Control Panel/Communicator
Installation Instructions
2
Specifications
Current & Voltage Ratings Loop Characteristics
Loop Voltage: -------------------------------- 5 Volts
Residential Burglary (4 Hour Standby)
Combined Standby Current: -------------- 500 mA
Loop Current : -------------------------------- Zones 1, 2, 3: 0.9 mA (2.2 K)
Bell Output: ----------------------------------- 2 A
Zones 4, 5, 6: 0.5 mA (3.9 K)
(Using Rechargeable 12 VDC 4 AH BATTERY, minimal requirement)
Residential Fire (24 Hour Standby) Loop Resistance: ---------------------------- 100Ω per zone (max.)
Combined Standby Current: -------------- 120 mA
Bell Output: ----------------------------------- 95 mA
(Using Rechargeable 12 VDC 7 AH BATTERY, minimal requirement) Device Specifications
Max # keypads: ------------------------------ 4, RPXP6GT current = 65 mA
Transformer and Battery
Required Transformer: -------------------- NAPCO TRF12 OR Max # of receivers: -------------------------- 2, GEM-RECV-XP8
BASLER 16.5 VAC 20VA current = 65 mA each
Maximum Charging Current: ------------- 165 mA Max Keypad wire length: ------------------- 1000’ total wire length
3
WI1372 XP-600 Installation Instructions
4
Programming the Panel using PCD2000 Software running PCPreset. 4. Site-Initiated (PCPreset & A6 )
Refer to XP-600 Programming Instructions (WI1373) For Site Initiated Downloaded, see Auto 5. Automatic Downloading (Using PCPreset)
Download ID Number [93].
Defaulting the Panel
1. Remove power from the panel. Local Downloading
2. Remove all wiring from terminal 15 (PGM)
Wire as shown in Figure 1. Use the power up or
and terminal 3. A6 method of establishing a connection. The
3. Connect terminal 15 (PGM) to terminal 3.
power up method is recommended if the panel is
4. Apply power to the XP-600 control panel. attempting to report.
5. After a few seconds the W ARMED, X +12 -13 14 15 16 17 18 19
+PWR GND GREEN PGM TIP RING TIP RING
READY and HSYSTEM TROUBLE LEDs (-)
TELCO PHONE
GREEN
6. The keypad will beep 3 times indicating the BRN
+12 -13 14 15 16 17 18 19
panel default values have been loaded. +PWR GND GREEN PGM TIP RING TIP RING
RJ31X
NOTE: PCL2000A
Any programming in Dealer Options 1 [96] and Dealer PCI2000
Options 2 [97] will not be defaulted. If Dealer Code
Lockout has been programmed the panel will not default
MODEM J5 LINE
J3 J4
J1 J2 LOCAL TELCO OUT TO
the Dealer Code. TO COMPUTER TO EXTERNAL TO
MODEM
5
WI1372 XP-600 Installation Instructions
6
Burglary Zone Wiring Fire Zone Wiring Keypad Sounder
NAPCO’s EZ Zone DoublingTM is simple. Each Wire the Fire Zone as shown in the Wiring
terminal has 2 zones, use an E (2.2 K) type Diagram in the back of this manual. An EOL 3 QUICK BEEPS
Zone Doubling Resistor for the primary zone and resistor must be installed, even if the Fire Zone Panel Armed (System ON)
a Z (3.9 K) type Zone Doubling Resistor for the is not used. Chime ON
secondary zone. Fault Find Mode ON
Keypad Sounder ON
Fire Zone Normal 13.0 V Zone Bypassed
Terminals 2.2 K Primary 3.9 K
Fire Trouble 13.8V
3&4 Zone 1 Zone 4 Fire 0.0 V 6 QUICK BEEPS
5&4 Zone 2 Zone 5 Panel Disarmed (System OFF)
TABLE 4 VOLTAGE AT FIRE ZONE (Terminals Chime OFF
6&7 Zone 3 Zone 6
8&9) Fault Find Mode OFF
TABLE 2 EZ ZONE DOUBLINGTM Keypad Sounder OFF
PGM Wiring Zone Un-Bypassed
Wire zones as shown in the wiring diagram at The PGM is a switched negative output that is
the back of this manual (page 27). All resistors activated depending on the programming option
must be installed, even if the zone is not used. If 1 SECOND - STEADY TONE
(s) that have been selected [08], [23] - [25]. Incorrect Code Entered
required, unsupervised open circuit devices may Connect the device controlled by the PGM
be used instead of closed circuit devices. Invalid key entry
between +PWR and the PGM terminal
Program the zone as an Open Circuit Zone [06] (maximum load of 50 mA).
(Zone Doubling Resistor required). If necessary, 4 LONG BEEPS (PRIORITY CONDITION)
use the voltage chart below to verify proper 1. Entering an Arm Code with a faulted zone
voltages. Keypad Operation (Not an Auto-Bypass Reentry Zone).
2. Entering an Arm Code when the Bell or
Primary (2.2K) and Secondary (3.9K) zones normal 1.9 V
Keypad zone LEDs indicate zone status. W PGM is ON (Bell and PGM will turn OFF).
Secondary (3.9K) open 2.5 V 3. Arming with the Fire LED ON - reset
ARMED, X READY and HSYSTEM LEDs
Primary (2.2K) open 3.2 V required. Press the B key.
provide system status. The keypad sounder
Primary (2.2K) and Secondary (3.9K) open 5.0 V
provides feedback beeps for correct and
Primary (2.2K) and/or Secondary (3.9K) shorted 0.0 V incorrect entries.
(Sys. Trbl 7-Zone Trbl)
7
WI1372 XP-600 Installation Instructions
Keypad LEDs Panel Operation 84]. To arm the system with all zones protected,
W ARMED LED DEFINITION press the K key. Press and hold the M or
Arming (System ON) N key for 1.5s to fully set the system (the LED
Armed ON Before arming the system close all protected
Instant Mode Rapid Flash on the Keyfob indicates the Keyfob has
zones (unless programmed as Auto-Bypass transmitted the signal). Program Keyfob/
Zone in Alarm Flashing Reentry Zones). Enter a 4-digit Arm/Disarm Keyswitch Chirp [23-4] for an audible indication
code, the keypad will provide a feedback beep of system arming and disarming.
X READY LED DEFINITION for each key pressed. If a valid Arm/Disarm
Ready to be Armed ON code is entered, the keypad will beep 3 times. If
an incorrect Arm/Disarm code is entered, the
Arming/Disarming with a Keyswitch
Zone faulted OFF The system can be armed/disarmed by using a
keypad will sound a 1-second tone indicating an
momentary Keyswitch wired to Zone 6.
incorrect entry.
HSYSTEM LED DEFINITION Program Keyfob/Keyswitch Chirp [23-4] for an
audible indication of system arming and
AC Failure Flashing Arming without Entry Delay (Instant disarming.
System Trouble(s) ON Mode) NOTE:
Enter the A 1 to eliminate the entry delay. Faulted Keyswitch or silent 24 hour zone normally do not
FIRE LED DEFINITION The W ARMED LED will flash rapidly to indicate display at the keypad. If a silent 24 hour zone or Keyswitch
Fire Alarm Flashing the panel is in Instant Mode. If an Exit/Entry
is faulted at the time of arming the faulted zone will display
Fire Memory/*Fire Trbl ON only while the priority sound is ON.
Zone is tripped while the panel is in Instant
*See Note 1 Mode the panel will go into alarm immediately.
8
Delay Tone. Enter a valid Arm/Disarm code. If Home Bypassing a zone
a valid Arm/Disarm code is entered, the keypad Exit/Entry Zone is not violated Press the C key, then the zone number to be
will beep 6 times, indicating the panel has been Zones selected as Home/Away with Delay bypassed. While the panel is DISARMED, the
disarmed. The red Armed LED will go out. If an Zones will be bypassed automatically. bypassed zone LED will flash slowly; indicating
incorrect Arm/Disarm Code is entered, the the zone has been bypassed. While the panel is
keypad will sound a 1-second tone, indicating Away with Delay W ARMED, the bypassed zones will only be
incorrect entry. Press the B key and re-enter Exit/Entry Zone is violated displayed if the Display Bypassed [21-3] option
the code. Zones selected as Home/Away with Delay has been selected.
Zones will have a fixed 20-second entry
Disarming after an Alarm (Alarm Memory) delay when violated before an Exit/Entry Unbypassing a zone (Disarmed only)
The armed LED and the zone(s) that caused the Zone. Press the C key then the number of the
alarm will be be flashing. Disarm the panel. zone to be unbypassed.
The system is currently not detecting zone faults Full Setting the System with Automatic
or displaying system trouble. The zone(s) that Bypassing - Home/Away with Delay Group Bypass
caused the alarm will continue to flash. The Zones Press C C to Bypass all Exit/Entry
Ready and H SYSTEM TRBL LEDs are out Follower Zones [02] or Home/Away Zones
indicating: From the Keypad [01] (only if the system is programmed
Press C B to return protection to exclusively for Home/Away with Delay
The system is displaying Alarm Memory. Home/Away with Delay Zones that have zones).
been automatically bypassed. Three .
Press the B key to clear Alarm Memory. minutes are allowed to walk through Exit/ Using A Keyfob (GEM-KF)
Entry and Exit/Entry Follower Zones. Hold the M or N key on the Keyfob to
Bypass all Exit/Entry Follower Zones [02] or
Bypassing Using A Keyfob (GEM-KF) Home/Away Zones [01] (only if the system is
All zones in the system can be armed programmed exclusively for Home/Away
Automatic Bypassing regardless of the state of the Exit/Entry with Delay zones).
Home/Away with Delay Zones Zone when arming with a Keyfob and using
This zone type has the following operation an AUX key programmed as Full Set. User Program Mode
depending on whether an Exit/Entry Zone has Press K and press and hold the M or
To prevent the loss of the User 1 Code, the
been violated during the Exit Delay time. N keys for 1.5s when leaving the
panel default program includes User 1 Code
premises. All zones, including Home/Away Lockout [96-2].
Zones are armed.
9
WI1372 XP-600 Installation Instructions
To change the User 1 Code from its default While in User Program Mode the Armed, specified output. If the battery cannot sustain
value of 1234, program the 4-digit User 1 Code READY and HSYSTEM Trouble LEDs will the load, a low battery indication will be
through Dealer Programming [95]. User 1 Arm/ continue to flash, follow the example below to displayed. A battery test is also performed on
Disarm code is also used to program User program User 2’s code to 1923. power-up after a 3 minute delay.
Codes 2 - 6. By default, the User 1 code cannot
be re-programmed by the user. *A battery test occurs every 4 hours when
User Mode Programming Example: Household Fire [96-3] has been selected.
If it is necessary to change the User 1 code, it
1.Press 2, Zone 2 LED will Flash
can be changed through downloading or Dealer CC Group Bypass
keypad programming. From Dealer Program 2.Enter 1 9 2 3, Zone 2 LED will
Enter this command to bypass all Exit/Entry
Mode, change the User 1 Code Lockout ([96-2] continue to flash until the 4th digit is Follower Zones or Home/Away Zones (only if
LED=OFF) to disabled. entered. The keypad will beep 4 times the system is programmed exclusively for
confirming a valid entry (Zone LED steady). Home/Away with Delay zones).
Entering User Program Mode
Deleting a User Code A 4 Instant
1. Enter A 8 Press the number of the User to be deleted, the Enter this command before or after arming to
2. Enter User 1 Code zone LED will be flashing indicating that the user remove the entry delay on Entry/Exit Zones.
has been selected. Press A 4, the LED The keypad ARMED LED will flicker rapidly.
(1 2 3 4) associated with the user will now be OFF. Faulting a Exit/Entry Zone will result in an
(Default) immediate alarm.
Exiting User Program Mode
To exit User Program Mode press the b key. A 5 Chime ON/OFF
Enter this command to turn chime ON/OFF.
Zone LED Meaning
The Keypad will chime on any zone that has not
XP-600 Commands been selected as an Exit/Entry Follower Zone,
OFF User Arm/Disarm Code not programmed
Home/Away with Delay Zones, or 24 Hour Zone.
Flashing User Arm/Code is currently being programmed User Commands
A 1 Bell Test
Steady User Arm/Disarm Code has been programmed Enter this command to turn on the Bell, keypad
sounder and keypad LEDs for 2 seconds. The
TABLE 5 ZONE LED DEFINITION-USER PROGRAM battery is tested during a Bell Test, and
MODE automatically every *24 hours to ensure proper
battery operation under load. The Alarm output
requires a battery in order to supply the
10
A 8 + User 1 Code - User Program ready, tell the installer to arm, then disarm. Then SIGNAL STRENGTH KEYPAD SOUNDER
Mode enter A 6 in order to establish a connection. 3 or less .25S BEEP
Phone connection to installer will go "dead" as 4 BEEP
A 9 Keypad Sleep Mode ON/OFF downloader and panel connect. 5 BEEP BEEP
Enter this command to turn the keypad sounder
6-7 BEEP BEEP BEEP
ON/OFF. When the keypad is in Sleep mode all A 7 Fault Find ON/OFF
keypad sounds will be silenced except for 8-10 BEEP BEEP BEEP BEEP
Hardwired Zone Operation
keypad feedback beeps and Keypad Sounder Enter this command to turn Fault Find ON/OFF.
on Alarm. TABLE 6 AUDIBLE SIGNAL STRENGTH INDICATION
While in Fault Find mode, the loop response for
all zones will be set to the faster response of 40
User Commands - Optional ZONE 1 ZONE 1 ZONE 1 ZONE 1
ms. The keypad will beep for .25-seconds when
A0 Easy Exit/Easy Arm hardwired zones are faulted and for 1-second ZONE 2 ZONE 2 ZONE 2 ZONE 2
If enabled in Dealer programming, enter this when zones are restored. ZONE 3 ZONE 3 ZONE 3 ZONE 3
command while the panel is Armed to allow 3 ZONE 4 ZONE 4 ZONE 4 ZONE 4
minutes to exit the premises through Exit/Entry Wireless Operation 4 5 6-7 8-10
and Exit/Entry Follower Zones. Enter a0
to arm the panel. To disarm the panel a valid
(Signal Strength)
While in Fault Find mode the keypad will provide
FIGURE 5 VISUAL SIGNAL STRENGTH INDICATION
Arm/Disarm code must be entered. Requires
Easy Exit/Easy Arm [21-2] to be enabled.
an audible (Table 6) and visual (Figure 5) Signal Strength Logging Mode
indication of each transmitter’s signal strength. The Signal Strength Logging Mode is a
The signal strength metering is based on a scale troubleshooting tool which allows the collection
of 4 to 10, with 4 being marginal and 10 being of signal strength information for all transmitters
A 3 Access on PGM excellent. on the system. Normally the Signal Strength of
If enabled in Dealer programming, enter this Supervisory Signals are not logged; during
command to activate the PGM output (Terminal The keypad will beep out a number, from 1-4, Signal Strength Logging Mode the signal
15) for 5 seconds. corresponding to the signal strength of the strength information for all supervisory signals
transmitter. See Table 6. Each beep is 1- received over a two hour period will be saved to
second long. The keypad will sound a short the LOG.
Dealer Commands beep for transmitters with signal strengths of 3 Local Activation
or less. Enable [92-4=ON], this will initiate a two hour
A6 Download (Programming
test period where all supervisory signals will log
Required) signal strength information.
Establish a connection between the PCD phone
line and the Control Panel phone line. When
11
WI1372 XP-600 Installation Instructions
NOTE:
Remote Activation Zone Features If A0 is Entered during Exit Time, Home/Away with
Using NAPCO’s Quickloader Software [00]Exit/Entry Zones Delay Zones will be automatically bypassed, even if the
(Version 3.26 or higher), follow the Delay allows exit and entry through an Exit/ Exit/Entry Zone is violated. Easy Exit/Easy Arm [22-2] must
instructions below: be enabled.
Entry Zone after the system is armed
From the Status Screen without setting off an immediate alarm. Exit [02]Exit/Entry Follower Zones
Press F6 Delay allows the user to leave the premises Entry Delay allows the user time to enter
Select Miscellaneous Control after arming. Entry Delay allows the user and disarm. Allows exit after the panel is
Select Enable Signal Strength Logging time to enter and disarm. The entry delay armed without setting off an immediate
may be canceled by pressing a 4. alarm and allows entry only if an Exit/Entry
Uploading Signal Strength Information
Zone [00] has been violated first. Zones of
from the Log this type have a three (3) minute power-up
After approximately (2) two hours, re-establish [01]Home/Away with Delay Zones
Zones that automatically bypass at the delay, and do not display or cause an alarm
a connection with the panel. Signal strength if faulted when the system powers up.
expiration of the exit delay if the EXIT/
log information ranges from 1 to 10. The Pressing the b key cancels the 3 minute
ENTRY zone(s) are not violated. Zones of
logging of signal strength should appear this type have a three (3) minute power-up timer.
similar to the sample LOG below: delay, and do not display or cause an alarm Group Bypassing - Zones programmed as
07/24/97 17:44 QL: Full Program Uploaded if faulted when the system powers up. Exit/Entry Follower Zones will be Group
07/24/97 17:42 QL: Technical Connection Pressing the b key cancels the 3 minute
(callback) Technician 2 bypassed if the c c is pressed while
07/24/97 15:23 Transmitter Status: GEM_SMK 1 timer. disarmed or within the Exit Delay.
(7A0DB5): SS=7
07/24/97 15:13 Transmitter Status: GEM_SMK 2 If Exit/Entry zone(s) are violated during the Auto Interior Bypassing - Also program
(768447): SS=8 exit delay, zones programmed as Home/ zones as Home/Away with Delay Zone(s)
07/24/97 15:13 Transmitter Status: Zone 2, SS=6 Away with Delay Zone(s) will have a fixed [01] to automatically bypass at the expiration
07/24/97 14:27 Trouble: RF Link, GEM_RECV 1 20-second entry delay, if violated before the
07/24/97 14:25 Panic: Keypad of the exit delay if the EXIT/ENTRY Zone(s)
07/24/97 14:25 Panic: Keyfob 1(933780) SS=8 Exit/Entry zone. are not violated during the exit delay.
07/24/97 14:25 Dealer Program Mode Entered
To eliminate this fixed 20-second entry
07/24/97 14:24 Instant: Keyfob 1(933780) SS=8
delay, also program zones as Exit/Entry
[03]Auto-Bypass Reentry Zones
07/24/97 14:24 QL: Connection Terminated (10
Zones programmed as this zone type are
MIN T/O) Follower Zones [02].
07/24/97 13:13 QL: Full Program Downloaded permitted to be faulted at the time of arming.
06/24/97 12:06 Open: User 2 Once the zone is restored, while the control
06/24/97 12:06 Close: EasyArm To return protection to zones of this type,
panel is still armed, the zone will
06/24/97 11:55 Trouble Restore: Low Battery, press cb from the keypad or M or
GEM_SMK 2(768447) SS=8
automatically be unbypassed and any
N from a Keyfob. Program the Keyfob subsequent violations of the zone will cause
06/24/97 10:21 Transmitter Status: GEM_SMK
(7A0DB5): SS=6 AUX 1 or AUX 2 button for Full Set [81-7].
12
an alarm condition. [07]Burg (Steady) Output [11]Entry Delay
Enables the Bell Output on a zone trip for Delay time permits entry through Exit/Entry
[04]24-Hour Protection
A zone that provides protection at all times, each zone selected. The Bell Output will Zone(s) after the system is armed without
whether or not the system is armed. remain ON for the length of time setting off an immediate alarm. Entry Delay
programmed for Burg (Steady) Output [07] allows the user time to enter and disarm the
[05]40 ms Loop Response or it will remain ON until turned off by system. Upon entering, the keypad sounder
Normally loop response is 750 ms, select entering a valid Arm/Disarm Code; 0 means will sound a steady tone (Entry Sound) to
this option to change the loop response to
output will stay ON until reset. remind the user to disarm the system. Entry
40 ms. The slower the loop response, the
Delay Time [11] may be programmed for up
less sensitive the system will be to
intermittents (swingers). The programming [08]PGM Output to 255 seconds (4¼ minutes); a value of 0
option is not permitted for UL installations. Enables the PGM Output on a zone trip for defaults to 30 seconds. Entry Delay may be
each zone selected. The PGM Output will canceled by pressing a 4 before or
[06]Open Circuit Zones remain ON until reset. after arming.
Program this zone type if unsupervised
normally open circuit devices are required
The programming option is not permitted for [09]Selective Bypass [12]Burg (Steady) Output Time-out
UL installations. If programmed, selected zones will be able Can be programmed from 1 to 255 min (4¼
to be bypassed by the User. By default, all hours); 0 means output will stay ON until
zones are permitted to be bypassed. turned off by entering an Arm/Disarm Code.
Normally Open Zone Wiring
(Z)
as shown (Zone 4). The delay time which permits exit through hours); 0 means output will stay ON until
EZ Zone DoublingTM an Exit/Entry Zone [00] after the system is turned off by entering an Arm/Disarm Code.
ZONE 4
resistor
armed, allows a user to leave the premises
is required.
2.2K
(E)
without setting off an immediate alarm. Exit [14]Test Timer Interval
Program the
Delay may be programmed for up to 255 Program the interval, in days, between Test
zone for
Open Circuit [06]. ZONE 1 seconds (4¼ minutes); a value of 0 defaults Timer reports. Test Timer Interval may be
to 60 seconds. programmed from 1 to 255 days.
13
WI1372 XP-600 Installation Instructions
[15]Line Cut Time-to-Fail [18]Test Timer Offset (3) Enable Keypad Panic (gG)
Enable this feature by programming the Enter the time, in hours, that a Test Timer Additional Programming required:
delay time required to declare a line cut will be reported after Dealer Mode has been Select reporting to Telco 1 [36-3] or Telco 3
failure. Programming 000 will disable line exited. With the default value of 12, the test [56-3].
cut detection. timer will be sent 12 hours after exiting (4) Enable Ambush - If enabled, the 6th
Dealer Mode. The test timer can also be User Code will send an Ambush report
offset using NAPCO PCD3000 Downloading when entered to disarm the system.
[16]Wireless Supervisory Timer Software. On power up the test timer is sent Additional Programming required:
A transmitter will send a transmission every immediately. Follow the commands below Program User 6 Arm/Disarm Code.
time it is tripped; when there is no activity, to offset the test timer using Quickloader Select reporting to Telco 1 [36-2] or Telco 3
the transmitter sends a supervisory Software: [56-2].
transmission about once an hour. If the UL Installations: If Keypad Fire [20-1] is
receiver does not receive any signal (either From the Status Screen enabled, the keypad must be mounted
a trip or a status) from a transmitter in the • Press F6 within (3) three feet from the Control Panel.
time specified, a system trouble ‘RF • Select Miscellaneous Control [21]Keypad Features 2
Supervisory Failure' will be indicated at the • Select Test Timer Offset (1) Audible Panic - Keypad Panic will not
keypad. Timer is programmable from 1-26 • Enter New Test Timer Offset: 12 turn the Bell on unless this option is
hours; 0 means NO supervision. hours programmed.
• Enter u to advance the test timer (2) Exit/Entry with Urgency - select to give
due in time by 12 hours. an audible indication of Exit and Entry times.
[17]Wireless Smoke Supervisory Timer During the last 10 seconds of entry and exit
A smoke detector will send a transmission time, the keypad sounds a distinct sound to
every time it is tripped; when there is NO System Features indicate the premises must be left or the
activity, the smoke detector sends a panel must be disarmed.
supervisory transmission about once an
[20]Keypad Features 1 (3) Display Bypassed (Armed) - Select to
(1) Enable Keypad Fire (ee) display bypassed zones while the panel is
hour. If the receiver does not receive a
Additional Programming required: armed.
signal (either a trip or a status) from a
Select reporting to Telco 1 [36-1] or Telco 3 (4) Disable Code Entry Beeps - Program
transmitter in the time specified, a system
[56-1]. to disable keypad beeping on valid code and
trouble ‘RF Supervisory Failure' will be (2) Enable Keypad AUX (ff) function entries.
indicated at the keypad. The Supervisory Additional Programming required:
timer is programmable from 1-8 hours; 0 Select reporting to Telco 1 [36-2] or Telco 3
means NO supervision. [56-2].
14
[22]Miscellaneous Features 1 command. PGM on a Low Battery condition.
(1) Abort Delay - Program to allow a 15 (3) Follow Keypad Sounder - The following (3) *Trouble - Program to activate the PGM
second Delay (except 24 Hour Zones) after keypad sounds will activate the PGM output: on a Trouble condition.
a zone trip before reporting. Disarm the Entry Sounder, Keypad Pulsing Sounder, (4) Armed - Program to activate the PGM
system within 15 seconds to prevent Keypad Output on Alarm, Chime, Fault Find. when the panel is Armed. The PGM output
reporting. (4) Keyfob/Keyswitch Chirp - Program to will flash when the panel has gone into
(2) Easy Exit/Easy Arm - Enables A 0 chirp the PGM Output (1) one time when the alarm.
panel is armed or (2) two times when the panel
command. While the system is armed, *Includes Bell Cut, Fire Trouble, Receiver
is disarmed. Wire as shown in Figure 7.
entering this command allows 3 minutes to Fail-to-Respond, Receiver Tamper,
Exit through Exit/Entry and Exit/Entry Receiver JAM, Wireless Smoke Low
Follower Zones. Enabling this option also PGM BLK K1 Battery, Wireless Smoke Supervisory Fail.
enables Easy Arm, enter a 0 to arm
+AUX RED
[26]Miscellaneous Features 2
the system. (1) Momentary Keyswitch Arming -
(3) Swinger Shutdown - Automatically Typically, connect a normally-open
disables armed zones with excessive alarm/ COM N/C N/O Keyswitch across the zone AND its 3.3K
restores (swingers). Non-24-Hour zone-doubling resistor.
Protection zones: allows only 3 alarms and Siren Driver (2) Reserved.
Steady Input (3) Inhibit Fail-to-Communicate Display -
2 restores per zone per arming before the +AUX
This option prevents the keypad from either
zone is disabled. FIGURE 7 KEYFOB/KEYSWITCH indicating or sounding when a Fail to
(4) Bell on Line Cut (Armed) - Program to [24]Programmable Output Features 2 Communicate has occurred.
turn the Bell Output on if the telephone line (1) I Fire - Program to activate the PGM (4) Inhibit Low Battery Display - Program
has been cut while the panel is armed. on a Fire alarm. to inhibit the Low Battery Display at the
(2) AUX - Program to activate the PGM on a keypad. Low Battery Reporting is not
[23]Programmable Output Features 1 AUX alarm. inhibited. The programming option is not
(1) Audio Verification - Program to activate (3) Panic - Program to activate the PGM on permitted for UL installations.
the PGM during reporting. Select specific a Panic alarm.
zones for audio verification by programming (4) Test Timer - Program to activate the
the required zones in PGM Output [08], PGM during a Test Timer report.
PGM Features 2 [24] and PGM Features 3 Telephone Number 1 Programming
[25]. Connect the PGM to the VeriphoneTM [25]Programmable Output Features 3
trigger low input. (1) Y AC Fail - Program to activate the [30]Subscriber ID Number
(2) Access Output - Activates the PGM For 4/2 format enter a 4 digit number. If 3/1
PGM on the loss of AC. (15 minute delay)
output for 5 seconds using the A 3 format is required, enter a 3 digit number,
(2) Low Battery - Program to activate the
15
WI1372 XP-600 Installation Instructions
then press the i key to blank the last [33]Receiver Options [36]System Reporting, Telco 1
digit. (1) 2300 Hz HS/Kissoff - Select 2300 Hz (1) Keypad Fire - Program to activate a
Handshake and Kissoff. Keypad Fire report (ee).
[31]Telephone Number 1 (2) Sumcheck - Only used for the following
(2) AUX/AMBUSH - Program to activate an
Program the phone number to be dialed for Receiver Formats: Ademco Slow, Radionics
AUX or AMBUSH report (ff).
Telephone Number 1. Program the number Fast, Silent Knight Fast and Universal High
directly, just as it is entered on a TouchTone Speed. This is a sophisticated data format (3) Panic - Program to activate a Panic
phone. A fixed Dial Tone Detection (E) is used to enhance the speed and check the report (gG).
included prior to the Dialing Prefix (Block accuracy of the received transmission. This (4) Test Timer - Program to activate a Test
Number 44). Programming an E is not format should be used whenever the central Timer report.
required for Telco 1, Telco 2 and Telco 3. If
station has this capability. Instead of
dial tone detection is not desired select No
Dial Tone Detection in Communicator sending a second round to verify correct [37]System Reporting, Telco 1
Features [46-1]. Use the i key to blank data, the panel sends a Sumcheck digit after (1) Y AC Fail Report - Program to activate
out remaining digits in the phone number. sending the Subscriber ID and Alarm Code. an AC Fail report (15 minute fixed report delay).
(3) Single Digit - 3/1 Format. 3-digit (2) Low Battery Report - Program to
[32]Receiver Format Subscriber ID number and a 1-digit Alarm activate a Low Battery report.
Select the receiver format to be used to Code will be transmitted. (3) *Trouble Report - Program to activate a
report for Telephone Number 1: Program a (4) No Handshake - (All receiver formats Trouble report.
0 to disable reporting to Telco 1. except Pager Format). If programmed no (4) I Fire Report - Program to activate a
Handshake/Kissoff is required by the panel.
[0] Disabled [4] Universal High Speed Fire report.
[1] Ademco Slow [5] Reserved [34]Zone Report, Telco 1 *Includes Bell Cut, Fire Trouble, Receiver
[2] Radionics Slow [6] Point ID Select zone(s) required to send an alarm Fail-to-Respond, Receiver Tamper,
[3] Silent Knight Fast [7] Pager report to Telephone Number 1. Receiver JAM, Wireless Smoke Low
Battery, Wireless Smoke Supervisory Fail.
Point ID format will report trouble(s) by
[35]Zone Restore Report, Telco 1
device and ID number.
Select zone(s) required to send a restore
report to Telephone Number 1. The zones
[38]System Restore Report, Telco 1
will send a restore after Bell time-out, unless
(1) AC Restore - Program to activate an AC
programmed as silent zones.
Restore report.
(2) Battery Restore - Program to activate a
16
Battery Restore report. for Telco 2 (Backup reporting). Refer to break ratio when rotary dialing from 1.5:1 to
(3) Trouble Restore - Program to activate a section [32]. 2:1.
Trouble Restore report. (3) Backup if < 4 attemps - If Backup
(4) Fire Restore - Program to activate a Fire [43]Receiver Options (Telco 2) Reporting [45-4] has been enabled, the
Restore report. Refer to section [33] Receiver Options. communicator will use Telephone Number 2
[41] for the remaining retries when there are
[39]Opening/Closing Report, Telco 1 less than 4 retries remaining.
[44]Dialing Prefix
Select users required to send opening and (4) Reserved
Dialing prefix for Telco 1, Telco 2, and Telco
closing reports to Telephone Number 1.
3. Program if using an Outside access
Do not program for users that are intended
number.
to send an Opening After Alarm (Cancel Pager Programming
Code) or Conditional Closing reports. [45]Communicator Features 1 If Pager Format ([32]and/or[42]and/or[52] =
(1) Communicator Enabled - Program to 7) is selected, pager data will be displayed
Backup Telephone Programming enable the communicator. as shown in Figure 8. If Pager Format is
[40]Subscriber ID Number (Telco 2) (2) DTMF with Rotary Backup - The first selected 4/2 format must be programmed
For 4/2 format enter a 4 digit number. If 3/1 attempt to communicate is dialed using the and Sumcheck is not permitted. If a PIN
format is required enter a 3 digit number TouchTone method of dialing, subsequent number is required refer to Leading Digits
then press the i key. attempts are dialed using the pulse method [47].
of dialing. Disable this feature to dial using
[41]Telephone Number 2 only rotary dialing.
000 033-1234
Program the phone number to be dialed for (3) DTMF only - All attempts to
communicate dial using the TouchTone Leading Digits
Telephone Number 2. A fixed dial tone
detection (E) is included prior to the Dialing method of dialing. Report Code
Prefix [44]. Dial tone detection can be (4) Backup Reporting to Telco 2 - After 2 Subscriber ID Number
disabled by programming No Dial Tone attempts are made to communicate to Telco 1
Detection [46-1]. To program any additional the backup phone number is dialed (Telco 2). FIGURE 8 DEFAULT PAGER DISPLAY
delay enter a "D" where required in the [46]Communicator Features 2
phone number. (1) No Dial Tone Detection - Program to Pager Alarm data is the same as 4/2 format
disable dial tone detection for Telco 1, Telco with the exception that the 2 digit Report
[42]Receiver Format (Telco 2) 2 and Telco 3. Code is transmitted before the 4 digit
Select the format that will be used to report (2) 2:1 Rotary Dialing - Changes the make Subscriber ID.
17
WI1372 XP-600 Installation Instructions
18
System Report Code [63]. For example, if a (2) Conditional Closing Telephone 1 - Wireless
Low Battery System Report Code is F8 the When enabled, all users that are not
Battery Restore would be E8 (4/2 format). selected to report an Opening/Closing ([39], Up to two receivers can be wired to the XP-
[59]) will report a Closing only when zones 600. Each wireless transmitter can be
[65]Opening and Closing Codes have been bypassed. The Zone Trouble mapped to a zone. Only 1 wireless device
Program Opening and Closing Codes for Code [62-2] is used to report zones that is permitted per zone, however, the use of
Users 1 through 6. The second digit of the have been bypassed at the time of the both hardwired and wireless on a zone is
report code is the number of the user that closing report. permitted.
armed or disarmed the system. For To Map a transmitter to a zone:
(3) Reserved
example, if the Closing Code [65] is (4) Reserved
programmed 1. Enter the Programming Block Number
with a C, the closing code for User 2 would that the transmitter is to be mapped to.
[68]Telephone Number 3 2. Enter the 7-digit RF ID number directly,
be C2 (4/2 format).
(1) Opening after Alarm (Cancel Code) - just as it is shown on the device label.
see [67-1]. After the 7th digit is entered the keypad
[66]Ambush Report Code (2) Conditional Closing Telco 3 - see [67-1]. will beep.
Program a 2-digit report code for Ambush.
(3) Reserved
To send an ambush report, program a User
(4) Reserved A transmitter will send a transmission every
Code for User 6, Program report User 6 as
time it is tripped. The transmitter also sends
Ambush [20-4] and Select reporting for
a supervisory transmission about once
Telco 1 [36-2] and/or Telco 3 [56-2].
every hour. If the receiver does not receive
a signal from a transmitter in the time
programmed in Wireless Supervisory Timer,
Enhanced Communicator Features a system trouble ’RF Supervisory Failure'
will be indicated at the keypad.
[67]Telephone Number 1 Program Wireless Supervisory Timer [16] to
(1) Opening After Alarm (Cancel Code) - change the supervisory time from the default
When enabled, all users that are not of 12 hours.
selected to report on Opening/Closing [39] The Signal strength of a transmitter can be
will report an Opening only when opening checked at the keypad (see A 7 Fault
after an alarm has occurred. Find Mode) or saved to the LOG (see Signal
19
WI1372 XP-600 Installation Instructions
Strength Logging Mode - pg. 11). options for each Keyfob. 4 PGM
Program a 4 in the AUX 1 and/or AUX 2
[71-76] Wireless Transmitters AUX 1 & AUX 2 option to activate the PGM Output when the
Enter the RF ID# and the point number that Programming Options: M or N buttons on the Keyfob are
20
8 Interior Downloading signals received over a two hour period will
Program an 8 in the AUX 1 and/or AUX 2 be saved to the LOG.
option to Bypass Exit/Entry Follower Zones [90]Callback Telephone Number
or Home/Away with Delay Zones when the Program the phone number of the [93]Auto Download ID Number
M or N buttons on the Keyfob are downloading computer to be dialed by the Enter the Number that is used by PCPreset
pressed (only if the system is programmed panel during a high security download. when downloading using Site Initiated Auto
exclusively for Home/Away with Delay Downloading (A 6).
Zones). [91]Ring Count
Program the number of rings before the The requirements for Site Initiated Auto
[85] - [88] Wireless Smoke Detectors panel will pickup. Ring Method [92-1] Downloading are as follows:
Enter the RF ID# of the smoke detector. (Downloading Features) must also be 1. Download Computer running PCPreset.
selected. 2. Program the telephone number of the
A wireless smoke detector sends a Download Computer in location [90]
supervisory transmission about once every [92]Downloading Features
Callback Telephone Number.
hour. If the receiver does not receive a (1) Ring Method - Enable the ring method
signal from a transmitter in the time 3. Program location [93] with the number
of downloading. The panel will pick-up on
programmed in W ireless Smoke of the PCPreset account that is to be
the number of rings programmed in Ring
Supervisory Timer, a system trouble ‘RF downloaded.
Count [91].
Smoke Supervisory Failure' will be indicated PCPreset
(2) Answering Machine Override - Using
on the keypad. 1. Create the XP-600 account to be
the downloading computer, call the panel.
downloaded using PCD3000
Program Wireless Smoke Supervisory Timer When the operator has determined that the
Quickloader Software.
[17] to change the time from the default time panel has received 1-2 rings, pressing the
2. Create a List using PCPreset.
of 8 hours. Refer to Household Fire [96-3]. u key will cause the downloading 3. Select the account by pressing tt.
Note: Mark Smoke Detectors (Smoke 1 computer to immediately re-dial the panel. Select the desired account from the list
through Smoke 4) in order to identify them in The panel will pick-up on the first ring. of PCD3000 accounts available. (The
the event of a supervisory or battery failure. (3) Command 6 Download - Select to location in the list is the Auto Download
If Household Fire [96-4] is selected, enable the A 6 method of downloading ID Number [93])
Wireless Smoke Supervisory Time is fixed (pg. 5). 4. Tag the list by entering aD
at 4 hours. (4) Signal Strength Test Mode - Program (download)
to initiate a 2 hour test period. The signal 5. Enter Standby Mode by entering o.
strength information for all supervisory
21
WI1372 XP-600 Installation Instructions
The Computer is now in STANDBY [96]Dealer Options 1 polarity and removes supervision from the
Site (1) Dealer Code Lockout - Program to bell circuit.
At the site perform the following three steps: prevent the Dealer Code from changing with (3) System Trouble Auto Restore -
a panel default. Normally, System troubles require
• Arm the panel.
acknowledgment (View System Trouble) in
(2) User 1 Code Lockout - If programmed
• Disarm the panel. the User 1 Code cannot be programmed order to restore. If this option is selected
• Enter A 6. The panel will now call from User Program Mode. troubles will restore without requiring
(3) Household Fire - Activates the following acknowledgment.
the download computer running
PCPreset. PCPreset will answer the UL required features: (4) User 1 Code-Program only - If enabled
There is a 4 hour re-sound of wireless User 1 Code will function only as the User
call, establish a connection, and then
Smoke Low Battery and wireless Smoke Program Code and will not Arm/Disarm the
download the account that matches the
Supervisory system troubles. panel.
Auto Download ID Number [93] with the
account of the same number in the list • An active System Battery test performed Note: All programming within Programming
Blocks [96] & [97] will not change if the
that PCPreset is currently running. every 4 hours instead of 24 hours and
panel is defaulted.
Wireless Smoke Supervisory Timer is
Dealer Programming set to 4 hours. [98] Number of Re-Dials
[94]Dealer Code • Fire Bell Timing is March Time. The Number of re-dial attempts made by the
The default Dealer Code is 4567. Program
a new 4-digit Dealer Code. When the panel
• Wireless Smoke Supervisory Time is panel before indicating a Fail-to-Communicate
fixed at 4 hours. (System Trouble 1-3).
is defaulted, the Dealer Code will be
changed back to the default Dealer Code of (4) Fire Trouble on Fire LED - Normally all
troubles are displayed on the H SYSTEM
4567 only if Dealer Code Lockout [96-1]
has not been programmed. TROUBLE LED, including Fire Trouble. If
[95]User 1 Code required Fire Trouble can be displayed on
The 1st User code is a program code as the Fire I LED. Fire Trouble is indicated
well as an Arm/Disarm code. The default by a steady Fire LED.
User Code is 1234. If User 1 Code Lockout
[97]Dealer Options 2
is programmed the User 1 Code cannot be
programmed from User Program Mode. (1) International Dialing Protocol - No
dialing if no dial tone, 60 s between attempts
and 4 s wait for dial tone.
(2) Invert Bell Output - Inverts the Bell
22
System Troubles EXAMPLE - LOW BATTERY SYSTEM TROUBLE on zone 2 would beep the keypad sounder 3
times and turn on zone 2 LED.
Use the System Trouble chart on the following Press the i to enter System Trouble mode and
page to determine the specific System Trouble(s). determine the specific trouble. Press any key to Audible System Trouble Indication - For all
view all system troubles. system troubles, except when the only system
During normal panel operation the H SYSTEM
TROUBLE LED has the following two modes of trouble is the loss of AC, the keypad will beep
operation: Flashing System Trouble once every 10 seconds. The keypad will
(System Group # continue to beep until the reset button is pressed
Trouble or the trouble has been acknowledged by
STEADY 1-7 possible trouble Group Keypad H SYSTEM
Number) pressing the i key.
groups, AC is present Trouble LED is flashing
1 time indicating System
FLASHING 1-7 possible trouble Trouble Group 1. System Trouble Reporting
groups, AC is not present Beeping
(System Keypad Sounder beeps The following system troubles, when enabled to
Trouble 1 time indicating System report to Telco 1 [37-3] or Telco 3 [57-3], will
Viewing System Trouble(s) Group
Trouble Group 1.
send the report code programmed in Trouble
Number)
Press the i SYSTEM key on the keypad. Report [63] if reporting using a pulse format:
To determine the System Trouble Group System Trouble Pulse Report Code
Bell Cut F1
Number, count the number of times the HSYS- 2-Wire Fire Trouble F1
Rcvr Fail-to-Respond F1
TEM LED blinks. The keypad sounder will beep Receiver Tamper F1
at the same rate that the HSYSTEM LED Receiver JAM F1
Zone LED(s) is ON Specific Trouble
Tx Low Battery F1
blinks. indicates Tx Supervisory Failure F1
(Specific Trouble) Zone 2 LED is ON indicating If reporting using Point ID, a unique code will be
To determine the System Trouble, note the zone Low Battery. (1 Beep, LED 2)
LED that is ON. Look up the specific system sent for each of the following System Troubles.
trouble on the chart on the following page. System Trouble Point ID Report Codes
Bell Cut CODE 1 321 G00 ZN000-BELL 1 TROUBLE
FIGURE 9 SYSTEM TROUBLE EXAMPLE 2-Wire Fire Trouble CODE 1 373 G00 ZN000-FIRE LOOP TRBLE
The HSYSTEM LED and keypad sounder will Rcvr Fail-to-Respond CODE 1 382 G00 ZN000-SENSOR TROUBLE
Receiver Tamper CODE 1 145 G00 ZN000-EXP. MODL. TAMPER
continue to flash and beep. To view the next Receiver JAM CODE 1 373 G00 ZN000-FIRE LOOP TRBLE
System Trouble, if any, press the B key. Note: System Troubles Groups 3 through 7 - A 300 (SYSTEM TROUBLE RST) code is sent if a restore is
Continue pressing the B key, if there are no System Trouble Groups that have a zone or reported after multiple troubles.
more system troubles to view, the system will smoke detector associated with the trouble,
return to normal operation. such as RF low battery. The zone(s) of the
device with a low battery will be displayed by the
ZONE LED. For example, a wireless low battery
23
WI1372 XP-600 Installation Instructions
System Troubles
Keypad Beeps or Zone LED System Trouble Cause/Action
HSYSTEM ON Condition
Flashes
1 Beep 1 AC Power Failure This trouble will occur if AC power is not present. Ensure that the transformer is connected to an
unswitched power source.
2 Low Battery If there has been a recent power failure, the battery may be partially depleted and must be recharged by
the control panel. If the trouble does not go away in 24 hours, replace the battery.
3 Communication The system was not able to report to central station. Check panel programming and telephone line wiring.
Failure/PCPreset Fail The trouble will clear after it has been acknowledged by viewing the system trouble as long as the
telephone line has passed a line cut test (tested automatically by the panel). The Panel did not
sucsessfully connect and download/upload with the commputer running PCPreset - check Auto Download
ID number, Callback Number or PCPreset Setup.
4 Telephone Line Cut The telephone line has failed. If telephone service has been temporarily interrupted, the trouble will clear
when restored and acknowledged by viewing the system trouble.
2 Beeps 1 Bell/Siren line Cut There is a problem with the Bell or Siren wiring. EOL2.2K resistor must be installed.
2 2-wire Fire Trouble There is a problem with the wiring of the Fire Zone.
3 Rcvr Fail-to-Respond/Rcvr The receiver is not responding to the panel. The red LED on the receiver should be flashing, refer to
Tamper WI848. The cover is off the receiver causing a tamper signal to be transmitted.
4 Receiver Jam A signal is blocking the normal reception of transmissions from the wireless devices. Ensure that the
green LED on the receiver is not on continuously, refer to receiver manual WI848.
3 Beeps 1-6 Wireless The battery in the wireless transmitter is low and should be replaced. This transmitter is on the zone corresponding
Transmitter Low Battery to the number of the zone light flashing. The replacement battery for the GEM Trans2 door/window transmitter and
the GEM PIR wireless motion detector is the Duracell DL123A. (2 required for the GEM-PIR) WARNING: Replace
batteries only with the same type as specified above. Use of another battery may present a risk of fire or explosion.
Do not recharge or disassemble battery or dispose of in fire.
4 Beeps 1-6 Wireless The panel has not received a supervisory signal from the transmitter within the time programmed. Check
Transmitter Wireless Supervisory Timer [16] Programming. Check the placement of the transmitter and receiver, refer
Supervisory Failure to WI848.
5 Beeps 1-4 Wireless Smoke Detector The battery in the wireless smoke detector is low and should be replaced. This wireless smoke detector
Low Battery should be marked with a number corresponding to the number of the zone light flashing. The
replacement batteries required are *Duracell 9 Volt Alkaline (2).
6 Beeps 1-4 Wireless Smoke Detector The panel has not received a supervisory signal from the wireless smoke detector within the programmed
Supervisory time. Check Wireless Smoke Supervisory Timer [17] Programming. Check the placement of the wireless
smoke detector and receiver, refer to WI848.
7 Beeps 1-6 Zone Trouble The panel has one or more of the following 3 possible troubles: Zone Short, Transmitter Tamper or Dual
Tech Self Test Fail.
24
Troubleshooting Followers. 6. The PGM Output Pulses in Alarm.
5. Zones programmed for 24 Hour When the PGM lug of the control panel is
Protection. To Activate/Deactivate programmed for an Armed indication, it
1. The bell output drops to about 3 volts
the chime mode, Press A5. also incorporates an Alarm Memory
in alarm.
function which will indicate that the system
The battery/bell circuit is protected by a
4. When using a piezo on the Bell Output, is in an Alarm condition. If this output is
PC board trace which may have burned
it constantly buzzes. being used to trigger a long range radio, it
open by reversal of the battery leads. It is
This is due to a constant loop current can be converted to a steady output with
on the back of the PC board just adjacent
flowing through the Bell circuit for the use of a capacitor, negative to PGM
to the red & black battery leads. Send in
supervision. To eliminate the buzzing, cut Terminal 15, Pos to Aux. Pwr. Term 12.
for service if this occurs.
resistor R26 which is located directly (220 mF Electrolytic Capacitor, 25 Volts.
above Terminal 9 just below the heat sink. Increase to 470 mF if necessary)
2. How do I remove the Keypad Sounder
on Alarm?
5. Where are the fuses? 7. I short out the bell and the system does
The keypad sounder follows the Burg
The control panel incorporates advanced not indicate Bell Trouble.
Output. If you need to remove the Keypad
circuitry which automatically limits the The Bell Supervision circuit is only
Sounder, then you must remove the Burg
current when an over current condition designed to detect a "Bell Cut", it does not
Output from that zone.
exists without the use of traditional fuses. supervise for a short on the Bell.
The circuit will restore automatically when
3. How do I activate Chime by Zone?
the over current condition is corrected.
The Chime feature will automatically be
assigned to all zones, except for the
following:
3. Zones programmed as Home/
Away with Delay.
4. Zones programmed as Exit/Entry
25
WI1372 XP-600 Installation Instructions
8. How do I remove Keypad Sounder on If using internal reed, make sure J1 is 12. No Keypad Chime?
Alarm? cut and both Point 1 and Point 2 The keypad sounder is turned off with the
The keypad sounder follows the Burg terminals are jumped out. A9 command. This command will
Output. If you need to remove the Keypad 10. Keypad LEDs Flicker. silence all Keypad sounds except keypad
Sounder, then you must remove the Burg The Keypad is not receiving a POLL from sounder on alarm. Enter A9 to turn
Output from that zone. the Panel. keypad sounds back on.
Check Keypad wiring.
9. Transmitters not responding? 1. The Panel is in the process of being
Open Transmitter case - Keypad should Uploaded/Downloaded.
go into X-Mitter Tamper Trouble. If not: 2. The panel is powering up. LED’s will
• Check Receiver Red LED should be flicker until panel has reset and is
flashing once approx. once a second. polling the keypad.
3. The connection from the control
• Check Receiver wiring.
panel to the keypad is open.
• Check Programming of Transmitter
ID. 11. No Keypad Entry Sounder during
Entry Time?
If Keypad does go into X-Mitter Tamper
The keypad sounder is turned off with the
Trouble, check:
A9 command. This command will
• Transmitter point is programmed
silence all Keypad sounds except keypad
correctly.
sounder on alarm. Enter A9 to turn
• Transmitter is wired correctly:
keypad sounds back on.
• If using external switch, make sure it
is wired to point 1, and point 2 is
jumped out.
26
XP-600 WIRING DIAGRAM This equipment should be installed in accordance with Chapter
E1 (REFER TO PROGRAMMING INSTRUCTIONS WI1373) 2 of the National Fire Alarm Code, ANSI/NFPA 72-1996
+ RED (National Fire Protection Association Batterymarch Park,
RECHARGEABLE Quincy MA 02269). and local codes. Information describing
BATTERY
RESIDENTIAL BURG (4 HOUR STANDBY)
proper installation, operation, testing, maintenance, evacuation
12 VDC 4AH OR 7AH COMBINED STANDBY = 500 mA BELL = 2.0 AMP
E2 planning, and repair service is to be provided with this
BLACK RESIDENTIAL FIRE (24 HOUR STANDBY) (3) equipment. UL Listed Energy Cable is required.
RECOMMENDED BATTERIES YUASA COMBINED STANDBY = 120 mA BELL = 95 mA
NP4-12 AND NP7-12
REPLACE EVERY FIVE YEARS
DS1 TELE LINE IN USE
RED
GRN
GRAY
BRN
SEE WI1372).
Zone GOLD
Programmable
RED Class 2 + +
50 mA MAX.
RED
GRN
BLK
DoublingTM RED RED Transformer.
Output
LOAD
DO NOT
Resistors
outlet. (Supervised)
3.9K
3.9K
(Z) RPXP6GT
GROUND (Z) (Z) (Z)
+
GOLD
(+) WARNING
ORANGE +
WHITE RED TO PREVENT RISK
(1) ZONE 4 ZONE 5 ZONE 6
OF ELECTRIC SHOCK
(1) ALL ZONE RESISTORS MUST BE INSTALLED, EVEN IF DISCONNECT TELEPHONE
2.2K
2.2K
2.2K
ZONE IS NOT USED. (E) LINES PRIOR TO
(E) (E) GEM-RECV-XP8
(2) COMBINED STANDBY = KEYPAD CURRENT + AUX POWER
CURRENT + FIRE POWER + PGM CURRENT.
2.2K 2.2K SERVICING
2.2K EOLR 12
(3) RESIDENTIAL FIRE REQUIRES A 7AH BATTERY. 2.2K EOLR
(4) UNIT INTENDED TO BE MOUNTED VERTICALLY ON WALL. (E)
(5) REFER TO WI1372 FOR COMPATIBLE TWO WIRE SMOKE
ZONE 1 ZONE 2 ZONE 3 (SUPERVISED) +PWR
DETECTORS. DO NOT MIX DIFFERENT MODELS. (E)
(6) THIS PANEL SHALL BE CHECKED BY A QUALIFIED Normally Open
TECHNICIAN AT LEAST ONCE EVERY THREE YEARS. FT2200
Zone Wiring XP-600 Terminals
(7) THIS PANEL SUPPORTS ONLY ONE SMOKE DETECTOR IN RED
3.9K
27
WI1372 XP-600 Installation Instructions
28