Dated: 19th DEC 2019

Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

Technical Specification
For 11 KV SWITCH GEAR

NOIDA POWER COMPANY LIMITED

Document No. NPCL/TS/11KV/SWGR/VCB/12PB

Creation Date 19.12.2019 Revision Number 5

Patri Dileep
Created By No. Of Pages: 15
Deepak Mishra

Sanyog Raizada
Checked By
Ashish Ranjan

Sarnath Ganguly
(HOD- Operations)
Approved for Sarnath Ganguly
Approved By
Release By
Praveen Goyal
(HOD- Automation)
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

TECHNICAL SPECIFICATION - 11kV VCB SWITCHGEAR FOR


1250A OF ALL PANELS
The specification covers the Design, Manufacture, Assembly, Shop Testing, and Delivery at site
of 11kV switchgear. The 11kV, 1250A, 3 phases, 50 Hz Indoor type Free Standing, Floor
Mounted, Totally Enclosed, Single Copper Busbar, Fully Compartmentalized, Horizontal Draw
Out Type & fully interlocked Vacuum Circuit Breaker as per IEC 62271-100/200 and IS
13118. single break trip free breaker mounted on an integral truck carriage, fully interlocked
rack in & rack out mechanism, featured with mechanical ON & OFF Indicator with hand trip
device, Spring release coil, two nos. shunt trip coil, air insulated metal clad indoor Vacuum
Circuit Breaker as per IS 13118 (1991) and IEC- 60056 type switchgear shall be delivered
complete with all accessories, equipment instruments and wiring for making the equipment
complete and for warranting a trouble free and safe operation. All Breaker arms should be
completely insulated.

All the equipment shall be suitable for satisfactory operation in tropical climate and dry dust
laden atmosphere. The equipment shall be able to withstand wide range of temperature
variation.

All the parts / apparatus /equipment supplied shall comply in all respect with the
requirement of Indian Electricity Rule 1956, relevant IS and latest amendment thereof during
execution of contract where ever applicable. Panel should be fully compartmentalized sheet
steel enclosure floor mounting type with automatic safety shutters, independent pressure
discharge flaps along with shrinkable PVC sleeved 1250 Amps COPPER Busbar, foundation
bolts etc. with provision for termination of 2-nos. 3-core 300 Sq.mm XLPE cable using
heat shrinkable termination kits for outgoing panels & 3nos. 1 core 1000sqmm XLPE cable
using heat shrinkable termination kits for incomer panels. (Termination kits not in the scope
of supply), Gland plate of incomer panel should be of Aluminium metal.

Detailed Scope of Supply


Required Set of 12 Panel Indoor VCB Switch Board comprising of:
 Incoming Feeders (I/C) - 2 Nos.
 Outgoing feeder (O/G) - 8 Nos.
 Bus Coupler (B/C) -1 No.
 Bus Section / Adopter -1 No.

SCHEMATIC CONFIGURATION OF PANELS


Configuration:

O/G1 O/G2 O/G3 O/G4 I/C-1 B/ B/ I/C- O/G5 O/G6 O/G7 O/G8
C A 2
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

CODES AND STANDARDS


The switchgear shall comply, as a minimum requirement, with the IEC and IS publications.

RATING AND CHARACTERISTICS OF 11kV SWITCHGEAR

System Parameters

i. Rated voltage 11 kV (rms)


ii. Highest system voltage 12 kV (rms)
iii. Frequency 50 Hz±3%
iv. No. of phases 3
v. Neutral earthing Solidly earthed
vi. Normal Service Condition Indoor
vii. Temperature Min (-5deg. C, Max (50deg. C), Avg (40deg.
C)
viii. Degree of protection IP4X
ix Humidity Less than or equal to 95% (over 24hrs),
90% over 1 month
x Mechanical Endurance Above 30,000 operations
xi Earthing Low Resistance Earth Network

Circuit Breakers

i. Type of breaker Vacuum


ii. No of Poles 3
iii. Class Indoor
iv. Rated voltage 11 kV (rms)
v. Highest system voltage 12 kV (rms)
vi. Breaker Tripping time for both Less than 40 ms
trip coils
vii. Rated insulation level
a. Rated lightning impulse withstand 75 kV (peak)
voltage 1.2/50 us
b. Rated one minute power 28 kV (peak)
frequency withstand voltage
viii. Rated frequency 50 Hz
ix. Rated current 1250 A
x. Rated short circuit breaking 25 kA
current
xi. Duration of short circuit current 3 sec.
xii. First pole to clear factor 1.5
xiii. Rated transient recovery voltage 20.6 kV (peak) in 60 µs
for terminal faults
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

xiv. Rated short circuit making current 62.5kA peak

xv. Rated operating sequence O-0.3S-CO-3min-CO


xvi. Temperature rise over ambient As per IS 13118
temperature of 45 deg, C
xvii. Method of operation Electrically operated, spring stored energy
type with facility for emergency manual
charging
xviii. No. of free available auxiliary 6 NO and 6 NC contacts
switches
xix. Control voltage 110 V DC (variations 70% to 110%)
xx. Normal voltage for operating Single phase 50 Hz, 240 V(±10%) AC
mechanism i.e. charging motor
Current Transformers As per IS 2705

i. Rated system voltage 11kV


ii. Highest system voltage 12kV
iii. Type of supply and earthing Solidly earthed
conditions
iv. One minute power frequency 28 kV (rms)
withstand voltage
v. 1.2/50 µs impulse withstand 75 kV (peak)
voltage
vi. Frequency 50 Hz
vii. Short time thermal current and its 25 kA / 3 sec.
duration
viii. Temperature rise over an ambient As per IEC/IS 2705
temperature of 45 degree C

ix. CT Details
Incomer 1200/5-5-1A, Burden 15 VA, Class of
accuracy 0.5, 5P10,PS

Core-I (for Metering) Burden-15 VA, Class-0.5, ISF <5

Core-II (for Protection) Burden-15 VA, Class-5P10, ISF <5

Core-III (for Differential CL PS, VK>=300 V, RCT<=6 OHM,


Protection) Imag<=30 mA at VK/2; ISF <5
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

Bus Coupler 1200/5-5 A, Burden 15 VA, Class of


accuracy 0.5, 5P10

Core-I (for Metering) Burden-15 VA, Class-0.5, ISF <5

Core-II (for Protection) Burden-15 VA, Class-5P10, ISF <5

Outgoing
400-200/5-5A, Burden 15 VA, Class of
accuracy 0.5, 5P10
Core-I (for Metering)
Burden-15 VA, Class-0.5, ISF <5
Core-II (for Protection)
Burden-15 VA, Class-5P10, ISF <5

Voltage Transformers As per IS 3156

i. Rated system voltage 11kV


ii. Highest system voltage 12kV
iii. One minute power frequency 28kV (rms)
withstand voltage
iv. 1.2/50 µs impulse withstand 75kV (peak)
voltage
v. Type of supply and earthing 3 phase, star point solidly earthed
conditions
vi. Frequency 50 Hz

No. of phases 3
vii. Transformation ratio 11/√3 kV / 110/√3 Volt
viii. Rated Burden 100 VA
ix. Accuracy class 0.5
x. Winding connection Star

xi. Temperature rise over an ambient As per IEC and IS 3156


temperature of 45°C
xii. Rated voltage factor 1.2 times continuous
xiii. Winding connection
a. Primary Star
b. Secondary Star
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

Each panel shall be equipped and wired with the following equipment and to
be labelled accordingly:

1 Set Resin Cast CT: 1200/5-5-1 A for I/C


400-200/5-5 A for O/G
1200/5-5 A for B/C
Core 1: Class 0.5, Burden: 15 VA
Core 2: Class 5P10, Burden: 15 VA
Core 3: Class PS (for connection to both REF & Differential Protection) (For I/C Panel only)

1 Set. 3 phase Line PT with ratio of 11000V/√3 : 110V/√3, 100VA, CL 0.5 & , OVF 1.9 for 30
Sec. for metering & protection backed by HT & LT fuses connected on line side of the
each I/C.

1 No. MFM CL 0.5 3P4W with RS485 (SATEC PM 130EH: Ordering Code: PM130 EH+ -0-
5-0 3 Phase 4 wire, 110V AC L-L AC input, 5A Current input, 88-290VDC, RS485
comm., One pulsed output, Panel Gasket

1 No. 3 phase 4 wire DLMS supported, Electronic Trivector Meters (TVM) of 0.5 accuracy
class (Make: Secure, Model E3V055)

1 No. Test Terminal block for the MFM & TVM.

1 No. Test Terminal block for the Protection circuit.

1 No. Circuit Breaker control switch, T-N-C, spring return with pistol grip handle, 4 NO + 4
NC, rating 10 Amps.

8+3 Nos. LED (80-160V DC) type indicating lamps for the following indications in each panel:
1 No. Closing indication RED
1 No. Open indication GREEN
1 No. Spring charged indication BLUE
1 No. Auto Trip indication AMBER
2 No. Trip circuit healthy indication WHITE
(Associated with push button)
3 No. R, Y, B Phase indication at I/C
1 No. Breaker Test Position YELLOW
1 No. Breaker Service Position WHITE

Ferrule marking Guideline


Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

AC Circuit H1, H2, H3 .............


Metering Circuit D11,D31, D51 ..............
O/C and E/F protection circuit C11,C31,C51 ..................
REF/Differential protection
circuit A11,A31,A51 .........
Main DC distribution circuit J1,J2,J3 .............
Control and protection circuit K1,K2,K3 .................
Indication and annunciation
circuit L1,L2,L3 ................
Motor circuit M1,M2,M3 ................
PT circuit E11,E31,E51 .............
Spare contact circuit U1,U2,U3 .................
Printed type indicating both ends (one
Ferrule type additional red colour ferrule for all
wires in trip circuit)
Tinned copper, pre-insulated, fork type
Lugs
and pin type as applicable.
Spare contacts of relays Wired up to the terminal blocks

Wiring enclosure Plastic channels, All control cables shall


be of FRLS type.

IEC61850 complaint Protection relay for substation Automation system:

It is intended to automate the Switchgears specified in the scope of supply and use
communicable numeric relays for Protection, Control and Status monitoring. This
specification is based on the understanding that an integrated Automation System along
with protections shall be provided and same shall have provisions for Integration with
SCADA system. All the feeders shall be remote controlled from Employer’s SCADA and from
the local console of the numerical relays. Relay should be IEC 61850 compliant.
Conformance test certificate by KEMA shall be submitted along with Techno-
commercial bid & PICS,MICS , SCD file & PIXIT documents for relay shall be
provided by vendor before the FAT in soft copy.

Processor feature:
Relay shall be completely Numerical with protective elements having software algorithm
based on sampling of analog inputs. Sampling rate of analog signal: The sampling rate
should be 1000 Hz for 50 Hz signal or better for each analog channel. Hardware based
measurements shall not be acceptable.

Memory and Recording Feature:


Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

1. The relay setting and programming should be stored in EEPROM so that during Aux.
Power failure the said data is not lost.
2. Relay should have event log, trip log and DR record. All logs should go in to history.
3. All tripping of relay should initiate DR in auto without extra binary input. Triggering of
DR with binary input should be user configurable.
4. The last 5 fault DR records should be in flash memory and DR will not erase in case of DC
supply fail for more than 2 days.
5. Should be able to record at least 8 Oscillographic disturbances and 8 fault records and
200 event records.
6. Minimum Four no. of latest trip log with cause of trip should be stored in memory along
with date and time stamping. The memory should not be lost with the switching off of DC.
7. The relay should have fault-recording feature with current waveform and Digital Input
status. The fault waveform should consist of minimum four current waveforms of three
phase current and zero sequence current and DI status. Triggering time for Pre and Post
should have user selectable. This record should be in flash memory for minimum 7 days
even after switching off the DC supply.
8. The fault should be date and time stamped.
9. Communication protocol shall be IEC61850.

Output Relays for Numerical Relay:


1. All o/p contact should be freely programmable.
2. At least 4 nos. programmable contacts are required for close and open operation. Rest
of the contacts may be changeover type.
3. Rating of trip contacts:-
 Contact durability> 20K operation.
 15Amp make and carry for 3 sec for trip contact.
 Make and carry for trip contacts L/R<=40ms.

Rating of Alarm contacts:-


5 Amp make and carry continuously for 5 sec.
Measurement & setting of Output relays through keypad on relay fascia and relay HMI
software. Output relay dwell time shall be user programmable or fixed at 100ms.

Communication Port:
Three number of RJ45 port with IEC 61850 protocol having two nos. of IEC 61850 protocol
compliant Ethernet RJ45 port for communication with SCADA system through two managed
Ethernet Switches operating in redundant mode and one nos. of Front port Ethernet
RJ45/USB 2.0/USB 3.0 for relay parameterization and configuration etc. with the help of PC.
The communication shall be made in 1+1 mode between individual IED to Switch, such that
failure of one set of LAN shall not affect the normal operation of SCADA. However, it shall be
alarmed in SCADA. Two nos. of rear port Ethernet RJ45/USB 2.0/USB 3.0 for relay
goosing, communication and HMI etc. With the help of IEC 61850 relay should generate
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

GOOSE message as per IEC 61850 standard for interlocking and also ensure interoperability
with third party relays.

Watchdog and self-monitoring:


The relay should have facility to monitor the healthiness of its circuits and components by
own monitoring system. In case of any problems, the alarm should be generated by one of
the output contacts. The alarm as soft signal to be sent to SCADA system as well.
Necessary support documentation explaining the self-diagnostic feature shall be furnished.
Date and Time stamping with faults and record. The clock should be powered from internal
cell and Should not require setting after every DC switching. The internal cell life minimum
5 years. Time Synchronization by SNTP For time synchronization through SNTP is to be
provided from clock signal coming from RTU.

Relay & Switch Architecture

Documentation:

1. Manuals, Drawings and Literature for Protection Relay:


I. Configuration manual, User manual and operating manual shall be provided with
dispatch of panel.
II. All the internal drawings indicating the logics and block diagram details
explaining principle of operation should be provided with the dispatch of the
panel.
III. Mapping details shall be submitted in IEC format.
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

IV. GOOSE Details, Drawings with logic diagram shall be provided during FAT.

2. Standard documentation, file per Relay, according to IEC 61850 during FAT and SAT:
I. MICS document (model implementation conformance statement).
II. PICS (protocol implementation conformance statement).
III. PIXIT document.
IV. ICD file
V. CID file
3. Man Machine Interface:

I. Basic application software for setting change, parameterization.


II. CD with software (licensed) to download disturbance recorder, event log and
evaluation of those records. Graphical configuration tool for I/P, O/P and
functional building block for protection and control. Cable for connection of Relay
to laptop (USB port).
III. It shall be possible to transfer the data stored in the DFR to computer on
IEEE/COMTRAD format. The data format shall be compatible for dynamic
protection relay testing on relay test kit. COMTRADE Data viewer software is to
be provided.
IV. Remote Configuration software with latest version on the CD with license if
applicable.
V. Relay Connectivity package and other necessary supporting software.

SCADA signals mentioned below shall be available in SCADA T.B.s with ferruling. Remote
control & trip shall be possible through NPCL RTU using the T.B. s contacts with the
conditions mentioned below.

Monitoring from remote:

Signals provided in SCADA T.B.s to monitor the following conditions and status of VCB (at
SCADA Control Centre end through installing RTU).
I. Local/Remote switch position status.
II. PT healthy status.
III. Anti-pumping relay operated status.
IV. Master trip relay operated status.
V. Breaker in service/test position.
VI. C.B. Door Open/Close status.
VII. Panel Door Open/close status.

Closing from Remote:

Suitable arrangement should be provided at SCADA T.B.s to close the breaker from remote
end in case following Conditions are satisfied:-
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

I. DC healthy.
II. Breaker is OFF.
III. Spring for closing mechanism is charged.
IV. Breaker is in Remote.
V. Trip Circuit healthy.
VI. Breaker is not anti-pumping.

Tripping from Remote:

Suitable arrangement should be provided at SCADA T.B.s to trip the breaker from remote
end in case the breaker is ON and certain pre-set conditions to be satisfied.

Important notes:

1. Anti-pumping should be an integral feature of the VCB & should be achieved through
a contactor mounted inside the VCB.
2. The Limit Switch for Test & Service Positions shall have 4NO contacts for each for
Test & Service position.
3. For Numerical Relays, MLFB/order code no. shall be specified during drawing
approval.
4. All other component like name plates, MCBs(fuse not required), terminal blocks,
cable glands, space heater, hooter etc. are required for satisfactory operation, shall
be deemed to been included in the quoted price.
5. SCADA, Metering & protection T.B.s shall be separate & clearly label.
6. The Switch Board shall be painted with RAL 7032 - Pebble Grey
7. For PT manual change over switch and scheme provided in each incomer panel
8. All the wiring for SCADA control & status through relay needs to be shown at the
time of drawing approval.
9. No. of DI & DO of Numerical relay should be mentioned at the time of quotation
submission
10. Vendor has to submit panel mechanical design parameters at the time of drawing
approval.
11. Control operating voltage is 110 V DC.
12. For DI&DO and LED Indication please refer DI&DO & LED Indication sheet.
13. Relay base file should be submitted along with as built drawings.
14. During relay programming, all the protection signals, alarms signals, trip signals & Status
shall be configured in Datasets under “Reports & Logs” blocks.

FOR INCOMER & OUTGOING PANELS

1 No. Triple / Four pole IDMT non-directional/Directional over Current & Earth
Fault 5/1 Amp. Numerical Communicable Relay (ABB & Siemens Make relay)
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

conforming to latest communication protocol IEC 61850 with high set


instantaneous features for feeder protection (S/R Contacts) with Voltage
Input. Directional protection is required for Incomer panel only (minimum
16 DI & 10 DO should be available in relay, it may be increased at the time of
drawing/designing)

11kV IC:

DI SIGNAL DESCRIPTION D0 SIGNAL DESCRIPTION


1 BKR ON/ 1 BKR CLOSE
2 BKR OFF
3 SPR CHARGE 2 BKR TRIP
4 TRIP CIRCUIT PRE SUPEVISION 3 MASTER TRIP
TRIP CIRCUIT POST
5 SUPERVISION 4 CLOSING CIRCUIT
6 LOCAL Operation Indication 5 INTERNAL RELAY FAULT
7 REMOTE Operation Indication 6 SCADA CLOSE
8 PT MCCB Trip 7 SCADA TRIP
TRIP CIRCUIT-1
9 DC fail 8 HEALTHY
TRIP CIRCUIT-1
10 BREAKER IN TEST POSITION 9 HEALTHY
11 BREAKER IN SERVICE POSITION 10 PT UNHEALTHY
12 INC AS OG 11 SPARE
13 INC -I/INC II OFF
14 MASTER OPRATED
15 SPARE
16 SPARE

11kV OG:

DI SIGNAL DESCRIPTION D0 SIGNAL DESCR


1 BKR ON/OFF 1 BKR CLOSE
2 SPR CHARGE 2 BKR TRIP
3 TRIP CIRCUIT PRE SUPEVISION 3 MASTER TRIP
TRIP CIRCUIT POST
4 SUPERVISION 4 CLOSING CIRCUIT
5 LOCAL Operation Indication 5 INTERNAL RELAY FAULT
6 REMOTE Operation Indication 6 SCADA CLOSE
7 DC fail 7 SCADA TRIP
TRIP CIRCUIT-1
8 BREAKER IN TEST POSITION 8 HEALTHY
TRIP CIRCUIT-1
9 BREAKER IN SERVICE POSITION 9 HEALTHY
10 SPARE 10 PT UNHEALTHY
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

11 SPARE

FOR BUSCOUPLER PANEL


Triple / Four pole IDMT non-directional Over Current & Earth Fault 5/1 Amp.
Numerical Communicable Relay (ABB & Siemens Make relay) with sync check facility
conforming to latest communication protocol IEC 61850 with high set instantaneous
features for feeder protection (S/R Contacts). (Minimum 16 DI & 10 DO should be
available in relay, it may be increased at the time of drawing/designing)

11kV BC:

DI SIGNAL DESCRIPTION D0 SIGNAL DESCR


1 BKR ON/OFF 1 BKR CLOSE
2 SPR CHARGE 2 BKR TRIP
3 TRIP CIRCUIT PRE SUPEVISION 3 MASTER TRIP
TRIP CIRCUIT POST
4 SUPERVISION 4 CLOSING CIRCUIT
5 LOCAL Operation Indication 5 INTERNAL RELAY FAULT
6 REMOTE Operation Indication 6 SCADA CLOSE
7 DC fail 7 SCADA TRIP
TRIP CIRCUIT-1
8 BREAKER IN TEST POSITION 8 HEALTHY
TRIP CIRCUIT-1
9 BREAKER IN SERVICE POSITION 9 HEALTHY
10 Incomer 1 PT supply fail 10 PT UNHEALTHY
11 Incomer 2 PT supply fail 11 SPARE
12 SPARE
13 SPARE

Note:
For remote control we need CB closing & tripping from relay and also spare contacts of closing
and tripping contacts should be terminated in “SCADA terminal block” that means we need both
options for remote control, from relay and external DI/DO card. External DI/DO card is not in the
scope of switchgear manufacturer. It is required for redundancy purpose for remote controlling.
Relay Setting Software (compatible with Windows 7 or latest) & Communication cable (for laptop
to relay) for uploading & downloading relay parameterization & downloading of disturbance
records shall be supplied along with the relay.
Soft logic should be configured in relays in both local and remote selection with closing and
tripping operation.
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

1 No. Master Trip Relay, Contacts: 3 N/O + 1 N/C; S/R contacts and H/R flags. With pickup
time less than 10 ms and one spare contact.

1 No. Trip Circuit Supervision Relay for continuous supervision of tripping circuit,
Contacts: 2 N/O + 2 N/C (If two nos. of TCS relay is not inbuilt in relay)
As required. DC operated Contact Multiplication Relays: Contact: 3 C/O
1 No. 15A, 230V, 3 pin plug & socket and MCB
2 No. Heater with Humidistat should be used in Cable and VCB Chamber.
1 No Milli Amp meter for heating circuit
1 No. Cubicle illumination lamp (CFL) (Enclosed type)
1 No. Emergency Mechanical ON-OFF push button
1 each PT selector Switch in all panel & with PT fuse failure relay with hooter in Adaptor.
1 No. Local & Remote Selector Switch
1 No. Normal/Parallel selector Switch
12 No. Rack IN Rack OUT handle & Key for each Panel
(12 No. for 12 Panel board X 1 set)
2 No. Breaker handling trolley with each set/location of each type.
(If trolley is mounted with breaker then it is not necessary) 2 no. with each set of
each type.
2 No. Ethernet switch Industrial grade L2 managed with IEC 61850/IEEE 1613 Class 1
Compliant
1 No. PT rack out trolley.
1 No. wall mounted tools handling box.
2 No. Fiber glass slot on front and back side of the panel with min. dimension of
85mm*130mm shall be provided for feeder naming.

Specification for Industrial Grade L2 managed Switch:

1. Ethernet switches used in substation automation applications should comply with IEC
61850-3 Standards for EMI immunity and environmental requirements to ensure reliable
operation of networking equipment in substation environments.

2. Ethernet network will be involved in critical protection functions the Ethernet switches
should comply with the Class 2 device definition given in IEEE P1613 (i.e. error free
communications during the application EMI immunity type tests )

3. Managed Ethernet switches with advanced Layer 2 features such as:


 IEEE 802.3 Full-Duplex operation (no collisions)
 IEEE 802.1p Priority Queuing
 IEEE 802.1Q VLAN
 IEEE 802.1w Rapid Spanning Tree
 GMP Snooping / Multicast Filtering
Should be used to ensure real-time deterministic performance.
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

4. Should Support a variety of flexible network architectures offering different levels of


performance, cost and redundancy are achievable using managed Ethernet switches.

5. Switching: Non-blocking, store and forward switching

6. Protocols: IGMPv1/v2, GMRP, GVRP, SNMPv1/v2c/v3, DHCP Server/Client, DHCP, BootP,


TFTP, SNTP, SMTP, RARP, RMON, HTTP, HTTPS, Telnet, SSH, Ethernet/IP, SNMP, LLDP, NTP
Server/Client

7. Switch should be Rugged, fully managed, Modular Ethernet switch specifically designed to
operate reliably in electrically harsh and climatically demanding Electric substation and
industrial environments.

8. Web browser interface and console interface

9. Operating Temperature: (-40°C to +70°C) operating temperature (no fans)

10. Ingress Protection: IP40

11. Cyber security requirements: The supplier has to abide by all guidelines/notifications as
relevant to supplied system as issued by CERT-D, NCIIPC and ministry of power during the
entire warranty period. For meeting such requirements, the supplier may have to upgrade
the system components via. Updates for system software, enabling/disabling
ports/functions as recommended by NPCL

12. power inputs: (88 to 300 VDC,)

11kV Port 1. 18 X 10/100 Mbps Quantity Redundanc


Switchgears s TX RJ45 Ethernet 2 Nos. y
copper ports and 2 Goosing
X 1000 Mbps ports
(for Uplink)

Make: Moxa/ Kyland/ Ruggedcom with KEMA Certified.

Factory Acceptance test:


FAT consists of following:
1. Mechanical Closing & Opening (5 times each)
2. Measurement of resistance in main circuit
3. 2 kV test on Main & Aux Circuit
4. Electrical Functional Test
5. HV test
6. Primary injection test up to rated capacity of CT for all panels
7. Paint thickness & panel measurement.
8. Goose Testing without inter-panel wiring
9. Breaker tripping time.
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

Guarantee period: 5 Years+

Commissioning support:

The supervision and commissioning support for 7 man days shall be provided by the vendor free of
cost at the time of installation for each set of Panel. If required vender should provide IED
interoperability communication setup and testing between 3rd party numerical relay.

MANDATORY SPARES:

Sl. No. Materials Qty. UOM

1 Tripping Coil 110V DC 0 No.


2 Closing Coil 110V DC 0 No.
3 TNC Switch 0 No.
4 Master Trip Relay (S/R contact H/R contact) 0 No.
5 LED Lamp( all Colour) 0 each
6 Spring charging Motor 0 No.
7 Breaker Tulip Contact 0 No.
8 Breaker Pole 0 No.
9 Breaker Mechanism (internal) 0 No.
10 Complete Circuit Breaker trolley 0 No.
11 Breaker RACK IN & RACK OUT Mechanism 0 No.
12 Multi Core Resin Cast CT with ratio: 400-200/5-5A, 15
VA per phase25 kA for 3 Sec
0
1st Core: CL0.5
2ndCore:CL5P10 No.
13 Multi Core Resin Cast CT with ratio: 1200/5-5-1A, 15
VA per phase,25 kA for 3 Sec
1st Core: CL0.5
0
2ndCore:CL5P10
3rd Core: CLPS ,VK>=300 V, RCT<=6 OHM, Imag
<=30 mA at VK/2; ISF <5 No.
14 Multi Core Resin Cast CT with ratio: 900-450/5-5-1A,
15 VA per phase,25 kA for 3 Sec
1st Core: CL0.5
0
2ndCore:CL5P10
3rd Core:CLPS ,VK>=300 V, RCT<=6 OHM,Imag<=30
mA at VK/2; ISF <5 No.
15 Multi Core Resin Cast CT with ratio: 900/5-5-1A, 15 VA
per phase,25 kA for 3 Sec
1st Core: CL0.5
0
2ndCore:CL5P10
3rd Core:CLPS ,VK>=300 V, RCT<=6 OHM,Imag<=30
mA at VK/2; ISF <5 No.
16 3 phase PT with ratio 11000/√3/ 110/√3, 0 No.
Dated: 19th DEC 2019
Technical Specification for 11 kV Switchgear Doc. No.: NPCL/TS/11kV/SWGR/VCB/12PB

100VA/Phase, CL 0.5 & 3P, OVF 1.9 for 30 Sec. for


metering & protection backed by HT & LT fuses.
17 Breaker Handling Trolley (if it is not integrated with
0
CB) No.
18 Limit Switch (all types) 0 each
19 "C" type clip 0 No.
20 "M" Type Clip 0 No.
21 Roller 0 No.
22 Counter 0 No.
23 Auxiliary relay/switches (all types) 0 each
24 PT Selector Switch 0 No.
25 IC/OG Switch 0 No.
26 Relevant Loose Nuts, Bolts, washer etc. 0 each
27 Rectifiers for Sp. Ch. Motor 0 No.
28 Carbon Brush for Motor 0 No.
29 Contactors 0 No.
30 Door Locks(all types)+ Keys 0 each
31 Protection Relays REF-615/7SJ61/7SJ80( 1 FOR 11kV
0 No.
IC, 1 FOR 11kV OG & 1 FOR BC)
32 Protection Relays RET-615-HBTBBABANBA1BNN1XD
0 No.
for 33/11kV 12.5 MVA transformer

--------END-------