HZ, 63kA (3s) /163.8kAp, Operating 2007. PQ Letter:
mechanism: MMF-4 (for both DS). TS&SD Letter # 08-01807-03032301, Dated 16
July, 2008 for 380kV GIS.
MES: 550ERM/2016, 63kA (3s)
/163.8kAp , Operating mechanism: CONDITION:
MMF-5. Back to back capacitor switching test for C.B.
shall be done in independent laboratory in the
HSES: 550 LES/2016, 63kA(3s) presence of SEC Engineers whenever there is a
/163.8kAp Operating mechanism: requirement for this test in the PTS of forthcoming
MSF-4 (spring charged). SEC projects.
CB Capability:
Inductive load switching: xx YES
Capacitor bank back to back
Switching:xx NO
ES-550 ERM
HES-550 LES
MITSUBISHI ELECTRIC CORPORATION 420kV GIS ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN DURING APRIL 2005.
Type/ Model: 400-GPS
Plant -T&D Systems Center, Amagasaki
City, Japan Rating: 420kV, 4000A @40°C, 60Hz,
63kA(1s)/164kAp
Mitsubishi Electric Corporation, Tdsc,
Marketing Department, 8-1-1 CB:
Tsukaguchi-Honmachi, Amagasaki City,
Hyogo, 661-8661, Japan CB Capability:
Inductive load switching: xx
Contact Person - Mr. Yohei Okada Capacitor bank back to back Switching:
Phone - +81-6-6497-8288 xx
Email ID -
Okada.Yohei@dw.MitsubishiElectric.co.
jp
Website -
http://global.mitsubishielectric.com/
Total = 11
SWITCHGEAR
10. 5
SF6 GAS INSULATED SWITCHGEAR & HYBRID SF6 GAS INSULATED SWITCHGEAR, 550 KV Applicable Standards: 32-TMSS-02
GIS
GE Grid Solution SAS (GE & Alstom GIS: T155-550kV, 550kV, 63kA Type Tests were PQ letter:
Joint Venture) (1s)/163.8kAp, 3150A, 40ºC, 60Hz performed in Based on S&SD letter # 18-00209/01-30504101
FRANCE CERDA, France, dated July 11, 2018, GE Grid solutions SAS -
Circuit Breaker: T155-CB2, 550kV, KEMA, Netherland France is pre-qualified for 550kV GIS as
Plant -Aix-Les Bains, France 63kA (1s)/ 163.8kAp, 3150A, 40ºC, and CESI, Italy conforming to latest National Grid SA
60Hz with operating mechanism: specification # 32-TMSS-02, with the following
GE Grid Solution SAS (GE & Alstom T155-CI2 (Hydraulic), Capacitor bank conditions:
Joint Venture), 1, Rue Paul Doumer back to back switching: 1000A (C2),
73100 Aix-Les-Bains (France) Inductive current switching: 315A WARRANTY:
Ten (10) years Guarantee/Warranty in respect of
Aix-Les Bains Busbar Disconnector: T155-DS, 550kV, defects due to design, manufacture, installation &
63kA (1s)/ 163.8kAp, 3150A, 40ºC, workmanship from the date of Provisional
Contact Person - Mr. Zinedine RABAH 60Hz, Operating Mechanism: T155-ME Acceptance Certificate (PAC) of the project in
Phone - +33(0) 4 79 88 79 80 + 971 4 case of contract award and from the date of
4299 651 Line side Disconnector: T155-DS, delivery in case of direct material supply order,
550kV, 63kA (1s)/ 163.8kAp, 3150A, as confirmed by the manufacturer vide letter #
40ºC, 60Hz, Operating Mechanism: Nil, dated August 18, 2015
T155-ME
Line DS:
ELK-TV3/550(1HC0071250M0100),
Operating
Mechanism-DH(1HC0071250M0100)
MES:
ELK-EM3/550(1HC0071250M0100),
Operating
Mechanism-DH(1HC0071250M0100)
HES:
ELK-EB3/550(1HC0071250M0100),
Operating
Mechanism-DB(1HC0071250M0100)
Cable compartment:
ELK-HK3/550(1HC0071250M0100)
HYBRID GIS:
Based on S&SD letter #16-02585-02-30504401
dated April 10, 2016, pre-qualified Hyosung,
Korea 550kV GIS type 550 HSG has pre-qualified
for Hybrid GIS with following conditions:
• Ten (10) years extended warranty from the
date of PAC of the turnkey project in case of
contract award and date of delivery in case of
direct material supply order. This is applicable
from first project and subsequently reduced
yearly in case of future project. This was
confirmed by the manufacturer through letter #
HG-NG-HGIS-160221-550 dated February
21,2016
CONDITION:
As per 550kV GIS type 8DQ1
WARRANTY:
As per 550kV GIS type 8DQ1
Total = 4
SWITCHGEAR
10. 6
METAL CLAD GAS INSULATED MEDIUM VOLTAGE SWITCHGEAR (11KV,13.8KV.33KV OR Applicable Standards: 32-TMSS-03
34.5KV)
SIEMENS 33kV GIS PQ Letter:
GERMANY S&SD letter # 15-0186-01-30504401, dated
Type/ Model: 8DA10 January 22, 2015 and TS&SD Letter #
Berlin, Germany 10-02461-02-03032301, dated August 31, 2010,
IC SG EA MF Rating: 36kV, 2500A @40°C, 60Hz, the manufacturer is prequalified for 36kV GAS
Wernerwerkdamm 5, 25kA(3s)/65kAp Insulated Medium Voltage SWGR Type 8DA10.
13629, Berlin, Germany
CB: 3AH49 with vacuum interrupter CONDITION:
Phone - +49 (911) 433 8321 type VSG 40040, rated current up to
Website - 2500A, 40°C, 60Hz WARRANTY:
www.siemens.com/ingenuityforlife Seven (7) years extended warranty/guarantee in
CB: 3AH49 with vacuum interrupter respect of defects due to design, manufacture,
type VS 30040 (40kA), rated current installation & workmanship from the date of
up to 2375A 40°C, 60Hz Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
CB: 3AH49 with vacuum interrupter date of delivery in case of direct material supply
type VS 30040 (40kA), rated current order, as confirmed by Siemens trough letter #
up to 2375A 40°C, 60Hz 8DA10_PQR_R1 dated 24/08/2010
CB Capability:
Capacitor bank back to back Switching:
400A with CB type 3AH49, interrupter
VSG40040
Total = 1
SWITCHGEAR
10. 7
SF6 Non-Extensible Ring Main Unit, 11 KV through 34.5 KV Applicable Standards: 32-TMSS-07
Saudi Arabia
Website -
http://www.driescher.de/home/index.ht
m
Website -
http://www.schneider-electric.fr/
Website -
http://w1.siemens.com/entry/cc/en/
Website -
http://www.lucyswitchgear.com/T
Plant -France
Website - http://www.areva.com/
Total = 9
SWITCHGEAR
10. 8
LOAD BREAK SWITCHES UPTO 34.5kV Applicable Standards:
Saudi Arabia
AREVA
FRANCE
SIEMENS
GERMANY
Berlin, Germany
IC SG EA MF
Wernerwerkdamm 5,
13629, Berlin, Germany
FRITZ DRIESCHER
GERMANY
HITACHI
JAPAN
Total = 7
SWITCHGEAR
10. 9
Gas Insulated transmission Lines (GIL) for rated voltage 110kV and above Applicable Standards: 32-TMSS-05
Total = 1
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
TRIDELTA MEIDENSHA GMBH Previously " TRIDELTA ", the name has been
GERMANY changed to TRIDELTA Meidensha GmbH -
Germany, based on TRIDELTA Meidensha GmbH
Website - http://www.tridelta.de/ Letter #Nil dated August 10, 2016.
TE ENERGY / TYCO ELECTRONIC MDAE4-120 Class 4 up to 132 kV Type tested in CESI PQ Lettter
United Kingdom Lab Italy in the Based on S&SD letter # 15-09503-01-030504401,
presence of TE Witham Uk is prequalified for Surge Arrester
Plant -Witham Uk (Plant) SEC/National Grid type MDAE4-120 Class 4 up to 132 kV.
SA engineers & SGS
Bowthorpe Emp Stevenson Road Inspector on 7th to WARRANTY:
Brighton East Sussex Bn2 0Df 19th April 20414 Ten (10) years Guarantee / warranty for the in
.Seal Leak Test on respect of defects due to design, manufacture,
Contact Person - Mr. Oday M. Hindi conducted in TYCO installation & workmanship from the date of
Transmission Support Manager,Mr. Electronics test Provisional Acceptance Certificate (PAC) of the
Graeme Currie, Product Manager Laboratory (Whitam, first turnkey project in case of contract award or
Phone - +44-0-1273-692591 UK) in the presence date of delivery in case of direct material supply
Email ID - Oday.hindi@te.com, of SGS Inspector order, as confirmed by the manufacturer thru
Graeme.currie@te.com and CESI letter #nil, dt: Sep 14, 2011.
representative on
15th to 16th Sep
2015.
Report, General
report No.
TE-MDAE4-120
HUBBELL POWER SYSTEMS, INC. Previously OHIO BRASS [The name has been
United States changed based on S&SD/P&SFD letter#
14-07802-30504401 dated October 22, 2014 and
Plant -Columbia , United States based on Hubbell Power System Grid Letter # Nil
dated October 06, 2014]
Website - http://www.jaeps.com/eng/
SIEMENS ,GERMANY
GERMANY
Germany
Website -
http://www.siemens.de/Pages/EntryPa
geRedirect.aspx
Website -
http://www.toshiba.co.jp/index j3.htm
AREVA
FRANCE
Plant -France
Website - http://www.areva.com/
Total = 14
CIRCUIT BREAKERS
12. 1
CIRCUIT BREAKER, SF6, DEAD TANK, 69 KV Applicable Standards: 37-TMSS-01
Website -
http://www.toshiba.co.jp/index j3.htm
Website - http://www.areva.com/
Georgia
Website - http://
http://www.geindustrial.com/products/
static/circuitbreakers/manufacturing.ht
m
ABB ( T& D)
United States
Website - http://www.abb.us/
Total = 8
CIRCUIT BREAKERS
12. 2
CIRCUIT BREAKER, SF6, DEAD TANK, ,110 - 132 KV Applicable Standards: 37-TMSS-01
ABB
SWITZERLAND
Website -
http://www.toshiba.co.jp/index j3.htm
AREVA T&D INC. Type / Model: DT1-145FK SUSPENDED for all SEC/National Grid SA ongoing
United States and forthcoming projects based on VP,
Rating: 132kV, 2000A, 40kA Engineering letter # 13-01705-30504401 dated
Charleroi, United States March 23, 2013.
PQ Letter:
TS&SD letter # 10-02708-02-03032301 dated
25/10/2010, it is pre-qualified for 145kV Dead
Tank Circuit Breaker type DT1-145FK, 40KA,
2000A.
CONDITION:
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter as confirmed by the manufacturer thru
letter #nil, dt: 6th Mar, 2009.
Georgia
Website - http://
http://www.geindustrial.com/products/
static/circuitbreakers/manufacturing.ht
m
MITSUBISHI ELECTRIC CORPORATION Type / Model: 120-SFMT-40E ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN DURING APRIL 2005.
Rating: 145kV, 40kA 2000A
Plant -T&D Systems Center, Amagasaki
City, Japan
ABB ( T& D)
United States
Website - http://www.abb.us/
Total = 10
CIRCUIT BREAKERS
12. 3
CIRCUIT BREAKER, SF6, DEAD TANK, 230 KV Applicable Standards: 37-TMSS-01
Website -
http://www.toshiba.co.jp/index j3.htm
AREVA Type / Model: DT1-245 F3 SUSPENDED for all SEC/National Grid SA ongoing
United States and forthcoming projects based on VP,
Rating: 230kV, 2500A, 60Hz Engineering letter # 13-01705-30504401 dated
Plant -Charleroi , United States March 23, 2013.
CONDITION:
Di-electric test, riv test, continuous current
temperature rise test @ 2500 A, 60Hz is to be
carried out in the first batch in the presence of 3
SEC engineers and 1 IIA inspector.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
Georgia
Website - http://
http://www.geindustrial.com/products/
static/circuitbreakers/manufacturing.ht
m
MITSUBISHI ELECTRIC CORPORATION Type / Model: 200-SFMT-40E ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN DURING APRIL 2005.
Rating: 245 kV, 40kA, 3150 A
Plant -T&D Systems Center, Amagasaki
City, Japan
Website - http://www.abb.us/
Total = 7
CIRCUIT BREAKERS
12. 4
CIRCUIT BREAKER, SF6, LIVE TANK, 69 KV Applicable Standards: 37-TMSS-02
ABB
SWITZERLAND
SIEMENS, GERMANY
GERMANY
AREVA
SWITZERLAND
Website - http://www.areva.com/
AREVA
FRANCE
Website - http://www.areva.com/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
Total = 5
CIRCUIT BREAKERS
12. 5
CIRCUIT BREAKER, SF6, LIVE TANK, 110 - 132 KV Applicable Standards: 37-TMSS-02
SIEMENS, GERMANY
GERMANY
AREVA
FRANCE
Website - http://www.areva.com/
AREVA
GERMANY
Website - http://www.areva.com/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
Total = 4
CIRCUIT BREAKERS
12. 6
CIRCUIT BREAKER, SF6, LIVE TANK, 230 KV Applicable Standards: 37-TMSS-02
SIEMENS, GERMANY
GERMANY
AREVA
FRANCE
Website - http://www.areva.com/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
Total = 3
HAEFELY-TRENCH ELECTRIC
CANADA
Website -
http://www.electricityforum.com/produ
cts/htg.htm
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
Total = 2
ABB HV TECHNOLOGIES
SWITZERLAND
Total = 1
EFACEC SISTEMAS DE ELCTRONICA, Bandariyah International Type/Model - CLP500 Institue Electro PQ Lettter
S.A Co. Ltd Tecnico Portugues Based on TS&SD letter# 09-01819-03032301
PORTUGAL 3rd Fllor, Building 3 Portugal, Labecm dated 23rd June 2009, it is prequalified for for
Mutlaq Office comple Al Laboratoriao De. RTU type CLP500 as confirming to SEC
Plant -Maia/Portugal Khobar KSA compatibbilidate specification # 38-TMSS-03, rev.0 with the
Phone - 0553712308 electromagnet ica. following condition:
Rua Eng Frederico Ulrich, Ap 3078 Email - Test Date - jan 2010,
,4471-907 Maia Portugal Maia , Portugal rrami@bandariyah.com July 2010 WARRANTY
Test Report No. - Ten (10) years extended warranty/guarantee in
Contact Person - Mr. Ricardo Cunha, E-2009-1004.02 , respect of defects due to design, manufacture,
Mr. André Cruz 09-12-119-022a installation & workmanship from the date of
Phone - +351 932025959; +351 Provisional Acceptance Certificate (PAC) of the
229402000; +351 939333313 first turnkey project in case of contract award or
Email ID - ricardo.cunha@efacec.com; date of delivery in case of direct material supply
en@efacec.com; acruz@efacec.com. order.
Website -
http://www.efacec.pt/en/automation/
FOXBORO
AUSTRALIA
Website - http://www.foxboro.com/
Website - http://www.harris.com/view
pressrelease.aspact=lookup&pr id=318
Website - http://www.harris.com/
SAT
AUSTRIA
Website -
http://w1.siemens.com/entry/cc/en/
VA TECH
AUSTRIA
LSIS , PQ Lettter
SOUTH KOREA Based on TS&SD letter# 08-00492/1--03032301
dated 24th March, 2008, it is prequalified for for
Ls Tower, 127, Ls-Ro, Dongan-Gu, RTU, SOE and associated transducers with the
Anyang-Si, Gyeonggi-Do, following condition
AREVA
FRANCE
Plant -France
Website - http://www.areva.com/
Total = 14
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter # PSN/SCA/08022016/ 2016, dt: 06/11/2016.
Website - http://www.harris.com/view
pressrelease.aspact=lookup&pr id=318
LSIS , WARRANTY
SOUTH KOREA Seven (7) years extended warranty/guarantee in
respect of defects due to design, manufacture,
Ls Tower, 127, Ls-Ro, Dongan-Gu, installation & workmanship from the date of
Anyang-Si, Gyeonggi-Do, Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
Contact Person - Mr. Je-woo, Lee date of delivery in case of direct material supply
Assistant Manager order.
Phone - +82-2-2034-4541
Email ID - jwleea@lsis.com
Website - http://www.lsis.com
Website - http://www.ronan.com/
Total = 7
United States
Website -
http://www.ametekpower.com/
NEXANS
SWITZERLAND
PAN ALARM
United States
RONAN ENGINEERING
United Kingdom
Website - http://www.ronan.com/
STEINER
JAPAN
Website -
http://www.steiner-binoculars.com/ind
ex.html
Website - http://www.abb.fi/
PIRELLI
GERMANY
Berlin , Germany
Website - http://
http://www.pirelli.com/splash/index.htm
l
Phone - +61-3-5232-4709
Email ID - amjad.aziz@jpowers.co.jp
Website -
http://www.jpowers.co.jp/english/inde
x.html
LS PREVIOUSLY LG
SOUTH KOREA
Website - http://www.lscable.com/
SIEMENS
GERMANY
Website - http://www.ffcpg.com.my/
Total = 12
Contact Person - Mr. Ramaswami • Ten (10) years extended warranty in respect of
Bharath defects due to design , manufacturing, installation
Phone - +204-477-0591 , and workmanship from the date of PAC of the
Email ID - email Info@erlphase.com first turnkey project (in case of contract award)
Website - http://www.erlphase.com or from the date of first delivery of direct material
supply order as confirmed by the manufacturer
through their letter # Nil dated February 19, 2014.
DIGSILENT GMBH
GERMANY
Website - http://www.digsilent.de/
Website -
http://www.powertechnology.com/
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt:May 18, 2010.
KoCos Messtechnik Germany Mohammed Al-Ojaimi SHERLOG CRX •Fault Record PQ letter:
GERMANY Contracting Est. System Report # Based on S&SD letter # 17-06723-030504401
KoCoS Messtechnik AG (E170309E1) by dated October 31, 2017, KoCos Messtechnik
Plant -Korbach, Germany Suedring 42 Phoenix TestLab – Germany is pre-qualified for Dynamic System
D-34497 Korbach, Germany Monitor (DSM) as conforming to latest National
KoCoS Messtechnik AG Germany •DFR & DSM Report Grid SA specification # 38-TMSS-06
Suedring 42 Tel. +49 5631 9596-0 # (U170309E1) by
D-34497 Korbach, Germany info@kocos.com Phoenix TestLab – WARRANTY:
Germany Ten (10) years extended warranty/guarantee in
Korbach •Functional Test respect of defects due to design, manufacture,
Report # Nill by installation and workmanship from the date of
Contact Person - KoCos Germany KoCos Messtechnik Provisional Acceptance Certificate (PAC) of the
(Lea-Sophie Kotthoff, Sales), Local - Germany first turnkey project in case of contract award or
Agent- Mohammed Al-Ojaimi date of first delivery in case of direct material
Contracting Est. (Abbad S. Ahmed, supply order, as confirmed by the manufacturer
Manager Energy Services.) vide letter # Nil, dated October 08, 2015.
Phone - Tel. +49 5631 9596-0
Email ID - info@kocos.com
Contact Person Email ID -
lkotthoff@kocos.com
abbad.ahmed@alojaimi.com
Website - www.kocos.com
Total = 5
POWER DIAGNOSTIX SYSTEMS GMBH PDM PEHLA # 16005Ba, Based on S&SD letter # 16-05170/01-30504401
GERMANY dated 17-02-2016, dated June 23, 2016, it is prequalified for Partial
Type PDMAR 120S, PDMAR56S, PD system dated Discharge Monitoring System without UHF
Plant -. PDMCR 12-02-2016, PD Sensors as conforming to National Grid SA
system dated Material Specification 38-TMSS-07 with the
Vaalser Strasse 250, D-52064 16-02-2016, following condition:
Aachen Germany TUV Rheinland #
21248037-002, •Ten (10) years extended warranty from the date
Contact Person - Mr. Markus Soller dated of PAC of the turnkey project in case of contract
Contact Person Email ID - 19-23-02-2016, award and date of delivery in case of direct
support@pdix.com soller@pdix.com TUV Rheinland # material supply order, as confirmed by the
Website - WWW.pdix.com 21248033_003, manufacturer through letter # Nil dated
dated 31-03-2014.
23-24-02-2016,
EMC Test NRW #
P12-Z-00353-002,
dated 25-02-2016,
KERI #
2014TS02444, dated
18-09-2014
Hyundai Electric & Energy Systems Co. PDMS KERI, Korea # Based on S&SD letter # 16-05296-2-30504401
Ltd Type HiPDS-G (HiDAS) 2016TS00609, dated dated July 28,2016, it is prequalified for On-Line
SOUTH KOREA 09-03-2016, Partial Discharge Monitoring System (PDMS) and
Internal Sensor KERI, Korea # Internal Sensor as conforming to National Grid SA
Plant -Ulsan Type HiUC-P140 2016TS00627, dated Material Specification 38-TMSS-07 with the
18 Jan: - 23 Feb: following condition:
1000, Bangeojinsunhwan-doro, 2016,
Dong-gu, Ulsan, South Korea, KERI # •Ten (10) years extended warranty from the date
2016TS00755, dated of PAC of the turnkey project in case of contract
Ulsan 03 -04 March, 2016. award and date of delivery in case of direct
material supply order, as confirmed by the
Contact Person - Mr. Young Jun Bae manufacturer through letter # S370-1504-LSH3
(Regional General Manager) , Mr. Lee dated 31-07-2015.
Chung Hee (Vice President (Power
Infrastructure Sales & Marketing – II))
Phone - +966-11-293-2026, Previously Hyundai Heavy Industries Co. Ltd [The
+82-31-8006-6837 name has been changed based on P&SFD letter
Contact Person Email ID - #17-04234/01-030504401 dated May 24, 2017].
peterbae@hyundai-electric.com ,
kolch@hyundai-electric.com
Website -
http://www.hyundai-elec.com
APM TECHNOLOGIES INC APM Technologies KSA Type / Model: (PDMS) APM5000 & KERI # PQ Letter:
SOUTH KOREA APM Technologies KSA - APM2000 (Portable) 2014TS02416, dated S&SD letter # 14-08866-2-30504401 dated
Riyadh Second Industrial with UHF sensor 05 Aug, 2014, KERI December 11, 2014, it is pre-qualified for Partial
Plant -Seoul, Korea Republic Of City, # 2014TS02423, Discharge Monitoring System (PDMS).
Riyadh Saudi Arabia dated 05 Aug, 2014,
Mercedes-Benz Building 5F, 225-5, +966 53 66 77 212 KERI # WARRANTY:
Nonhyeon-Dong, Gangnam-Gu, Seoul jaypark@apmtech.co.kr 2014TS02444, dated Ten (10) years extended warranty/guarantee in
135-829, Korea 18-09-2014, KERI # respect of defects due to design, manufacture,
2014TS02568, dated installation & workmanship from the date of
Contact Person - Mr. JAY PARK 18 Aug. – 17 Sept. Provisional Acceptance Certificate (PAC) of the
Phone - + 82 2 545 6286,Mobile: +82 10 2014, KERI # first turnkey project in case of contract award or
5157 1255 2014TS02569, dated date of delivery in case of direct material supply
Email ID - jaypark@apmtech.co.kr 11 Aug- 15 Sept, order, as confirmed by the manufacturer thru
jaypark@psdholdings.com 2014, letter #nil, dt: May 12, 2014.
Website - http://www.apmtech,co,kr KOLAS #
STC-B14-375-01,
dated 18-22 –
09-2014, KOLAS,
Korea #
STC-B14-375-02,
dated 15-09-2014,
STC-B14-375-03,
dated
18-19-09-2014.
HYOSUNG HEAVY INDUSTRIES PD Monitoring System ,Type: GM-3000 Type tested in the PQ letter
CORPORATION (HICO) UHF Internal sensor presence of Based on S&SD letter # 15-09060-02-30504401
SOUTH KOREA type HiCMS-GM-IS, external Sensors SEC/National Grid dated December 09, 2015, it is pre-qualified for
type HiCMS-GEP-S-2, SA Engineers and PDM & Sensors with the following conditions:
Plant -Republic of Changwon, Korea UHF Noise sensor third party inspector
Type HiCMS-GNP-S-2 at KERI WARRANTY:
Eric Rhie, 450, Gongdeok-Dong, KERI, Korea # Ten (10) years Extended Guarantee / Warranty
Mapo-Gu, Seoul , Korea 2015TS02273, dated from the date of PAC of first Project (in case of
Tel:82-707-6180 10-11, August, contract award) or from the date of delivery for
2015, KERI, Korea # the direct material supply order. This is applicable
Contact Person - Mr. Eric Rhie Sale 2015TS02274, dated from first project and subsequently reduced
Manager & Mr. Joey W. J Kyung 10-11, August, yearly in case of future project. This was
Marketing Manager 2015, KERI, Korea # confirmed, through their Letter No.
Email ID - inseock@hyosung.com 2015TS02275, dated HS-PQ-150511-PDM-001 dated 17/07/2015.
Contact Person Email ID - 10, August, 2015,
inseock@hyosung.com , Keri # 2015TS02508
tsing@hyosung.com DATED 05-27
Website - august, 2015, Korea
http://www.hyosung.co.kr/eng/index.js testing & Research
p?, www.hyosung.com Institute,
Korea #
CUS2015-3092,
dated 17-19 August,
2015, Korea testing
& Research Institute,
Korea #
KOMERI-0306-15T24
16-1, dated 20-21,
August, 2015
ABB S.R.O (RFF) ABB Automation CO. Ltd. UHF Sensor Type WB3 (1HC0034454) PHELA # 15020Ba PQ Letter:
CZECH REPUBLIC Saudi Arabia rated for 300/420 kV dated 14-16 April, Based on S&SD letter # 17-03926-2-30504401
PO Box # 414: 2015, PHELA # dated August 03, 2017, ABB S.R.O LBU Brno
Stetkova 1638/18,140 00 Praha 4Czech Riyadh-11383 15015Ba-1, dated Factory – Czech Republic is pre-qualified for
Republic-Trutnov +966 (11) 2653030, 08-17 April, 2015, Partial Discharge Sensor (UHF Sensor) type WB3
+966504401696 ABB, Switzerland # (1HC0034454) rated for 300/420 kV as
Contact Person - Mr. Essam essam.bashraheel@sa.a HASH650969E, conforming to National Grid SA specification #
Bashraheel & Mr Aref Al-Arrak bb.com dated 04-06, March, 38-TMSS-07 Rev.0 with the following conditions:
Email ID - 2014
Essam.bashraheel@sa.abb.com WARRANTY:
&Aref.alarrak@sa.abb.com •Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed in writing by the
manufacturer through their letter #
PGHV-17-04-26/GIS-1 dated June 16, 2017.
ABB Power Equipment (Xiamen) ABB Electrical Industries UHF Partial Discharge Sensor Type ABB, China has PQ letter:
Company Limited, Zhangzhou Branch. Co. Ltd. WB14 rated for 145kV successfully Based on S&SD letter # 18-00461-2-30504401
CHINA P.O. Box 8796 Riyadh completed type tests dated February 25, 2018, ABB Power Equipment
11492 – Kingdom of on 1 Partial (Xiamen) Company Limited, Zhangzhou Branch -
Plant -China Saudi Arabia discharge Sensors China is pre-qualified for UHF Partial Discharge
+966 11 2653030 Type WB14 rated for Sensor Type WB14 rated for 145kV as
Wenpu Industrial Park, Taiwanese essam.bashraheel@sa.a 145kV at conforming to latest National Grid SA
Investment Zone, bb.com Independent testing specification # 38-TMSS-07
Zhangzhou, Fujian, P.R.China Postal laboratory PEHLA –
code: 363107 Germany during 09 WARRANTY:
to 12 May 2016. • Ten (10) years extended warranty/guarantee in
Zhangzhou respect of defects due to design, manufacture,
installation and workmanship from the date of
Contact Person - Ms. Jocelyn-Lihua Provisional Acceptance Certificate (PAC) of the
Ying first turnkey project in case of contract award or
Phone - +86 (0)596 5022001 , +86 date of first delivery in case of direct material
(0)18150892388 supply order, as confirmed by the manufacturer
Email ID - Jocelyn-Lihua Ying vide letter # Nil, dated January 23, 2018.
@cn.abb.com
Contact Person Email ID - Jocelyn-Lihua
Ying @cn.abb.com
Total = 8
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
GE
United States
Website - http://www.ge.com/
ELECTROTECNICA ARTECHE HNOS. Type / Model: Capacitive Voltage 1- For type 1- Type DDB-170
S.L./ E.A.H.S.L Transformer DDB-170, Test PQ Letter:
SPAIN 1-DDB-170 Report # 2010 10 3D S&SD Letter 12-03192-02-30504001 dated
Rating: 0571 February 19, 2012, pre-qualified for CVT
Plant -Mungia, Spain 132kV, CCVT Capacitor Voltage Transformer up to 132 kV.
2- For type
Electrotecnica Arteche Hnos. S.L./ 2-DFK-245 DFK-420, " The first WARRANTY:
E.A.H.S.L/ Mungia/ Spain/ Derio Bidea Rating: batch of 380kV Ten (10) years extended warranty/guarantee in
Nº28 48100/ 230kV, CVT Capacitor Voltage respect of defects due to design, manufacture,
Transformer (CVTs) installation & workmanship from the date of
Contact Person - Mr. Roberto Antuñano 3-DFK-420 type DFK-420 per Provisional Acceptance Certificate (PAC) of the
Phone - +946011200 Rating: 50-TMSS-01, Rev.01 first turnkey project in case of contract award or
Email ID - ra@arteche.es up to 380kV, CVT to be supplied to date of delivery in case of direct material supply
Website - http://www.arteche.es SEC/National Grid order, as confirmed by the manufacturer thru
SA shall be type letter #nil, dt: jan 11, 2010.
tested in an
accredited test 2- Type DFK-420
laboratory in PQ Letter
presence of three Based on S&SD letter MPQ # 10816213 dated
(3) SEC/National January 7, 2018, Electrotecnica ARTECHE
Grid SA and one (1) Hermanos, S.L. - Mungia, Spain is pre-qualified
SEC/National Grid for 380kV Capacitor Voltage Transformers
SA approved IIA (CVTs), type DFK-420 as conforming to National
Inspector as Grid SA specification # 50-TMSS-0,Rev.0, with
conformed through the following conditions:
Manufacturer Letter
# Nil dated Warranty
December 03,2017." Ten (10) years extended warranty from the date
of PAC of the first turnkey project (in case of
3. For type DFK-245, contract award) or date of first delivery (in case
"The first batch of of direct material supply order), as confirmed,
230kV Capacitor through their letter # Nil, dated July 21, 2016 shall
Voltage Transformer be applicable for all 380kV Capacitor Voltage
(CVTs) type Transformers (CVTs), type DFK-420 to be
DFK-245 per supplied to SEC/National Grid SA.
50-TMSS-02, to be
supplied to 3- Type DFK-245
SEC/National Grid PQ Letter:
SA shall be type Based on S&SD letter # 18-02331-030504401
tested in an dated July 8, 2018 Electrotecnica ARTECHE
accredited test Hermanos, S.L. - Mungia, Spain is pre-qualified
laboratory in for 230kV Capacitor Voltage Transformers
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
CONDITION:
All type, routine & special tests including the load
test shall be carried out on the first batch to be
supplied to SEC in securing an order in an
independent testing laboratory in the presence of
three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
HAEFELY-TRENCH ELECTRIC
CANADA
Website -
http://www.electricityforum.com/produ
cts/htg.htm
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
Website -
http://www.passoni-villa.com
Website - http://www.ritzusa.com/
Website - http://www.trench.at/Trench
Austria GmbH/News/Das neue
Familienmitglied - Trench Italia/
-8255-38-2-en-com-/cms.html
ABB HV TECHNOLOGIES
SWITZERLAND
Total = 12
METERS
14. 1
METERING DEVICES (KILOWATT HOUR METER ENERGY METER) Applicable Standards: 40-TMSS-02
SIEMENS
GERMANY
ADVANCE ELECTRONICS CO., LTD. Type (ADDAD-4) Based on the approval of Executive Director
Saudi Arabia through TS&SD Letter # 08-1105-03032301 dated
20/10/2008, this Manufacturer is pre-qualified for
Riyadh , Saudi Arabia Energy Meters Type (ADDAD-4).
ELSTER , ITS A3RAQ meters with configuration kEMA, Elster PREVIOUSLY ABB (T &D)
United States Riyadh KSA ZD3D44F00LD-16, ZD3E44F00LD-16, Engineering report
Phone - ZD3D46000LD-16. Test Date - Aug Based on S&SD Letter 12-00932-1-30504401
Plant -Raleigh, Nc,USA +966-56-666-2660 2011, Feb 2005 dated March 25, 2012, it is pre-qualified for
Email - A1860RALC meters with configuration Test Report No. - A3RAQ, A1860RALC and A1860RAL meters as
Elster Gmbh Otto-Hahn-Strasse 25 zia.shaban@its.sa ZE3KM4CF5LK-EL. 71240276-TIC confirming to SEC Specification # 40-TMSS-02,
D-68623 Lampertheim, Germany 6996-11, Rev.0 with the following condition:
Raleigh, Nc , United States A1860RAL meters with configuration PAKR-8ZNRH
ZE3KM4CF0LH-EL. Free Supply of Meter Type A3RAQ: Five (5)
Contact Person - Mr. Ali Mouslmani Revenue Meters Type A3RAQ shall be supplied
Email ID - ali.mouslmani@elster.com free of cost to SEC as confirmed through ELSTER
Website - http://www.elster.com/ letter # L1-ST12-001 dated January 21, 2012.
WARRANTY
Five (5) extended warranty/guarantee in respect
of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: 12-01-2012.
GEC MEASUREMENT
United Kingdom
Website -
http://www.gecinstruments.com/
LANDIS + GYR AG-ZUG Saudi Masar High Tech Type/Model - [(E650 (ZXD) & E850 ZXQ Test Report No. - Based on S&SD Letter 14-04075-30504401 dated
SWITZERLAND Marketing Co. Rating - Cl 0.2s Active Cl 0.5 Reactive Yes April 2014 July 01, 2014, it is pre-qualified for Revenue
Industrial City, Phase 3, Meters Type E650 (ZXD) & E850 (ZXQ)
Landis+Gyr Ag Zug/Switzerland Jeddah CR No conforming to National Grid SA specifications #
Theilerstr. 1 63O1 Zug,Switzerland. 4030118442, 40-TMSS-03, Rev.1 and 40-TMSS-02 Rev.0 with
Zug , Switzerland Phone - 0096612608 the following conditions:
0581
Contact Person - Mr. Akhlak WARRANTY
Husain,Area Manager. Ten (10) years extended warranty/guarantee in
Phone - +971 558854159 respect of defects due to design, manufacture,
Email ID - AkhIak.husain@landisgyr.com installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: jan 30, 2014.
WARRANTY
Five (05) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by TYCO Electronic UK
through their letter # INT-SEC-06 dated January
03, 2008 and its Amendment dated Nov 21, 2011.
Total = 8
METERS
14. 2
METERING DEVICES (AMMETER, VOLTMETER, MW, MVAR) Applicable Standards: 40-TMSS-02
AREVA
FRANCE
Plant -France
Website - http://www.areva.com/
CELSA, ITALY
ITALY
Italy
Website - http://www.celsa.com/
CEWE
SWEDEN
Website - http://www.cewe.com/
WARRANTY
ENTES (Turkey) has agreed to give SEC a
Guarantee/ Warranty on the proposed digital
meters for a period of two (02) years and eight
(08) years (for maintenance) for total of ten (10)
years from the date of PAC of the turnkey project
in case of contract award or date of delivery in
case of direct material supply order.
SCHNEIDER ELECTRIC Schneider Electric Type/Model - ION 6200 DIGITAL POWER METERS TYPE ION 6200 (0.5%
CANADA Contact Rating - upto 600V 0-5 amps 0.5 ACCURACY CLASS);
Person:Senthilkumar Kp accuracy class
Plant -Victoria, Canada senthilkumar.kp@schnei WARRANTY
der-electric.com ( and ) Ten (10) years extended warranty/guarantee in
2195 Keating Cross Road Saanichton ahm respect of defects due to design, manufacture,
British Columbia Canada V8M 2A5 installation & workmanship from the date of
Canada Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
Email ID - date of delivery in case of direct material supply
hares.habre@schneider-electric.com order.
Website -
http://www.schneider-electric.ca/
http://www/en/html/frontpage.htm
WARRANTY
Five (05) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by TYCO Electronic UK
through their letter #INT-SEC-06 dated January
03, 2008 and its Amendment dated Nov 21, 2011.
Total = 7
METERS
14. 3
AUTOMATIC METER READING (AMR) SYSTEM INTEGRATOR, AUTOMATIC METER READING Applicable Standards: 40-TMSS-03 (Rev.0)
(AMR) SYSTEM
ADVANCE ELECTRONICS CO., LTD. Based on approval of Executive Directive for
Saudi Arabia TS&SD Letter # 08-1105-03032301 dated
20/10/2008, it is pre-qualified for Energy Meters
Riyadh , Saudi Arabia Type (ADDAD-4) & Quality Meters
Type(SEL-734).
WARRANTY
Ten (10) years extended warranty from the date
of PAC of the first turnkey project (in case of
contract award) or date of first delivery in case
of direct material supply order as confirmed
through Ideal Technical Solutions (ITS), KSA,
Riyadh letter # W1-NG01-J13-001 dated January
08, 2013 and L1-ST12-020 dated December 03,
2012.
Total = 2
METERS
14. 4
ADVANCED METERING INFRASTRUCTURE (AMI) SYSTEM INTEGRATOR, ADVANCED Applicable Standards: 40-TMSS-03 (Rev.01)
METERING INFRASTRUCTURE (AMI)
WARRANTY
Ten (10) years extended warranty from the date
of PAC of the first turnkey project (in case of
contract award) or date of first delivery in case
of direct material supply order as confirmed
through Ideal Technical Solutions (ITS), KSA,
Riyadh letter #W1-NG01-J14-001 dated January
01,2014 and Letter#L1-NG01-J14-001 dated
December 03, 2013.
CONDITION
System Demo: Live Demo of the AMI System will
be conducted in presence of SEC/National Grid
SA Engineers on the first system to be
manufactured in SEP factory already confirmed
through Ideal Technical Solutions (ITS), KSA,
Riyadh letter #L1-NG01-J14-002, dated January
06,2014.
WARRANTY
Ten (10) years extended warranty in respect of
the defects due to design, manufacturing,
installation and workmanship from the date of the
Provisional Acceptance Certificate (PAC) of the
first turnkey project (in case of contract award)
and from the date of first delivery in case of
direct material supply order shall be provided as
confirmed by the manufacturer through their
letter # AES-AMI-PQA-2014/001 dated July 09,
2014.
Riyadh WARRANTY
• Ten (10) years extended warranty in respect of
Contact Person - Mr. Bruno Stocchi the defects due to design, manufacturing,
Contact Person Email ID - installation and workmanship from the date of the
majed@sep.com.sa, Provisional Acceptance Certificate (PAC) of the
bruno@sep.com.sa first turnkey project (in case of contract award)
and from the date of first delivery in case of
direct material supply order shall be provided as
confirmed by the manufacturer through their
letter No. SEP/AMI/2015/06 dated September
15,2015.
Total = 6
METERS
14. 5
REVENUE METER Applicable Standards: 40-TMSS-03
ADVANCE ELECTRONICS CO., LTD. Energy Meters Type (ADDAD-4) Based on approval of Executive Directive for
Saudi Arabia TS&SD Letter # 08-1105-03032301 dated
20/10/2008, it is pre-qualified for Energy Meters
Riyadh , Saudi Arabia Type (ADDAD-4) as confirming to SEC
Specification # 40-TMSS-03, Rev.0
LANDIS + GYR AG-ZUG Revenue Meters Type E650 (ZXD) & PQ Letter
SWITZERLAND E850 (ZXQ) Based on S&SD Letter 14-04075-30504401 dated
July 01, 2014, it is pre-qualified for Revenue
Landis+Gyr Ag Zug/Switzerland Meters Type E650 (ZXD) & E850 (ZXQ)
Theilerstr. 1 63O1 Zug,Switzerland. conforming to National Grid SA specifications #
Zug , Switzerland 40-TMSS-03, and 40-TMSS-02 with the following
conditions:
Contact Person - Mr. Akhlak
Husain,Area Manager. WARRANTY
Phone - +971 558854159 Ten (10) years extended warranty from the date
Email ID - AkhIak.husain@landisgyr.com of PAC of the first turnkey project in case of
contract award or date of first delivery in case of
direct material supply order. This was confirmed
by the manufacturer through their letter # Nil,
dated January 30, 2014.
WARRANTY
Five (5) years extended warranty from the date
of PAC of the first turnkey project in case of
contract award or date of first delivery in case of
direct material supply order as confirmed through
ELSTER letter # NIL dated 12-01-2012.
Total = 5
METERS
14. 6
POWER QUALITY METER Applicable Standards: 40-TMSS-03
ELECTRO INDUSTRIES / GAUGETECH Power Quality Meters type NEXUS Yes PQ Letter
United States 1500 Based on S&SD Letter 13-00862/03-030504401
dated April 20, 2013, Electro Industries/
New York United States GaugeTech, New York, USA is pre-qualified for
Power Quality Meters type NEXUS 1500 as
conforming to National Grid SA specification #
40-TMSS-03, Rev.0, with the following
conditions:
CONDITION:
Product Support: Continuous supply and product
support of Power Quality Meters type NEXUS
1500 to all SEC/ National Grid SA approved AMR
Manufacturers for a minimum period of ten (10)
years shall be ensured as confirmed through
their letter # Nil dated January 01, 2012.
WARRANTY:
Ten (10) years extended warranty from the date
of PAC of the first turnkey project (in case of
contract award) or from the date of first delivery
of direct material supply order as confirmed by
Electro Industries /Gauge Tech -New York, USA
through their letter # L1-NG01-J13-004 dated
January 29, 2013.
Total = 2
PROTECTIVE RELAYS
15. 1
TRANSMISSION LINE PROTECTIVE RELAYS 380/132/115/110kV Applicable Standards: 41-TMSS-01
Built In Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’s+12BO’s
8CT+4VT+16BI’s+16BO’s
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering Code:
P54631NK7M0710M
Built In Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
Hardware:
4CT+4VT+12BI’s+12BO’s
8CT+4VT+16BI’s+16BO’s
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
SCHNEIDER ELECTRIC Schneider Electric EPS Type/Model - 8 Models of MICOM Test Date - April Old Comments:
United Kingdom Ltd P546 2014 PQ Letter
PO Box 89249 Riyadh Rating - 380/132/115/110 kV Based on S&SD letter # 14-040883-2-30504401
Plant -United Kingdom-Stone 11682 Saudi Arabia Ordering Code: P54631NA7M0D08M dated June 12, 2014, M/s Schneider Electric from
Phone - Built in Functions: 87L, Under current United Kingdom – stone is prequalified for MiCOM
Schneider Electric Energy Ltd Unit 9 +966-11-291-28-77 x 37,Inrush Blocking, Under / over P546 as per the following conditions:
Opal Way Stone Business Park Stone 360 Frequency 81,open conductor
St15 0Ss United Kingdom Stone , United Email - protection, Second harmonic detection, CONDITION:
Kingdom padma.raja@schneider- 21P&G, 67DEF, 79 (1 CB or 2 CB) Type tests shall be carried out on the MiCOM
electric.com controlled + 25, SEF, 50/51PH&GR / P546 relays as per new IEC 61850-10 (2012-12)
Contact Person - Mr. Paul Kerr SEF/46, 67P/ 67N ,49 Thermal edition 2 in the approved Independent Testing
Phone - +44 7917 534038 Overload, 27/59/59N, 50BF, 74 DC laboratory witnessing by three (3) National Grid
Email ID - supply supervision, 74 Trip circuit SA engineers and one (1) approved Independent
paul.kerr@schneider-electric.com supervision, CT Supervision, 60 VT Agency Inspector (IIA). All costs of witnessing
Website - Supervision, DFR/SOE / Fault Locator the tests shall be borne by the manufacturer as
http://www.schneider-electric.com Hardware: 8xCT(Ph) + 5xVT, 32 Digital per their confirmation through letter # Nil dated
Inputs, 24Digital Outputs, Protection October 23, 2013.
data interface-1 850,
Protection data interface-2 850, WARRANTY:
IEC61850, 2 x Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
port(PRP) installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
Old Ordering Code: first turnkey project in case of contract award or
P54631NL7M0D08M date of delivery in case of direct material supply
New Ordering Code: order.
P54631QL7M0H88M
Built in Functions: 87L, Under current PQ Letter
37,Inrush Blocking, Under / over Based on S&SD letter # 14-040883-2-30504401
Frequency 81,open conductor dated June 12, 2014, M/s Schneider Electric from
protection, Second harmonic detection, United Kingdom – stone is prequalified for MiCOM
21P&G, 67DEF, 79 (1 CB or 2 CB) P543 as per the following conditions:
controlled + 25, SEF, 50/51PH&GR /
SEF/46, 67P/ 67N ,49 Thermal CONDITION:
Overload, 27/59/59N, 50BF, 74 DC Type tests shall be carried out on the MiCOM
supply supervision, 74 Trip circuit P543 relays as per new IEC 61850-10 (2012-12)
supervision, CT Supervision, 60 VT edition 2 in the approved Independent Testing
Supervision, DFR/SOE / Fault Locator laboratory witnessing by three (3) National Grid
Hardware: 8xCT(Ph) + 5xVT, 32 Digital SA engineers and one (1) approved Independent
Inputs, 24Digital Outputs, Protection Agency Inspector (IIA). All costs of witnessing
data interface-1 1300, Protection data the tests shall be borne by the manufacturer as
interface-2 850, IEC61850, 2 x per their confirmation through letter # Nil dated
Built in Functions: 87L, Under current United Kingdom – stone is prequalified for MiCOM
37,Inrush Blocking, Under / over P841 as per the following conditions:
Frequency 81,open conductor
protection, Second harmonic detection, CONDITION:
21P&G, 67DEF, 79 (1 CB or 2 CB) Type tests shall be carried out on the MiCOM
controlled + 25, SEF, 50/51PH&GR / P841 relays as per new IEC 61850-10 (2012-12)
SEF/46, 67P/ 67N ,49 Thermal edition 2 in the approved Independent Testing
Overload, 27/59/59N, 50BF, 74 DC laboratory witnessing by three (3) National Grid
supply supervision, 74 Trip circuit SA engineers and one (1) approved Independent
supervision, CT Supervision, 60 VT Agency Inspector (IIA). All costs of witnessing
Supervision, DFR/SOE / Fault Locator the tests shall be borne by the manufacturer as
Hardware: 4CT+4VT+ 12BI's+12BO's, per their confirmation through letter # Nil dated
CH-1 1550nm, CH-2 850nm, IEC61850, October 23, 2013.
2 x port(PRP)
WARRANTY:
Ten (10) years extended warranty/guarantee in
Models of MICOM : P142 respect of defects due to design, manufacture,
Ordering Code: P14231NC7M0468J installation & workmanship from the date of
Built in Functions: 87L High Impedance, Provisional Acceptance Certificate (PAC) of the
95 CT bus wire supervision, first turnkey project in case of contract award or
50/51PH&GR / SEF/46, 67P/ 67N , date of delivery in case of direct material supply
SEF,49 Thermal Overload, 27/59/59N, order.
50BF, 74 DC supply supervision, 74
Trip circuit supervision, CT
Supervision, 60 VT Supervision,
DFR/SOE / Fault Locator
Hardware: 5xCT(Ph) + 3xVT, 16 Digital
Inputs, 7Digital Outputs, IEC61850, 2 x
port(PRP)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’S+12BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering code:
L90-K03-HKH-F8L-H6L-L6U-W73(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’S+12BO’S
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering code:
L90-K05-HKH-F8L-H6L-L8N-N6D-S67-
U67-W7K(*)
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
L90
Ordering code:
L90-K05-HKH-F8L-H6L-L8N-N6D-S67-
U67-W73(*) (*)
CH2 to be attenuated to fit SDH
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’s+12BO’s
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P0
1-B1X-CB-KB-B-B6X0-D1A-CA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
Hardware:
4CT+4VT+12BI’s+12BO’s
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P0
1-B1X-CB-KB-B-B6B6-D1A-BA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Relay Type:
RED 670
Ordering code:
RED670*1.2-B32X00-B10B11B21C24P0
1-B1X-CB-KB-B-B6B6-D1A-CA-XE
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering code:
0411L1X6X1C7CEXH5C424XX
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
27/59/59N
50BF
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
8CT+4VT+16BI’S+16BO’S
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
Hardware:
4CT+4VT+12BI’S+12BO’S
CH-1 1300nm, CH-2 850nm
IEC 61850,2-PORTS
Ordering code:
7SD5221-5CB99-9HK0+L0S+M0J+N7A
Built in Function:
87L(Dual Combined Slope)
21P&G(5 Zones,Quad+Mho+Bi)
67DEF with comm. Schem
79(2CBs OR 1CB controlled)+25
50/51PH&GR/SEF/46
67P/67N
49 Thermal overload
27/59/59N
50BF
74DC supply supervision
74 trip relay Coil Supervision
CT Supervision
60 VT Supervision
DFR/SOE /F locator
Hardware:
4CT+4VT+12BI’S+12BO’S
CH-1 1550nm, CH-2 850nm
IEC 61850,2-PORTS
(NEW TYPE):
Type 7SL87
Ordering code:
7SL87-P1C69289
Built-in functions:
87L Dual Combined Slop
21P&G
67DEF with Comm. Scheme
79+25
50/51PH&GR/SEF/46
67P/67N
49
27/59/59N
50BF
Inrush Blocking
Supervision & Monitoring Functions:
74DC Supervision
74TC
74 Lockout Supervision
CT supervision
60VT
DFR/SOE/F locator
1/3 POLE
Hardware:
4 CT
4 VT
23 BI
22 BO
Protection Interface 1:1550nm (100km)
Type 7SL86
Ordering code:
7SL86-P1C42556
Built-in functions :
87L Dual Combined Slop
21P&G
67DEF with Comm. Scheme
79+25
50/51PH&GR/SEF/46
67P/67N
49
27/59/59N
50BF
Inrush Blocking
Supervision & Monitoring Functions:
74DC Supervision
74TC
74 Lockout Supervision
CT supervision
60VT
DFR/SOE/F locator
Hardware:
4 CT
4 VT
23 BI
22 BO
Protection Interface 1:1300nm (60km)
Protection Interface 2:820nm (1.5km)
IEC61850 -PRP x 2 FO ports
Type 7SL86
Ordering code:
7SL86-P1C40594
Hardware:
4 CT
4 VT
23 BI
22 BO
Protection Interface 1:1550nm (100km)
Protection Interface 2:820nm (1.5km)
IEC61850 -PRP x 2 FO ports
Total = 6
PROTECTIVE RELAYS
15. 2
POWER TRANSFORMER PROTECTION RELAYS Applicable Standards: 41-TMSS-01
Ordering code:
8IDVD4F22Z904VKL
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67N/67N(All windings)
50 BF
49T
74 DC supply supervision.
Hardware:
3-WINDING:
12xCT(Ph)+2xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
SCHNEIDER ELECTRIC Schneider Electric EPS Type/Model - 9 Models of MICOM P643 Old Comments:
United Kingdom Ltd + MiCOM P849 Test Date - April PQ Letter
PO Box 89249 Riyadh Rating - 380/132/115/110 kV 2014 Based on S&SD letter # 14-040883-2-30504401
Plant -United Kingdom-Stone 11682 Saudi Arabia Old Ordering Code: dated June 12, 2014, M/s Schneider Electric from
Phone - P64332QA6M0B08M + United Kingdom – stone is prequalified for MiCOM
Schneider Electric Energy Ltd Unit 9 +966-11-291-28-77 x P84930NA6M0A08K P643 + MiCOM P849 as per the following
Opal Way Stone Business Park Stone 360 New Ordering Code: conditions:
St15 0Ss United Kingdom Stone , United Email - P64332QABM0B28M +
Kingdom padma.raja@schneider- P84930QE7M0B18M CONDITION:
electric.com Built in Functions: 87T ( Dual Combined Type tests shall be carried out on the MiCOM
Contact Person - Mr. Paul Kerr Slope), 87REF (low Impedance), 87REF P643 + MiCOM P849 relays as per new IEC
Phone - +44 7917 534038 (High Impedance), 87/50 Instantaneous 61850-10 (2012-12) edition 2 in the approved
Email ID - Diff, 50/51PH&GR All Windings, Independent Testing laboratory witnessing by
paul.kerr@schneider-electric.com 67P/67N (All Windings), 27/59/25, three (3) National Grid SA engineers and one (1)
Website - 81U/O, 50BF, 49T, 24, 74 DC supply approved Independent Agency Inspector (IIA). All
http://www.schneider-electric.com supervision, 74 Trip circuit supervision, costs of witnessing the tests shall be borne by
CT Super. (All Windings), 60 VT the manufacturer as per their confirmation
Supervision, DFR/SOE, through letter # Nil dated October 23, 2013.
Hardware: 15xCT(Ph) + 3xCT(Gnd) +
4xVT, 32+16 Digital Inputs, 16+16 WARRANTY:
Digital Outputs, IEC61850, 2 x port Ten (10) years extended warranty/guarantee in
(PRP) respect of defects due to design, manufacture,
installation & workmanship from the date of
Old Ordering Code: Provisional Acceptance Certificate (PAC) of the
P64332QA6M0B08M + first turnkey project in case of contract award or
P84930NE6M0A08K date of delivery in case of direct material supply
New Ordering Code: order.
P64332QABM0B28M +
P84930QE7M0B18M
Built in Functions: 87T ( Dual Combined PQ Letter
Slope), 50/51PH&GR/SEF/46, 67P/67N, Based on S&SD letter # 14-040883-2-30504401
49Therma l overload, 27/59/81/59N, dated June 12, 2014, M/s Schneider Electric from
50BF74 DC supply supervision, CT United Kingdom – stone is prequalified for MiCOM
Supervision, 60 VT Supervision, P642 + MiCOM P849 as per the following
DFR/SOE conditions:
Hardware: 9xCT(Ph) + 3xCT(G) +
4xVT , 16+64 Digital Inputs, 16+16 CONDITION:
Digital Outputs, IEC61850, 2 x port Type tests shall be carried out on the MiCOM
(PRP) P642 + MiCOM P849 relays as per new IEC
61850-10 (2012-12) edition 2 in the approved
MiCOM P642 – MiCOM P849 Independent Testing laboratory witnessing by
Old Ordering Functions: three (3) National Grid SA engineers and one (1)
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
14xCT(Ph)+4xCT(Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2-ports
Ordering code:
RET670*1.2-B40X00-A01A02D04E01P
01-B1X-C-B-KB-B-B3B3-D1A-XE
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
14xCT(Ph)+4xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Hardware:
2-WINDING:
9xCT (Ph) + 4xCT (Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2-ports
Ordering code:
P64532NA6M0040K
Built in Functions:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instantaneous Diff
50/51PH&GR all windings
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC Supply Supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
15xCT(Ph)+3xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
GE MULTILIN
CANADA T 60
Ordering code:
Markham , Canada T60-K22-HKH-F8F-H6L-M8N-PXX-U8N-
WXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
50/51PH&GR all windings.
67P/67N(All windings)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
2-WINDING:
15xCT(Ph)+5xCT(Gnd)
8xcontact inputs
4xcontact outputs
3-WINDING:
IEC 61850 2-ports
Ordering code:
T60-K22-HKH-F8F-H6L-M8N-P6T-U8N-
WXX
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
87/50 Instan Diff
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
74 Lockout coil supervision
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
15xCT(Ph)+5xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Hardware:
2-WINDING:
8xcontact inputs
4xcontact outputs
3-WINDING:
15xCT(Ph)+3xCT(Gnd)
Hardware:
2-WINDING:
9xCT(Ph)+4xCT(Gnd)
3-WINDING:
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
Ordering code:
7UT6351-5EB92-1BC1+L0S
Built in Function:
87L (dual combined slope)
87 REF (low impedance)
87 REF (High impedance)
27/59/25
81 U/O
50 BF
49T
24
74 DC supply supervision.
CT Super (All windings)
60
DFR/SOE
Hardware:
3-WINDING:
12xCT(Ph)+4xCT(Gnd)
16xcontact inputs
8xcontact outputs
IEC 61850 2 ports
(NEW TYPE):
Type 7UT85
Ordering code:
7UT85-P1F29980
Built-in functions:
87T Dual combined slop
87REF low Impedance
87REF High Impedance
87/50 Instantaneous Diff
50/51PH&GR All Windings
67/67N All Windings
27/59/25
81U/O
50BF
49T
24
Inrush Blocking
Supervision & Monitoring Functions:
74DC Supervision
74TC
74 Lockout Supervision
CT supervision
60VT
DFR/SOE
Hardware:
9 PH CT + 3 GND CT
4 VT
21 BI
28 BO
IEC61850 -PRP x 2 FO ports
Total = 7
PROTECTIVE RELAYS
15. 3
Double BUS-BAR Single CB 132/115/110 kV Relays Applicable Standards: 41-TMSS-01
ABB-Ludvika REB500 CU
SWEDEN Ordering code:
REB500-CU03-V76-S30-P0-B0-CA3-C
Plant -Sweden B3
Hardware:
CU: 8BI’s+8BO’s
24 PU connected to CU
IEC 61850, 2-PORTS
Ordering code:
REB500-CU03-V76-S50-P0-B0-CA3-C
B3
Built in Function:
87BB: Biased Current Differential high
speed BBP with built in check zone
CT Supervision
Intertrip facility
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BI’s+8BO’s
48 PU connected to CU
IEC 61850, 2-PORTS
:
REB500 PU
Ordering code:
REB500-BU03-C2-A40-P0-F1-BB2-IO0-
R0-OC0-BFP1-E
FP1-PD0-DR0-L0-T0+1MRB150073R00
52
Built in Function:
50BF: stage1
50BF: stage2
End fault protection with Interntrip or
Dead Zone
HMI
DFR/SOE
Hardware:
PU: 4CT+16BI’S+12BO’S
Hardware:
CU: 8BI’S+8BO’S
24 PU connected to CU
IEC 61850, 2-PORTS
MICOM P740
Ordering code:
P74331NA6M0510K
Built in Function:
50BF: stage1
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or
Dead Zone
HMI
DFR/SOE
Hardware:
PU: 4CT+16BI’s+12BO’S
IEC 61850, 2-PORTS
SIEMENS 7SS52x CU
GERMANY Ordering code:
7SS5220-4AB92-1CA0+L0R
Nonnendammallee 104, 13629 Berlin
Germany Built in Function:
87BB: Biased Current Differential high
Contact Person - Mr. Andre Holldorf speed BBP with built in check zone
Phone - +49-(30)-386-57542 50BF: stage1
Email ID - andre.holldorf@siemens.com 50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or
Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BI’s+8BO’s
24 PU connected to CU
IEC 61850, 2-PORTS
Ordering code:
7SS5220-4AB92-1FA0+L0R
Built in Function:
87BB: Biased Current Differential high
speed BBP with built in check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or
Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
CU: 8BI’s+8BO’s
48 PU connected to CU
IEC 61850, 2-PORTS
7SS52x PU
Ordering code:
7SS5231-5CA01-1AA1
*BO=6 with double contact
Built in Function:
87BB: Biased Current Differential high
speed BBP with built in check zone
50BF: stage1
50BF: stage2
CT Supervision
50/51 : Phase Over current Protection
50N/51N : Earth Fault
Intertrip facility
End fault protection with interntrip or
Dead Zone
Selective Zone tripping and blocking
HMI
DFR/SOE
Hardware:
PU: 4CT+16BI’s+12BO’S
Total = 3
PROTECTIVE RELAYS
15. 4
33kV Plain OH Feeder + UG + Incomer Relays Applicable Standards: 41-TMSS-01
ABB-Ludvika
SWEDEN REL 670
Ordering code:
Plant -Sweden REL670*1.2-A31X00-H07P01-B1X-AX-
KB-B-B6X0-D1A-XX-XE
Ludvika, Sweden
Built in Function:
Contact Person - Mr. Magnus Control & MIMIC
Johansson 21 P&GD
Phone - +46 240 783228 50N/51 P&G
Email ID - 67P/67N
magnus.s.johansson@se.abb.com 49 Thermal Overload
Website - http://www.abb.se/ Phase unbalance 46
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16 BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Hardware:
16 BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
(NEW TYPE):
Type 7SL86
Ordering code:
7SL86- P1C69261
Built-in functions:
87L Dual Combined Slop
21P&G
67DEF with Comm. Scheme
79+25
50/51PH&GR/SEF/46
67P/67N
49
27/59/59N
50BF
Inrush Blocking
Supervision & Monitoring Functions:
74DC Supervision
74TC
74 Lockout Supervision
CT supervision
60VT
DFR/SOE/F locator
Hardware:
3 PH CT+ 1 SENSITIVE GND CT
4 VT
23 BI
22BO
Protection Interface 1:1300nm (24km)
Protection Interface 2:1300nm (24km)
IEC61850 -PRP x 2 FO ports
SEL SEL421
United States Ordering code:
04214611XC2X43224XXXX
Website -
http://www.selindustrial.com/ Built in Function:
Control & MIMIC
21 P&GD
50N/51 P&G
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
15BI+23 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Total = 4
PROTECTIVE RELAYS
15. 5
13.8kV Plain OH Feeder + UG + Incomer Relays Applicable Standards: 41-TMSS-01
- REF620
Ordering code:
NBFNAANNEA1XF
GE MULTILIN F650
SPAIN Ordering code:
F650-NFD-F2G1-HI-6E
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Hardware:
16 BI+ 07 BO
3CT(Ph) + 1CT(GD)+3VT
IEC 61850, 2-Optical Ports PRP
Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
14BI+6 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
SEL SEL-451
United States Ordering code:
04515611XC2X4H244XXXX
Website -
http://www.selindustrial.com/ Built in Function:
Control & MIMIC
50N/51 P&GD
67P/67N
49 Thermal Overload
Phase Unbalance 46
Undercurrent 37
27/59
Auto reclosure 79
50BF
Trip circuit Supervision 74TC
Inrush Blocking
Under/Over frequency 81
CT Supervision
60 (VT Fuse Supervision)
DFR/SOE
Hardware:
16BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
Hardware:
15BI+07 BO
3CT(Ph)+1CT(GD)+3VT
IEC 61850,2-PORTs FIBER OPTIC
(NEW TYPE);
Type 7SL86
Ordering code:
7SL86- P1C69261
Built-in functions:
87L Dual Combined Slop
21P&G
67DEF with Comm. Scheme
79+25
50/51PH&GR/SEF/46
67P/67N
49
27/59/59N
50BF
Inrush Blocking
Supervision & Monitoring Functions:
74DC Supervision
74TC
74 Lockout Supervision
CT supervision
60VT
DFR/SOE/F locator
Hardware:
3 PH CT+ 1 SENSITIVE GND CT
4 VT
23 BI
22BO
Protection Interface 1:1300nm (24km)
Protection Interface 2:1300nm (24km)
IEC61850 -PRP x 2 FO ports
Total = 6
PROTECTIVE RELAYS
15. 6
13.8kV and 33kV Capacitor Bank Relays Applicable Standards: 41-TMSS-01
ABB-Ludvika REC670
SWEDEN Ordering code:
1MRK 002 814-AC
Plant -Sweden
Built in Function:
Ludvika, Sweden 27P
50/51 P&G
Contact Person - Mr. Magnus Undercurrent
Johansson 50 2
Phone - +46 240 783228 59B&59N
Email ID - 59 2
magnus.s.johansson@se.abb.com Harmonic Overload
Website - http://www.abb.se/ 60P&N
87V phase&neutral
67 P&G
67 2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+16BI’s+24BO’s
IEC 61850,2-PORTS
GE MULTILIN C70
CANADA Ordering code:
C70-K03-HKH-F8N-H6D-M8V-P67-U6D-
Markham , Canada W67
Built in Function:
27P
50/51 P&G
Undercurrent
50 2
59B&59N
59 2
Harmonic Overload
60P&N
87V phase&neutral
67 P&G
67 2
60 VT Supervision
DFR/SOE
Hardware:
6CT+6VT+16BI’s+20BO’s
IEC 61850,2-PORTS
Hardware:
6CT+6VT+15BI’s+23BO’s
IEC 61850,2-PORTS
Total = 3
PROTECTIVE RELAYS
15. 7
Tripping and Lockout Relay Applicable Standards: 41-TMSS-01
ALSTOM MVAJ
United Kingdom Ordering code:
MVAJ101RA0802A
United Kingdom
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any
configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC:
7500VA/W with Max of 30A,300V
(Make & Carry (continuous))AC/DC:
1250VA/W with Max of 5A,300V
(Break) AC/DC: 1250VA/W with MAX
of 5A,300V,DC 80w Resistive,40w
Inductive (L/R=0.04sec)
Ordering code:
MVAJ105RA0802A
Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any
configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC:
7500VA/W with Max of 30A,300V
(Make & Carry (continuous))AC/DC:
1250VA/W with Max of 5A,300V
(Break) AC/DC: 1250VA/W with MAX
of 5A,300V,DC 80w Resistive,40w
Inductive (L/R=0.04sec)
Note-Withdrawable from Case
ELECTRO-SWITCH LOR/HR
United States Ordering code:
LOR/HR-7810F
Website -
http://www.electroswitch.com/ Standard Specification :
Hand & Electrical Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any
configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC:
7500VA/W with Max of 30A,300V
(Make & Carry (continuous))AC/DC:
1250VA/W with Max of 5A,300V
(Break) AC/DC: 1250VA/W with MAX
of 5A,300V,DC 80w Resistive,40w
Inductive (L/R=0.04sec)
Ordering code:
LOR/SR-7868FD
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any
configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC:
7500VA/W with Max of 30A,300V
(Make & Carry (continuous))AC/DC:
1250VA/W with Max of 5A,300V
(Break) AC/DC: 1250VA/W with MAX
of 5A,300V,DC 80w Resistive,40w
Inductive (L/R=0.04sec)
RELAY MONITORING SYSTEM (RMS) Relays group of High Speed Tripping Relay , Type test witnessed PQ Letter
AUSTRALIA Companies Type: 6RJ21 by three Based on S&SD letter # 15-02815-2-030504401
P.O. Box 101709 , Ordering Code: 6RJ21-10-D-8M2B SEC/National Grid dated 30 June 2015, the manufacturer is
6 Anzed Court Mulgrave 3170 Riyadh 11665 Kingdom High Burden Tripping Relay , SA Engineers during prequalified for: High Speed Tripping Relay, Type:
Melbourne Victoria Australia Po Box of Saudi Arabia Type: 6RJ25 25th May-3rd June 6RJ21
1166 Huntingdale Tel: 00 9661 Ordering Code: 6RJ25-10-D-8M2B 2015.
4727902/4724320/47324 Test were As conforming to National Grid SA specification #
Contact Person - Mr. Alphonse 61 - Fax: 00 966 Conducted in RMS 41-TMSS-01,
Fernandez Export Manager E-Mail: Lab and Report No. Rev.0 with the following condition:
Phone - +61-3-8544-1200 thuraibi@erelaysgroup.c 19301901001 (TUV)
Email ID - rms@rmspl.com.au , om, rbakshi@erelays SEC Report#Nil WARRANTY:
Alphonse.fernandez@rmspl.com.au Dated 14-10-2014 Ten (10) years extended warranty from the date
Website - http://www.rmspl.com.au of PAC of the first turnkey project in case of
contract award and subsequently reduced
yearly (in case of future project award). and
from the date of first delivery in case of direct
material supply order. This was confirmed in
writing by the manufacturer, as confirmed by the
manufacturer thru letter #nil dt: Nov 07, 2013.
SIEMENS TR241
GERMANY Ordering code:
TR241-7PG1524-1JC60-1AF0
Berlin, Germany
IC SG EA MF Standard Specification :
Wernerwerkdamm 5, Hand & Electrical Reset
13629, Berlin, Germany High Burden
Flag indication, hand reset
Phone - +49 (911) 433 8321 Upto 10 contracts (in any
Website - configuration)(8 NO & 2 NC)
www.siemens.com/ingenuityforlife Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC:
7500VA/W with Max of 30A,300V
(Make & Carry (continuous))AC/DC:
1250VA/W with Max of 5A,300V
(Break) AC/DC: 1250VA/W with MAX
of 5A,300V,DC 80w Resistive,40w
Inductive (L/R=0.04sec)
Note-Withdrawable from Case
TR212
Ordering code:
TR212-7PG1521-2JC60-1AF0
Standard Specification :
Self Reset
High Burden
Flag indication, hand reset
Upto 10 contracts (in any
configuration)(8 NO & 2 NC)
Standard Hand Reset Flag Available
Operating Time in ms. (10ms)
Contact Ratings:
(Make & Carry (3 sec))AC/DC:
7500VA/W with Max of 30A,300V
(Make & Carry (continuous))AC/DC:
1250VA/W with
Max of 5A,300V
(Break) AC/DC: 1250VA/W with MAX
Total = 5
PROTECTIVE RELAYS
15. 8
Short Cable - all voltage levels Applicable Standards: 41-TMSS-01
ABB-Ludvika RED670
SWEDEN Ordering code:
RED670*1.2-B32X00-C24P02-B1X-C-B-
Plant -Sweden KB-B-B6X0-D1AX-AAXXXX
-XE
Ludvika, Sweden Built in Function:
Basied diff. Protection
Contact Person - Mr. Magnus Breaker Failure (50BF)
Johansson DC Supply Supervision
Phone - +46 240 783228 50/51+50N/51N
Email ID - Current Circuit Supervision
magnus.s.johansson@se.abb.com Hardware:
Website - http://www.abb.se/ Analog Inputs (6CT+6VT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 850nm, CH-2 850nm (up to 3km)
IEC 61850 -2 Ports
Relay Type:
RED670
Ordering code:
RED670*1.2-B32X00-C24P02-B1X-C-B-
KB-B-B6X0-D1AX-BBXXXX
-XE
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT+6VT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 1310nm, CH-2 1310nm (up to
80km)
IEC 61850 -2 Ports
GE L90
CANADA Ordering code:
L90-K03-HKH-F8L-H6G-L6T-N67-S67-
W77
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Ordering code:
L90-K03-HKH-F8L-H6G-L6T-N67-S67-
W2B
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to
24km)
IEC 61850 -2 Ports
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
Hardware:
Analog Inputs (5CT+4VT)
Binary Inputs – 16 Inputs
Binary Outputs 14
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Ordering code:
P54331NC7M0610M
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (5CT+4VT)
Binary Inputs – 16 Inputs
Binary Outputs 14
CH-1 1300nm, CH-2 1300nm (up to
50km)
IEC 61850 -2 Ports
SEL SEL411L
United States Ordering code:
0411L1X6X1C7CCXH5C424XX (2KM)
Website - Built in Function:
http://www.selindustrial.com/ Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1km)
IEC 61850 -2 Ports
Ordering code:
0411L1X6X1C7DDXH5C424XX (24KM)
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (6CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to
24km)
IEC 61850 -2 Ports
SIEMENS 7SD52
GERMANY Ordering code:
7SD5221-5CB99-9CJ0+L0S+M0A+N0A
Berlin, Germany
IC SG EA MF Built in Function:
Wernerwerkdamm 5, Basied diff. Protection
13629, Berlin, Germany Breaker Failure (50BF)
DC Supply Supervision
Phone - +49 (911) 433 8321 50/51+50N/51N
Website - Current Circuit Supervision
www.siemens.com/ingenuityforlife
Hardware:
Analog Inputs (3CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 820nm, CH-2 820nm (up to 1.5km)
IEC 61850 -2 Ports
Ordering code:
7SD5221-5CB99-9CJ0+L0S+M0G+N0G
Built in Function:
Basied diff. Protection
Breaker Failure (50BF)
DC Supply Supervision
50/51+50N/51N
Current Circuit Supervision
Hardware:
Analog Inputs (3CT)
Binary Inputs – 16 Inputs
Binary Outputs 24
CH-1 1300nm, CH-2 1300nm (up to
24km)
IEC 61850 -2 Ports
Total = 6
PROTECTIVE RELAYS
15. 9
High Impedance BBP for all levels Applicable Standards: 41-TMSS-01
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
ABB
SWEDEN REC670
Ordering code:
REC670*1.2-A30X00-A02C31P02-B1-A
A-KB-B-B6X0-D1A-XXX-XE
Built in Function:
87 3-Phase High Z Differential
(based on Voltage)
50/51N
Internal CT Bus Wire Supervision
(based on voltage )
74TC Trip circuit Supervision
External Stabilizing
Resistor
External Metrosil
External CT Shorting
Hardware:
6I+6U
24BO
16BI
IEC 61850,2-Optical Ports (PRP)
REB650
Ordering code:
1MRK006520-AD
Built in Function:
87 3-Phase High Z Differential
(based on Voltage)
50/51N
Internal CT Bus Wire Supervision
(based on voltage )
74TC Trip circuit Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
6I+4U
27BO
18BI
IEC 61850,2-Optical Ports (PRP)
Hardware:
3 CT Inputs
2 Output Contacts
Ordering code:
MCAG14SSD**** *A
Built in Function:
87 3-Phase High Z Differential
(Current Base)
External CT Bus Wire Supervision
External Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
1 CT Phase Inputs
2 Output Contacts
MFAC
Ordering code:
MFACI4S1B*0001A
Built in Function:
87 3-Phase High Z Differential.
(Based on Voltage)
External CT Bus Wire Supervision
Internal Stabilizing Resistor
External Metrosil
External CT Shorting
Hardware:
1 elements / phases voltage based
4 Output Contacts
SIEMENS 7SJ64
GERMANY Ordering code:
7SJ6411-5EB92-1FE0+L0S
Plant -Berlin. Germany
Built in Function:
Freyeslebenstr 1 91058 Erlangen 87 3-Phase High Z Differential
(based on current)50/51N
Contact Person - Mr. Yaser Salih Internal CT Bus Wire Supervision
Phone - +49-9131725216 (based on current )
Email ID - yaser.salih@siemens.com 74TC Trip circuit Supervision
Website - http:// External Stabilizing Resistor
http://www.siemens.de/Pages/EntryPa External Metrosil
ge Redirect.aspx External CT Shorting
Hardware:
4 CT Inputs
13BO
15BI
IEC 61850, 2-Optical Ports (PRP)
Total = 5
PROTECTIVE RELAYS
15. 10
Auxiliary Relays Applicable Standards: 41-TMSS-01
ALSTOM MVTP31
United Kingdom Ordering code:
MVTP31V1CB0751E
United Kingdom
Built in Function:
CT Supervision
Hardware:
SIEMENS AR 901
GERMANY Ordering code:
7PG1110-7AE10-0AF0
Plant -Berlin. Germany
Built in Function:
Freyeslebenstr 1 91058 Erlangen CT Shorting
Total = 4
PROTECTIVE RELAYS
15. 11
Bus Coupler and Bus Section 110 kV to 380 KV Applicable Standards: 41-TMSS-01
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
Total = 1
PROTECTIVE RELAYS
15. 12
Line 380kV CBF Applicable Standards: 41-TMSS-01
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
Total = 2
PROTECTIVE RELAYS
15. 13
380 KV LINE REACTOR Applicable Standards: 41-TMSS-01
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
Total = 1
PROTECTIVE RELAYS
15. 14
132-115-110 KV REACTOR BANK AND CAPACITOR BANK Applicable Standards: 41-TMSS-01
Total = 1
PROTECTIVE RELAYS
15. 15
13.8 KV CONSUMER FEEDER Applicable Standards: 41-TMSS-01
Hardware:
3 PH CT+ 1 SENSITIVE GND CT
4 VT
23 BI
22 BO
Protection Interface 1:1300nm (24km)
Protection Interface 2:1300nm (24km)
IEC61850 -PRP x 2 FO ports
Total = 2
PROTECTIVE RELAYS
15. 16
Inter Trip Send/Receive 380/132/115/110kV Applicable Standards: 41-TMSS-01
Total = 1
QUALITROL HATHAWAY
NORTHERN IRELAND
AMETEK (ROCHESTER)
United States
United States
Website -
http://www.ametekpower.com
ERL PHASE POWER TECHNOLOGIES Diyar Al Mobtekroon Int. TESLA 4000 Based on S&SD letter # 15-01879/02-030504401
LTD Co.\PO Box 89109 dated April 28, 2015, the manufacturer is
CANADA Riyadh 11682 KSA prequalified to supply Fault Recorder with the
Eng. Ali Al Ameel following conditions:
74 Scurfield Blvd, Winnipeg, Mb a.alameel@diyarksa.com
Canada R3Y 1G4 info@diyarksa.com - Ten (10) years extended for the Fault recorder
from the date of PAC of the turnkey project in
Contact Person - Mr. Ramaswami case of contract award or date of delivery in
Bharath case of direct material supply order. as
Phone - +204-477-0591 , confirmed through the manufacturer letter # Nil
Email ID - email Info@erlphase.com dated 18.10.2013.
Website - http://www.erlphase.com
DIgSILENT Al Haider For Trading & PFM 300 Type tests were Letter
GERMANY Contracting conducted in Based on S&SD letter # 16-10016-030504401
P.O. Box 18. Ras Tanura, DigSILENT test lab dated December 25, 2016, DIgSILENT,
Plant -Gomaringen Germany 31941,m KSA and S-Team Gomaringen Germany is pre-qualified for Digital
+966 3 667 0552 / 667 Electronic test lab Fault Recorder type PFM 300 as conforming to
Heinrich-Hertz-Strabe 9 3700 / 667 1660 during 21st to 23rd National Grid SA specification # 41-TMSS-02
72810 Gomaringen alhaiderpersonnel@yaho September 2016 Rev.0, with the following condition:
o.com /
Contact Person - Dr. Martin Schmieg, salahf4@yahoo.com warranty
Managing Director •Ten (10) years extended warranty from the date
Contact Person Email ID - of PAC of the first turnkey project (in case of
m.schmieg@digsilent.de contract award) and date of first delivery (in
Website - http://www.digsilent.de case of direct material supply order), as
confirmed, through their Letter No. Nill dated 12
August 2014 shall be applicable for all supplies to
the Company by DIgSILENT, Gomaringen
Germany
KoCos Messtechnik Germany Mohammed Al-Ojaimi SHERLOG CRX •Fault Record PQ letter:
GERMANY Contracting Est. System Report # Based on S&SD letter # 17-06723-030504401
KoCoS Messtechnik AG (E170309E1) by dated October 31, 2017, KoCos Messtechnik
Plant -Korbach, Germany Suedring 42 Phoenix TestLab – Germany is pre-qualified for Digital Fault
D-34497 Korbach, Germany Recorder (DFR) as conforming to latest National
KoCoS Messtechnik AG Germany •DFR & DSM Report Grid SA specification # 41-TMSS-02
Suedring 42 Tel. +49 5631 9596-0 # (U170309E1) by
D-34497 Korbach, Germany info@kocos.com Phoenix TestLab – WARRANTY:
Germany Ten (10) years extended warranty/guarantee in
Korbach •Functional Test respect of defects due to design, manufacture,
Report # Nill by installation and workmanship from the date of
Contact Person - KoCos Germany KoCos Messtechnik Provisional Acceptance Certificate (PAC) of the
(Lea-Sophie Kotthoff, Sales), Local – Germany first turnkey project in case of contract award or
Agent- Mohammed Al-Ojaimi date of first delivery in case of direct material
Contracting Est. (Abbad S. Ahmed, supply order, as confirmed by the manufacturer
Manager Energy Services.) vide letter # Nil, dated May 27, 2015.
Phone - Tel. +49 5631 9596-0
Email ID - info@kocos.com
Contact Person Email ID -
lkotthoff@kocos.com
abbad.ahmed@alojaimi.com
Website - www.kocos.com
Total = 5
CAPACITOR
17. 1
SHUNT CAPACITOR BANK, 13.8KV THROUGH 380KV Applicable Standards: 43-TMSS-01
NEW WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation and workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project (in case of project award)
and from the date of delivery for the direct
material supply order, as confirmed by the
manufacturer vide letter # Nil, dated May 01,
2017.
GRID SOLUTIONS OY LTD. Previously " Nokian Capacitors Ltd. –Finland", the
FINLAND name has been changed to Areva T&D Ltd. –
Finland based on TS&SD/ESD Letter #
Tampere , Finland 10-00145-03032301 dated January 16, 2010 and
P.O.Box 4, Kaapelikatu 3 fl-33331 Areva T&D Ltd.-Finland Letter # Nil dated January
Vehmaistenkatu 5 fl-33730 04, 2010, then the name has been changed again
to ALSTOM Grid Ltd. –Finland based on Dept Mgr,
Phone - +358 3 388311 S&SD E-mail dated February 26, 2012 and
Email ID - firstname.surname@ge.com ALSTOM Grid Ltd. letter # RN-2012-02-18 dated
Website - www.gegridsolutions.com February 18, 2012.
SAMWHA CAPACITOR CO. LTD Type / Model: Shunt Capacitor Banks PQ Letter:
KOREA, Republic of TS&SD Letter # 11-02016/01-03032301 dated
Rating: 13.8kV to 36kV Only 06/07/2011, it is pre-qualified for Substation Type
13.8kV to 36kV Only Shunt Capacitor Banks.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order as confirmed by the manufacturer through
their letter no.nil, dt: 12/03/2010..
Total = 6
Website - http://www.bae-berlin.de/
FIAMM
ITALY
Website -
http://www.fiamm.com/index.aspx
GOULD (GNB)
United States
Website - http://www.goulds.com/
HOPPECKE Cell
GERMANY Up to 24 OPzS
Website - http://www.hoppecke.com/.
Website - http://www.tab.si/
Website - http://tungstonepower.com/
YUASA
JAPAN
Website -
http://www.yuasabatteries.com/
C&D
United States
Website - http://www.cdtechno.com/
EXIDE
United States
Website - http://www.exide.com/
Website - http://www.varta.com/
Total = 12
AEG POWER SOLUTIONS SAS Originally was SAFT Power System SAS-France
FRANCE
BORRI S.P.A Sela for Power Type/Model - RTB.e The type test have PQ Letter:
ITALY Automation & Safety been conducted on S&SD Letter # 14-03226-01-030504401 dated
System Input 400 Vac 125 Vdc, 300 A June 4, 2014, pre-qualified for Battery Charger
Plant -Bibbiena(Arezzo) Italy Contact Person:Mr. Emad Output 125 Vdc battery charger at (125VDC, Type RTB.e).
Abu Samha, PO Box CETACE
Bossir S.P,A Via 8 Marzo. 2-52010 - 53146, Riyadh 11583 Laboratories, 50018 WARRANTY:
Soci-Bibbiena, Italy Phone - Scandicci (FI) – Italy Ten (10) years extended warranty/guarantee in
+966-509-23-5676 from 18/03/2014 to respect of defects due to design, manufacture,
Contact Person - Mr.Paolo como Email - power 19/03/2014. Test installation & workmanship from the date of
Phone - +39-0575-5351 ryd@selanet.com Report No. Provisional Acceptance Certificate (PAC) of the
Email ID - info@borri.it TRP _064_14, Date: first turnkey project in case of contract award or
19/03/2014. date of delivery in case of direct material supply
order, as confirmed in writing by the
manufacturer through letter # Nil, dated May 23,
2011.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by Braga Moro- Italy through
their letter # SEC Prequalification dated April 13,
2011.
C&D
United States
Website - http://www.cdtechno.com/
ERSKINE
United Kingdom
Website -
http://www.erskine-systems.co.uk/
EXIDE
United States
Website - http://www.exide.com/
Website - http://www.gutor.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed in writing by the
manufacturer through their letter #Nil dated June
17, 2011.
VERTIV Industrial System S.A.S Project Execution Previously "AEES ", the name has been changed
FRANCE Development Co. Ltd to Emerson Network Power Industrial Systems -
(PEDCO) France based on Emerson Network Power
Plant -Previously AEES & Emerson 011 4648970, 2312462, Industrial Systems letter # nil dated 12/04/2013.
Network Power Industrial System 4169319 Then, the name has been changed again to
S.A.S Mr. Ilamettin Canimoglu, VERTIV Industrial Systems S.A.S based on
pedco@pedco.com.sa VERTIV Industrial Systems S.A.S letter # nil dated
Lyon , France 29/06/2017.
Lyon
Website - www.VertivCo.com
Website -
http://www.emisa.es/web/index.asp?l
ang=ing
LEVER S.R.L. 125Vdc-400A Battery Charger type Based on S&SD letter# 16-03205-02-30504401
ITALY SME 125/400/SEC dated May 08, 2016, it is prequalified for
125Vdc-400A Battery Charger type
Plant -. SME 125/400/SEC as conforming to National Grid
SA Material Specification 46-TMSS-02 with the
Viale del Lavoro , 17-37024 Arbizzano following conditions:
(VR), Italy
•Ten (10) years extended warranty from the date
Contact Person - Mr. Llamettin of PAC of first Project in case of contract award
Canimoglu ,Sales Manager or from the date of delivery for the direct material
Email ID - pedcoltd@pedco.com.sa supply order and shall be subsequently reduced
Contact Person Email ID - yearly in case of future project, as confirmed by
i.canimoglu@pedco.com.sa the manufacturer through letter#
GG/nm/28042016 dated 28-04-2016.
Total = 15
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by Braga Moro- Italy through
their letter # SEC
Preq. dated April 13, 2011.
Website - http://www.gutor.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed in writing by the
manufacturer through their letter #Nil dated June
17, 2011.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer
Statron AG through their letter # bm dated August
13, 2012.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
HUAWEI TECHNOLOGIES CO.LTD. Huawei Technologies UPS 2000 & UPS 5000 (A&E) Type tests were PQ Letter
CHINA Investment Saudi Arabia conducted from 12 – Based on S&SD letter # 18-02334-03-30504401
Ltd. Co. 16 February 2017 at dated November 15, 2018, HUAWEI Technologies
Bantian, Longgang District, Shenzhen, Prince Mohammed Bin China Co. Ltd. - China is pre-qualified for Uninterrupted
P. R. China Postal Code : 518129 Abdulaziz Street (Tahliah Telecommunication Power Supply (UPS 2000 & UPS 5000) Used in
St.) Olaya – Riyadh Technology Telecom / Data Centers as conforming to National
Contact Person - Mr. Ryan Liu C-Center. P.O. Box Laboratory (CTTL) in Grid SA specification # 46-TMSS-03, with the
Phone - +966 507981437 295320, Riyadh 11351 Baoding, Beijing, following conditions:
Email ID - Liuyong31@huawei.com +966 507981437 China and following
Mr. Ryan Liu; test reports have Warranty
Liuyong31@huawei.com been issued vide: Ten (10) years extended warranty/guaranty
1) KEMA from the date of (PAC) of the Turnkey project (In
Inspection Report case of contract award) and from the date of
No. 1127-7 for delivery for the direct material supply order. The
Huawei UPS 5000 guarantee/warranty shall be applicable from first
(A&E), project and shall cover all the cost of material and
2) SGS Inspection labor as per warranty/guarantee of material and
Report No. IN-SUZ- workmanship and will be subsequently reduced
5802-17009 for the yearly in case of future project award. This was
type testing of confirmed in writing by HUAWEI Technologies Co.
Huawei UPS 5000 Ltd. - China through their letter #
(A&E). 18102402-Mrk-SEC/F dated October 25th, 2018.
Total = 7
FIAMM
ITALY
Website -
http://www.fiamm.com/index.aspx
HOPPECKE Cell
GERMANY 260SP.HC2730
Website - http://www.hoppecke.com/.
AEG POWER SOLUTIONS SAS Originally was SAFT Power System SAS-France
FRANCE
C&D
United States
Website - http://www.cdtechno.com/
Website -
http://www.chloridepower.com
GNB
United States
HAWKER LTD
United Kingdom
Website - http://www.hawker.co.uk
SAB
GERMANY
Website - http://www.sab.com/
SEC
United States
Website - http://www.sec.gov/
VARTA
GERMANY
Website - http://www.varta.com/
YUASA EXIDE
United States
Website -
http://www.yuasabatteries.com/
Total = 11
AEG POWER SOLUTIONS SAS originally was SAFT Power System SAS-France
FRANCE
BRAGA MORO Itea International Ltd Type / Model: BATTERY CHARGER, Prequalified for BATTERY CHARGER, 48 VDC
ITALY 2nd Floor Office No. (For Telecom Applications) (For Telecom Applications).
4036 , Al Bustan Centre
Plant -Milan , Italy Near Kingdom tower Rating: 48V DC
Olaya Riyadh
Via Canzo 4 20068 Peschiera Phone - +966504367244
Borromeo, Milano, Milan ,Italy Email -
mhmagzoub@iteaint.com
Email ID - giorgio.moro@bragamoro.com
Website - http://www.bragamoro.com/
CONDITION:
All type, design, special & routine tests as per
SEC specifications/standards shall be carried out
on the first batch to be supplied to SEC in
securing an order in the manufacturer's
laboratory in the presence of three (3) SEC
engineers & one (1) approved independent
inspection agency Inspector as confirmed by the
manufacturer through their letter no. nil, dt:
05/02/2009.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order as confirmed by the manufacturer through
their letter no. nil, dt: 05/02/2009..
Website - http://www.exide.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer
Statron AG through their letter # bm dated August
13, 2012.
COM 10 INTERNATIONAL PTY. LTD. Type / Model: SWITCH MODE SWITCH MODE RECTIFIERS / BATTERY
AUSTRALIA RECTIFIERS / BATTERY CHARGERS CHARGERS ONLY FOR TELECOM APPLICATION.
ONLY FOR TELECOM APPLICATION.
Alpha , Australia
Website - http://www.force10.com.au/
VERTIV Industrial System S.A.S Project Execution Previously "Emerson Network Power Industrial
FRANCE Development Co. Ltd Systems", the name has been changed again to
(PEDCO) VERTIV Industrial Systems S.A.S based on
Plant -Previously AEES & Emerson 011 4648970, 2312462, VERTIV Industrial Systems S.A.S letter # nil dated
Network Power Industrial System 4169319 29/06/2017.
S.A.S Mr. Ilamettin Canimoglu,
pedco@pedco.com.sa
Lyon , France
Lyon
Website - www.VertivCo.com
Website -
http://www.emisa.es/web/index.asp?l
ang=ing
Website -
http://www.harmerandsimmons.com/
T.D.I Type / Model: SWITCH MODE SWITCH MODE RECTIFIERS ONLY FOR TELECOM
United States RECTIFIERS ONLY FOR TELECOM APPLICATIONS
APPLICATIONS
Website - http://www.tdipower.com/
Total = 11
EXIDE
United States
Website - http://www.exide.com/
GNB
United States
Website - http://www.varta.com/
VERTIV Industrial System S.A.S Project Execution Previously "CHOLORIDE ", the name has been
FRANCE Development Co. Ltd changed to Emerson Network Power Industrial
(PEDCO) Systems - France based on Emerson Network
Plant -Previously AEES & Emerson 011 4648970, 2312462, Power Industrial Systems letter # nill dated
Network Power Industrial System 4169319 12/04/2013.
S.A.S Mr. Ilamettin Canimoglu, Then, the name has been changed again to
pedco@pedco.com.sa VERTIV Industrial Systems S.A.S based on
Lyon , France VERTIV Industrial Systems S.A.S letter # nill
dated 29/06/2017.
Lyon
Website - www.VertivCo.com
ALCAD
SWEDEN
EMISA
SPAIN
Website -
http://www.emisa.es/web/index.asp
lang=ing
Website - http://www.friwo.de/
WARRANTY:
Seven (07) years extended warranty/guarantee
in respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer through
their letter no.nil, dt: 9th June, 2008..
SAFT AB •Type: SBLE up to 1660AH (updated) Cell Type SBLE have Based on S&SD letter # 15-05875-30504401
SWEDEN •Type: SBM up to 1390AH been tested for dated September 17, 2015, the prequalification of
•Type: SBH up to 920AH 1660 AH max. at the manufacturer is updated for NICKEL
Plant -Oskarshamn/ Sweden SAFT AB on Feb. CADMIUM (NiCd) BATTERY .
20, 2015. Report No. Previously " SAFT-NIFE, Sweden", the name has
Saft Ab, Jungnergatan,P.O. Box 709, REP 0927 been changed to SAFT AB, Sweden, based on
Se-572 28 Oskarshamn Sweden SAFT AB Letter #Nil dated January 25, 2016.
Total = 9
BRAGA MORO Itea International Ltd Type / Model: The type test PQ Letter:
ITALY 2nd Floor Office No. MDCCT conducted for Prequalified for DC-DC Converters, 48 Volts
4036 , Al Bustan Centre MDCCT BM 48V, 30 based on S&SD Letter 15-11268-01-30504401
Plant -Milan , Italy Near Kingdom Tower A, 1+1 at Tecnolab dated January 13, 2016.
Olaya Riyadh in Verbania, Italy
Via Canzo 4 20068 Peschiera Phone - +966504367244 Rating: 48 Vdc Output from March 24 – 28, WARRANTY:
Borromeo, Milano, Milan ,Italy Email - 2014. Ten (10) years Extended Guarantee / Warranty
mhmagzoub@iteaint.com from the
Email ID - giorgio.moro@bragamoro.com date of PAC of first Project (in case of contract
Website - http://www.bragamoro.com/ award) or from
the date of delivery for the direct material supply
order. This was confirmed, through their Letter #
SEC Preq. dated April 13, 2011.
Total = 1
SIEMENS CANADA LIMITED RSG 2100, RSG2488 RX1500 for SAS Type test were PQ Lettter:
CANADA witnessed during Based on S&SD letter# 15-07416-030504401
19th to 26th dated October 28, 2015, it is pre-qualified for
I Ia Sc Ci Rc 300 Applewood Crescent Novmebr 2014.Test RUGGEDCOM Ethernet Switches and Routers
Concord On, L4K 5C7 Laboratories Ultra type RSG 2100, RSG 2488, RX 1500 for SAS as
Tech Oakville conforming to National Grid SA specification #
Contact Person - Mr. Mudassar Ahmed Canada and CRiQ 47-TMSS-01, with the following conditions:
Regional Sales Manager Montreal Canada
Phone - +905-856-5288 Letter Report No. WARRANTY:
Email ID - 3629159WT-03& 04 Ten (10) years Extended Warranty shall be
Mudasar.ahmed@siemens.com applicable for the RUGGEDCOM Ethernet
Website - http://www.siemens.ca Switches and Routers type RSG 2100, RSG
2488, RX 1500 for SAS, to be supplied
toSEC/National Grid SA as confirmed through
Letter # Nil dated 26.08.2014.
SCHWEITZER ENGINEERING Ahmad Alanezi - Ethernet Switches type SEL 2730M Test conducted at PQ Letter:
LABORATORIES, INC (SEL) Business Development KEMA Laboratories,
United States Manager & Saad Bin Netherlands. Test Based on S&SD letter # 17-04021/02-30504401
Nawaz - Sales Account Report # dated May 28, 2017, SCHWEITZER ENGINEERING
SCHWEITZER ENGINEERING Manager 1172860831, LABORATORIES, INC (SEL), USA is pre-qualified
LABORATORIES, INC 2350 NE Hopkins +996556866625 1172860827, for Ethernet Switches type SEL 2730M as
Court, Pullman, WA 99163 - USA ahmad_alanezi@selinc.c 117286O828 conforming to National Grid SA specification #
om 47-TMSS-01 with the following conditions:
Pullman Saad_Bin_nawaz@selin
c.com
Phone - +1.509.332.1890 WARRANTY:
Email ID - info@selinc.com
Website - www.selinc.com Ten (10) years extended warranty in respect of
the defects due to design, manufacturing,
installation and workmanship from the date of the
Provisional Acceptance Certificate (PAC) of the
first turnkey project (in case of contract award)
and from the date of first delivery in case of
direct material supply order shall be provided as
confirmed by the manufacturer through their
letter # NIL dated July 16, 2015.
Total = 3
SIEMENS CANADA LIMITED RSG2100 RX1500 for metering System. Type test were PQ Lettter:
CANADA witnessed during Based on S&SD letter# 15-07416-030504401
19th to 26th dated October 28, 2015, it is pre-qualified for
I Ia Sc Ci Rc 300 Applewood Crescent Novmebr 2014.Test RUGGEDCOM Ethernet Switches and Routers
Concord On, L4K 5C7 Laboratories Ultra type RSG 2100, RX 1500 for Metering System as
Tech Oakville conforming to National Grid SA specification #
Contact Person - Mr. Mudassar Ahmed Canada and CRiQ 47-TMSS-02, with the following conditions:
Regional Sales Manager Montreal Canada
Phone - +905-856-5288 Letter Report No. WARRANTY:
Email ID - 3629159WT-03& 04 Ten (10) years Extended Warranty shall be
Mudasar.ahmed@siemens.com applicable for the RUGGEDCOM Ethernet
Website - http://www.siemens.ca Switches and Routers type RSG 2100, RX 1500
for Metering System, to be supplied to
SEC/National Grid SA as confirmed through Letter
# Nil dated 26.08.2014.
Total = 1
Website -
http://www.masskablo.com/about us
company.asp?md=7
STEINER
GERMANY
Website -
http://www.steiner-binoculars.com/ind
ex.html
RIYADH CABLES
Saudi Arabia
TAIHAN ELECTRIC WIRE COMPANY Taihan Electric Wire Rating - 500 V Test Date - Aug KTC Korea testing Certification
SOUTH KOREA Co.,Ltd. Branch 2011
P. O. box 300201,Riyadh
Plant -Dangjin Factory Dangjin /Republic 11372, Al-Rossais
Of Korea Building, 6th Floor Office
No. 613 -
180, Simin-Daero, Dongan-Gu, Phone - 0500108547
Anyangsi, Gyeonggi-Do, Korea Korea, Email -
Republic Of jsnam@taihan.com
SAUDI CABLE
Saudi Arabia
Jeddah
Website -
http://www.mesccables.com/
Plant -jeddah
jeddah
LS CABLES Previously LG
SOUTH KOREA
Plant -Gumi/Korea
Total = 11
ALCATEL
SWEDEN
Website - http://www.alcatel.se/
B.V.TWENTSCHE KABELFABRIEK
NETHERLANDS
Website - http://www.tkf.nl/
BICC
United Kingdom
Website -
http://www.generalcable.com/General
Cable/
BRUGG TELECOM AG
SWITZERLAND
Website - http://www.brugg.com/
CORNING CABLES
United Kingdom
Website -
http://www.corningcablesystems.com/
FUJIKURA LTD.
JAPAN
FURUKAWA
JAPAN
Website -
http://www.furukawa.co.jp/english/ind
ex.htm
Website - http://www.mefcf.com/
Website - http://www.nkf.nl/
CONDITION:
The first batch of each type of Non Metallic Fiber
Optic Cable to be supplied to SEC shall be type
tested per relevant International and SEC
Specifications in presence of three (3) SEC
Engineers and one (1) SEC approved IIA
Inspector and all cost pertaining to the test shall
be borne by the Manufacturer as confirmed
through Letter# Nil dated September 12, 2009.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order as confirmed by the manufacturer through
their letter no.EU.SEC.PQ.01, dt: 17th June, 2009..
SUMITOMO
JAPAN
Yokohama
Website - http://www.sei.co.jp/
HITACHI
JAPAN
LS PREVIOUSLY LG
SOUTH KOREA
Website - http://www.lscable.com/
RIYADH CABLES
Saudi Arabia
SIEMENS
GERMANY
Website -
http://www.mesccables.com/
DRAKA NK
FINLAND
Website - http://www.draka.com/
PIRELLI
ITALY
Website - http://www.afltele.com/
PRYSMIAN TELECOM Zamil Group Holding co, Model: Test Performed at PREVIOUSLY "PIRELLI"
SPAIN Commerical Div Kinectrics Canada in
6728, 48 Cores , May, 2014
Plant -Vilanova I La Geltru/Spain Report#
K-419533-RC-0003-
Ctra. C-15,Km, 2-P.I. Masia D’En Notari R01
08800 Vilanova I La Geltru ( Spain)
Total = 23
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #Nil dated June 18, 2014.
FUJITSU
JAPAN
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt:mar 15, 2013.
Japan-Tokyo
TELETTRA
FRANCE
NORTEL
CANADA
Website - http://www.nortel.com/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
PHILIPS
HOLLAND
Website -
http://www.philips.nl/index.page
ABB ABB Automation CO. Ltd. FOX515 Access Multiplexer KEMA Inspection Based on TADD letter# 09-0576-030225 dated
SWITZERLAND Saudi Arabia Report reference June 10, 2009, SCADA letter# SOCW/ DIV/97 and
PO Box # 414: No. 1119-17 Telecommunication Dep. letter#
Contact Person - Mr. Klaus Lohse Riyadh-11383 09-136-03040001. ABB, Switzerland is
Phone - +41 58 588 33 50 +966 (11) 2653030, FOX615 Access Multiplexer (With pre-qualified for FOX515 Access Multiplexer.
Email ID - Klaus.lohse@ch.abb.com +966504401696 OPIC1 Card)
Website - http://www.abb.ch/ essam.bashraheel@sa.a
bb.com Based on S&SD letter # 17-04894-01-30504401
dated July 18, 2017, ABB, Switzerland is
pre-qualified for FOX615 Access Multiplexer
(With OPIC1 Card) as conforming to National Grid
SA specification # 48-TMSS-06, with the
following conditions:
WARRANTY:
•Ten (10) years extended warranty/Guarantee
from the date of PAC as confirmed; through their
Letter No. 16-05762-01-030504401 dated
27/07/2016 shall be applicable for the equipment
to be supplied to SEC/National Grid SA.
ALCATEL
FRANCE
Website - http://www.alcatel.fr/
Total = 12
Turgi , France
Website - http://www.abb.fr/
LICOM
United States
Website - http://www.licom.net/
PRISM
CANADA
SIEMENS
GERMANY
Total = 4
Total = 1
ZTE Corporation Landis + Gyr AG- ZXONE 9700 ZTE Corporation - PQ letter:
CHINA Greece China has Based on S&SD letter # MPQ 11819920-classI(a)
3rd floor, Tawaren successfully -2016-class I(b) dated November 08, 2017, ZTE
Plant -LiuXian Rd Xili Shenzhen China Center Building King completed the type Corporation - China is pre-qualified for DWDM as
PRC Fahad Road tests of DWDM conforming to latest National Grid SA
P.O.BOX#58970 Riyadh, Equipment at China specification # 48-TMSS-08
LiuXian Rd Xili Shenzhen China PRC Saudi Arabia Telecommunication
+966 539467479 Technology Labs WARRANTY:
Shenzhen yang.shuai130@zte.com (CTTL). Bearing • Ten (10) years extended warranty/guarantee in
.cn report # B17X60154 respect of defects due to design, manufacture,
Contact Person - Eng. Fox Yang & B17X20741 during installation and workmanship from the date of
Phone - +966 539467479 August 14-26, 2017 Provisional Acceptance Certificate (PAC) of the
Email ID - yang.shuai130@zte.com.cn; in the presence of first turnkey project in case of contract award or
zhou.rong35@zte.com.cn; SEC/National Grid date of first delivery in case of direct material
ou.rong@zte.com.cn SA Engineers and supply order, as confirmed by the manufacturer
Contact Person Email ID - SGS inspector vide letter # ZTE-20170402-SECDWDM-01, dated
yang.shuai130@zte.com.cn bearing report March 03, 2017.
Website - www.landisgyr.com #IN-SZ-5802-17082-
1&
IN-SZ-5802-17082-2
.
HUAWEI TECHNOLOGIES CO.LTD. Huawei Technologies Optix OSN 8800 Type tests were PQ Letter:
CHINA Investment Saudi Arabia conducted from 20 Based on S&SD letter # 18-07410-03-30504401
Ltd. Co. to 29 January 2016 dated November 15, 2018, HUAWEI Technologies
Bantian, Longgang District, Shenzhen, Prince Mohammed Bin at Huawei Co. Ltd. - China is pre-qualified for OTN-DWDM
P. R. China Postal Code : 518129 Abdulaziz Street (Tahliah Technologies Co. Ltd Equipment as conforming to National Grid SA
St.) Olaya – Riyadh at Shenzhen, China specification # 48-TMSS-08, with the following
Contact Person - Mr. Ryan Liu C-Center. P.O. Box and from 21 – 22 conditions:
Phone - +966 507981437 295320, Riyadh 11351 November 2016 at
Email ID - Liuyong31@huawei.com +966 507981437 Mr. China Warranty:
Ryan Liu Telecommunication Ten (10) years extended warranty/guaranty
Liuyong31@huawei.com Technology from the date of (PAC) of the Turnkey project (In
Laboratory (CTTL) in case of contract award) and from the date of
Baoding, China. The delivery for the direct material supply order. The
following test guaranty/warranty shall be applicable from first
reports have been project and shall cover all the cost of material and
issued vide: labor as per warranty/guaranty of material and
KEMA Inspection workmanship and will be subsequently reduced
Report No. DNV- GL yearly in case of future project award. This has
1067-16 for Huawei been confirmed in writing by HUAWEI
OTN-DWDM Technologies Co. Ltd. - China through their letter
Equipment and Ref. 18102408-Mrk-SEC/F dated October 25,
SGS Inspection 2018.
Report No.
IN-SUZ-5802-16066
for the type testing
of Huawei
OTN-DWDM
Equipment.
ALCATEL-LUCENT AlCatel Lucent Type 1830 PSS-32 Type tested during PQ Lettter
ITALY Riyadh 20th -31st October Based on S&SD letter # 15-0010-02-30504401
2014 and 4, 27-28 dated 12th February 2015, the manufacturer is
Trieste, Italy Nov, 2014. prequalified for OTN-DWDM equipment Type 1830
PSS-32 as conforming to National Grid SA
Contact Person - Mr. Eric Saniard, Test Report Nos: specification # 48-TMSS-08, Rev.0 with the
Account Sale Manager 80SO00094, following condition:
Email ID - 80SO00096, CSi
eric.es.saniard@alcatel-lucent.com Test Report WARRANTY
No.0118/ME/CMP/14 Ten (10) years extended warranty/guarantee in
Rev.2, respect of defects due to design, manufacture,
Centrotecnica SRL installation & workmanship from the date of
report No. Provisional Acceptance Certificate (PAC) of the
VR1400223IMRK.do first turnkey project in case of contract award or
c. date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: 6th june, 2014.
Total = 4
ALCATEL-LUCENT PQ Lettter
CHINA Based on S&SD letter # 14-07395-30504401,
dated 23/10/2014, the test facility of Alcatel
Shanghai China Lucent in (Bydgoszcz, Poland) is allowed to
conduct Factory Routine test and Integration
testing of communication equipment
manufactured in Alcatel-Lucent Factory in
Shanghai China confirming to National Grid SA
requirements.
CONDITION
Based on TS&SD letter #10-03519/03-03032301
dated 17/04/2011, it is pre-qualified for Fiber
Optic Communication Terminal type
Optenix1660SM with the following conditions:
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter # ALU/172/SI/2010 dated 12/12/2010.
CONDITION
Type, Special, sample & routine tests shall be
conducted on the first batch of 1511MAX Series
to be supplied to SEC, in the presence of three
(3) SEC Engineers & one (1) SEC approved
independent inspection agency Inspector in an
independent testing laboratory. All the related
costs for witnessing the tests will be borne by
the manufacturer. This was confirmed by Alcatel
Lucent (ASB) Shanghai China through response
letter # ALU/25/SI/2011 dated 30/01/2011 and
letter # Nil dated 27/04/2011.
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: 30/01/2011.
manufacturer.
Total = 3
Website -
http://www.corningcablesystems.com/
Website - http://www.ericson.com/
WARRANTY:
Five (5) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #Nil, dt: June 10, 2013.
TELECT PQ Lettter
Poland Based on TS&SD letter# 09-01095-03032301
dated 18th. April 2009 for the following
Wroclaw , Poland accessories:
- Management Rack E-9000 series
- Distribution & Termination Unit LCX.
- Wall mounted unit LanLinxs.
WARRANTY:
Seven (7) years extended warranty from the
date of PAC of the turnkey project in case of
contract award or date of delivery in case of
direct material supply order. This was confirmed
by Amwaj Telecom MFG. Co. letter dated
09/06/2010.
Website - http://www.nokia.com/
INDUSTRIAS ARRUTI
SPAIN
Website -
http://www.grupoarruti.com/empresa.a
sp
JIANGSU ZHONGTIAN TECHNOLOGY OPGW Joint Box, Type ST up to 192 Tests performed at: PQ Letter
CO.LTD (ZTT) splices China Based on S&SD Letter # 17-02628-01-30504401
CHINA Telecommunication dated May 09, 2017it is prequalified with the
Technology Labs following condition:
Chinanantong, China (January 09-13,
2017) WARRANTY:
Report # B17X70084 Ten (10) years extended warranty from the date
of PAC of the first turnkey in case of contract
award or date of first delivery in case of direct
material supply order as confirmed through ZTT
letter # ZTT-G-2016-06-10-01 dated 10/6/2016.
AFL TELECOMMUNICATIONS GMBH OPGW Joint Box Previously Draka Comteq Germany GmbH & KG.
GERMANY
WARRANTY:
Monchengladbach , Germany Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order.
Total = 13
ERICSON
SWEDEN
Website - http://www.ericson.com/
NORTEL
CANADA
Website - http://www.nortel.com/
ALCATEL NV
FRANCE
MITEL CORP.
CANADA
Website - http://www.mitel.com/
NORTHERN TELECOM
CANADA
Website -
http://www.northerntelecom.com/
PHILIPS
HOLLAND
Website -
http://www.philips.nl/index.page
RAYCHEM
United States
United States-Ca
SIEMENS
GERMANY
AT & T
United States
Website - http://www.att.com/
ALCATEL
FRANCE
Website - http://www.alcatel.fr/
Total = 10
BARCELONA PQ Lettter
Based on TS&SD Letters# 09-01439-2-03032301
Contact Person - Marco Sensei dated 7th July 2009 & 10-00845-1-03032301
Phone - +34 944 522 003 dated April 04, 2010. It is pre- qualified for
Email ID - Tele-protection Equipment type TPU-1 with the
marco.senesi@zivautomation.com following conditions:
Contact Person Email ID -
marco.senesi@zivautomation.com WARRANTY
Website - www.zivautomation.com Five (05) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
Ljubljana WARRANTY
•Ten (10) years extended warranty in respect of
the defects due to manufacturing and
workmanship, from the date of PAC of the first
turnkey project (in case of contract award) or
date of first delivery (in case of direct material
supply order), as confirmed through their Letter
No. DTE349/14-KIP dated September 05,2014
shall be applicable.
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
SIEMENS
GERMANY
Berlin, Germany
IC SG EA MF
Wernerwerkdamm 5,
13629, Berlin, Germany
AREVA
FRANCE
Total = 5
IPG PHOTONICS Al Salam Industrial & OSTP-DWDM Type Tests were PQ Lettter
United States Trdg Est Erbium Amplifier rack Mount(EAR) and conducted in VDE Based on S&SD letter # 15-05564-2-30504401
Head Office,PO Raman Amplifier Rack Mount(RAR) Germany in dated July 05, 2015, it is pre-qualified for supply,
50 Old Webster Road Oxford Ma01540 Box:17176 presence of three installation and configuration of Optical Service
T 508 373 1100 F 508.373.1101 Jeddah-21484 Saudi SEC/National Grid Transport Platform (OSTP-DWDM), Erbium
Arabia SA Engineers during Amplifier rack Mount (EAR) and Raman Amplifier
Contact Person - Mr. Mark Cannata Tel: +966 12 608 1028 8th to 19th Rack Mount (RAR) manufactured by IPG
Director & Marketing &Mr. Yasser Fax: +966 12 608 1035 December Photonics, Oxford, Massachusetts, USA plant as
Adnan Skik yasserad@electroi.com 2014.Three Failed conforming to National Grid SA specification #
Website - test (EMC Emission 48-TMSS-08 with following condition:
http://www.ipgphotonics.com of
Enclosure,Dielectric/I WARRANTY
nsulation Resistance Ten (10) years Extended Warranty as confirmed
and Mechanical through
Operation tests) IPG Letter # NIL dated 2nd April 2014 shall be
were repeated applicable for all supplies made to the Company
during 13th to 17th by IPG Photonics Oxford, Massachusetts, USA.
April 2015.Test Lab
RMS and Type Test
Report # MI-1220-4
dated 09-05-2011
IPG PHOTONICS Al Salam Industrial & OSTP-DWDM Type Tests were PQ Lettter
ITALY Trdg Est Erbium Amplifier rack Mount(EAR) and conducted in VDE Based on S&SD letter # 15-05564-3-30504401
Head Office,PO Raman Amplifier Rack Mount(RAR) Germany in dated July 05, 2015, it is pre-qualified for supply,
50 Old Webster Road Oxford Ma01540 Box:17176 presence of three installation and configuration of Optical Service
T 508 373 1100 F 508.373.1101 Jeddah-21484 Saudi SEC/National Grid Transport Platform (OSTP-DWDM), Erbium
Arabia SA Engineers during Amplifier rack Mount (EAR) and Raman Amplifier
Contact Person - Mr. Mark Cannata Tel: +966 12 608 1028 8th to 19th Rack Mount (RAR) manufactured by IPG
Director & Marketing &Mr. Yasser Fax: +966 12 608 1035 December Photonics, Milan Italy conforming to National Grid
Adnan Skik yasserad@electroi.com 2014.Three Failed SA specification # 48-TMSS-08 with following
Website - test (EMC Emission condition:
http://www.ipgphotonics.com of
Enclosure,Dielectric/I WARRANTY
nsulation Resistance Ten (10) years Extended Warranty as confirmed
and Mechanical through
Operation tests) IPG Letter # NIL dated 2nd April 2014 shall be
were repeated applicable for allSupplies made to the Company
during 13th to 17th by IPG Photonics Milan Italy.
April 2015. Type
Test
Report#MI-1220-4
dated 09-05-2011
Total = 2
SIEMENS
United States
Website -
http://www.usa.siemens.com/entry/en/
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB EJF
CZECH REPUBLIC
Website -
http://www.abb.com/substation-autom
ation
ELEQ B.V. Hamid Nazar Malik Up to 380 kV Type Test were PQ Lettter
GERMANY Contracting Co. Ltd ( Split core and continuous Ring type witnessed Based on S&SD letter# 15-10406-01-30504401,
HNCC) CTs successfully by dated
Zweigniederlassung Deutschland , Contact Person:Mr. umer SEC/ National Grid December 10, 2015. the manufacturer is
Karl-Ferdinand-Braun-Strabe 150170 Shaikh, P.O.Box 132631 SA engineers during prequalified for Split Core and Continuous Ring
Kerpen Germany Jeddah 21382,Kingdom 20th to 24th October type CTs up to 380kV as conforming to National
of Saudi 2015 in IPH Germany Grid SA 50-TMSS-01 Rev.0 with the following
Contact Person - Dr. Andreas Roos, Arabia,http://hnccsa.com Type Test Report, condition
General Manager / SGS Germany
Phone - +49-0-2273-988-70 Tel : 00966 2 ref#3534308-10 WARRANTY:
Email ID - Andreas.roos@eleq.com 6752400,Tel : 00966 2 Ten (10) years Extended Warranty shall be
Website - http://www.eleq.com 6758838, Mobil applicable for Split Core and Continuous Ring
Email : type CTs up to 380kV to be supplied to
info@hnccsa.com,sales SEC/National Grid SA as confirmed through Letter
@hnccsa.com # Nil dated 05.08.2015.
Website - http://www.pfiffner.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: jan 11, 2010.
Website - http://www.kuhlman.com/
GE
United States
Website - http://www.ge.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order as confirmed by the manufacturer through
their letter no.MEMF/YS/LET/08/180, dt: 21st Sep,
2008...
Total = 12
SIEMENS
United States
Website -
http://www.usa.siemens.com/entry/en/
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
Website - http://www.trench.at/Trench
Austria GmbH/News/Das neue
Familienmitglied - Trench Italia/
-8255-38-2-en-com-/cms.html
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
Website - http://www.pfiffner.com/
E. PFIFFNER
SWITZERLAND
Website -
http://www.pmw.ch/default.htm
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: Jan 11, 2010.
Website - http://www.sadtem.com/
WARRANTY
Ten (10) years Extended Warranty shall be
applicable for Split Core and Continuous Ring
type CTs up to 380kV to be supplied to
SEC/National Grid SA as confirmed through Letter
# Nil dated 05.08.2015.
Website - http://
http://www.alstom.com/home/
GE
United States
Website - http://www.ge.com/
ALSTOM GRID, WAYNESBORO Previously RITZ- United States [The name has
United States been changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].
Plant -Waynesboro , United States
CONDITION:
TYPE TEST SHALL BE DONE AT AN INTL.
TESTING LAB IN PRESENCE OF 3RD PARTY
INSPECTOR
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
AREVA
United Kingdom
Website - http://www.areva.com/
Total = 19
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
TRENCH ITALIA Type / Model: OIL TYPE PREVIOUSLY AS VA TECH (NOUVA MAGRINI
ITALY GALILEO);
Website - http://www.trench.at/Trench
Austria GmbH/News/Das neue
Familienmitglied - Trench Italia/
-8255-38-2-en-com-/cms.html
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
Website - http://www.pfiffner.com/
ELECTROTECNICA ARTECHE HNOS. Type / Model: Current transformer Tests done in LCOE PQ Letter:
S.L./ E.A.H.S.L Laboratoty (Spain) Based on S&SD letter # 16-010639-030504401
SPAIN •Type CA-170 in presence of dated February 16,2017, Electrotecnica Arteche,
Rating: 110 kV SEC/National Grid Spain-Mungia is pre-qualified for 110 kV CTS as
Plant -Mungia, Spain SA Engineers from conforming to National Grid SA specification #
11th to 19th July, 50-TMSS-01, with the following condition:
Electrotecnica Arteche Hnos. S.L./ 2016).
E.A.H.S.L/ Mungia/ Spain/ Derio Bidea •Ten (10) years extended warranty from the date
Nº28 48100/ of PAC of the first turnkey project (in case of
contract award) or date of first delivery (in case
Contact Person - Mr. Roberto Antuñano of direct material supply order), as confirmed
Phone - +946011200 through Electrotecnica Arteche letter # NIL dated
Email ID - ra@arteche.es January 11, 2010 G.
Website - http://www.arteche.es
Website - http://www.sadtem.com/
WARRANTY
Ten (10) years Extended Warranty shall be
applicable for Split Core and Continuous Ring
type CTs up to 380kV to be supplied to
SEC/National Grid SA as confirmed through Letter
# Nil dated 05.08.2015.
Website - http://www.kuhlman.com/
Website - http://
http://www.alstom.com/home/
ALSTOM GRID, WAYNESBORO Previously RITZ- United States [The name has
United States been changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].
Plant -Waynesboro , United States
CONDITION:
All Type, Special, Routine tests per SEC
Standards shal be performed on the first batch,
at anaccredited testing laboratory in the
presence of 03 SEC/National Grid SA engineers
and one approved third party inspector and the
cost of which shall be borne by the
manufacturer.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
AREVA
United Kingdom
Website - http://www.areva.com/
Total = 16
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
TRENCH ITALIA Type / Model: OIL TYPE PREVIOUSLY AS VA TECH (NOUVA MAGRINI
ITALY GALILEO);
Website - http://www.trench.at/Trench
Austria GmbH/News/Das neue
Familienmitglied - Trench Italia/
-8255-38-2-en-com-/cms.html
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
Warranty:
Ten (10) years extended warranty/guaranty from
the date of PAC of the first turnkey project (in
case of contract award) and from the date of
delivery (in case of direct material supply order),
as confirmed, through their letter # Nil, dated July
2, 2018 shall be applicable for all 230kV Current
Transformers (CTs), type CA-245 to be supplied
to SEC/National Grid SA.
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
Website - http://www.pfiffner.com/
Website - http://www.sadtem.com/
WARRANTY
Ten (10) years Extended Warranty shall be
applicable for Split Core / Ring type CTs up to
380kV to be supplied to SEC/National Grid SA as
confirmed through Letter# Nil dated 05.08.2015.
Website - http://www.kuhlman.com/
Website - http://
http://www.alstom.com/home/
ALSTOM GRID, WAYNESBORO Previously RITZ- United States [The name has
United States been changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].
Plant -Waynesboro , United States
CONDITION:
All type, design, special & routine tests as per
SEC Specifications/standards shall be carried out
on the first batch to be supplied to SEC/National
Grid in the presence of three (3) SEC/National
Grid SA Engineers & one (1) approved
independent inspection agency Inspector.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
AREVA
United Kingdom
Website - http://www.areva.com/
Total = 15
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
Website - http://www.trench.at/Trench
Austria GmbH/News/Das neue
Familienmitglied - Trench Italia/
-8255-38-2-en-com-/cms.html
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
CONDITION:
All type, design, special & routine tests as per
SEC Specifications/standards shall be carried out
on the first batch to be supplied to SEC/National
Grid in the presence of three (3) SEC/National
Grid SA Engineers & one (1) approved
independent inspection agency Inspector, as
confirmed by the manufacturer through their
letter no.CH-5042 Hirchthal, dt: 17th May, 2009..
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer through
their letter no.CH-5042 Hirchthal, dt: 17th May,
2009...
Website - http://www.sadtem.com/
WARRANTY:
Ten (10) years Extended Warranty shall be
applicable for Split Core / Ring type CTs up to
380kV to be supplied to SEC/National Grid SA as
confirmed through Letter # Nil dated 05.08.2015.
- Previously KWK Messwandler
Website - http://www.kuhlman.com/
Website - http://
http://www.alstom.com/home/
ALSTOM GRID, WAYNESBORO Previously RITZ- United States [The name has
United States been changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].
Plant -Waynesboro , United States
CONDITION:
All type, design, special & routine tests as per
SEC Specifications/standards shall be carried out
on the first batch to be supplied to SEC/National
Grid in the presence of three (3) SEC/National
Grid SA Engineers & one (1) approved
independent inspection agency Inspector.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
AREVA
United Kingdom
Website - http://www.areva.com/
Electrotecnica ARTECHE Hermanos, Innovative Systems Co. CA-420 type test was PQ letter:
S.L. Ltd. performed in LCOE Based on S&SD letter # MPQ # 102210921 dated
SPAIN P.O. Box 60606, Riyadh, lab - Spain 10th to November 08, 2017, Electrotecnica ARTECHE -
KSA 16th July 2017 Spain is pre-qualified for CURRENT
Plant -Mungia, Spain kamal@isys.sa TRANSFORMER,( 380KV CTS)as conforming to
latest National Grid SA specification #
Electrotecnica ARTECHE Hermanos, 50-TMSS-01
S.L.
DERIO BIDEA, 28 (Bº Zabalondo) WARRANTY:
48.100 - MUNGIA Spain Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
Mungia installation and workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
Contact Person - LANDER ZUGAZAGA first turnkey project in case of contract award or
& Kamal Al Muhanna date of first delivery in case of direct material
Phone - +34 94 601 1200 supply order, as confirmed by the manufacturer
Email ID - info@arteche.es vide letter # Nil, dated June 30, 2016.
Contact Person Email ID -
lrz@arteche.es & Kamal@isys.sa
Website - www.arteche.es
Total = 15
SIEMENS
GERMANY
Website - http://
http://www.siemens.de/Pages/EntryPa
geRedirect.aspx
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB EJF
CZECH REPUBLIC
Website -
http://www.abb.com/substation-autom
ation
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: jan 11, 2010.
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
Website - http://
http://www.alstom.com/home/
PFIFFNER, HIRSCHTHAL
SWITZERLAND
Website - http://www.pfiffner.com/
GE
United States
Website - http://www.ge.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: oct 24, 2011.
AREVA
United Kingdom
Website - http://www.areva.com/
Total = 14
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: jan 11, 2010.
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
Website - http://
http://www.alstom.com/home/
PFIFFNER, HIRSCHTHAL
SWITZERLAND
Website - http://www.pfiffner.com/
ALSTOM GRID, WAYNESBORO Previously RITZ- United States [The name has
United States been changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].
Plant -Waynesboro , United States
CONDITION:
All type, design, special & routine tests as per
SEC Specifications/standards shall be carried out
on the first batch to be supplied to SEC/National
Grid in the presence of three (3) SEC/National
Grid SA Engineers & one (1) approved
independent inspection agency Inspector.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
AREVA
United Kingdom
Website - http://www.areva.com/
Total = 11
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: jan 11, 2010.
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
Website - http://
http://www.alstom.com/home/
ALSTOM GRID, WAYNESBORO Previously RITZ- United States [The name has
United States been changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].
Plant -Waynesboro , United States
CONDITION:
All type, design, special & routine tests as per
SEC Specifications/standards shall be carried out
on the first batch to be supplied to SEC/National
Grid in the presence of three (3) SEC/National
Grid SA Engineers & one (1) approved
independent inspection agency Inspector.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order..
AREVA
United Kingdom
Website - http://www.areva.com/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #P/900-25112010, dt: 22 mar, 2011.
Total = 11
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
Warranty
Ten (10) years extended warranty/guaranty from
the date of PAC of the first turnkey project (in
case of contract award) and from the date of
delivery (in case of direct material supply order),
as confirmed, through their letter # Nil, dated July
2, 2018 shall be applicable for all 230kV Potential
Transformers (VTs), type UTF-245 to be supplied
to SEC/National Grid SA.
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
Website - http://
http://www.alstom.com/home/
ALSTOM GRID, WAYNESBORO Previously RITZ- United States [The name has
United States been changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].
Plant -Waynesboro , United States
CONDITION:
All type, design, special & routine tests as per
SEC Specifications/standards shall be carried out
on the first batch to be supplied to SEC/National
Grid in the presence of three (3) SEC/National
Grid SA Engineers & one (1) approved
independent inspection agency Inspector.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
AREVA
United Kingdom
Website - http://www.areva.com/
CONDITION:
All type, special, routine and sample tests as per
SEC specifications/ standards shall be carried
out on the first unit of Inductive Voltage
Transformers to be supplied to SEC in case of
securing an order in the presence of three (3)
SEC Engineers & one (1) approved independent
inspection agency Inspector in an independent
testing laboratory or at the manufacturer’s testing
laboratory. All the related costs for witnessing
the tests will be borne by the manufacturer. This
was confirmed by PFIFFNER Instrument
Transformers Ltd through letter #
P/900-17052011 dated 17 May 2011.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #P/900-25112010, dt: 22 mar, 2011.
Total = 11
HAEFELY-TRENCH ELECTRIC
SWITZERLAND
Website -
http://www.electricityforum.com/produ
cts/htg.htm
ABB ( T& D)
United States
Website - http://www.abb.us/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
NISSIN
JAPAN
Website - http://www.nissin.co.jp/e/
Website - http://
http://www.alstom.com/home/
ALSTOM GRID, WAYNESBORO Previously RITZ- United States [The name has
United States been changed based on S&SD/P&SFD letter #
13-06262-30504401 dated December 02, 2013].
Plant -Waynesboro , United States
CONDITION:
All type, design, special & routine tests as per
SEC Specifications/standards shall be carried out
on the first batch to be supplied to SEC/National
Grid in the presence of three (3) SEC/National
Grid SA Engineers & one (1) approved
independent inspection agency Inspector.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
AREVA
United Kingdom
Website - http://www.areva.com/
Total = 9
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed through Saudi Federal
Transformers L.L.C., Riyadh letter #
SFTL/TES/545/2012 dated May 05, 2012.
Website -
http://www.sauditransformers.com/
Total = 9
TRANSFORMER, SPECIALTY
23. 1
GROUNDING TRANSFORMER, 13.8KV, 33KV OR 34.5KV Applicable Standards: 52-TMSS-01
CG POWER SYSTEMS
BELGIUM
Website - http://www.pauwels.com/
Website - http://www.cglonline.com/
ABB
United States
Website - http://www.abb.us
ABB ( T& D)
ITALY
Website - http://www.abb.it/
ABB SECHERON,
SWITZERLAND
Geneva , Switzerland
Website - http://www.abb.ch/
1000, Bangeojinsunhwan-doro,
Dong-gu, Ulsan, South Korea,
Ulsan
Total = 8
TRANSFORMER, SPECIALTY
23. 2
AIR CORE NEUTRAL GROUNDING REACTOR FOR 11 KV THROUGH 132 KV SYSTEM Applicable Standards: 52-TMSS-02
Total = 1
POWER TRANSFORMERS
24. 1
Power Transformer rated up to 100 MVA Applicable Standards: 53-TMSS-01
1000, Bangeojinsunhwan-doro,
Dong-gu, Ulsan, South Korea,
Ulsan
ILJIN ELECTRIC CO. LTD. Type / Model: for Power Transformers PQ Letter:
SOUTH KOREA Based on S&SD Letter # 12-03077-30504401
Rating: 230kV, 166.7MVA dated
Plant -Hongseong, South Korea September 15, 2012 and S&SD letter
#15-02407-02-30504401 dated June 23, 2015.
905-17, Mannyeon-ro, Hwaseong-si, ILJIN ELECTRIC Co. Ltd – Hongseong city, Korea
Gyeonggi, KOREA is prequalified for Power Transformers up to 230
kV, 166.7 MVA as conforming to
Contact Person - Mr. Jeong Kyung Woo SEC/National Grid SA Specification # 53-TMSS-01
, Mr. Jaeho Kim with the following conditions:
Phone - +82-2-707-9161
Contact Person Email ID - CONDITION:
jkwoo@iljin.co.kr , jaeho.kim@iljin.co.kr All Type, Routine and Special tests as per
Website - http://www.iljinelectric.co.kr SEC/National Grid
SA Specifications shall be conducted on the
proposed Power Transformers in the
Manufacturer's Testing Laboratory in the
presence of three (3) SEC/National Grid SA
Engineers & one (1) SEC/National Grid SA
approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing
by the manufacturer through their letter #
IL2014-11-05-01 dated November 5, 2014.
WARRANTY:
Ten (10) years extended Warranty for the
proposed Power Transformers in respect of the
defects due to design, manufacturing, installation
and workmanship from the date of the Provisional
Acceptance Certificate (PAC) of the project (in
case of contract award) and from the date of
delivery for the direct material supply order as
confirmed through the manufacturer letter # Nil
dated November 5, 2014
AREVA
GERMANY
Website - http://www.areva.com/
CG ELECTRIC SYSTEMS ZRT. Type / Model: Power Transformers Based on TS&SD Letter 11-01981-1-03032301
(PREVIOUSLY GANZ TRANSELEKTRO dated July 11, 2011, it is pre-qualified for Power
ELECTRIC CO., LTD.) Rating: 132kV, 100MVA Transformers rated up to 132kV/100MVA as
HUNGARY conforming to SEC Specification #53-TMSS-01,
Rev.0, with the following condition:
Budapest , Hungary • Ten (10) years extended warranty from the
date of PAC of the first turnkey project in case of
contract award or date of first delivery in case of
direct material supply order. This was confirmed
in writing by the manufacturer through their letter
# Nil dated June 15, 2010.
EFACEC ENERGIA MAQUINAS E 132kV, 100MVA Pre-qualified for Power Transformers rated up to
EQUIPAMENTOS ELECTRICOS, S.A 132kV, 100MVA
PORTUGAL
Plant -Porto/Portugal
GETRA POWER S.P.A Type / Model: Power Transformer Based on S&SD Letter # 14-04523-01-03504401
ITALY dated 7th July 2014, it is pre-qualified for Power
Rating: 132kV , 100MVA Transformer up to 100MVA, 132kV as confirming
Plant -Plant Location : Marcianise (Ce) , to National Grid SA specification # 53-TMSS-01,
Italy Rev.01 with the following conditions:
• All Type, Special & Routine tests as per National
Grid SA Specifications/Standards shall be carried
out on the first unit to be supplied to National Grid
SA in an Approved Independent
Testing Laboratory and/or in the manufacturer’s
Testing Laboratory in the presence of three (03)
National Grid SA Engineers & one (01) Approved
Independent Inspection Agency (IIA) Inspector.
All the costs of which shall be borne by the
manufacturer. This was confirmed in writing by
the
manufacturer through their letter #
GPJLT/SECNG/SSD/009, dated 8th June 2014.
• WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer through
their letter # GPJLT/SECNG/SSD/0010 dated 8th
June 2014.
KONCAR D&ST INC. Type / Model: Power Transformer Pre-qualified for Power Transformers rated up to
CROATIA 132kV, 67MVA
Rating: 132kV, 67MVA
Plant -Zagreb/ Based on S&SD Letter # 14-03217-1-30504401
Croatia-Hrvatskaaddress: dated May 18, 2014, it is pre-qualified for Power
Transformer up to 67MVA, 132kV as confirming
Koncar Distribution & Special to National Grid SA specification # 53-TMSS-01,
Transformers D&St, J. Mokrovica 8; Rev.01 with the following conditions:
P.P. 100; Hr-10090 Zagreb, Croatia • All Type, Special & Routine tests as per National
Grid SA Specifications shall be carried out on the
Contact Person - Mr. Kopjar Boris first unit to be supplied to National Grid SA in the
Phone - +385 1 3783 728 Mob: + 385 Approved Independent Testing Laboratory or in
99 2110 846 the manufacturer’s Testing Laboratory in
Email ID - Boris.kopjar@koncar-dst.hr presence of three (03) National Grid SA
Website - http://www.koncar-dst.hr/ Engineers & one (01) Approved Independent
Inspection Agency (IIA) Inspector. All the costs of
which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer
through their letter # Nil, dated May 04, 2014.
• Ten (10) years extended warranty from the
date of PAC of the first turnkey project (in case
of contract award) and from the date of first
delivery in case of direct material supply order as
confirmed by the manufacturer through their
letter # Nil dated May 04, 2014.
SC ELECTROPUTERE SA Type / Model: Power Transformer ON HOLD for the procurement of Power
Romania Transformer for all ongoing and forthcoming
Rating: 132kV, 100MVA projects of company including the Eight (8) spare
Plant -Craiova, Romania transformers against purchase order #
4500217223 as per S&SD fax#
16-05458-30504401 dated 23/06/2016.
KONCAR POWER TRANSFORMERS Type / Model: Power Transformer Based on S&SD Letter # 14-08041-01-03504401
LTD dated 13/02/2014 & 14-08041-02-03504401
CROATIA Rating: up to 132kV, 100MVA dated 25/03/2014, it is pre-qualified for Power
Transformer up to 100MVA, 132kV as confirming
Plant -Josipa Mokrovica 6 to National Grid SA specification # 53-TMSS-01,
Rev.01 with the following conditions:
10 090 Zagreb, Coratia • All Type, Special & Routine tests as per National
Grid SA Specifications/Standards shall be carried
Contact Person - Mr. Ivan Milcic, GM out on the first unit to be supplied to National Grid
Phone - +385 1 3795 555 SA in the Approved Independent Testing
Laboratory or in the manufacturer’s Testing
Laboratory in presence of three (03) National
Grid SA Engineers & one (01) Approved
Independent Inspection Agency (IIA) Inspector.
All the costs of which shall be borne by the
manufacturer. This was confirmed in writing by
the manufacturer through their letter # Nil, dated
01-04-2014.
• Ten (10) years extended warranty from the
date of PAC of the first turnkey project (in case
of contract award) or from the date of first
delivery in case of direct material supply order,
as confirmed by the manufacturer through their
letter # 2014/02, dated 01-04-2014 dated April 06,
2014
HYUNDAI HEAVY INDUSTRIES CO. Type / Model: for Power Transformers Based on TS&SD letter # 11-00438-03-03032301
Bulgaria dated 15/05/2011, it is prequalified for Power
Rating: 132kV, 100MVA Transformers up to 132kV, 100MVA as
Plant -Sofia, Bulgaria confirming to SEC specification # 53-TMSS-01,
Rev.0 with the following conditions:
• All type, special, routine and sample tests as
per SEC specifications/standards for Power
Transformers up to 132kV, 100MVA shall be
carried out in case of contract award or SEC
direct purchase order at SEC approved
independent laboratory or at manufacturer’s
testing laboratory in presence of three (3) SEC
Engineers and one (1) SEC approved
independent inspection agency. All the related
costs for witnessing of the tests will be borne by
the manufacturer. This was confirmed by HHI–
Bulgaria through letter # D-0353 dated
20/08/2010.
• Ten (10) years extended warranty from the
date of PAC of the turnkey project in case of
contract award or date of delivery in case of
direct material supply order. This was confirmed
by HHI–Bulgaria through letter # D-0355 dated
20/08/2010.
PJSC ZAPOROZHTRANSFORMATOR Type / Model: Power Transformers Based on S&SD letter# 13-07568-30504401
(ZTR) dated December 31, 2013, it is pre-qualified for
Ukraine Rating: 132kV, 100MVA Power Transformers rated up to 100MVA, 132
kV as conforming to National Grid SA
Plant -Zaporizhia , Ukraine specification # 53-TMSS-01, Rev.01, with the
following conditions:
• All Type, Special & Routine tests as per latest
National Grid SA Specifications/Standards & IEC
requirements together (with Thermal & Dynamic
short-circuit calculations per IEC 60076-5) shall
be carried out on the next unit to be supplied to
SEC/ National Grid SA in an Accredited Testing
Laboratory in the presence of three (3) National
Grid SA Engineers & one (1) National Grid SA
approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing
by the manufacturer through their letter
1/115-2261 dated August 15, 2011.
• Ten (10) years extended warranty from the
date of PAC of the first turnkey project in case of
contract award or date of first delivery in case of
direct material supply order. This was confirmed
in writing by the manufacturer through their letter
# 1/115-2266 dated August 15, 2011.
LIAONING - EFACEC ELECTRICAL Rating: SUSPENDED for all SEC/National Grid SA ongoing
EQUIPMENT CO., LTD (LEEEC) Up to 100MVA and forthcoming projects based on VP,
CHINA Engineering letter #13-07937-30504401 dated
December 24, 2013.
Liaoning Province , China
The old remark before suspension was:
Based on S&SD Letter 12-01675-30504401 dated
May 20, 2012. It is prequalified for Power
Transformers rated up to 100 MVA as conforming
to SEC Specification# 53-TMSS-01 with the
following condition:
• Ten (10) years extended warranty from the
date of PAC of the first turnkey project in case of
contract award or date of first delivery in case of
direct material supply order. This was confirmed
in writing by Liaoning - Efacec Electrical
Equipment Co., Ltd (LEEEC) through their letter #
Nil dated April 18, 2012.
SAUDI POWER TRANSFORMERS Type / Model: Power Transformers Type Test Certificate PQ Lettter:
COMPANY (SPTC) #B6003867 dated 24 Based on S&SD Letter # 15-04608-03-30504401
Saudi Arabia 100 MVA, 132 kV February 2017 dated August 18, 2015, It is prequalified for
Power Transformers up to 132 kV, 100 MVA,
Plant -Dammam-Saudi Arabia
CONDITION:
Po Box 6140 Dammam 32232, Building
No. 4292 Unit No. 19 , Saudi Arabia WARRANTY:
Mr. Hosam Al Shaikh, CEO Ten (10) years extended Warranty for the
Phone: +966 13 814 4622 ext 111 proposed Power Transformers rated up to 132
Fax. +966 13 814 4627 kV, 100 MVA in respect of the defects due to
Mobile: +966 50 680 3900 design, manufacturing, installation and
workmanship from the date of the Provisional
Mr. Bahaa Abduieh, Sales & Marketing Acceptance Certificate (PAC) of the project (in
Manager case of contract award) and from the date of
Phone: + +966 13 814 4622 ext 133 delivery for the direct material supply order as
Fax. +966 13 814 4627 confirmed through the manufacturer letter# CEO
Mobile: +966 50 0082841 /2015 /008 dt:Aug 8, 2015.
Email ID - ceo@sptc.com.sa,
sales@sptc.com.sa
SCHNEIDER ENERJI ENDUSTRISI SAN Type / Model: Power Transformers Pre-qualified for Power Transformers rated up to
VE TIC A.S 132kV, 67MVA
TURKEY Rating: 132kV, 67 MVA Based on S&SD letter# 14-02364-1-30504401
dated April 01, 2014, it is pre-qualified for Power
Plant -Cayirova-Kocaeli-Turkey Transformers up to 67 MVA and, 132 kV
conforming to National Grid SA specification
Tosb Organize Sanayi Bölgesi 1.Cadde 53-TMSS-01, Rev. 01, with the following
No:6 Çayırova Kocaeli conditions:
• All Type, Special & Routine tests as per National
Contact Person - Mr. Orhan Unal Sales Grid SA Specifications/Standards shall be carried
Manager out on the first unit to be supplied to National Grid
Email ID - SA in the manufacturer Testing
orhan.unal@schneider-electric.com Laboratory in the presence of three (03) National
Grid SA Engineers & one (01) National Grid SA
approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing
by the manufacturer through their letter #
MKT_132KV Trafo_005, dated June 18, 2013.
• Schneider Electric Transformer Factory -
Cayirova, Istanbul, Turkey has confirmed that
“improvement needs implementation will be
complied during the FAT for the first transformer
order” confirmed through letter # MKT_132KV
Trafo_010 dated February 12, 2014.
• Ten (10) years extended warranty from the
date of PAC of the first turnkey project (in case
of contract award) or from the date of first
delivery in case of direct material supply order as
confirmed by the manufacturer through their
letter # MKT_132KV Trafo_007-1 dated March
19, 2014.
- Previously "AREVA-Turkey", the name has been
changed to Schneider Electric-Turkey based on
Schneider Electric letter # MKT-18.01.11 dated
18/01/2010 and AREVA T&D letter #
BF/BL25.11.2010.
ABB ELEKTRIK SANAYI A.S. ABB Saudi Arabia, Type / Model: ZTR CONDITION:
[PREVIOUSLY ABB ESAS] Al-Khobar Pre-Qualification & Participation for current &
TURKEY CONTACT PERSON: Rating: 132kV, 100MVA future SEC's Projects subjected to the mutual
Rasim Duran agreement between SEC & ABB dated 09 March
Plant Phone: 0554446258 2009
-Turkey-Istanbul/Kartaladdress:Esentep rasim.duran@sa.abb.co
e Mahallesi, Milangaz Cad m
CG POWER SYSTEMS
BELGIUM
Website - http://www.pauwels.com/
SIEMENS AG (DRESDEN) Type / Model: Power Transformer Prequalified Power Transformer up to 230kV
GERMANY PRIMARY, 200MVA
Rating: up to 230kV, 200MVA
Website - http://www.simense.com based on TS&SD letter# 09-01501-03032301
dated 25th May 2009 , Siemens AG from
Germany-Dresden for Power Transformer up to
230kV, 200MVA as confirming to SEC
specification # 53 TMSS-01, rev.0 & 53-TMSS-02,
rev.0 with the following conditions:
SIEMENS AG (NURNBERG)
GERMANY
Website -
http://www.energy.siemens.com/cms/
us/US
Products/Portfolio/Transformers/Pages/
TransformerandLTCRenewalPartSolutio
ns.aspx
Weiz , Austria
Website - http://www.vatechetg.at/
Website -
http://www.toshiba.co.jp/index j3.htm
Total = 27
POWER TRANSFORMERS
24. 2
Power Transformer rated above 100 MVA Applicable Standards: 53-TMSS-01
1000, Bangeojinsunhwan-doro,
Dong-gu, Ulsan, South Korea,
Ulsan
WARRANTY:
Ten (10) years extended Warranty for the
proposed Power Transformers in respect of the
defects due to design, manufacturing, installation
and workmanship from the date of the Provisional
Acceptance Certificate (PAC) of the project (in
case of contract award) and from the date of
delivery for the direct material supply order as
confirmed through manufacturer letter # Nil dated
November 5, 2014.
AREVA
GERMANY
Website - http://www.areva.com/
MITSUBISHI ELECTRIC CORPORATION Type/Model - Shell type ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN DURING APRIL 2005.
ABB ELEKTRIK SANAYI A.S. ABB Saudi Arabia, Type / Model: Power Transformer Prequalified for power transformer up to 250 MV
[PREVIOUSLY ABB ESAS] Al-Khobar only
TURKEY CONTACT Rating: 380kV, 250MVA
PERSON:Rasim Duran Based on S&SD letter# 14-02898/03-030504401
Plant Phone - 0554446258 dated June 17, 2014, it is pre-qualified for Power
-Turkey-Istanbul/Kartaladdress:Esentep Email - Transformer up to 380kV, 250MVA as confirming
e Mahallesi, Milangaz Cad rasim.duran@sa.abb.co to National Grid SA specification # 53-TMSS-02,
m Rev.01 with the following conditions:
Esentepe Mahallesi, Milangaz Cad No.
52 Kartal 34870, Istanbul -Turkey • All Type, Routine and Special testes as per NG
Specifications/Standards and IEC requirement
Contact Person - Mr. Sezgin Perdahci together with Thermal & Dynamic short-circuit
Phone - +90-533-666-8067 calculations per IEC 60076-5 shall be carried out
Email ID - E-mail : on the First unit to be supplied to SEC/NG of
sezgin.perdahci@tr.abb.com Power Transformers in the Manufacturer's
Website - http://www.abb.com Testing
Laboratory in the presence of three (3) SEC/NG
Engineers & one (1) SEC/ NG approved
Independent Inspection Agency (IIA) Inspector.
All costs of which shall be borne by the
manufacturer. This was confirmed in writing by
the manufacturer through their letter # Nill dated
February 04, 2013 .
• Ten (10) years extended warranty from the
date of PAC of the first turnkey project (in case
of contract award) and from the date of first
delivery in case of direct material supply order as
confirmed by the manufacturer through their
letter #Nill dated May 24, 2013.
CG POWER SYSTEMS
BELGIUM
Website - http://www.pauwels.com/
SIEMENS AG (DRESDEN) Type / Model: Power Transformer Prequalified for Power Transformer up to 230kV,
GERMANY 200MVA
Rating: up to 230kV, 200MVA
Website - http://www.simense.com based on TS&SD letter# 09-01501-03032301
dated 25th May 2009 , Siemens AG from
Germany-Dresden for Power Transformer up to
230kV, 200MVA as confirming to SEC
specification # 53-TMSS-01, rev.0 &
53-TMSS-02, rev.0 with the following conditions:
• All type, special & routine tests for each voltage
class as per SEC specifications/standards shall
be carried out on the first batch to be supplied to
SEC in securing an order in the presence
of three (3) SEC engineers & one (1) approved
independent inspection agency Inspector.
• Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award
or date of delivery in case of direct material
supply order.
ABB CORDOBA ABB Saudi Arabia, Type / Model: Power Transformer Prequalified for power transformer up to 500
SPAIN Al-Khobar MVA
CONTACT Rating: up to 380kV, 500MVA
Plant -Cordoba, Spain PERSON:Rasim Duran Based on TS&SD letter#
Phone - 0554446258 09-F011657/03-03032301 dated August 16, 2009.
Escritor Conde Zamorea, S/N ,14004 Email - It is pre-qualified for Power Transformer up to
Cordoba (Spain) rasim.duran@sa.abb.co 380kV, 500MVA as confirming to SEC
m specification # 53-TMSS-02, rev.0 with the
Contact Person - Mr. Evan Smith following conditions:
Phone - +34608749306 • All type, design, special (exclude Short-Circuit
Email ID - evan.smith@es.abb.com Test) & routine tests as per SEC
Website - Specifications/Standards together with Thermal &
http://new.abb.com/products/transform Dynamic short-circuit calculations per IEC
ers 60076-5 shall be carried out on the first unit to be
supplied to SEC in an accredited Independent
Testing Laboratory or in the manufacturer 's
testing laboratory in the presence of three (3)
SEC Engineers & one (1) SEC approved
Independent Inspection Agency (IIA) Inspector.
All costs of which shall be borne by the
manufacturer. This was confirmed in writing by
the manufacturer through their letter #
PPTR-002.2 dated February 14, 2009 and the
submitted "Confirmation Letter" # Nil dated
November 18, 2008. [this condition has been
modified based on S&SD letter#
12-0395-01-30504001 dated February 12, 2012]
SIEMENS AG (NURNBERG)
GERMANY
Website -
http://www.energy.siemens.com/cms/
us/US
Products/Portfolio/Transformers/Pages/
TransformerandLTCRenewalPartSolutio
ns.aspx
Weiz , Austria
Website - http://www.vatechetg.at/
WARRANTY:
Six (6) years extended Warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
Old Remark
Previously AREVA T&D-Turkey [The name has
been changed based on S&SD/P&SFD letter #
12-01064-30504401 dated March 14, 2012].
WARRANTY:
Ten (10) years extended warranty from the date
of PAC of the first turnkey project (in case of
contract award) and date of first delivery (in
case of direct material supply order), as
confirmed, through their Letter No.
BEST-100316-SEC-01 dated 10 March 2016.
KONCAR POWER TRANSFORMERS, Siemens Ltd.- Saudi up to 380kV & 500MVA Based on S&SD letter # 17-03229-05-30504401
Croatia (A joint Venture of Siemens and Arabia dated May 17, 2017, Koncar Power
Koncar) Siemens Ltd., 02nd floor, Transformers Ltd, Croatia (A joint Venture of
CROATIA Juffali Tower , P.O Siemens and Koncar) is pre-qualified for Power
Box#719, Al-Khobar Transformer rated up to 380kV & 500MVA as
Josipa Mokrovica 12, 10090 Zagreb 31952, Kingdom of Saudi conforming to National Grid SA specification #
Arabia 53-TMSS-01, with the following conditions:
Contact Person - Mr. Nidzar +966 (13) 865 9680
Turcinhodzic Kaisar.langoo@siemens. •Ten (10) years extended warranty from the date
Phone - +38513794075 com of PAC of the project (in case of contract award)
Email ID - Kpt.hr@siemens.com or date of delivery (in case of direct material
Contact Person Email ID - supply order), as confirmed, through their Letter
Nidzar.turcinhodzic@siemens.com No. NIL dated June 6, 2016 shall be applicable for
Website - http://www.koncar-dst.hr/ all Power Transformers rated up to 380kV &
500MVA to be supplied to SEC/National Grid SA.
HYOSUNG HEAVY INDUSTRIES Type / Model: Power Transformer Prequalified for power transformer up to 500
CORPORATION (HICO) MVA
SOUTH KOREA Rating: 380kV, 500MVA
Based on TS&SD fax#09-F01255/02-03032301
Plant -Republic of Changwon, Korea dated 25th. July 2009, it is pre-qualified for
Power Transformer up to 380kV, 500MVA as
Eric Rhie, 450, Gongdeok-Dong, confirming to SEC specification # 53-TMSS-02,
Mapo-Gu, Seoul , Korea rev.0
Tel:82-707-6180 with the following conditions:
Contact Person - Mr. Eric Rhie Sale • All type, design, special & routine tests as per
Manager & Mr. Joey W. J Kyung SEC specifications/standards shall be carried out
Marketing Manager on the first batch to be supplied to SEC in
Email ID - inseock@hyosung.com securing an order in the presence of three
Contact Person Email ID - (3) SEC engineers & one (1) approved
inseock@hyosung.com , independent inspection agency Inspector.
tsing@hyosung.com • Seven (7) years warranty from the date of PAC
Website - of the turnkey project in case of contract award
http://www.hyosung.co.kr/eng/index.js or date of delivery in case of direct material
p?, www.hyosung.com supply order.
Website -
http://www.toshiba.co.jp/index j3.htm
Total = 18
WARRANTY:
Five (05) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order as confirmed by the manufacturer through
their letter no.SSG/SEC/11, DT: 20TH April, 2007
Website - http://www.chemtrade.com
NYNAS
SWEDEN
Website -
http://www.nynas.com/default.aspx?e
pslanguage=EN
SAVITA
INDIA
Website - http://www.savita.com/
SHELL Type / Model: Previously Shell (France), The location has been
GERMANY The acceptable mineral oil type is Shell changed to Hamburg, Germany Based on the
Diala Type S2-ZU-I. manufacturer email dated 19/08/2013.
Hamburg , Germany
Website - http://www.shell.com/
Total = 5
RESISTOR
26. 1
NEUTRAL GROUNDING RESISTOR, 11 KV THROUGH 34.5 KV Applicable Standards: 57-TMSS-01
CRESSAL RESISTOR
United Kingdom
Website - http://www.cressall.com/
M.S.RESISTANCES WARRANTY:
FRANCE Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
Website - installation & workmanship from the date of
http://www.msresistances.com Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
METAL DEPLOYE
FRANCE
Website -
http://www.metaldeploye.com
NATIONAL
INDIA
FURSE
United Kingdom
Website -
http://www.furse.com/home.htm
Total = 6
REACTOR
27. 1
OIL IMMERSED REACTORS, (33 KV TO 69 KV ) Applicable Standards: 58-TMSS-01
Website -
http://www.toshiba.co.jp/index j3.htm
SIEMENS AG (NURNBERG)
GERMANY
Website -
http://www.energy.siemens.com/cms/
us/US
Products/Portfolio/Transformers/Pages/
TransformerandLTCRenewalPartSolutio
ns.aspx
Weiz , Austria
Website - http://www.vatechetg.at/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed in writing by the
manufacturer through their letter #1/115-3552
dated December 14, 2011.
CONDITION:
All Type, Special & Routine tests as per latest
National Grid SA Specifications & IEC
requirements [excluding Short circuit test ] shall
be carried out on the first unit to be supplied to
SEC/National Grid SA in the manufacturer
Laboratory in the presence of three (3) National
Grid SA Engineers & one (1) National Grid SA
approved Independent Inspection Agency (IIA)
Inspector. All costs of which shall be borne by
the manufacturer. This was confirmed in writing
by the manufacturer through their letter #Nil dated
November 10, 2012.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer through
their letter #Nil dated 25 November 2014.
Website - http://www.areva.com/
WARRANTY:
•Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation and workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
vide letter # BEST-100339-SEC-02, dated August
08, 2016.
Hyundai Electric & Energy Systems Co. Type / Model: Shunt Reactor PQ Letter:
Ltd TS&SD Letters # 10-02438-02-03032301 dated
SOUTH KOREA August 31,2010 and 13-05782-1-30504401,
December 11, 2013, pre-qualified for Shunt
Plant -Ulsan Reactor as conforming to National Grid SA
specification # 58-TMSS-01, Rev.0 with the
1000, Bangeojinsunhwan-doro, following condition.
Dong-gu, Ulsan, South Korea,
CONDITION:
Ulsan
WARRANTY:
Contact Person - Mr. Young Jun Bae Ten (10) years extended warranty/guarantee in
(Regional General Manager) , Mr. Lee respect of defects due to design, manufacture,
Chung Hee (Vice President (Power installation & workmanship from the date of
Infrastructure Sales & Marketing – II)) Provisional Acceptance Certificate (PAC) of the
Phone - +966-11-293-2026, first turnkey project in case of contract award or
+82-31-8006-6837 date of delivery in case of direct material supply
Contact Person Email ID - order and subsequently reduced yearly in case
peterbae@hyundai-electric.com , of future project award. This was confirmed by
kolch@hyundai-electric.com HHI –Korea through letter #S370 -1008-0182
Website - dated 18/08/2010.
http://www.hyundai-elec.com
MITSUBISHI ELECTRIC CORPORATION Type / Model: ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN DURING APRIL 2005.
Total = 15
REACTOR
27. 2
OIL IMMERSED REACTORS, (110 KV TO 132 KV ) Applicable Standards: 58-TMSS-01
Website -
http://www.toshiba.co.jp/index j3.htm
HITACHI LTD Rating - upto 380 kv Class Test Report No. - will Originally JAPAN AE POWER SYSTEM CORP and
JAPAN be submitted after subsequent change affected as per HITACHI
CN letter # XAE-VR-121213, dated 13-12-2012 and
Plant -Tokyo, Japan FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
SIEMENS AG (NURNBERG)
GERMANY
Website -
http://www.energy.siemens.com/cms/
us/US
Products/Portfolio/Transformers/Pages/
TransformerandLTCRenewalPartSolutio
ns.aspx
Weiz , Austria
Website - http://www.vatechetg.at/
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed in writing by the
manufacturer through their letter # 1/115-3552
dated December 14, 2011.
CONDITION:
All Type, Special & Routine tests as per latest
National Grid SA Standards & IEC requirements
[excluding Short circuit test ] shall be carried out
on the first unit to be supplied to SEC/National
Grid SA in the manufacturer Laboratory in the
presence of three (3) National Grid SA Engineers
& one (1) National Grid SA approved Independent
Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer
through their letter # Nil, dated November 10,
2012.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed in writing by the
manufacturer through their letter #Nil dated 25
November 2014.
Website - http://www.areva.com/
WARRANTY:
•Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation and workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of first delivery in case of direct material
supply order, as confirmed by the manufacturer
vide letter # BEST-100339-SEC-02, dated August
08, 2016.
ABB ( T& D)
United States
Website - http://www.abb.us/
Hyundai Electric & Energy Systems Co. Type / Model: Shunt Reactor PQ Letter:
Ltd TS&SD Letters # 10-02438-02-03032301 dated
SOUTH KOREA Rating: 132kV August 31,2010 and 13-05782-1-30504401,
December 11, 2013, pre-qualified for Shunt
Plant -Ulsan Reactor.
MITSUBISHI ELECTRIC CORPORATION Type / Model: ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN DURING APRIL 2005.
Rating: 132kV
Plant -T&D Systems Center, Amagasaki
City, Japan
Total = 15
REACTOR
27. 3
OIL IMMERSED REACTORS, (230 KV) Applicable Standards: 58-TMSS-01
Website -
http://www.toshiba.co.jp/index j3.htm
HITACHI LTD Rating - upto 380 kv Class Test Report No. - will Originally JAPAN AE POWER SYSTEM CORP and
JAPAN be submitted after subsequent change affected as per HITACHI
CN letter # XAE-VR-121213, dated 13-12-2012 and
Plant -Tokyo, Japan FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
SIEMENS AG (NURNBERG)
GERMANY
Website -
http://www.energy.siemens.com/cms/
us/US
Products/Portfolio/Transformers/Pages/
TransformerandLTCRenewalPartSolutio
ns.aspx
Weiz , Austria
Website - http://www.vatechetg.at/
Website - http://www.areva.com/
ABB ( T& D)
United States
Website - http://www.abb.us/
Hyundai Electric & Energy Systems Co. Type / Model: Shunt Reactor PQ Letter:
Ltd TS&SD Letters # 10-02438-02-03032301 dated
SOUTH KOREA Rating: 230kV August 31,2010 and 13-05782-1-30504401,
December 11, 2013, pre-qualified for Shunt
Plant -Ulsan Reactor.
MITSUBISHI ELECTRIC CORPORATION Type / Model: ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN DURING APRIL 2005.
Rating: 230kV
Plant -T&D Systems Center, Amagasaki
City, Japan
Total = 12
REACTOR
27. 4
OIL IMMERSED REACTORS, (380 KV ) Applicable Standards: 58-TMSS-01
Website -
http://www.toshiba.co.jp/index j3.htm
HITACHI LTD Type / Model: Oil Immersed Shunt Originally JAPAN AE POWER SYSTEM CORP and
JAPAN Reactors subsequent change affected as per HITACHI
letter # XAE-VR-121213, dated 13-12-2012 and
Plant -Tokyo, Japan Rating: FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
FUJI ELECTRIC CO. Type / Model: Oil Immersed Shunt Originally JAPAN AE POWER SYSTEM CORP and
JAPAN Reactors subsequent change affected as per HITACHI
letter # XAE-VR-121213, dated 13-12-2012 and
Rating: FUJI letter # AT-LTR-121115-1, dated 18-12-2012.
HYOSUNG HEAVY INDUSTRIES Type / Model: Oil Immersed Shunt Type, Routine PQ Letter:
CORPORATION (HICO) Reactors &Special tests shall S&SD letter # 14-10289-02-30504401 dated 18
SOUTH KOREA be conducted January 2015, the manufacturer is prequalified
Rating: 380kV for Oil Immersed Reactor up to 380 KV.
Plant -Republic of Changwon, Korea
CONDITION:
Eric Rhie, 450, Gongdeok-Dong, All type, special, routine tests for Oil Immersed
Mapo-Gu, Seoul , Korea Shunt Reactors per National Grid SA
Tel:82-707-6180 specifications and IEC standards & technical
requirements shall be conducted at
Contact Person - Mr. Eric Rhie Sale Manufacturer's Testing Laboratory in presence of
Manager & Mr. Joey W. J Kyung three (3) SEC/National Grid SA engineers & one
Marketing Manager (1) company approved independent inspection
Email ID - inseock@hyosung.com agency Inspector, at the sole expenses of
Contact Person Email ID - manufacturer on the first unit to be supplied to
inseock@hyosung.com , SEC/National Grid SA. This was confirmed
tsing@hyosung.com through their letter # HS-SR-141027-01 dated
Website - October 27, 2014.
http://www.hyosung.co.kr/eng/index.js
p?, www.hyosung.com WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by manufacturer and
subsequently reduced yearly in case of future
project award through their letter#
HS-SRPQ-150107-01 dated January 7, 2015.
GRID SOLUTIONS ENERJI ENDUSTRISI Type / Model: Oil Immersed Shunt Previously ALSTOM GRID, GEBZE
ANONIM SIRKETI Reactors
TURKEY PQ Letter:
Rating: 380 kV S&SD letter# 13-04034-2-30504401 dated
September 12, 2013, pre-qualified for 380 kV Oil
Immersed Shunt Reactors.
CONDITION:
All type/special, routine tests for 380 kV Oil
Immersed Shunt Reactors on one unit of each
rating supplied to SEC shall be conducted at
Manufacturer's Testing Laboratory in presence of
three (3) SEC/National Grid SA engineers & one
(1) SEC approved independent inspection agency
Inspector, all the related costs for witnessing the
tests will be borne by the manufacturer. This
was confirmed by Alstom Grid, Turkey through
their letter # Nil, dated July 22, 2013.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order as confirmed by Alstom Grid, Turkey
through their letter # Nil, dated July 22, 2013.
SIEMENS AG (NURNBERG)
GERMANY
Website -
http://www.energy.siemens.com/cms/
us/US
Products/Portfolio/Transformers/Pages/
TransformerandLTCRenewalPartSolutio
ns.aspx
Weiz , Austria
Website - http://www.vatechetg.at/
Website - http://www.abb.us/
Hyundai Electric & Energy Systems Co. Type / Model: Oil Immersed Shunt PQ Letter:
Ltd Reactors TS&SD Letters # 10-02438-02-03032301 dated
SOUTH KOREA August 31,2010 and 13-05782-1-30504401,
Rating: 380kV December 11, 2013, pre-qualified for Shunt
Plant -Ulsan Reactor.
MITSUBISHI ELECTRIC CORPORATION Type / Model: Oil Immersed Shunt ORIGINALLY TMT&D CORP. & DISSOLVED
JAPAN Reactors DURING APRIL 2005.
Total = 12
REACTOR
27. 5
AIR CORE SERIES REACTOR, 13.8KV THROUGH 380KV (230 KV AIR CORE Applicable Standards: 52-TMSS-02, 58-TMSS-02
NOKIAN – GRID SOLUTIONS OY LTD. Type / Model: Air core series reactor PQ Letter:
FINLAND S&SD letter # 14-03642-01-30504401 dated June
Rating; 145kV 11, 2014, NOKIAN – ALSTOM Grid oy Ltd.
Tampere , Finland Tampere-Finland is pre-qualified for Air Core
P.O.Box 4, Kaapelikatu 3 fl-33331 Series Reactors up to145 kV.
Vehmaistenkatu 5 fl-33730
WARRANTY:
Phone - +358 3 388311 Ten (10) years extended warranty/guarantee in
Email ID - firstname.surname@ge.com respect of defects due to design, manufacture,
Website - www.gegridsolutions.com installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer through
their letter # Nil, dated 20th June 2012.
POWER ECONOMY MIDDLE EAST CO. Type / Model: Air core Reactor. PQ Letter:
United Arab Emirates Based on TS&SD letter #07-F691-03032300
Rating: Limited to 34.5kV only dated May 21, 2007, it is pre-qualified for Air Core
Plant -Abu Dhabi , United Arab Emirates Reactors Limited to 34.5kV only
Website - WARRANTY:
http://www.powereconomy.net/ Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed through the manufacturer
letter # O-694-KSA-SEC, dated 20th Nov,2006.
WARRANTY:
Seven (7) years Extended Warranty shall be
applicable for the Air Core Series Reactors to be
supplied to SEC by TRENCH CANADA as
confirmed through their letter # NIL dated April 28,
2010.
Total = 4
CELLMEC
BAHRAIN
Website - http://www.cellmec.com/
Total = 1
ABB
SWITZERLAND
Total = 2
Website -
http://www.atlanticwood.com/
COLFAX CREOSOTING CO
United States
KOPPERS INDUSTRIES
United States
Pa , United States
Website - http://www.koppers.com/
STALLWORTH TIMBER
United States
Website -
http://www.stella-jones.com/welcome
eng.htm
Website -
http://www.taylorlumberinc.com/
Total = 7
Website -
http://www.atlanticwood.com/
COLFAX CREOSOTING CO
United States
KOPPERS INDUSTRIES
United States
Pa , United States
Website - http://www.koppers.com/
STALLWORTH TIMBER
United States
Website -
http://www.stella-jones.com/welcome
eng.htm
Website -
http://www.taylorlumberinc.com/
Total = 7
UNIBUS
United States
ABB ( T& D)
United States
Website - http://www.abb.us/
WESCOSA
Saudi Arabia
Total = 3
SWITCHES
32. 1
LV AUTO-TRANSFER SWITCH Applicable Standards:
ALSTOM
FRANCE
Website -
http://www.alstom.com/home/
ASCO
United Arab Emirates
Website - http://www.asco.co.ae
WESTINGHOUSE
United States
Website -
http://www.westinghouse.com
Total = 3
SWITCHES
32. 2
PAD MOUNTED SF6/OIL SWITCH, 34.5 KV Applicable Standards:
FRITZ DRIESHER KG
GERMANY
Website -
http://www.driescher.de/home/index.ht
m
Total = 1
SWITCHES
32. 3
CIRCUIT SWITCHER, 69 –230 KV Applicable Standards:
SIEMENS
GERMANY
Berlin, Germany
IC SG EA MF
Wernerwerkdamm 5,
13629, Berlin, Germany
S&C
United States
Website - http://www.sandc.com/
S&C
CANADA
Total = 3
TRANSDUCERS
33. 1
FREQUENCY TRANSDUCERS Applicable Standards:
ALSTOM
United States
Website -
http://www.alstom.com/home
ISKRA MIS Adnan Sabban Type/Model - Saprk Energy DZ9 ACCEPTANCE SUBJECTED TO SUCCESSFUL
SLOVENIA Est Office #6 1st Floor Al PRODUCT EVALUATION / ACCEPTANCE BY SEC
Hamad II Center Al Zahra CONCERNED END USER DEPARTMENT FOR EACH
Kranj , Slovenia District PURCHASE ORDER / PROJECT DURING
050-55-989-84 ,Phone - TENDER/BIDDING STAGE.
050-55-989-84
zakaria@ase-ksa.com
Total = 2
TRANSDUCERS
33. 2
TAP POSITION TRANSDUCERS Applicable Standards:
AREVA
United Kingdom
Website - http://www.areva.com/
Total = 1
TRANSDUCERS
33. 3
TRANSDUCERS Applicable Standards:
CEWE INSTRUMENTS AB
SWEDEN
Website -
http://www.ceweinstrument.se/
ENERDIS
FRANCE
Website -
http://www.chauvin-arnoux.com/
TILLQUIST
SWEDEN
Website - http://www.tillquist.com/
LSIS , WARRANTY
SOUTH KOREA Seven (07) years extended warranty/guarantee
in respect of defects due to design, manufacture,
Ls Tower, 127, Ls-Ro, Dongan-Gu, installation & workmanship from the date of
Anyang-Si, Gyeonggi-Do, Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
Contact Person - Mr. Je-woo, Lee date of delivery in case of direct material supply
Assistant Manager order.
Phone - +82-2-2034-4541
Email ID - jwleea@lsis.com
Website - http://www.lsis.com
WARRANTY
Five (05) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order. This was confirmed by TYCO Electronic,
UK through their letter # INT-SEC-06 dated
Jamuary 03, 2008 and its amendment dated
November 21, 2011
Total = 5
TRANSDUCERS
33. 4
WATTHOURS/VARHOURS TRANSDUCERS Applicable Standards:
ISKRA MIS Adnan Sabban Type/Model - Sparklight , ADM 16 ACCEPTANCE SUBJECTED TO SUCCESSFUL
SLOVENIA Est Office #6 1st Floor Al PRODUCT EVALUATION / ACCEPTANCE BY SEC
Hamad II Center Al Zahra CONCERNED END USER DEPARTMENT FOR EACH
Kranj , Slovenia District PURCHASE ORDER / PROJECT DURING
Phone - 050-55-989-84 TENDER/BIDDING STAGE.
Email -
zakaria@ase-ksa.com
MITSUBISHI ELECTRIC
JAPAN
Website -
http://global.mitsubishielectric.com/
SCIENTIFIC COLUMBUS
United States
Website -
http://www.scientificcolumbus.com/
Total = 3
TRANSDUCERS
33. 5
VOLTAGE TRANSDUCERS Applicable Standards:
Montreal , Canada
Website - http://www.abb.ca/
TRANSDATA
United States
Website -
http://www.transdatainc.com/index.ht
m
AREVA
United Kingdom
Website - http://www.areva.com/
Total = 4
TRANSDUCERS
33. 6
WATTS/VARS TRANSDUCERS Applicable Standards:
Montreal , Canada
Website - http://www.abb.ca/
TRANSDATA
United States
Website -
http://www.transdatainc.com/index.ht
m
AREVA
United Kingdom
Website - http://www.areva.com/
Total = 4
CONDITION
Type test shall be conducted in independent
testing laboratory for the SAS System as per
National Grid SA Specifications/Standards,
IEC61850 Edition2, and latest amendments of IEC
in an accredited laboratory in presence of three
(03) SEC/National Grid SA engineers and one
(01) National Grid SA approved Independent
Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer by
ALSTOM Grid AG –France, U.K through their
letter SAS/TSSD/2014/WR1201-1 dated January
12, 2014.
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
ABB Electrical Industries Company Ltd ABB Automation Co. Ltd Note:
,SAUDI ARABIA Riyadh Previously " ABB Automation ", the name has
Saudi Arabia Phone - 0504417681 been changed to "
Email - ABB Electrical Industries Company Ltd ". based
Plant -2Nd Industrial Area,Riyadh, Aref.alarrak@sa.abb.co on their letter # PGGA/SM-001 dated February
m 08,
Po Box 325841 Riyadh,11371 KSA 2018.
Warranty
•Ten (10) years extended warranty from the date
of PAC of the first turnkey project (in case of
contract award) or date of first delivery (in case
of direct material supply order), as confirmed,
through their letter # PGGA/SAS/0101, dated
February 4, 2018 shall be applicable for all 380
kV SUBSTATION AUTOMATION SYSTEM (SAS),
to be supplied to SEC/National Grid SA.
Type Test
•Type Tests shall be conducted on the SAS
System as per the new IEC 61850-10 (2012-12)
Edition 2 in an accredited laboratory in presence
of three (3) SEC/National Grid SA Engineers and
one (1) Company approved IIA Inspector at the
sole expense of ABB as confirmed through their
letter # PSN/SAS/0709/08/2013, dated July 9,
2013
Old remarks:
PQ Lettter
Based on S&SD letter# 14-00953-1-30504401
dated February 27, 2014, ABB Automation Co.
Ltd., Riyadh is pre-qualified for integration and
testing of SAS systems for substations rated up
to 230kV against specification # TES-P-107.01,
Rev.00 with the following conditions:
CONDITION
Type test shall be conducted in independent
testing laboratory for the SAS System as per
National Grid SA Specifications/Standards,
IEC61850 Edition2, and latest amendments of IEC
in an accredited laboratory in presence of three
(03) SEC/National Grid SA engineers and one
(01) National Grid SA approved Independent
Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer by
ABB-Riyadh through their letter #
PSN/SAS/0709/08/2013 dated July 09, 2013.
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order.
30 DO + 8 AI}
( 8 Analog Current Inputs selectable 4-20 mA, 0-1
mA, 0-5 mA, 0-10 mA, 0-20 mA )
SAS Equipment:
SEL PQ Lettter
United States Based on the S & SD letter# 14-01257-30504401
dated 23 March 2014, Schweitzer Engineering
Laboratory (SEL) -U.S.A is prequalified for
Substation Automation System (SAS) with
Integration and Testing of SAS to be performed
only by (SEL), at SEL Al-Khobar, KSA for SAS
Panels as Integration and testing of SAS panels
with following condition:
CONDITION
Type Tests: The manufacturer has confirmed to
perform the required type tests in Independent
Testing laboratories- KEMA as per SEC/National
Grid SA requirements, IEC 61850 Edition 2
standards in the presence of three (3)
SEC/National Grid SA Engineers and one (1)
Independent Inspector through reference letter #
SEL/SAS/08/2013.
WARRANTY
The manufacturer has agreed to give guarantee/
warranty to SEC/National Grid SA for the
proposed Substation Automation System (SAS)
from SEL U.S.A with Integration & Testing facility
at SEL Al-Khobar, KSA for SAS Panels as
Integration and testing of SAS panels in respect
of the defects due to design, manufacturing,
installation and workmanship for a period of ten
(10) years , This was confirmed in writing by the
manufacturer through their letter ref:
LSELSA/17-34,
dated June 14, 2017.
SIEMENS Siemens Ltd IC SG EA Type/Model - Substation Automation Bay Controller Unit Old comments:
GERMANY Pro System (FOR NEW TYPE):
Jeddah 21412 Baladiyah Rating - 380 kV 13.8 kV Type test Report PQ Lettter
Plant -NURNBERG Germany Street PO Box 4621 Mr. #G0M-1412-4383-S Based on the S&SD letter#
Ahmad Ainousah 0C000-V01 Dated: 14-03345-02-30504401 dated May 20, 2014,
Ic Sg Ea Mf Wernerwerkdamm 5 13629 Phone - Bay Controller Unit December,2014 SIEMENS -Germany is prequalified for Substation
Berlin Germany. +966-12-6618869 (Old Type) Automation System (SAS) with Integration and
Email - Type 6MD85 Laboratory:Eurofins Testing at SIEMENS–Jeddah K.S.A up to 380kV
Phone - +49(30)386-26688 ahmad.ainousah@sieme Ordering code: ProductService projects subject to the following conditions
Email ID - ns.com 6MD85-P1G33877 GmbH
hartmut.von.zander@siemens.com Built-in functions: & RTDS Test Report CONDITION
CONTROL & MIMIC # EM DG PTI PSC Type test shall be conducted in independent
SYNCH Check /pc200768 / VH testing laboratory for the SAS components as
Metering Dated per National Grid SA requirements latest revision
Interlocking December,016 of IEC 61850 (edition 2) on the approved
Supervision & Monitoring Functions: Laboratory: Independent Testing laboratory witnessing by
CT supervision Siemens Germany three (3) National Grid SA engineers and one (1)
74TC AG approved Independent Agency Inspector (IIA). All
74DC Supervision costs of witnessing the tests shall be borne by
74 Lockout Supervision the Siemens – Jeddah K.S.A as per their
60VT confirmation through letter # Nil dated April 21,
DFR/SOE 2014.
Hardware:
4 CT Measurements WARRANTY:
12 VT = 3 X 4 VT SETS ( Upper BB, Ten (10) years extended warranty/guarantee in
Lower BB, respect of defects due to design, manufacture,
line ) VT`s installation & workmanship from the date of PAC
115 BI of the first turnkey project (in case of contract
09 BO award) or from the date of first delivery in case
IEC61850 -PRP x 2 FO ports of direct material supply order as confirmed from
(New Type) SIEMENS -Germany & for Integration & Testing
Type 6MD85 facility at SIEMENS –Jeddah K.S.A the
Ordering code: Siemens-Germany & Siemens –Jeddah K.S.A
6MD85-P1G33886 through their letter # Nil dated November 12,
Built-in functions: 2012.
CONTROL & MIMIC
SYNCH Check Bay Controller Unit (BCU) : type 6MD6 from
Metering SIEMENS –Germany is with ordering code
Interlocking (6MD6631-4EB90-0AA4+L0S) shall be used.
Supervision & Monitoring Functions:
CT supervision Protection IEDS: From Manufacturers listed in
74TC section 15 of the data base of Approved
WARRANTY:
Ten (10) years extended warranty from the date
of PAC of the first turnkey project (in case of
contract award) or date of first delivery (in case
ofdirect material supply order), as confirmed,
through their letter # EA PRO/Pz, dated April 22,
014 shall be applicable for all (SIPROTEC 5
Relays) to be supplied to SEC/National Grid SA.
SPRECHER AUTOMATION GMBH ALFANAR ELECTRICAL up to 380KV Based on the S & SD fax #
AUSTRIA SYSTEMS Saudi Arabia 16-08451-02-30504401 dated 16/11/2016
Plant -3Rd Industrial Sprecher Automation GmbH –Austria with
Plant -Franckstrabe 51,4018 Linz, Zell Area, Al Integration and FAT at Al-Fanar Electrical System
am See & Vienna in Austria Kharaj Road, Riyadh –Riyadh K.S.A for Substation Automation
Saudi Arabia System- SAS up to 380KV is prequalified against
Contact Person - Mr. Peter Wach –Area Po Box 301 , Riyadh TES-P-107.01, Rev.00, with the following
Sales Manager 11411 , North conditions:
Contact Person Email ID - Righ Road Between Exit
peter.wach@sprecher-automation.com 5&6 1. Type Tests: The manufacturer has confirmed
Riyadh , Saudi Arabia to perform the required type tests in SEC/National
Contact Person - Mr. Grid SA approved Independent Testing laboratory
Samer Y. Mokdad , as per SEC/National Grid SA requirements , IEC
Executive Manager. 61850 Edition 2 standards in the presence of
Email: three (3) SEC/National Grid SA Engineers and one
samer.mokdad@alfanar. (1) Independent Inspector through reference
com letter dated 24/10/2016 , ref#
ashraf.mohamed@alfan AES-SAS-PQA-2016/008.
ar.com
Phone - 2. Guarantee/Warranty: The manufacturer (Both
+966-540339574 Sprecher & Al-Fanar) has agreed to give
guarantee/ warranty to SEC/National Grid SA for
the proposed Substation Automation System
(SAS) from SPRECHER Automation GmbH
-Austria with Integration and FAT at AL-FANAR
ELECTRICAL SYSTEM –Riyadh K.S.A in respect
of the defects due to design, manufacturing,
installation and workmanship for a period of ten
(10) years , This was confirmed in writing by the
manufacturer through their letter for SAS.
Edition.
Total = 7
NEST OY/NAPS
FINLAND
Total = 1
ATOFINA CHEMICALS
United States
Website - http://www.atofina.com
Website -
http://www.dielectrictechnologies.com/
index.html
INDOPOL
FRANCE
Lavera , France
Website - http://www.indopol.com/
Website - http://
http://www.furukawa.co.jp/english/ind
ex.
SIEMENS
GERMANY
Total = 5
DC POWER SYSTEMS
37. 1
DC POWER SYSTEMS Applicable Standards:
EXIDE CORP.
United States
Pa , United States
Website - http://www.exide.com/
Website -
http://www.harmerandsimmons.com/
Website -
http://www.powersupplysystems.com/
index2.htm
Total = 4
NERA
NORWAY
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
Turgi , France
Website - http://www.abb.fr/
Website - http://www.ge.com/
SIEMENS
GERMANY
Berlin, Germany
IC SG EA MF
Wernerwerkdamm 5,
13629, Berlin, Germany
AREVA
FRANCE
Total = 6
POSITRON INDUSTRIES
CANADA
Montreal,Canada
Total = 1
VF INTERFACE EQPT.
40. 1
VF INTERFACE EQPT. Applicable Standards:
Turgi , Switzerland
Website - http://www.abb.ch/
TELLABS INC.
United States
Website - http://www.tellabs.com/
Total = 2
ELECTRONIA
Saudi Arabia
Website - http://www.electronia.com/
GE/ERICSON
United States
GLENAYRE
CANADA
Bc , Canada
Website - http://www.glenayre.com
KENWOOD
United States
Website -
http://www.kenwoodusa.com/
MOTOROLA
United States
Website -
http://www.motorola.com/us/products.j
sp
NEC
United States
Website - http://www.nec.com/
PHILIPS
United Kingdom
Website -
http://www.philips.co.uk/index.page
NOKIA
FINLAND
Website - http://www.nokia.com/
Total = 8
TEST EQUIPMENT
42. 1
TEST EQUIPMENT Applicable Standards:
PHILIPS
United Kingdom
Website -
http://www.philips.co.uk/index.page
ACTERNA
United States
Website - http://www.acterna.com/
Tokyo , Japan
Website - http://www.ando.nl/
Website - http://www.hp.com/
IFR
United States
Website -
http://www2.rohde-schwarz.com/
TREND
SPAIN
Website -
http://es.trendmicro.com/es/home/
Total = 8
TEST EQUIPMENT
42. 2
TEST EQUIPMENT (FIBER OPTIC RELATED) Applicable Standards: 48-TMSS-14
ANRITSU CORPORATION
JAPAN
Tokyo , Japan
Website - http://www.anritsu.com/
Total = 1
TEST EQUIPMENT
42. 3
TEST EQUIPMENT (RADIO RELATED) Applicable Standards:
BIRD
United States
Website -
http://www.bird-electronic.com/
MARCONI
United Kingdom
Website -
http://mecss.com.sa/contact.html
Total = 2
TEST EQUIPMENT
42. 4
TEST EQUIPMENT (RADIO/PAGING RELATED) Applicable Standards:
NEC
United States
Website - http://www.nec.com/
Total = 1
TEST EQUIPMENT
42. 5
RADIO/PAGING EQUIPMENT (ACCESSORIES) Applicable Standards:
ALLEN
United States
ANDREW
United States
Il , United States
Website - http://www.andrew.com/
CELWAVE
United States
Website - http://www.celwave.com/
DECIBEL
United States
FLEXWELL
United States
JAYBEAM
United Kingdom
Website -
http://www.jaybeamwireless.com/inde
x.php
Website - http://uk.rs-online.com/web/
Total = 8
UHF RADIO
43. 1
UHF RADIO Applicable Standards:
ASCOM
United Kingdom
Website -
http://www.ascom.co.uk/uk-en
SIMOCO
United Kingdom
Website -
http://www.simoco.com/index.php
ALCATEL
FRANCE
Website - http://www.alcatel.fr/
Total = 3
NOKIA
FINLAND
Website - http://www.nokia.com/
ABB-Ludvika
SWEDEN
Plant -Sweden
Ludvika, Sweden
NORTEL
CANADA
Website - http://www.nortel.com/
Total = 3
JANUS FIRE SYSTEMS Mr. John Parker CO2 UL Listed The manufacturer is added based on
United States + 9733888644 Low pressure & High Pressure confirmation by Industrial Security Sector
john.parker@amerex-fire Systems /Industrial Security Performance Department
1102 Rupccih Drive .com Manager as per email message of
Millennium Park January,16,2017”.
Crown point ,IN 46307
“ Janus Fire Systems, USA, has agreed to give
Telephone :219.663.1600 Guarantee/ Warranty to SEC/ National Grid SA
Fax : 219.663.4562 vide letter # Nil, dated April 07, 2017, for the
proposed Fire Fighting System-High Pressure
Contact Person - Barry Cornel Carbon Dioxide (CO2) in respect of the defects
Email ID - due to design and manufacturing for a period of
bcornell@janusfiresystems.com ten (10) years from the date of the Provisional
Acceptance Certificate (PAC) of the project (in
case of contract award) or from date of delivery
for the direct material supply order. The
guarantee/ warrant shall be applicable for the
first project and shall subsequently be reduced
yearly in case of future project award
NAFFCO NAFFCO UL listed Co2 extinguisheres ,model UL listed The manufacturer is added based on
United Arab Emirates PO BOX 67716 RIYADH 451,456,466, C -50-SE ,and C-100-SE. LPCB approved UL confirmation by Industrial Security Sector
11517 UL listed Dry Chemical Extinguishers listed Fire /Industrial Security Performance Department
NAFFCO, P.O Box :17014, Dubai, TEL : 0112824444 Wheeled type. Extinguishers ,and Manager as per email message of
United Arab Emirates. 'Sathiskumar@naffco.co LPCB Mobile Fire Extingishres. LPCB/BSI approved January,16,2017”, and April 24, 2017
m'; Fire Extinguishers
Tel :- # 97148066666 'ksa.est1@naffco.com'
Fax: # 971 48816229
Dubai
Website - http://www.kiddeus.com/
Website -
http://www.atd-cardox.com/atd-cardo
x-vertretungen.htm
Website -
http://www.chemetron.com/utcfs/Temp
lates/Pages/Template-46/1,8060,pageId
=1192&siteId=374,00.html
FIKE
United States
Website - http://www.fike.com/
HYGOOD
United States
Website -
http://www.hygood.co.uk/default.asp
Total = 7
GRINNEL
United States
Website - http://www.grinnell.com/
Website -
http://www.reliablesprinkler.com/
SPRAYSAFE
United States
Website -
http://www.centralspraysafe.com/cgi-
bin/webscripts/nph-home.pl
Website -
http://www.vikingrange.com/consumer
/index.jsp
WATTS
United States
Website - http://www.watts.com/
Total = 5
Viking GmbH & Co. KG Advanced Elements for FM200 System: UL/FM/VdS The manufacturer is added based on
GERMANY Fire Protection Systems Model VSN200 @ 25, 42& 50 bars UL/FM/VdS confirmation by Industrial Security Sector
Tel: 0114722799 /Industrial Security Performance Department
INDUSTRIESTRASSE 10/12 Manager as per email message of
23480 BAD OLDESLOE, GERMANY January,16,2017
FIRETRACE Guarantee Business FM200 System: UL & ULC listed The manufacturer is added based on
United States Contracting Est Models,01-001372,01-001407, confirmation by Industrial Security Sector
KSA – P.O Box 26018 01-001487,01001587,01-001712,01-00 /Industrial Security Performance Department
USA L L C EX15893 Riyadh 1897,01-002537 all @360 psig (25 bar) Manager as per email message of
SUITE 2 0114919669 January,16,2017”.
8435 N 90TH ST
SCOTTSDALE, AZ 85258 USA
Middle East, North Africa & Caspian
SIEX Engineering Field Est. 1) SIEX –HC 227 (25 & 24 bar). UL Listed FM The manufacturer is added based on
SPAIN Phone : 02-6579028 2) SIEX –HC227 S- Flow (32.34.50.& approved. confirmation by Industrial Security Sector
Fax : 026579028 55 bar) /Industrial Security Performance Department
2001 SL Agil Alattas Manager as per email message of
POL INDUSTRIAL VILLAONQUEJAR info@ef.com.sa January,16,2017
C/MERINDAD DE MONTIJA NO 6
09001 BURGOS,SPAIN
Fike Corporation NAFFCO Fike UL /FM approved FM 200 UL Listed FM The manufacturer is added based on
United Arab Emirates PO BOX 67716 RIYADH Using Fike impulse Valve with burst approved confirmation by Industrial Security
11517 disc Sec-or/Industrial Security Performance
Plant -Dubai Gulf Star Security & Department Manager per email mess-age of
Safety Jan-uary,16,2017”, and April 24, 2017.
Sheikh Zayed Road P.O Box 125917 Head office ,2nd floor ,Al
kaaf Al Akhdr Bldb,
Steen street , Jeddah
Al-Sarh Al-Methali
Trading
6th street ,off 95th
street. 2nd industrial City
Dammam
TEL : 0112824444
SIEMENS BUILDING TECHNOLOGIES – Siemens Ltd. Sinorix 227 (360 PSI) Fire Extinguishing UL Listed The manufacturer is added based on
FIRE SAFETY Business Gate, P.O. Box System. confirmation by Industrial Security Sector
United States 9510, 11423 Riyadh, •The gas is identified as:UL scope of fil /Industrial Security Performance Department
Saudi Arabia EX6288, SHANGHAI Waysmos Fine Manager as per email message of
SIEMENS INDUSTRY INC EX4724 Chemical Co Ltd (DBA Waysmos USA, January,16,2017”.
8 Fernwood Rd Tel +966 (11) 277 8208, Product tradename MH227),388 Liangle
Fax +966 (11) 277 8497, Rd, Laogang Town Pudong New
Florham Park, NJ 07932-1906 USA Mobile +966 (54) 335 District 201322 Shanghai, CHINA
0691, +966 (54) 346
3238
ashfaq.abdul-jabbar@si
emens.com
DUPONT
United States
GREAT LAKES
United States
Total = 8
FENWAL
United States
FIGGIE
United States
FIREATER
United States
KIDDE
United States
Website - http://www.kiddeus.com/
MINIMAX PQ Lettter
GERMANY Based on S&SD Letter 12-02704-02-30504001
dated February 19, 2012. It is pre-qualified for
Bad Oldesloe , Germany Fire Protective Signaling Panel as conforming to
SEC Specification # 90-TMSS-01 Rev.0
CONDITION
All Type, Routine and Special testes shall be
carried out on the first batch of Fire Protective
Signaling Panel in an Independent Testing
Laboratory in the presence of three (3) SEC
Engineers & one (1) SEC approved Independent
Inspection Agency (IIA) Inspector. All costs of
which shall be borne by the manufacturer. This
was confirmed in writing by the manufacturer
through their letter # Nil dated January 11, 2011.
WARRANTY
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #nil, dt: jan 11, 2011.
Website -
http://www.chemetron.com/utcfs/Temp
lates/Pages/Template-46/1,8060,pageId
=1192&siteId=374,00.html
FIKE
United States
Website - http://www.fike.com/
HYGOOD
United States
Website -
http://www.hygood.co.uk/default.asp
Website - https://
http://www.ansul.com/en/home.asp
Total = 10
JANUS FIRE SYSTEMS Mr. John Parker Novec1230 System: UL Listed “The manufacturer is added based on
United States Ph: + 9733888644 Sv, Mv and Lv Series confirmation by Industrial Security Sector
E Mail: /Industrial Security Performance Department
1102 Rupccih Drive john.parker@amerex-fire Manager as per email message of
Millennium Park .com January,16,2017”.
Crown point ,IN 46307 Janus Fire Systems, USA, has agreed to give
Guarantee/Warranty to SEC/National Grid SA vide
Telephone :219.663.1600 letter # Nil, dated April 07, 2017, for the proposed
Fax : 219.663.4562 Fire Fighting Systems-Novec 1230 Fluid
(F-K-1-12 Dodecafluoru-2-methylpentan-3-one
Contact Person - Barry Cornel CF2CF2C(O)CF(CF3)2) in respect of the defects
Email ID - due to design and manufacturing for a period of
bcornell@janusfiresystems.com ten (10) years from the date of the Provisional
Acceptance Certificate (PAC) of the project (in
case of contract award) or from date of delivery
for the direct material supply order. The
guarantee/warrant shall be applicable for the first
project and shall subsequently be reduced yearly
in case of future project award.
Viking GmbH & Co. KG Advanced Elements for Novec1230 System: UL/FM/VdS The manufacturer is added based on
GERMANY Fire Protection Systems Model VSN1230 @25, 42 &50 bars. UL/FM/VdS confirmation by Industrial Security Sector
Tel: 0114722799 /Industrial Security Performance Department
INDUSTRIESTRASSE 10/12 Manager as per email message of
23480 BAD OLDESLOE, GERMANY January,16,2017”.
FIRETRACE Guarantee Business Novec1230 System: UL & ULC listed The manufacturer is added based on
United States Contracting Est Models : 01-001352, confirmation by Industrial Security Sector
KSA – 01-001366,01-001399, /Industrial Security Performance Department
USA L L C EX15893 P.O Box 26018 01-001440,01-001490, Manager as per email message of
SUITE 2 Riyadh 01-001564,01-001705,01- January,16,2017”.
0114919669 0011827 all @34 bar
8435 N 90TH ST
SCOTTSDALE, AZ 85258 USA
Middle East, North Africa & Caspian
SFFECO 3M Novec 1230 Fire protection UL Listed FM The manufacturer is added based on
Saudi Arabia Extinguishing system units having approved. confirmation by Industrial Security Sector
nominal ging capacitiec of Multiple Listing with /Industrial Security Performance Department
2ND INDUSTRIAL AREA 38,65,,130,2277,and 895 lb @ 25 bar. SEVO Manager as per email message of
AL-KHARJ RD Design & installation per Sevo VDS January,16,2017”.
PO BOX 58469 software Novec –Calculationprogram.
RIYADH, 11515 SAUDI ARABIA
Total = 4
Website -
http://www.simplexgrinnell.com/
THORN
United Kingdom
Website -
http://www.thornlighting.co.uk/gb/en/in
dex.htm
AUTOCALL (GRINNEL)
United States
MIRETONE
United States
SHIELD FIRE SAFETY & SECURITY LTD NAFFCO Extinguishing Control panel mpdel A-Xt. UL Listed FM The manufacturer is added based on
United Kingdom PO BOX 67716 RIYADH Poto –Electric smoke detector model S approved. confirmation by Industrial Security Sector
11517 C2011 /Ind-ustrial Sec-urity Perform-ance Depart-ment
SHIELD FIRE SAFETY & SECURITY LTD TEL : 0112824444 Heat Detector S-C2013 Standard Mana-ger as per email mess-age of
S25191 Eng Selva. mounting base S-c2001Abort switich Jan-uary,16,2017”
REDBURN HOUSE S111R AB
2A TONBRIDGE ROAD Fire Alarm Bell FB-1000C6
ROMFORD, ESSEX RM3 8QE UNITED
KINGDOM
Hochiki America Corporation Engineering Field Est. Addresable (Fire net seies ) & UL Listed FM The manufacturer is added based on
United States Agil Alattas Conventional (HCA seies)Fire Alarm & approved. confirmation by Industrial Security Sector
Phone : 02-6579028 Detection Systems :- /Industrial Security Performance Department
7051 Village Drive, Suite 100 Buena Fax : 026579028 • Fire Control Panels. Manager as per email message of
Park, CA 90621-2268 info@ef.com.sa • Gas Extinguishing Control Panels. January,16,2017”.
• Fire Detection & Alarm Devices.
Phone - Phone : 714/522-2246
Email ID -
technicalsupport@hochiki.com
Website - WWW.Hochiki.com
Total = 9
Website - http://www.aurora.com/
FAIRBANK MORSE
United States LOCAL AGENT –SAUDI PUMP >=500GPM
Website -
http://www.fairbanksmorse.com/
FLOWAY
United States
Website -
http://www.weiroilandgas.com/weirw
eb/oilandgas/home.nsf
Website -
http://www.peerlesspump.com/
PETTERSON
United States
Website -
http://www.ie.pattersonpumps.com/
REDDY BUFFALOU
United States
Website - http://www.rbpump.com/
Website -
http://www.worthington-biochem.com/
Illinois
Total = 8
SFFECO
Saudi Arabia
Total = 2
Website - https://
http://www.ansul.com/en/home.asp
Website -
http://www.sentry-equip.com/display/r
outer.aspx
Website - http://www.kiddeus.com/
Total = 3
Website - https://
http://www.ansul.com/en/home.asp
Website -
http://www.sentry-equip.com/display/r
outer.aspx
Total = 2
Website -
http://www.sentry-equip.com/display/r
outer.aspx
Total = 1
ANGUS
United Kingdom
Website -
http://www.angusfire.co.uk/utcfs/Temp
lates/Pages/Template-46/0,8060,pageId
%3D1260%26siteId%3D404,00.html
Website - http://www.chemguard.com/
Website -
http://www.kidde-fire.com/utcfs/Templ
ates/Pages/Template-50/0,8061,pageId
%3D3513%26siteId%3D465,00.html
HILTI INTERNATIONAL, Hilti construction Hilti Saudi Arabia P.O FIRESTOP PRODUCTS; UL Listed FM The manufacturer is added based on
chemicals ,Div.of Hilti Inc. box 286701 Firestop Sealants, firestop Foams, approved. confirmation by Industrial Security Sector
United States Riyadh11323 Firestop collars & Wraps ,Firestop /Industrial Security Performance Department
T: 0114608974 Mortars & Boards, Firestop cast in Manager as per email message of
5400 122nd East Ave Fax: 0114606255 Devices ,Firestop Blocks ,Plugs January,16,2017”.
Tusla ,OK 74146 Mobile : 0504657548 ,Cushions. Fire Protection Coatings &
abusheikha@ hilti.com Fire stop Transit Systems.
WWW.hilti.sa
Total = 4
HVAC Units
47. 1
HVAC Units Applicable Standards: 73-TMSS-01
TRANE
Saudi Arabia
PETRA
JORDAN
Total = 7
Total = 4
Total = 2
SIEMENS
GERMANY
Berlin, Germany
IC SG EA MF
Wernerwerkdamm 5,
13629, Berlin, Germany
Saudi Arabia
WESCOSA
Saudi Arabia
Total = 3
Geneva, Switzerland
CG POWER SYSTEMS
BELGIUM
Website - http://www.pauwels.com/
Total = 2
ABB ( T& D)
United States
Website - http://www.abb.us/
Total = 1
SIEMENS PQ Letter:
Saudi Arabia Based on S&SD letter # 14-08957-02-30504401
dated 17 December 2014, the manufacturer is
Plant -Jeddah prequalified for Integration (Assembly) and
Testing of Communication Equipment from
Website - http://www.siemens.com.sa Original Equipment Manufacturer (OEM) type
tested and approved by National Grid SA as
conforming to National Grid SA specification #
48-TMSS-06, Rev.0 with the following condition:
WARRANTY:
Ten (10) years extended warranty/guarantee in
respect of defects due to design, manufacture,
installation & workmanship from the date of
Provisional Acceptance Certificate (PAC) of the
first turnkey project in case of contract award or
date of delivery in case of direct material supply
order, as confirmed by the manufacturer thru
letter #Fe/08/14 dated October 10, 2012.
Total = 3