International Energy Services Ltd.

Project Title:

DUPORT ENERGY PARK PROJECT

Document Title

Fire Water Demand Calculation Report

Document Number: DMCL-IES-DEP-PRO-CAL-00003


Sequential Doc.
Company Originator Discipline Document Type Code
Number

DMCL IES-DEP PRO CAL 00003

A.Gobir E. Sylvester L.Barango

B 10-12-19 Issued for Review A.Gobir E.Sylvester L.Barango

A 28-11-19 Issued for IDC A.Gobir E.Sylvester L.Barango

Rev Rev. Date Description Prepared By Checked By Approved By


DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 2 of 23

REVISION MODIFICATION LOG

Revision Section Description


A 4&5 Revised Calculation
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 3 of 23

TABLE OF CONTENTS
LIST OF TABLES .......................................................................................................... 5 
LIST OF FIGURES ........................................................................................................ 5 
1  INTRODUCTION ................................................................................................. 6 
  Objective ....................................................................................................................... 6 

  References ................................................................................................................... 7 

2  BASIS OF DESIGN ............................................................................................ 8 


  General ......................................................................................................................... 8 

  Maximum Risk Evaluation........................................................................................... 8 

  Fire Zone Definition ..................................................................................................... 8 

  Application rate ............................................................................................................ 8 

  Building/Offices ........................................................................................................... 8 

  Maximum Water Velocity............................................................................................. 8 

  Monitor and Hose Reel ................................................................................................ 9 

  Fire Water Line Sizing ................................................................................................. 9 

3  FIRE WATER/FOAM SPRAY APPLICATION ................................................. 10 


3.1  Fire Intensity Control ................................................................................................. 10 

3.2  Fire Water Surface Area Calculation ........................................................................ 10 

3.3  Minimum Fire Water Feeding Pressure ................................................................... 10 

3.4  Hose Reel System ...................................................................................................... 10 

3.5  Fire Hydrant System .................................................................................................. 10 

3.6  Foam System ............................................................................................................. 10 

4  FIRE ZONE DEFINITION.................................................................................. 12 


5  FIRE WATER DEMAND PER ZONE ............................................................... 14 
5.1  Calculation Table Summary ...................................................................................... 14 

5.2  Demand Summary ..................................................................................................... 15 

5.3  Nozzle Calculation and Selection ............................................................................. 17 

Features .................................................................................................................................. 17 


DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 4 of 23

Spray Characteristics ............................................................................................................ 17 


5.4  Nozzle Selection Criteria ........................................................................................... 18 

5.5  Nozzle Calculation Summary; Refer to Appendix D for Vendor Data ................... 19 

APPENDICES .............................................................................................................. 20 


APPENDIX A: Fire Water System Surface Area Calculation ................................. 20 
APPENDIX B: Cooling Water And Foam Water Requirement ............................... 21 
APPENDIX C: Crude Storage Tanks Fire Water And Foam Demand Calculation 22 
APPENDIX D: BETE NOZZLE .................................................................................... 23 
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 5 of 23

LIST OF TABLES
Table 5-1: Calculation Table Summary ................................................................................... 14 

Table 5.2: Demand Summary .................................................................................................. 15 

Table 5-3: Nozzle Selection Criteria ........................................................................................ 18 

Table 5-4: Nozzle Calculation Summary ................................................................................. 18 

LIST OF FIGURES
Figure 3-1: Foam Tank ............................................................................................................ 11 
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 6 of 23

1 INTRODUCTION
This document is to provide the basic design information required to engineer the Duport
Midstream Company Limited 2,500 BPD Crude Distillation Unit and 1,400 BPD Naphtha
Stabilizer Unit to process crude into the following products at their facility near Benin
City in Edo State, Nigeria:

 Full-Range Stabilized Naphtha (FRN)


 Dual Purpose Kerosene (DPK) (Jet A-1 if possible)
 Automotive Gas Oil (AGO)
 Atmospheric Tower Bottoms (ATB)

The simulation model comprises the Full Well Stream (FWS) from Otien-1 into HP
separator, separating into Gas phase and total liquid phase (oil + water). The oil and
water produced are channeled to the feed stock tank.

The LP gas received are boosted in the booster compressor as to meet the downstream
HP gas pressure. The total is comingling before sending to Gas Processing Facility
(GPF).

The gas produced shall be further treated at the Gas Processing Facility (GPF). Dry gas
from GPF is distributed into export pipeline, CNG plant, and Fuel Gas System, at
24MMscfd, 15MMscfd and 5MMscfd respectively.

This report provides the outcome of HYSYS simulation heat and material balance for
the scope limit and export gas hydraulic analysis.

Objective
The fire water demand calculation is aimed at achieving the following:

1. To determine the system zoning of the entire Duport refinery

2. To establish the demand for each zone and identify the largest/highest

demand

3. To determine the firewater storage tank and pumps capacity

4. To ensure the overall safety of the Duport refinery is cover for fire water

suppression system
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 7 of 23

References

General Site layout + pebez battery limit (Rev. 3)


DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 8 of 23

2 BASIS OF DESIGN

General
This analysis will be based on the Codes and Standards as required by relevant NFPA
13, 14, 15, 16, 20; IP 19D; API publ. 2021, 2030; BS EN 1284 Guidance., and Exxon
Mobil GP 70-01-07

Maximum Risk Evaluation

 It is assumed that only one Fire Zone will be considered at a time.

 Multiple fire scenarios have been excluded.

Based on these considerations the fire water and foam water demand shall be calculated
for the single Fire Zone worst case.

Fire Zone Definition

A fire zone consists of equipment containing hydrocarbons concentrated in an area and


separated from others by space.

Application rate

The following specific discharge densities shall be adopted (IP Part 19D.3 Table D.1):

 Production process: 6.5Lit/min/m2 (on the plan view)

 Vessel protection: 6.1 Lit/min/m2 (on the vessel surface)

 Product Tanks: 10.2 lit/min/m2 for reference tank and 6.1 lit/min/m2 for

adjacent tank(s).

Building/Offices

Discharge is based on sprinkler spread. The maximum area protected by a single


sprinkler does not exceed 13.4m2. (NFPA 13, 2016 8.8.2.2.1)

Maximum Water Velocity

Hydraulic calculations shall be used to design the distribution system. The water
maximum velocity of 6 m/s (NFPA 20, 2016, A.4.16.6) shall be considered in the line
size calculation on the distribution area.
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 9 of 23

Monitor and Hose Reel

The following systems and equipment operating on supply of firewater or foam water:

 Fixed water spray systems dedicated to protecting equipment containing volatile


hydrocarbons
 One/Two water monitors (114 m3/hr each) for general area protection. (GP 70 01
07)
 One/ Two water/foam hose reels (23 m3/hr each) as support. (GP 70 01 07 NFPA
13-1999, 7-2.3.1.3)

Fire Water Line Sizing

Hazen-Williams Equation shall be used to determine pressure drop which states thus:
(NFPA 15-1996,5-5.1.1)

. .
DP . . ;DP< 0.5psi/100ft

.
V ;3ft/s<V< 15ft/s

Where Q = Product flow rate (bpd)

d = Internal diameter of the pipe (inch)


DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 10 of 23

3 FIRE WATER/FOAM SPRAY APPLICATION

3.1 Fire Intensity Control

System design densities, volumes and monitor/hydrant orientation shall be selected


based on “projected equipment area” or “actual surface area”. Regardless of the methods
used, the design for nozzle placement shall ensure that all portions of the protected
equipment’s are effectively covered by the spray pattern of selected monitor/hydrant.

3.2 Fire Water Surface Area Calculation

Calculations determining equipment’s area shall be classified as “projected or plan area”


LxB……………………………………………………………………………Equation 1

See Appendix A for fire water calculations table.

3.3 Minimum Fire Water Feeding Pressure

The fire water system requires a minimum of 7 barg feeding pressure at all points.
However, the fire water pumps shall discharge at 10 barg as to meet the most remote
nozzle or monitor within the network. (NFPA 13, A-10.2.2.1; NFPA 14, 5-7)

3.4 Hose Reel System

Hose reel system will be designing to provide firewater in the administrative building of
the Duport refinery. The spray water system will be supplied from the firewater system.

3.5 Fire Hydrant System

Fire hydrant system will be provided on firewater network (or ring main) round the facility
with branches line to all system to be protected. Foam-water monitor / water monitor shall
be appropriately spaced around the tanks, separators and other risk areas within Duport
refinery. Monitors are essentially designed and installed for providing pressurized fire
water for surface cooling and firefighting. This shall form the main approach to fight fire
on Duport refinery.

3.6 Foam System


Liquid hydrocarbon fire shall be extinguished with a mixture of pressurized water and
Aqueous film forming foam chemical (AFFF). Foam vessel shall be of bladder type. This
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 11 of 23

shall comprise of foam proportional (pre-mixer), 3% foam concentrate contained in a


bladder and the pressurized vessel. Figure 1 below shows a typical foam tank.

Figure 1: Foam Tank 1 3-1: Foam Tank


DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 12 of 23

4 FIRE ZONE DEFINITION


DUPORT refinery facility equipment, has been considered for these calculations and has
been subdivided in to the following fire zones.

Fire Zone (A)


The hazardous equipment included in this fire zone is:

 Tank 1 - Condensate tank

 Tank 2 – Condensate tank

 Tank 3 – Naphtha tank

 Tank 4 – Naphtha tank

 Tank 5 – AGO tank

 Tank 6 – AGO tank

 Tank 7 – DPK tank

 Tank 8 – DPK tank

 Tank 9 - HFO tank

 Tank 10 – HFO tank

 Tank 11 – Slop tank

Fire Zone (B)

The hazardous equipment included in this fire zone is:

 Gas Turbines

 Tank (2)

 Waste Water

Fire Zone (C)


The hazardous equipment included in this fire zone is:

 Oil Pump (3)

 GA Processing plant

 Tank

 Pump
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 13 of 23

Fire Zone (D)


The hazardous equipment included in this fire zone is:

 Modular Refinery

 Pump

Fire Zone (E)


The hazardous equipment included in this fire zone is:

 Security Accommodation

 Medical Bay

 Fire Station

Fire Zone (F)


The hazardous equipment included in this fire zone is:

 Lab and Office (2)

 Workshop

 Tank

Fire Zone (G)


The hazardous equipment included in this fire zone is:

 Gantry

 Tank

 Parking Bay (2)

 Guard House (2)

Zone (H)
The hazardous equipment included in this fire zone is:

 Kitchen

 Reception

 Admin Offices
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 14 of 23

Each zone has been treated as an independent fire risk area due to the physical separation
of equipment (safety distances).

5 FIRE WATER DEMAND PER ZONE


1

5.1 Calculation Table Summary

Equipt. Equip Fire Equipment Equipment Applicatio Calculate


t Water . . n d
In Zones
Types Syste Area (m2) Area Type Rate Flowrates
m
(lit/min/m2) (m3/hr)

ZONE B
Gas Turbines PP FW 300 P.A 4.1 74
Tank (2) PP FW 41 P.A 6.1 15
Waste Water PP FW 192 P.A 6.1 47
ZONE C
Oil Pump (3)
GA Processing
368.8
Plant PP 6.1 135
P.A
Tank
Pump FW
ZONE D
Modular PP FW 1058 P.A 4.1 260
Refinery
Pump
Metering PP FW 127 P.A 4.1 31
Station
ZONE E
Security PP FW 160 P.A 4.1 39
Accommodatio
n
Medical Bay PP FW 160 P.A 4.1 39
Fire Station PP FW 230 P.A 4.1 57
ZONE F
Lab and Office Pp\P FW 372 P.A 4.1 92
(2)
Workshop PP FW 750 P.A 4.1 185
ZONE G
Gantry PP FW 118 P.A 6.1 43
Tank PP FW 21 P.A 6.1 8
Parking Bay (2) PP FW 80 P.A 6.1 29
Guard House PP FW 22 P.A 4.1 5
(2)
ZONE H
Kitchen PP FW 35 P.A 4.1 9
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 15 of 23

Equipt. Equip Fire Equipment Equipment Applicatio Calculate


t Water . . n d
In Zones
Types Syste Area (m2) Area Type Rate Flowrates
m
(lit/min/m2) (m3/hr)
Reception PP FW 127 P.A 4.1 31
Admin Offices PP FW 821 P.A 4.1 202

LEGEND

P.A = Projected Area

S.A = Surface Area

PP = Production Process

PT = Product Tank

NA = Not Applicable

FW = Fire Water

FM = Foam Water

2Table 5.2 Demand Summary

5.2 Demand Summary

MAXIMUM FIRE WATER DEMAND


FIRE WATER FOR TOTAL
FIXED FIRE
FIXED SPRAY HOSE
EQUIPMENTS /FOAM WATER
SYSTEMS REELS
MONITORS FLOWRATE
m3/hr. (23m3
/hr.)
(114 m3/hr.) (m3/hr.)
Condensate Tank 1 101 - - -

Condensate Tank 2 101 - - -

Naphtha Tank 3 306 - - -

Naphtha Tank 4 195 114 23 -

AGO Tank 5 101 - - -

AGO Tank 6 101 - - -

DPK Tank 7 42 - - -
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 16 of 23

MAXIMUM FIRE WATER DEMAND


FIRE WATER FOR TOTAL
FIXED FIRE
FIXED SPRAY HOSE
EQUIPMENTS /FOAM WATER
SYSTEMS REELS
MONITORS FLOWRATE
m3/hr. (23m3/hr.)
(114 m3/hr.) (m3/hr.)
DPK Tank 8 42 - - -

HFO Tank 9 27 - - -

HFO Tank 10 29 - - -

Slop Tank 11 18 - - -
TOTAL - - -
Zone A Maximum Demand - - 678
Gas Turbines 74 - - -
Tank (2) 15 - - -
Waste Water 47
TOTAL 138 - - -
Zone B Maximum Demand 114 23 272
Oil Pump (3)
GA Processing Plant
135 - - -
Tank
Pump
TOTAL 135 114 23 -
Zone C Maximum Demand - - 272
Modular Refinery
260 114 23 -
Pump
Metering Station 31 - - -
TOTAL 291 114 23 -
Zone D Maximum Demand 428
Security
Accommodation
39 - - -
Medical Bay 39 - - -
Fire Station 57 - - -
TOTAL 135 - - -
Zone E Maximum Demand 135
Lab and Office (2) 92 - - -
Workshop 185 - - -
-
366 - -
TOTAL
Zone F Maximum Demand - - 366
Gantry 43 114 23 -
Tank 8 - - -
Parking Bay (2) 29 - - -
Guard House (2) 5 - - -
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 17 of 23

MAXIMUM FIRE WATER DEMAND


FIRE WATER FOR TOTAL
FIXED FIRE
FIXED SPRAY HOSE
EQUIPMENTS /FOAM WATER
SYSTEMS REELS
MONITORS FLOWRATE
m3/hr. (23m3/hr.)
(114 m3/hr.) (m3/hr.)
TOTAL 86 114 23 -
Zone G Maximum Demand - - 222
Kitchen 9 - - -
Reception 31 - - -
Admin Offices 202 - - -
TOTAL 242 - - -
Zone H Maximum Demand - - 242

5.3 Nozzle Calculation and Selection

A nozzle’s effectiveness is based on the size, shape, velocity, and distribution of its
droplets. From the BETE Catalog, a Fire Protection specific nozzle used for: Deluge
Protect offshore platforms, storage tanks, hazardous loading areas, and equipment bays.
The BETE Nozzle N-Type has the following characteristics;

Features

 Simplicity of design

 One-piece/no internal parts

 Clog-resistant

 Three standard pipe sizes—1/2”, 1”, and 1-1/2”

 Male connection

 Factory Mutual, U.S. Coast Guard, and Lloyd's Register approved models

Spray Characteristics
• Two spray cones: an outer, wide angle cone and a narrower inner cone combine to give
full cone effect

Spray pattern: Full Cone

Spray angles: 90° and 120° standard

Flow rates: 3.0 to 534 gpm


DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 18 of 23

Based on Water Demand Flow Rates, different BETE N-Type has been specified. See
range below:

3 Table 5-3 Nozzle Selection Criteria

5.4 Nozzle Selection Criteria

Flow Rate (m3/hr) Selected Nozzle Number

1 - 20 N1

21 - 40 N2

41 - 60 N3

61 - 80 N4

81 - 100 N5

>100 N6

5-4 Nozzle Calculation Summary


DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 19 of 23

5.5 Nozzle Calculation Summary; Refer to Appendix D for Vendor Data

Minimum
Flow Rate Flow Rate
FLOW Male Pipe Nozzle Number of Required
EQUIPMENT NAME @ 60psi @ 60psi
RATE Size Number 3 Sprinklers Number of
(GPM) (m /hr)
Sprinklers
Tank 1 265 1/2" N6 51.40 11.67 22.70 23

Tank 2 265 1/2" N6 51.40 11.67 22.70 23

Tank 3 306 1/2" N6 51.40 11.67 26.21 27

Tank 4 306 1/2" N6 51.40 11.67 26.21 27

Tank 5 265 1/2" N6 51.40 11.67 22.70 23

Tank 6 265 1/2" N6 51.40 11.67 22.70 23

Tank 7 119 1/2" N6 51.40 11.67 10.19 11

Tank 8 119 1/2" N6 51.40 11.67 10.19 11

Tank 9 84 1/2" N5 13.00 2.95 28.45 29

Tank 10 84 1/2" N5 13.00 2.95 28.45 29

Slop Tank 52 1/2" N3 7.35 1.67 31.15 32


ZONE A (SUB-TOTAL) M2

Gas Turbines 74 1/2" N4 29.50 6.70 11.01 12

Tank (2) 15 1/2" N1 7.35 1.67 9.05 10

Waste Water 47 1/2" N3 20.20 4.59 10.29 11


ZONE B (SUB-TOTAL) M2 136

Oil pump (3) & GA 135 1/2" N6 51.40 11.67 11.57 12

2
ZONE C (SUB-TOTAL) M 135

Modular Refinery & Pump 260 1/2" N6 51.40 11.67 22.27 23

Metering Station 31 1/2" N2 13.00 2.95 10.58 11

2
ZONE D (SUB-TOTAL) M 291

Security Accomodation 39 1/2" N2 13.00 2.95 13.33 14

Medical Bay 39 1/2" N2 13.00 2.95 13.33 14

Fire Station 57 1/2" N3 20.20 4.59 12.33 13


2
ZONE E (SUB-TOTAL) m 135

Lab and Office (2) 92 1/2" N5 40.40 9.18 9.97 10

Workshop 185 1/2" N6 51.40 11.67 15.80 16


2
ZONE F (SUB-TOTAL) M 276

Gantry 43 1/2" N3 20.20 4.59 9.43 10

Tank 8 1/2" N1 7.35 1.67 4.52 5

Parking Bay (2) 29 1/2" N2 13.00 2.95 9.93 10

Guard House (2) 5 1/2" N1 7.35 1.67 3.27 4


2
ZONE G (SUB-TOTAL) m 86

Kitchen 9 1/2" N1 7.35 1.67 5.13 6

Reception 31 1/2" N2 13.00 2.95 10.55 11

Admin Offices 202 1/2" N6 51.40 11.67 17.30 18


2
ZONE H (SUB-TOTAL) m 327
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 20 of 23

APPENDICES

APPENDIX A: Fire Water System Surface Area Calculation


APPLICATIO FLOW FLOW FLOW
Length- Breadth- AREA
EQUIPMENT NAME D/H 2 N RATE RATE RATE RATE
L (m) B (m) (m ) 2 3
(L/min/m ) (L/min) (m /hr) (gpm)

Gas Turbines 15 20 300.00 4.1 1230 74 325


Tank (2) 6.14 3.36 41.26 6.1 252 15 66
Waste Water 8 24 192.00 4.1 787 47 208
2
ZONE B (SUB-TOTAL) m 533 2269 136 599

Oil Pump (3)


GA Processing Plant
368.81 6.1 2250 135 594
Tank
Pump
2
ZONE C (SUB-TOTAL) m 368.81 2250 135 594

Modular Refinery
1,058.20 4.1 4339 260 1146
Pump
Metering Station 127.00 4.1 521 31 138
2
ZONE D (SUB-TOTAL) m 1,185 4859 292 1284

Security Acommodation 160.00 4.1 656 39 173


Medical Bay 160.00 4.1 656 39 173
Fire Station 230.00 4.1 943 57 249
2
ZONE E (SUB-TOTAL) m 550.00 2255 135 596

Lab and Office (2) 372.00 4.1 1525 92 403


Workshop 750.00 4.1 3075 185 812
2
ZONE F (SUB-TOTAL) m 1,122.00 4600 276 1215

Gantry 10.04 11.77 118.17 6.1 721 43 190


Tank 6.14 3.36 20.63 6.1 126 8 33
Parking Bay (2) 80.08 6.1 488 29 129
Guard House(2) 22.18 4.1 91 5 24
2
ZONE G (SUB-TOTAL) m 241.06 1426 86 377

Kitchen 6.75 5.16 34.83 4.1 143 9 38


Reception 14.29 8.86 126.61 4.1 519 31 137
Admin Offices 821.20 4.1 3367 202 890
2
ZONE H (SUB-TOTAL) m 982.64 4029 242 1064
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 21 of 23

APPENDIX B: Cooling Water And Foam Water Requirement


COOLING WATER REQUIREMENT
(shell and Roof of TANK on Fire and Adjacent TANK)
(See Ref. below ) SHELL ROOF TOTAL TOTAL TOTAL
AREA OF AREA OF TOTAL
THE TANK THE TANK AREA OF
S/N TANK TANK DIA. SHELL ROOF THE TANK APPLICATION RATE (SHELL) FLOW RATE FLOW RATE FLOW RATE FLOW RATE FLOW RATE
(m) (m 2 ) (m 2 ) (m 2 ) Lit/min/m 2 (linear circum.) Lit/min Lit/min Lit/min gpm m 3 /hr
1 Condensate Tank 1 14.89 346 174 520 6.5 1125 566 1691 447 101
2 Condensate Tank 2 14.89 346 174 520 6.5 1125 566 1691 447 101
3 Naphtha Tank 3 16.76 390 221 610 10.2 3974 1125 5099 1347 306
4 Naphtha Tank 4 16.76 390 221 610 6.5 2533 717 3250 859 195
5 AGO Tank 5 14.89 346 174 520 6.5 1125 566 1691 447 101
6 AGO Tank 6 14.89 346 174 520 6.5 1125 566 1691 447 101
7 DPK Tank 7 7.45 173 44 217 6.5 563 142 705 186 42
8 DPK Tank 8 7.45 173 44 217 6.5 563 142 705 186 42
9 HFO Tank 9 5.40 126 23 148 6.5 408 74 482 127 29
10 HFO Tank 10 5.40 126 23 148 6.5 408 74 482 127 29

SLOP TANKS
Slop Tank 11 5.40 126 23 4.1 257 47 304 80 18
Reference: IP Standard Part 19A.2.4.3.1 and A.2.4.3.2

REFERENCE:
1). Application rates: API 2030

ASSUMPTIONS:
1). No double jeopardy.
2). TANK 3 is on fire.
3). TANK 1,2,4,5,6,7 and 8 are adjacent tanks.
4). Half of adjacent TANK surface is exposed.

FOAM WATER REQUIREMENT FOR THE TANK ON FIRE AND SLOP TANK

(see References below)


S/N TANK TANK DIA. AREA OF TANK APPLICATION RATE(FOAM CHAMBERS) FLOW RATE FLOW RATE
(m) (m 2 ) Lit/min/m 2 Lit/min gpm
1Naphtha Tank 3 14.89 174.13 6.5 1131.86 299.04

2 Slop Tank 11 5.4 23 4.1 94 25

FOAM WATER REQUIREMENT FOR THE LOADING GANTRY


S/N LENGTH BREADTH AREA APPLICATION RATE (Ref. 2) FLOW RATEFLOW RATE
(m) (m) (m 2 ) Lit/min/m 2 Lit/min gpm

1 10.04 11.77 118 6.5 768 203

Notes:

1) Minimum application rate for hydrocarbon storage tanks = 4.1 L/min/m2. (Ref: NFPA 11, 1998; 3-2.4.3).

2). Minimum application rate for equipment in a deluge zone = 6.5 L/min/m2. (Ref: NFPA 16, 1999; 4-3.2)
3). Foam-water solution contains 3% foam and 97% water. (Ref: NFPA 11, 1998; 2-3.2.5).
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 22 of 23

APPENDIX C: Crude Storage Tanks Fire Water And Foam Demand Calculation
DETERMINATION OF MAXIMUM FIRE WATER DEMAND

(a) Water Demand For Cooling Adjacent Tanks and Foam Solution For Internal Tank Firefighting

Tank No Foam Water Cooling Water Requirement Requirement


Requirement (liters/min) per tank
(liters/min) Full Shell Half Shell Full Roof (liters/min)
Condensate Tank 1 - - 1,125 566 1,691
Naphtha Tank 3 1,131.86 3,974.26 - 1,125 6,231
Naphtha Tank 4 - - 2,533 717 3,250
Slop Tank 11 - - 47 74 121
Water demand
11293
Actual Total
water
demand: (litres/min) 11293

(gpm) 2984

3
(m /hr) 678 0.00

Approximated Total water demand (m 3 /hr) 678 0.00

Note 2 Approximated Total water storage (m 3 ) 2710

(b) Water Demand by Monitors and Hand Hoselines To Support Firefighting

Equipment Flowrate (m3/hr) Quantity Water Required (m 3/hr) gpm


Fixed Monitor 114.00 1 114.00 500.00
Hand Hoselines 23.00 1 23.00 100.00
Total 137 600
380
(m 3/hr) gpm
Overall Water Demand 678 2984
Approx. Overall Water
Demand for 1 hour (m3/hr) 678 2984
Approx. Overall Water
Demand per pump for @ 50%
capacity (m 3 /hr) 338.8 1492
Approx. Overall Water
Demand for 4HRS (m 3 ) 2710 11935 0
For Jockey pumps 1-2% of total
fire water demand 7 30

(m 3/hr) gpm
Pump Flowrate (m 3/hr)@100% 338.80 1491.83
Note 4,5 Selected Pump Rate (m 3/hr) 341.00 1500.00
(c) Foam concentrate requirement:
LOADING
Min. foam conc. reqmt. = actual foam solution flow rate X induction rate X operating time TANK AREA GANTRY
but, induction rate =
operating time = % 3 3
highest foam req. = min 55 10
Therefore minimum foam conc. reqmt lit/min 1225.76 768
Add a nominal 3% foam loss in line = litres 2,023 230
litres 2,083.18 237
m3 2.08 0.237
Notes: m3 3.00 1.00

1). For the purpose of foam system demand, the covered (internal) floating roof tank

shall be considered to a fixed-roof (cone) tank for the same diameter. (Ref: NFPA 11 pg.10 3-4.1.1

1). Reference to IP standard part 19 A 2.4.3.1 and 2.4.3.2

2). Design time for water supply = 4 hours (Minimum). Ref. NFPA 16; 3-2.3

3). Type I foam (according to tender document) discharge outlet requires 30 minutes discharge time.
NFPA 11, 3-2.3.2.2
4). As per NFPA 20
5). Selected pump is at 50% capacity
DUPORT Energy Park Project

DMCL-IES-DEP-PRO-CAL-00003 Rev. B

Fire Water Demand Calculation Report Page 23 of 23

APPENDIX D: BETE NOZZLE