Вы находитесь на странице: 1из 13

Applied Energy 89 (2012) 430–442

Contents lists available at SciVerse ScienceDirect

Applied Energy
journal homepage: www.elsevier.com/locate/apenergy

Effect of thermal mass on performance of insulated building walls and the concept
of energy savings potential
Sami A. Al-Sanea a,⇑, M.F. Zedan a, S.N. Al-Hussain b
a
Department of Mechanical Engineering, College of Engineering, King Saud University, P.O. Box 800, Riyadh 11421, Saudi Arabia
b
SABIC’s Technology and Innovation (T&I) Division, P.O. Box 42503, Riyadh 11551, Saudi Arabia

a r t i c l e i n f o a b s t r a c t

Article history: Effects of varying amount and location of thermal mass on dynamic heat-transfer characteristics of insu-
Received 31 January 2011 lated building walls with same nominal resistance (Rn-value) are investigated numerically under steady
Received in revised form 31 July 2011 periodic conditions using climatic data of Riyadh. Concepts of ‘‘thermal-mass energy-savings potential’’
Accepted 7 August 2011
(D) and ‘‘critical thermal-mass thickness’’ (Lmas,cr) are developed and utilized in order to determine ther-
Available online 6 September 2011
mal mass thickness (Lmas) required for a selected desirable percentage of energy savings. Results show
that daily transmission loads are not affected by Lmas for representative days of months in summer
Keywords:
and winter. However, for moderate months, daily cooling and heating transmission loads decrease with
Thermal mass
Heat transfer characteristics
increasing Lmas and either diminish to zero or be reduced asymptotically to constant values. For all
Insulated building walls months, peak transmission loads and decrement factor decrease, while time lag increases, with increas-
Steady periodic conditions ing Lmas. For a given Lmas, a wall with outside insulation gives better overall performance than a wall with
Energy savings potential inside insulation. While Rn-value is constant, wall dynamic resistance (Rd-value) changes and represents
actual variations in transmission loads. For D in the range 70–99%, Lmas,cr ranges between 6 and 30 cm by
using heavyweight concrete. It is found that maximum savings in yearly cooling and heating transmission
loads are about 17% and 35%, respectively, as a result of optimizing Lmas for same Rn-value. It is recom-
mended that building walls should contain Lmas,cr that corresponds to high D (95%) and with insulation
placed on outside for applications with continuously operating year-round AC.
Ó 2011 Elsevier Ltd. All rights reserved.

1. Introduction and damp down large fluctuations in temperature. As such, the


building envelope should provide the necessary thermal comfort
The demand for electricity is increasing as a result of increasing for the occupants as well as reduce energy consumption require-
population, expansion and development plans, and maintaining a ments for cooling and heating. This is usually done through increas-
good indoor thermal comfort conditions. Besides, the increasing ing thermal resistance (R-value) of this envelope and, hence,
cost of energy and adverse impact on the environment by energy reducing transmission loads. Therefore, addition of thermal insula-
production plants, all contribute to the need to find means to sub- tion is important, particularly in regions with extreme climates. Of
stantially reduce energy consumption. Buildings, through cooling importance too is to provide means to increase time lag and de-
and heating requirements, are major contributors to energy con- crease decrement factor through increasing thermal energy storage
sumption worldwide. It is estimated that about two-thirds of the capability. The latter is usually regulated through thermal mass in
electric energy generated in the Kingdom of Saudi Arabia is used the building envelope.
in buildings and two-thirds of that is used by air-conditioning Using heavy thermal masses in building walls is well known in
(AC) equipment [1]. A major part of the energy consumed by AC moderate climates (e.g. Mediterranean climate) as means of regu-
is due to heat transmission through the outer walls. Therefore, lating indoor temperature through nighttime natural ventilation.
reducing this load becomes one of the most effective energy con- However, such an advantage cannot be utilized in dusty climates
servation measures in buildings. The use of special building mate- in which reliance is made on the AC equipment (for cooling and
rials, thermal insulation, as well as employing good design heating) for almost all days of the year. While thermal mass con-
practices should serve this objective. trols the amount and rate of heat storage in building components
Insulated building walls are integrated parts of a building enve- and reduces temperature fluctuations and increases time lag, it
lope. They protect the inner space from extreme weather conditions does not often preclude the need for using thermal insulation.
Accordingly, two important issues must be dealt with; firstly,
⇑ Corresponding author. Tel.: +966 1 4676682; fax: +966 1 4676652. means of increasing the R-value usually by adding thermal insula-
E-mail address: sanea@ksu.edu.sa (S.A. Al-Sanea). tion, and secondly, means of increasing thermal energy storage

0306-2619/$ - see front matter Ó 2011 Elsevier Ltd. All rights reserved.
doi:10.1016/j.apenergy.2011.08.009
S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442 431

Nomenclature

c specific heat capacity (J/kg K) Tf,i indoor air temperature (°C)


df decrement factor Tf,o outdoor air temperature (°C)
hc,i convection coefficient at inside surface (W/m2 K) t time (s or h)
hc,o convective coefficient at outside surface (W/m2 K) tlag time lag (h)
hi combined convection and radiation coefficient at inside x coordinate distance normal to wall surface (m)
surface (W/m2 K)
Is solar radiation flux (W/m2) Greek letters
k thermal conductivity (W/m K) a thermal diffusivity (m2/s)
L layer thickness (m) D thermal-mass transmission-load-savings potential (%)
Lins insulation thickness (m) Dt time step (s)
Lmas thermal mass (masonry) thickness (m) Dx internodal distance (m)
Lmas,cr critical thermal mass thickness (m) k surface absorptivity of solar radiation
N number of layers q density (kg/m3)
n number of nodes
Qi total transmission load (kW h/m2 day) or (kW h/m2 yr) Subscripts
qc,o outside convection heat transfer rate (W/m2) c cooling or convection
qi instantaneous transmission load (W/m2) f fluid (ambient)
qpeak peak transmission load (W/m2) h heating
qr,o long wave radiation exchange (W/m2) i inside surface or nodal point
qst rate of energy stored j layer number
Rd, Rn dynamic and nominal (static) thermal resistances N outside layer
(m2 K/W) o outside
T temperature 1 inside layer or nodal point 1

capability typically by increasing thermal mass. Insulation materi- The main objective of the present study is to investigate effects
als, while they increase R-value, are not commonly been looked of thermal mass on transmission loads, energy storage rate, dy-
upon as elements that can increase time lag and decrease decre- namic thermal resistance, time lag, and decrement factor in build-
ment factor; these are usually associated with thermal mass. On ing walls for same Rn-value. Besides, these thermal characteristics
the other hand, thermal masses, while they increase energy storage are investigated for cases of outside and inside insulation under
capability, are not commonly been looked upon as materials that steady periodic conditions (i.e. continuous operation of AC system)
can effect substantial reduction in daily transmission load; the lat- using climatic data of Riyadh. Concepts of ‘‘thermal-mass energy-
ter is commonly associated with thermal insulation. These com- savings potential’’ and ‘‘critical thermal mass’’ are introduced and
mon beliefs are based upon facts that increasing amount of mass developed for the first time in order to determine the thermal mass
would not much increase the R-value and increasing amount of required for a selected desirable percentage of energy savings.
insulation would not much increase energy storage capability. This
view is simply based upon thermal properties and behavior of
building and insulation materials under static (steady state) condi- 2. Previous studies
tions. Studies under dynamic conditions have shown that these is-
sues are rather complicated and interactive; both insulation and Early studies on optimum locations of insulation and concrete
thermal mass have wider effects on thermal characteristics than layers in building walls and roofs, with the objective to obtain
commonly believed. There are indeed common effects between conditions for best load leveling, are those of Sodha and co-
insulation and thermal mass as well as much interaction between investigators in the late 1970s [2]. In their Fourier series analysis,
them with regard to their amounts and relative locations within the authors used the sol–air temperature for a typical hot sum-
the building structure as can be appreciated next in the literature mer’s day in Delhi and ignored long wave radiation effect. The heat
review. flux to the inside space was evaluated for two configurations: (i)
Effects of climatic conditions and operating conditions of AC concrete/insulation/air–gap/concrete and (ii) concrete/air–gap/
equipment add to the complexity of the problem. Building ele- insulation/concrete. They showed that, for a given total thickness
ments are, in general, subjected to either steady periodic condi- of concrete, best load leveling was achieved when the thickness
tions or initial transient conditions both of which are dynamic in of the outer concrete layer was as small as possible. Interchanging
nature. Steady periodic conditions are often reached after a suffi- position of insulation and air gap did not significantly affect opti-
ciently long time from start of AC operation and when initial tran- mum condition for best load leveling. The air gap had no significant
sient effects subside. Practically, steady periodic conditions take effect on the time lag but reduced the heat flux markedly. Using
place when daily climatic conditions prevail in a periodic manner, the same analysis, Seth et al. [3] investigated optimum distribution
or approximately so, and when AC system operates continuously. of insulation and concrete in an insulation/air–gap/concrete/air–
Short intermittent periods of AC shutdown, as controlled by ther- gap/insulation (IACAI) slab and in a concrete/air–gap/insulation/
mostat settings, should not upset reaching steady periodic condi- air–gap/concrete (CAIAC) slab. It was shown that, for a typical
tions. Initial transient conditions, on the other hand, often prevail hot summer’s day in Kuwait and for given total thicknesses of insu-
before reaching steady periodic behavior and take place when AC lation and concrete, the best load leveling was obtained (i) in IACAI,
system is shutdown for prolonged periods of time. Thermal charac- when the insulation thicknesses on the outside and inside were
teristics and roles played by insulation and thermal mass are so identical and (ii) in CAIAC when the thickness of the outside con-
much dependent on climatic conditions and operating conditions crete layer was least. Of the two structures, IACAI was better from
of AC equipment. a load leveling point of view.
432 S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442

Zaki and Hassan [4] determined thermal performance of a two- under steady periodic conditions using climatic data of Riyadh.
layered wall with periodic change of outside air temperature and Results showed that insulation location had a minimal effect on
solar radiation taking into consideration effects of building materi- daily total transmission load. However, outside insulation gave
als, orientation, and relative position of insulating layer. Average smaller amplitude of load fluctuation and, hence, peak load in both
heat flux was shown not to be affected by the relative position of summer and winter for all wall orientations. Under initial transient
layers. Effect of insulation and energy storing layers upon cooling effects, on the other hand, Al-Sanea and Zedan [17] showed that
load was investigated by Al-Turki and Zaki [5]. Analysis showed insulation layer location had a significant effect on instantaneous
that dispersion of insulation material within building material and daily total loads. It was recommended that for spaces where
was less effective than using a continuous equivalent insulation AC system is switched on and off intermittently, the insulation
layer placed on the outdoor facade. A whole building energy anal- should be placed on the inside. In [16,17], attention was focused
ysis, based on thermal response factor method, was performed by on effect of insulation/mass location for same amount of thermal
Eben Saleh [6,7] to investigate effect of insulation material, thick- mass and insulation.
ness, and arrangement on the thermal performance of buildings The finite difference method was used by Asan [18] and by Ozel
in a hot–dry climate. Results showed that better performance and Pihtili [19] to determine optimum distribution of multi insula-
was achieved by locating the insulation on the outer side of build- tion layers in walls for maximum time lag and minimum decre-
ing envelope. ment factor. Al-Sanea and Zedan [20] carried out thermal
Balaras [8] reviewed design tools for calculating cooling loads analysis of walls consisting of one, two and three layers of insula-
and indoor air temperatures in buildings accounting for thermal tion in which locations of insulation layers were varied with the
mass effects. The review demonstrated the effectiveness of thermal objective of achieving best overall dynamic performance under
mass in providing more comfortable indoor conditions and energy optimum thickness of insulation. Ogoli [21] measured tempera-
conservation particularly for locations with large diurnal tempera- tures in buildings with low and high thermal mass and showed
ture swings. In general, a high mass building reduces interior air that materials with high mass had long time lag and moderating
temperature variation, increases time lag, and decreases peak load effects on temperature swings and thus were effective in lowering
compared to a low mass building. Keeping overall thickness and indoor maximum temperatures below high outdoor maxima.
U-value of a three-layered building envelope constant, Bojic and Cheng et al. [22] presented results of experiments for effects of
Loveday [9] investigated influence of layer distribution of insula- envelope color and thermal mass and showed that use of lighter
tion/masonry on thermal behavior. It was shown that for intermit- surface color and high mass could dramatically reduce maximum
tent heating, the insulation/masonry/insulation structure was indoor temperature. However, the benefit of applying thermal
better. However, for intermittent cooling, it was preferable for mass depended on AC operation mode and occupancy pattern.
the slab to be of the masonry/insulation/masonry structure. If cool- Tsilingiris [23] used the implicit finite-difference method to
ing was continuous, then the slab structure did not matter. Bojic evaluate daily quasi steady-state energy losses from walls and
et al. [10] investigated influence of insulation position in walls showed that when heating was intermittent the insulation per-
on the cooling load in residential flats in high-rise buildings in formed better when installed at the interior wall side. Tsilingiris
Hong Kong. They found that the peak cooling load was decreased [24] investigated effect of space distribution of heat capacity and
by about 7% when a 5 cm polystyrene insulation was used facing thermal resistance on transient behavior of a wall exposed to har-
either the inside or outside depending on the flat orientation. How- monically time-varying conditions. Results showed that using
ever, no much reduction in load was observed when the thickness large heat capacity walls with insulation at ambient side led to a
of insulation was increased above 5 cm and that of concrete above substantial increase of thermal time constant and suppression of
10 cm. room temperature swings. In another study, Tsilingiris [25] fixed
Kossecka and Kosny [11] and Kossecka [12] presented concept wall R-value and investigated effects of spatial distribution of heat
of ‘‘thermally equivalent wall’’ which is a plane 1-D multilayer capacity. Analysis was carried out using climatic data of Athens for
structure of dynamic characteristics similar to those for complex typical days in January and July, while neglecting radiation. It was
structure in which 3-D heat flow occurs. It was shown that the re- concluded that spatial distribution of heat capacity strongly influ-
sponse factor, which represented heat flux at one surface due to enced transient wall heat flux and asymptotic approach to quasi
temperature excitation at the opposite surface, decayed relatively steady-state periodic behavior but had no effect on time-average
quickly when the thermal mass was placed on the outside and/or quasi steady-state heat flux.
the inside of wall structures. Kossecka and Kosny [13,14] analyzed Gregory et al. [26] studied impact of thermal mass on perfor-
effect of mass and insulation location on heating and cooling loads mance of Australian residential constructions by using the com-
in a continuously used residential building. They concluded that mercial AccuRate energy rating tool which is based on the
material configuration of exterior wall could significantly affect an- frequency response method. They found that thermal mass had a
nual thermal performance depending on climate. They found that dramatic impact on thermal behavior of modules studied, particu-
walls with massive internal layers had better annual thermal per- larly in those where mass was within a protective envelope of
formance than those with inside insulation. However, for intermit- insulation. Zhou et al. [27] developed a simple heat balance model
tent heating and cooling, inside insulation could result in better to estimate impact of external and internal thermal mass on indoor
performance. air temperature of naturally ventilated buildings. Different walls
Al-Sanea [15] developed and applied a computer model, based were compared and found that use of heavy wall with external
on the finite-volume implicit procedure, to evaluate dynamic ther- insulation had the lowest amplitude of indoor air temperature.
mal characteristics of building walls. Concept of dynamic thermal Effects of thermal mass and thermal insulation must be consid-
resistance (Rd-value) was developed in order to account for influ- ered simultaneously since, under dynamic conditions, their effects
ences of wall orientation, long wave radiation exchange, thermal are interactive. Type, thickness, and location of thermal mass and
energy storage, as well as nominal (static) thermal resistance insulation layers are crucial parameters that affect the thermal
parameters. It will be shown later that this Rd-value is very much behavior of the building envelope. Research in the last 10 years
indicative of effects of varying amount and location of thermal has concentrated more on optimization of insulation layer thick-
mass, the main subject of the present paper. The same computer ness than on thermal mass. For example, Al-Sanea and Zedan
model was utilized by Al-Sanea and Zedan [16] to study effects [28] determined optimum thickness of insulation (Lopt) in walls
of insulation location on thermal performance of building walls under steady periodic conditions using the climatic data of Riyadh.
S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442 433

It was found that Lopt increases with cost of electricity, building T j ðx; 0Þ ¼ T 0 ð2Þ
lifetime and inflation rate; and decreases with increasing cost of
where T0 is equal to mean outdoor air temperature (Tf,o,mean). It is
insulation material, coefficient of performance of AC equipment
noted that the steady periodic solution is independent of initial
and discount rate. Wall orientation was found to have a significant
temperature conditions, and that Tf,o,mean is a convenient value to
effect on thermal characteristics but a relatively smaller effect on
start calculations. The boundary conditions are:
Lopt. Recently, Daouas [29] calculated Lopt in walls under the cli- 
matic conditions of Tunisia, while Ozel [30] calculated Lopt under @T 
k1 ¼ hi ðT f ;i  T x¼0 Þ ð3Þ
the climatic conditions of Elazig, Turkey. In both studies [29,30], @x x¼0
the authors obtained effects of wall orientation on transmission
loads and Lopt similar to those obtained earlier by Al-Sanea and at the inside surface, where k1 is the thermal conductivity of the
Zedan [28]. wall inner layer and hi is the combined convection and radiation
In a recent study, Taleb and Sharples [31] assessed energy con- heat-transfer coefficient, and

sumption in an apartment complex under the climatic conditions @T 
kN ¼ hc;o ðT x¼L  T f ;o Þ  kIs  qr;o ð4Þ
of Jeddah, Saudi Arabia. They used DesignBuilder; a building en- @x x¼L
ergy simulation software package based on EnergyPlus. It was esti-
mated that by improving thermal insulation, using more efficient at the outside surface, where kN is the conductivity of the wall outer
glazing, and fitting external shading devices, energy consumption layer, hc,o is the outside convection coefficient, and k is the solar
reduction of over 30% could be achieved. The present authors absorptivity taken as 0.4 for light-colored surfaces.
would like to emphasize here that additional energy savings are The heat transfer coefficients (hi and hc,o) were determined from
possible by using nontraditional energy conservation measures correlations, Kusuda [32]. The outdoor air temperatures (Tf,o) were
such as the newly developed design practices concerning the opti- obtained from hourly measurements in Riyadh averaged over a
mum use of thermal insulation [20] and the use of optimum ther- number of years. The solar radiation (Is) was calculated from the
mal mass; the concept of the latter is developed and quantified in ASHRAE clear-sky model [33] with results adjusted to account for
the current paper. local dust and cloud conditions, Al-Sanea et al. [34]. The nonlinear
In summary, it can be concluded that there is a growing interest long wave radiation exchange with the sky and ground (qr,o) was
in determining optimum locations of insulation and thermal mass accounted for rigorously including refined means for estimating
layers in building walls. However, there is still a need for detailed the sky temperature. Calculations of these parameters are given
and systematic studies to investigate effects of thermal mass on by Al-Sanea et al. [35]. The indoor temperature (Tf,i) was fixed for
energy storage, transmission loads, time lag, and decrement factor. the representative day of each month of the year but varied be-
Quantifying effects of amount and location of thermal mass on en- tween the months according to appropriate monthly thermostat
ergy savings potential is obviously lacking. The present study aims settings as summarized in Table 1. These indoor air temperatures,
at addressing these issues as well as utilizing wall dynamic R-value and those in their proximity, were selected to give low operational
as an indicative of transmission loads under dynamic conditions. cost while maintaining thermal comfort in dry climates, Al-Sanea
and Zedan [36].
3. Mathematical formulation and calculation procedure The present nonlinear problem was solved by a control volume
finite-difference method using the implicit formulation. A wall of N
A wall of N layers is shown in Fig. 1. The outside is exposed to layers was discretized into a number of nodes, see Fig. 1, and the
convection heat transfer (qc,o), long wave radiation exchange with finite-volume equations were derived by applying the overall en-
surroundings (qr,o), and solar radiation (Is). The inside is exposed to ergy balance. These equations can be represented by the general
combined convection and radiation (qi) which gives the cooling or form:
heating transmission load in terms of the indoor air temperature ai T i ¼ bi T iþ1 þ ci T i1 þ di ð5Þ
(Tf,i). Assuming no heat generation, constant properties, and 1-D
heat transfer, the governing equation becomes: and were solved by the TDMA for i = 1, 2, . . . , n. The temperature Ti
at node i is linked to neighboring temperatures, Ti+1 and Ti1, and
@2T j 1 @T j the previous time-step temperature through coefficients ai through
¼ ð1Þ
@x2 aj @t di. Expressions for these coefficients are given in [35].
Results were checked to be fully converged, and grid and time
where aj is the thermal diffusivity (=k/qc) of layer j. The initial tem-
step independent. Besides, solution was carried through a number
perature distribution is taken uniform across the whole wall as:
of periods (each lasting 24 h) until a steady periodic state was fully
obtained. The numerical model has been validated in previous

Fig. 1. Composite wall of N-layers showing boundary conditions and grid arrangement.
434 S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442

Table 1
Monthly settings of indoor air temperature [36].

Month January February March April May June July August September October November December
Tf,i (°C) 21 21 21 24 26 26 26 26 26 24 21 21

studies and was shown to produce very accurate results under dy- temperatures at previous and current time steps. It is noted that,
namic conditions by comparison with exact analytic solution for a for a given thermal mass, qst reflects average wall temperature fluc-
one-layered wall [15] and semi-analytic solutions for a three- tuation with time.
layered wall [16,17].
4.7. Nominal thermal resistance (Rn-value)
4. Definition and calculation of parameters
This is equal to 2.86 m2 K/W and is calculated as the sum of the
All the following parameters are calculated after solution has following resistances:
reached a steady periodic state. N  
X L 1 1
Rn ¼ þ þ ð9Þ
4.1. Time lag (tlag) j¼1
k j hi hc;o

Is time span between attaining peak temperatures at outside


and inside surfaces of wall. This is calculated for the representative 4.8. Dynamic thermal resistance (Rd-value)
day of each month of the year. The yearly average time lag is then
determined as the arithmetic average of these monthly values. The daily average dynamic thermal resistance is calculated for
the representative day of each month of the year as follows:
4.2. Decrement factor (df) R 24h
jðDTÞjdt
Rd;day ¼ 0R 24h ð10Þ
Is amplitude of temperature fluctuation on inner surface of wall 0
jqi jdt
divided by that on outer surface. This is calculated for the repre-
where DT = Tf,o  Tf,i. The yearly average dynamic R-value is then
sentative day of each month of the year. The yearly average decre-
determined as the weighted average of these monthly values with
ment factor is then determined as the arithmetic average of these
respect to transmission loads. As will be seen later, Rd is not con-
monthly values.
stant for a wall with a given Rn and its variation represents the dy-
namic nature of the problem in an informative way.
4.3. Instantaneous cooling and heating transmission loads (qi)

These are calculated from wall inner surface temperature (Tx=0) 5. Presentation and discussion of results
obtained from the solution as:
Firstly, effects of amount and location of thermal mass on trans-
qi ¼ hi ðT x¼0  T f ;i Þ ð6Þ mission loads, energy storage rate, dynamic resistance, time lag,
and decrement factor are dealt with. Secondly, concepts of critical
4.4. Daily total cooling and heating transmission loads (Qi) thermal mass and thermal-mass energy-savings potential are
developed and utilized. Climatic data of Riyadh are used and a
These are calculated from qi by integration over a 24-h period west-facing wall is considered. It is noted that the thermal mass
as: is basically the mass times specific heat. For a 1-D problem, this
Z boils down to density  specific heat  thickness of layer. In the
24h
present study, heavyweight concrete is the masonry material used
Qi ¼ qi dt ð7Þ
0 which means that the density and specific heat are fixed and, there-
fore, the thermal mass can be characterized by layer thickness.
It is noted that values of qi are summed up separately for cooling
and for heating.
5.1. Wall configurations (W1 and W2) and conditions of constant Rn-
value
4.5. Yearly total cooling and heating transmission loads

Two walls are considered: wall W1 with the insulation placed


These are calculated from the corresponding daily total values.
on the outside and wall W2 with the insulation placed on the in-
The daily value of the representative day of each month is multi-
side. The thermal mass (heavyweight concrete) and thermal insu-
plied by the number of days in that month and then summed up
lation (molded polystyrene) are sandwiched by thin plastering
over the whole year. Of course, cooling and heating transmission
layers as shown in Fig. 2a and b. Table 2 summarizes properties
loads (Qi,c and Qi,h, respectively) are summed up separately.
of materials used, [33,37]. The thermal mass thickness is varied
in the range 0 6 Lmas 6 50 cm while keeping the wall Rn-value con-
4.6. Wall energy storage rate (qst)
stant. This is done by corresponding adjustments made to the insu-
lation layer thickness (Lins), see Table 3. Since kmas  kins, an
This is calculated from:
increase in Lmas by 100 mm, for example, would correspond to a
X
N X
n
T new
i;j  T old
i;j
mere reduction in Lins by about 2 mm.
qst ¼ qi;j ci;j Dxi;j ð8Þ
j¼1 i¼1
Dt
5.2. Instantaneous thermal characteristics variations with time of day
where i refers to node in layer j, n is total number of nodes in this
layer, N is total number of layers in wall, Dx is internodal distance, Instantaneous transmission loads (qi) are presented versus time
Dt is time interval, and superscripts old and new refer to for wall W1 in Fig. 3a for representative days of August, January,
S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442 435

Inside Outside (a) 9 Aug., 20 cm


Jan., 20 cm
Nov., 20 cm
Cement plaster (1.5 cm) Cement plaster (1.5 cm) 7
Aug., 5 cm
Jan., 5 cm
Nov., 5 cm
5

Thermal mass Thermal Insulation


3

qi (W/m2)
1

-1

(a) Wall W1
-3

Inside Outside
-5
0 6 12 18 24

Cement plaster (1.5 cm) Cement plaster (1.5 cm) Time (h)

(b) 9 Aug., 20 cm
Jan., 20 cm
Nov., 20 cm
Thermal Insulation Thermal mass 7 Aug., 5 cm
Jan., 5 cm
Nov., 5 cm
5

3
qi (W/m2)

(b) Wall W2
1
Fig. 2. Schematic of wall configurations with same and constant Rn-value; (a) wall
W1 with outside insulation and (b) wall W2 with inside insulation.
-1

Table 2
Material properties [33,37]. -3

Material k (W/m K) q (kg/m3) c (J/kg K)


Cement plaster 0.72 1860 840 -5
Molded polystyrene 0.034 23 1280 0 6 12 18 24
Heavyweight concrete 1.73 2243 840 Time (h)

Fig. 3. Transmission load variation with time of day in August, January, and
November with Lmas = 20 cm and 5 cm; (a) for wall W1 (outside insulation) and (b)
Table 3 for wall W2 (inside insulation).
Adjustments made to insulation layer thick-
ness (Lins) by varying thermal mass thickness
(Lmas) in order to keep Rn-value constant. fluctuations are damped down appreciably by using the heavy-
Lmas (m) Lins (m)
weight structure (Lmas = 20 cm). Peak transmission load is, hence,
reduced and its time of occurrence is delayed giving longer time
0.000 0.0900
0.050 0.0890
lag. These are clear advantages of using increased thermal mass.
0.100 0.0880 Corresponding results for wall W2, presented in Fig. 3b, show sim-
0.150 0.0871 ilar trends but with larger fluctuations. Therefore, placing insula-
0.200 0.0861 tion on outside provides more damping of load fluctuation and
0.250 0.0851
smaller peak load.
0.300 0.0841
0.400 0.0821 Integrated values of qi over a 24-h period give the daily total
0.500 0.0802 transmission loads (Qi), see Eq. (7). Table 4 summarizes and com-
pares these daily total cooling and heating loads. Any of these loads
is also represented by the area enclosed under its corresponding
and November. Results are also compared for Lmas = 20 cm and curve in Fig. 3a and b and the zero datum line shown. It is noted
5 cm, corresponding to heavyweight and lightweight structures. that the daily cooling loads are practically the same in August for
It is seen that qi has a periodic variation and oscillates with positive both thermal masses and for both walls with a value of about
values in August (representing heat transmission to space), nega- 0.085 kW h/m2 day. The same can be said about the daily heating
tive values in January (representing heat transmission out of loads in January with a value of about 0.06 kW h/m2 day. However,
space), and both positive and negative values in November. Load this is not true for the daily loads in November, where both cooling
436 S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442

Table 4
Daily total cooling and heating transmission loads for walls W1 and W2 using Lmas = 5 cm and 20 cm for representative days of August, January, and November.

Qi Wall W1 Wall W2
(kW h/m2 day)
Lmas = 5 cm Lmas = 20 cm Lmas = 5 cm Lmas = 20 cm
August January November August January November August January November August January November
Cooling  100 8.511 0.000 1.064 8.509 0.000 0.126 8.522 0.069 1.478 8.539 0.000 0.351
Heating  100 0.000 5.999 1.722 0.000 6.001 0.786 0.000 6.061 2.126 0.000 5.983 0.986

45
Aug. (a) 40

Jan.
40 Nov.
20

35
Tf,o 0
Tf,o
30
Tf,i for Aug.

qst (W/m2)
Tf,i for Aug.
T (ºC)

-20
25
Tf,i for Jan. & Nov.
Tf,i for Jan. & Nov. Aug., 20 cm
20 -40 Jan., 20 cm
Tf,o
Tf,o Nov., 20 cm
15 Aug., 5 cm
Tf,o -60
Tf,o Jan., 5 cm
10 Nov., 5 cm

-80
5 0 6 12 18 24
0 6 12 18 24
Time (h)
Time (h)

Fig. 4. Outdoor air temperature (Tf,o) variation with time of day in August, January,
and November showing fixed thermostat settings of indoor air temperature (Tf,i).
(b) 150 Aug., 20 cm
120 Jan., 20 cm
and heating loads are present and are quite different between the Nov., 20 cm
two thermal masses as well as between the two walls, as can 90 Aug., 5 cm
clearly be seen in Table 4. These loads are substantially reduced
Jan., 5 cm
by increasing mass for the same Rn-value. It may also be noted that 60
these loads are smaller for wall W1 compared to wall W2. Nov., 5 cm
qst (W/m2)

The variations of qi with time presented earlier in Fig. 3a and b 30


are very much the outcome of effects of outdoor and indoor air
temperatures (Tf,o and Tf,i) presented in Fig. 4. It is seen that Tf,o is 0
always above Tf,i in August; the opposite is true in January. How-
ever, in November Tf,o variation crosses Tf,i; i.e. it is higher during -30
part of day (10:00 < t < 20:00) and is lower during the rest of the
day. This explains the occurrence of both cooling and heating -60
transmission loads in November and, as will be seen later, is the
reason behind potential energy savings due to thermal mass in -90
moderate months or, indeed, moderate climates.
Further insight into results is made by examining variations of -120
thermal energy storage rate with time. These are shown for wall 0 6 12 18 24
W1 in Fig. 5a for August, January, and November for Lmas = 20 cm Time (h)
and 5 cm. Positive values signify energy storage, while negative
Fig. 5. Energy storage rate variation with time of day in August, January, and
values signify energy loss. As seen, the wall gains energy during November with Lmas = 20 cm and 5 cm; (a) for wall W1 and (b) for wall W2.
daytime (7:00 < t < 16:00) and dissipates it predominantly during
the evening and night time. The dominant source of energy gain
is solar radiation absorbed by the wall outer surface, a large per- mass. It seems surprising at first that increasing thermal mass does
centage of which is stored in the wall and is ultimately dissipated not really increase heat storage rate; however, a careful look at Eq.
to outside through the same surface. Daily total storage rate is the (8) shows that the average wall temperature fluctuation drops
area under the curve using positive values of qst, while daily total with increasing thermal mass.
dissipation rate is the area under the curve using negative values The corresponding results for wall W2, presented in Fig. 5b,
of qst. These two quantities must be equal under steady periodic show that qst variations with time have rather similar trends to
conditions, i.e. net heat storage over 24 h must be zero. It is inter- those of wall W1 but with larger fluctuations. Moreover, the effect
esting to note that energy storage and dissipation rates have sim- of thermal mass on qst is much more noticeable for wall W2. There-
ilar time variations in August, January, and November, and that fore, placing the insulation layer on the outside has very much re-
these rates are not much affected by varying amount of thermal duced energy storage rates and damped temperature fluctuations.
S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442 437

2 10
W1, cool. W2, cool.
W1, cool. W2, cool.
W1, heat. W2, heat.
1 9

Qi,c (kWh/m2.day) × 100


Qi (kWh/m2.day) × 100

0 8

-1 7

-2 6

-3 5
0 0.1 0.2 0.3 0.4 0.5 0 0.1 0.2 0.3 0.4 0.5
Lmas (m) Lmas (m)

Fig. 6. Daily cooling and heating transmission loads variation with masonry Fig. 7. Daily cooling transmission load variation with masonry thickness in August
thickness in November for walls W1 and W2. for walls W1 and W2.

5.3. Effect of thermal mass on daily thermal characteristics


12
Fig. 6 presents variations of the daily total transmission loads
(Qi) with masonry thickness (Lmas) for the representative day of
10
November. Positive values signify cooling loads (Qi,c), while nega-
tive values signify heating loads (Qi,h). It is seen that Qi,c decreases
with increasing Lmas and diminishes to zero at Lmas  0.25 m for 8
Rd (m2.K/W)

W1 and Lmas  0.35 m for W2. Similarly, the magnitude of Qi,h


decreases with increasing Lmas but reaches asymptotically a con-
stant value at Lmas  0.3 m. For Lmas < 0.3 m, and for both cooling 6
and heating, wall W1 gives smaller Qi than wall W2 for any given W1, Aug. W2, Aug.
Lmas. Corresponding results for August, presented in Fig. 7, show W1, Jan. W2, Jan.
4
that values of Qi,c stay practically constant with increasing Lmas W1, Nov. W2, Nov.
and are practically equal for both walls. These behaviors are attrib-
uted largely to the swing of the outdoor temperature (Tf,o) relative 2
the indoor temperature (Tf,i) as shown earlier in Fig. 4. Similar
trend of variation is obtained for January to that obtained for
August but for Qi,h. 0
The variations of the daily average Rd-value with Lmas for the 0 0.1 0.2 0.3 0.4 0.5
representative days of August, January, and November are pre- Lmas (m)
sented in Fig. 8. It is seen that Rd-values in August stay practically
Fig. 8. Daily average dynamic R-value variation with masonry thickness in August,
constant with increasing Lmas. This reflects the daily transmission January, and November for walls W1 and W2; Rn-value = 2.86 m2 K/W.
load behavior already shown in Fig. 7. The same is true for January.
For these months, Rd-values can hardly be distinguished from the
Rn-value which is 2.86 m2 K/W. In November, however, it is seen the heavier mass (Lmas = 20 cm) shown in Fig. 9b. Here, Rd-values
that while the Rn-value is constant, the Rd-value increases with increase substantially above the Rn-value in March, April, October,
Lmas. This reflects decreasing daily cooling and heating transmis- and November. It is also noted that wall W1 has higher Rd-values
sion loads with increasing Lmas as shown in Fig. 6. Besides, for a than wall W2 in March and November. These results emphasize
given Lmas, Rd-value for wall W1 is greater than that for wall W2 the importance of both amount and location of thermal mass and
up to Lmas  0.4 m, beyond which Rd-values of the two walls are indicate that the moderate months are responsible for achieving
approximately the same. This also reflects Qi versus Lmas behavior energy savings due to sole effect of mass for a given wall Rn-value.
presented in Fig. 6. It is concluded, therefore, that the Rd-value The relationship between amount of thermal mass and percentage
gives a true and indicative representation of the actual daily trans- energy savings is dealt with later.
mission loads while the Rn-value falls short of such a complete rep-
resentation, as expected.
Fig. 9a compares Rd-values for the representative days in all 5.4. Concept and significance of dynamic R-value
months. This is done for both walls with Lmas = 5 cm while showing
Rn-value as a reference. For this light structure, it is seen that The present authors have developed, refined, and adopted the
Rd-values are generally smaller than the Rn-value and that they concept of the dynamic R-value for a while now. Its advantage over
are different for the two walls in the moderate months with wall the nominal R-value has been noticed. However, it has now been
W1 having the larger values. The picture changes significantly for realized through the present work that it has a much wider scope
438 S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442

(a) 3.5 thermal mass and reaches asymptotically a constant value at large
thermal mass, see Fig. 8. Due to these moderate months, the same
trend is obtained for the yearly average dynamic R-values as will
3
be seen later.
With reference to Table 4, and by considering for example wall
2.5 W1 with Lmas = 5 cm, it is clearly noted that the sum of the absolute
values of daily cooling and heating transmission loads for the rep-
R (m2.K/W)

2 resentative day of November is much less than either the cooling


load in the representative day of August or the heating load in
the representative day of January. This is attributed to two factors;
1.5
the first factor is related to reduction in difference between out-
door air and indoor air temperatures in November compared to
1 August and January, see Fig. 4. The second factor is related to the
W1, dyn. R
dynamic nature of the problem, i.e. thermal energy storage and
W1, nom. R
0.5 time lag effects in the wall and their interaction with varying
W2, dyn. R
amount of thermal mass. This second factor cannot be accounted
W2, nom. R
for by the nominal R-value during the moderate months where
0 both cooling and heating are present during the day, in which heat
1 2 3 4 5 6 7 8 9 10 11 12
transfer to the inner space reverses direction accordingly. The dy-
Month
namic R-value, on the other hand, has responded to this effect by
showing changes, see Fig. 9a, reflecting variations in both trans-
(b) 9
W1, dyn. R mission loads and the driving temperature differences between
8 W1, nom. R outdoor and indoor over the representative days in the months.
W2, dyn. R By referring to the same previous variables in Table 4 but at
7 W2, nom. R Lmas = 20 cm, results reveal much reduced cooling and heating
transmission loads in November; this may also be noted in Fig. 6.
6 Since the driving temperature differences between outdoor and in-
door are the same, the dynamic R-value must have increased
R (m2.K/W)

5 appreciably to represent such large reduction in transmission


loads. This is exactly what the results in Fig. 9b indicate. This
4 may be looked upon as an enhancement in dynamic R-value as a
result of increasing thermal mass for same nominal R-value.
3
5.5. Effect of thermal mass on yearly thermal characteristics
2

Variation of yearly total cooling transmission load (Qi,c) with


1
Lmas is presented in Fig. 10a. It is seen that Qi,c decreases sharply
with increasing Lmas reaching asymptotically a constant value for
0
1 2 3 4 5 6 7 8 9 10 11 12 either wall. The asymptotic values are represented by the two low-
Month er dotted horizontal lines. The two upper dotted horizontal lines
will be referred to later when considering the critical thermal mass
Fig. 9. Daily average dynamic and nominal R-values for walls W1 and W2 for thickness. Similar behavior is obtained for the yearly total heating
representative days in months; (a) with Lmas = 5 cm and (b) with Lmas = 20 cm.
transmission load (Qi,h) shown in Fig. 10b. It is noted that for a gi-
ven Lmas, wall W1 gives lower yearly cooling and heating loads. For
of use than had been anticipated. The following account highlights Lmas > 30 cm, the two walls give practically the same yearly loads.
its advantage and importance. At the other end, when Lmas = 0, Qi is the same since both walls
The R-value employed exclusively in the literature is the static would have identical configurations; see Fig. 2.
R-value. It is presently termed nominal R-value [Eq. (9)] in order By comparing values of Qi at the asymptotes with those at
to distinguish it from the dynamic R-value [Eq. (10)]. This nominal Lmas = 0 in Fig. 10a and b, the maximum possible savings in yearly
R-value, which represents transmission load under steady-state transmission loads affected by thermal mass alone are estimated at
conditions, is merely used here as a datum for comparison. Caution about 17% for cooling and 35% for heating. Such potential savings
must be exercised in using this R-value under dynamic conditions. in transmission loads are quite substantial and, as emphasized ear-
The present results have demonstrated that both dynamic and lier, are caused by reduction in loads with increasing Lmas while
nominal R-values are close for winter and summer months in keeping Rn-value constant. These results are consistent with the
which only heating or cooling is present during the whole day, traditional practice of constructing walls with large masses in re-
see Figs. 8 and 9, and therefore both R-values give adequate repre- gions with moderate climates. Nevertheless, this does not preclude
sentation of the transmission loads. In contrast, during the moder- the need for using sufficient amount of thermal insulation. The use
ate months in which both heating and cooling are present during of even heavily insulated but lightweight walls must, therefore, be
the day, only the dynamic R-values have responded and propor- carefully scrutinized under different climatic conditions.
tionately represented corresponding changes in transmission loads Fig. 11 displays the variations of the peak cooling (August) and
while the nominal R-value completely fails to do that. As a conse- peak heating (January) transmission loads with Lmas. It is seen that
quence, there is no physical reasoning to why, in the moderate qpeak decreases appreciably with increasing Lmas and resembles
months, the nominal R-value is greater than the dynamic R-values variations of the yearly total cooling and heating transmission loads
for lightweight walls and is smaller than the dynamic R-values for presented above. However, a main difference is that qpeak continues
heavyweight walls, cf. Fig. 9a and b. Indeed, in the moderate to decrease and does not seem to reach an asymptotic value with
months, the dynamic R-value increases all the way with increasing increasing Lmas over the range considered. For Lmas < 0.4 m, wall
S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442 439

(a) 15 10
W1, cool. W2, cool.
W1, cool. W2, cool.
8 W1, heat. W2, heat.
14.5

14
Qi,c (kWh/m2.yr)

qpeak (W/m2)
13.5 2

0
13

-2

12.5
-4

12 -6
0 0.1 0.2 0.3 0.4 0.5 0 0.1 0.2 0.3 0.4 0.5
Lmas (m) Lmas (m)

Fig. 11. Yearly peak cooling and heating transmission loads variation with masonry
(b) -4 thickness for walls W1 and W2.
0 0.1 0.2 0.3 0.4 0.5
-4.5

14 W1 W2
-5
Qi,c (kWh/m2.yr)

12
-5.5

10
-6
tlag (h)

-6.5
6

-7
4
W1, heat. W2, heat.
-7.5 2
Lmas (m)

Fig. 10. Yearly cooling and heating transmission loads variation with masonry 0
thickness for walls W1 and W2 showing asymptotes and corresponding critical 0 0.1 0.2 0.3 0.4 0.5
thermal mass thicknesses by using 5% criterion; (a) cooling load and (b) heating Lmas (m)
load.
Fig. 12. Yearly average time lag variation with masonry thickness for walls W1 and
W2.
W1 gives lower qpeak. At Lmas > 0.4 m, the two walls give practically
the same qpeak; this suggests that qpeak is not sensitive to insulation
layer location at large Lmas. gives larger Rd-value over that of wall W2. The increase in Rd-value
The yearly average time lag (tlag) variations with Lmas are pre- with Lmas is consistent with the decrease in Qi and qpeak with
sented in Fig. 12. It is seen that for Lmas > 10 cm, tlag increases lin- increasing Lmas presented earlier in Figs. 10a and b, and 11. As seen
early with Lmas. For a given Lmas, wall W1 gives a time lag that is from the latter figures, Qi,c, Qi,h, and qpeak practically cease to de-
about half an hour longer compared to wall W2. It is estimated that crease with increasing Lmas beyond 0.3 m; this is exactly reflected
tlag increases at a rate of about 1 h per 4 cm increase in Lmas. Fig. 13 by Rd-value becoming constant for Lmas > 0.3 m as seen in Fig. 14.
presents the variations of the yearly average decrement factor (df) Compared to the constant Rn-value, it is clear that the Rd-values
with Lmas. It is seen that df decreases with increasing Lmas. The ini- are in harmony with varying values of Qi and qpeak; as such, they
tial rate of decrease is steeper for wall W1 which is an advantage better represent the dynamic nature of the problem.
for the outside insulation. At Lmas = 0, df  0.04; this is reduced It is interesting to note that the nominal R-value is still in com-
by an order of magnitude for wall W1 when Lmas = 30 cm compared mon use in the literature and in building codes and standards un-
to a reduction by a factor of 5 for wall W2. der the name of ‘‘recommended R-value’’. In view of the present
The yearly average Rd-value variations with Lmas are presented results, the accuracy and legitimacy of using the nominal R-value
in Fig. 14 and compared with the Rn-value. These are weighted under dynamic conditions may be quantified under the present
average with respect to transmission loads. It is seen that Rd-values conditions with reference to Fig. 14. As seen, noticeable differences
of both walls increase with Lmas and reach asymptotically the same exist between the dynamic R-values and the constant nominal
value at Lmas > 0.3 m. For a given Lmas, and for Lmas < 0.3 m, wall W1 R-value depending on the amount of thermal mass present and
440 S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442

4 Table 5
W1 W2 Percentage criterion, energy savings potential, yearly cooling transmission load, and
critical thermal mass thickness for wall W1a.

% Criterion D (%) Transmission loadb (kW h/m2 yr) Lmas,cr (cm)

3 30 70 13.223 6.5
20 80 12.972 8.4
15 85 12.847 9.8
10 90 12.721 12.1
7 93 12.646 14.2
df ×100

5 95 12.596 15.9
2
3 97 12.545 18.2
2 98 12.520 20.0
1 99 12.495 23.7
a
Largest load = 14.98 kW h/m2 yr and asymptotic load = 12.47 kW h/m2 yr.
b
1 Load = % criterion  (largest load  asymptotic load) + asymptotic load.

(Lmas,cr) is obtained corresponding to a percentage energy-savings


0 potential (D). This is demonstrated with reference to Fig. 10a
0 0.1 0.2 0.3 0.4 0.5 where the two lower horizontal dotted lines represent the asymp-
Lmas (m) totic cooling loads for walls W1 and W2. An asymptotic load gives
the minimum yearly total transmission load obtained at ‘‘large’’
Fig. 13. Yearly average decrement factor variation with masonry thickness for walls thermal mass. Adding more mass will not further reduce this load,
W1 and W2.
and is pointless as far as savings in energy consumption are con-
cerned. This fact leads to the notion of optimum thickness of ther-
mal mass to use in building walls.
3.5
For the present demonstration, a ‘‘5% criterion’’ is chosen; this
constitutes a 95% of the maximum possible savings on yearly cool-
ing transmission load through using thermal mass alone for a given
wall Rn-value. Firstly, the difference between yearly cooling load at
Lmas = 0 and asymptotic load is calculated. Secondly, 5% of this dif-
3 ference is added to the asymptotic load. These new loads, for walls
R (m2.K/W)

W1 and W2, are represented by the two upper dotted horizontal


lines shown in Fig. 10a which cut the Qi,c versus Lmas curves at
Lmas,cr. Fig. 10a shows that Lmas,cr = 15.9 cm and 22.7 cm for walls
W1 and W2, respectively.
By repeating the above procedure for the yearly total heating
2.5
transmission loads, as shown in Fig. 10b, the Lmas,cr obtained are
W1, dyn. R W1, nom. R 15.6 cm and 22.5 cm for walls W1 and W2, respectively. By com-
paring these values with those for cooling, it becomes evident that
W2, dyn. R W2, nom. R
Lmas,cr for cooling and heating are practically the same for a given
D. This finding is quite important since, otherwise, one will have
2 to compromise between what would have been two different
0 0.1 0.2 0.3 0.4 0.5 Lmas,cr, one for cooling and one for heating.
Lmas (m) In order to construct a chart that can be used to obtain thermal
mass required to achieve desired percentage savings in yearly
Fig. 14. Yearly average dynamic and nominal R-values variation with masonry transmission loads, critical thermal mass variations with energy
thickness for walls W1 and W2.
savings potential are developed as shown in Table 5. The table
summarizes values of critical thermal mass thickness (Lmas,cr) and
its location in the wall. If, for the sake of argument, the recom- energy savings potential (D) for cooling calculated for wall W1.
mended R-value is taken as the nominal R-value shown in the fig- The first column specifies the % criterion used. The second column
ure, then in practice the wall would be under-designed for Lmas less contains energy savings potential which is simply 100%  % crite-
than about 0.1 m and over-designed for Lmas greater than about rion used. The third column contains the transmission load calcu-
0.1 m because of dynamic effects. Accordingly use of lightweight lated by using the % criterion. The fourth column contains Lmas,cr
walls, even when sufficiently insulated, must be scrutinized for obtained from corresponding value of transmission load just calcu-
proper thermal mass especially in moderate climates. lated by using Qi,c versus Lmas curve presented in Fig. 10a. Due to
space limitation, other such tables for heating and for wall W2
are not presented.
5.6. Critical thickness of thermal mass (Lmas,cr) and energy savings Fig. 15 presents Lmas,cr variations with D and compares results
potential (D) between walls W1 and W2 for cooling and heating. It is seen that
Lmas,cr increases with D; the increase is initially gradual and then
Energy savings potential is short for ‘‘thermal-mass transmis- becomes much steeper as a high energy savings potential is sought.
sion-load-savings potential’’ and represents percentage savings Accordingly, if a high D is selected, this would be on the expense of
on that part of energy caused by transmission load that can poten- having to use large Lmas,cr. The initial gradual increase of Lmas,cr with
tially be achieved by thermal mass. This excludes savings that are D is quite advantageous since much of the energy savings potential
normally affected by thermal insulation. Based on yearly transmis- can be achieved by slightly increasing Lmas. Results also show that
sion load (Qi) variations with Lmas, a critical thermal mass thickness values of Lmas,cr are practically the same for cooling and heating
S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442 441

35 3. Yearly cooling and heating transmission loads decrease with


W1, cool. W1, heat. increasing Lmas and reach asymptotically constant values.
W2, cool. W2, heat. 4. Peak cooling and heating transmission loads and decrement fac-
30
tor decrease with increasing Lmas, while the time lag increases
with increasing Lmas.
25 5. While the Rn-value is constant, wall Rd-value changes with
amount and location of Lmas and represents actual variations
in transmission loads.
Lmas,cr (cm)

20
6. Relations between critical thermal-mass thickness (Lmas,cr) and
thermal-mass energy-savings potential (D) are obtained by
15 using heavyweight concrete. It is found that:
(a) Lmas,cr increases with increasing D.
(b) For a given Lmas, cooling and heating energy-savings poten-
10
tials are the same.
(c) For D in the range 70–99%, Lmas,cr ranges between 6 and
5 30 cm.
(d) For a given D, Lmas,cr is smaller for a wall with outside insu-
lation compared to a wall with inside insulation. Con-
0
70 75 80 85 90 95 100 versely, for a given Lmas,cr, higher D is obtained for the
wall with outside insulation.
Energy savings potential, Δ (%)
7. Maximum savings in yearly transmission loads are about 17%
Fig. 15. Critical thermal mass thickness variation with cooling and heating energy- for cooling and 35% for heating as a result of optimizing thermal
savings potentials for walls W1 and W2. mass.
8. For a given thermal mass, a wall with outside insulation gives
energy-savings potentials as demonstrated by nearly perfect better overall thermal performance compared to a wall with
agreement between the solid and dashed lines. Trend of variations inside insulation.
of Lmas,cr with D is very similar for both walls; however, for a given
D, wall W1 gives about 5 cm less Lmas,cr. In other words, the energy It is recommended that building walls should contain as a min-
savings potential of a wall with outside insulation is superior to imum critical amount of thermal mass that correspond to energy
that with inside insulation having the same thermal mass. savings potential in the range 90% 6 D 6 97% and that the insula-
Further examination of results in Fig. 15 reveals that the range of tion layer should be placed on the outside for applications with
energy savings potential given by 70% 6 D 6 99% corresponds to a continuously operating AC. Future work may investigate effects
wide range of critical thermal mass given by 6.4 cm 6 Lmas,cr 6 of using different climatic conditions.
29.6 cm. The precise value of Lmas,cr would, of course, depend on
the selected value of D and thermal insulation location. It is noted Acknowledgments
that values of Lmas,cr corresponding to D < 70% are not presented
since it is believed that under such conditions the walls would be The authors would like to acknowledge the College of Engineer-
wasting high percentage of valuable energy that could have easily ing Research Center and Deanship of Scientific Research at King
been saved. Besides, walls with such correspondingly small Lmas,cr Saud University in Riyadh for support.
(e.g. Lmas,cr < 10 cm) would be highly under-designed with regard
to peak loads, time lag, and decrement factor (cf. Figs. 11–13). From
References
the practical application point of view, the use of Fig. 15 is simply to
select a desired percentage of energy savings potential, and then [1] Studies and Statistics Department, Electrical Affairs Agency: Electricity Growth
determine the corresponding required thermal mass thickness. and Development in the Kingdom of Saudi Arabia up to the year 1420 H (1999/
The present investigators suggest a minimum value of D of no less 2000 G), Ministry of Industry and Electricity, Kingdom of Saudi Arabia; 2002.
[2] Sodha MS, Kumar A, Srivastava A, Tiwari GN. Thermal load levelling in a
than 90% to be selected and recommend consideration of D in the multilayered wall/roof. Energy Res 1981;5:1–9.
range 90% 6 D 6 97%. [3] Seth SP, Bansal NK, Nayak JK, Seth AK. Optimum distribution of insulation and
concrete in a multilayered wall or roof. Appl Energy 1981;9:49–54.
[4] Zaki GM, Hassan K. Thermal performance of composite building components
6. Conclusions and recommendations with periodic solar insolation and ambient temperature. Solar Wind Technol
1986;3:103–9.
While keeping nominal resistance (Rn-value) constant, effects of [5] Al-Turki A, Zaki GM. Cooling load response for building walls comprising heat
storing and thermal insulating layers. Energy Convers Manage
amount and location of thermal mass in insulated building walls 1991;32:235–47.
on total and peak transmission loads, time lag, decrement factor, [6] Eben Saleh MA. Thermal insulation of buildings in a newly built environment
and dynamic resistance (Rd-value) were investigated under steady of a hot dry climate: the Saudi Arabian experience. Int J Ambient Energy
1990;11:157–68.
periodic conditions using the climatic data of Riyadh. The concept [7] Eben Saleh MA. Impact of thermal insulation location on buildings in hot dry
of thermal-mass energy-savings potential was developed and uti- climates. Solar Wind Technol 1990;7:393–406.
lized for the first time to construct a chart to determine the ther- [8] Balaras CA. The role of thermal mass on the cooling load of buildings. An
overview of computational methods. Energy Build 1996;24:1–10.
mal mass thickness (Lmas) required to obtain desirable [9] Bojic MLj, Loveday DL. The influence on building thermal behavior of the
percentages of energy savings through using thermal mass alone insulation/masonry distribution in a three-layered construction. Energy Build
for any thickness of insulation. The results show that: 1997;26:153–7.
[10] Bojic M, Yik F, Sat P. Influence of thermal insulation position in building
envelope on the space cooling of high-rise residential buildings in Hong Kong.
1. Daily transmission loads are not affected by Lmas for summer Energy Build 2001;33:569–81.
and winter months. [11] Kossecka E, Kosny J. Equivalent wall as a dynamic model for a complex thermal
2. For moderate months, daily cooling and heating loads decrease structure. J Therm Insul Build Env 1997;20(January):249–68.
[12] Kossecka E. Relationships between structure factors, response factors, and z-
with increasing Lmas and either diminish to zero or be reduced transfer function coefficients for multilayer walls. ASHRAE Trans
asymptotically to constant values. 1998;104(1A):68–77.
442 S.A. Al-Sanea et al. / Applied Energy 89 (2012) 430–442

[13] Kossecka E, Kosny J. The effect of insulation and mass distribution in exterior [25] Tsilingiris PT. The influence of heat capacity and its spatial distribution on the
walls on the dynamic thermal performance of whole buildings. In: Conference transient wall thermal behavior under the effect of harmonically time-varying
proceedings: ‘‘thermal performance of the exterior envelopes of buildings VII’’, driving forces. Build Environ 2006;41:590–601.
December 6–10, 1998, Clearwater Beach, Florida. p. 721–31. [26] Gregory K, Moghtaderi B, Sugo H, Page A. Effect of thermal mass on the
[14] Kossecka E, Kosny J. Influence of insulation configuration on heating and thermal performance of various Australian residential constructions systems.
cooling loads in a continuously used building. Energy Build 2002;34: Energy Build 2008;40:459–65.
321–31. [27] Zhou J, Zhang G, Lin Y, Li Y. Coupling of thermal mass and natural ventilation in
[15] Al-Sanea SA. Evaluation of heat transfer characteristics of building wall buildings. Energy Build 2008;40:979–86.
elements. J King Saud Univ, Eng Sci 2000;12(2):285–313. [28] Al-Sanea SA, Zedan MF. Optimum insulation thickness for building walls in a
[16] Al-Sanea SA, Zedan MF. Effect of insulation location on thermal performance of hot–dry climate. Int J Ambient Energy 2002;23:115–26.
building walls under steady periodic conditions. Int J Ambient Energy [29] Daouas N. A study on optimum insulation thickness in walls and energy
2001;22(2):59–72. savings in Tunisian buildings based on analytical calculation of cooling and
[17] Al-Sanea SA, Zedan MF. Effect of insulation location on initial transient thermal heating transmission loads. Appl Energy 2011;88:156–64.
response of building walls. J Therm Env Build Sci 2001;24(4):275–300. [30] Ozel M. Effect of wall orientation on the optimum insulation thickness by
[18] Asan H. Investigation of wall’s optimum insulation position from maximum using a dynamic method. Appl Energy 2011;88:2429–35.
time lag and minimum decrement factor point of view. Energy Build [31] Taleb HM, Sharples S. Developing sustainable residential buildings in Saudi
2000;32:197–203. Arabia: a case study. Appl Energy 2011;88:383–91.
[19] Ozel M, Pihtili K. Optimum location and distribution of insulation layers on [32] Kusuda T. Heat transfer in buildings. In: Rohsenow WM, Hartnett JP, Ganic EN,
building walls with various orientations. Build Environ 2007;42: editors. Handbook of heat transfer applications. New York: McGraw-Hill; 1985
3051–9. [chapter 9].
[20] Al-Sanea SA, Zedan MF. Improving thermal performance of building walls by [33] ASHRAE, handbook of fundamentals, American Society of Heating,
optimizing insulation layer distribution and thickness for same thermal mass. Refrigerating and Air-conditioning Engineers, Inc., Atlanta; 1997.
Appl Energy 2011;88:3113–24. [34] Al-Sanea SA, Zedan MF, Al-Ajlan SA. Adjustments factors for the ASHRAE clear-
[21] Ogoli DM. Predicting indoor temperatures in closed buildings with high sky model based on solar-radiation measurements in Riyadh. Appl Energy
thermal mass. Energy Build 2003;35:851–62. 2004;79:215–37.
[22] Cheng V, Ng E, Givoni B. Effect of envelope colour and thermal mass on indoor [35] Al-Sanea SA, Zedan MF, Al-Ajlan SA, Abdul Hadi AS. Heat transfer
temperatures in hot humid climate. Solar Energy 2005;78:528–34. characteristics and optimum insulation thickness for cavity walls. J Therm
[23] Tsilingiris PT. Wall heat loss from intermittently conditioned spaces – the Env Build Sci 2003;26:285–307.
dynamic influence of structural and operational parameters. Energy Build [36] Al-Sanea SA, Zedan MF. Optimized monthly-fixed thermostat-setting scheme
2006;38:1022–31. for maximum energy-savings and thermal comfort in air-conditioned spaces.
[24] Tsilingiris PT. Parametric space distribution effects of wall heat capacity and Appl Energy 2008;85:326–46.
thermal resistance on the dynamic thermal behavior of walls and structures. [37] Croy DE, Dougherty DA. Handbook of thermal insulation applications. New
Energy Build 2006;38:1200–11. Jersey: Noyes Publications; 1984.

Вам также может понравиться