Академический Документы
Профессиональный Документы
Культура Документы
Reference No:
Fire and Jockey Pump Installation SIP-FP-0001
VER 001INSTRUCTION PROCESS
SITE Page of 12 SIP-FP-0001
1.0 Introduction
2.0 Purpose
3.0 Scope
4.0 Application
5.0 Materials/ Equipment
6.0 Procedure
7.0 Points to Note
8.0 References
1.0 INTRODUCTION
A fire pump is designed to increase water pressure. The pump intake and discharge piping must be
capable of flowing the required volume to which the pump will add the needed pressure for fire
protection. The pump can be started manually, but is usually arranged to start automatically upon a
drop in system pressure or the activation of a fire suppression system.
A Jockey pump is a small pump connected to a fire sprinkler system and is intended to maintain
pressure in a fire protection piping system to an artificially high level so that the operation of a single
fire sprinkler will cause a pressure drop which will be sensed by the fire pump automatic controller,
causing the fire pump to start. Jockey pumps should be sized for 3% of the flow of the main fire pump
and to provide 10psi more pressure than the main fire pump.
2.0 PURPOSE
Fire pumps are needed for main reason; to protect lives & properties against fire by supplying adequate
water supply to automatic sprinklers or standpipe systems. To meet building codes & insurance
requirements.
3.0 SCOPE
Provide a complete fire pumps system as defined by the latest edition of NFPA20.
4.0 APPLICATION
Fire pumps are powered by an electric motor or diesel engine. The sprinkler system pressure drops
significantly when one or more fire sprinklers are activated or alternatively when other firefighting
connections are opened, causing a pressure drop.
2. Storage Warehouse:
Large expanses of space have higher water pressure demands if a fire begins to spread. Warehouse
is a prime example because they don’t have walls or doors to slow the fire as its spread.
Listing Authorities;
1. Underwriters Laboratories (UL)
2. Factory Mutual Research Corporation (FM)
Jockey Pump
6. PROCEDURE
A. Site planning
Receiving: Upon receiving the pump, it should be inspected for damage or shortages. If damage
has occurred, file a claim immediately with the company that delivered the pump. If the manual
is removed from the crating, do not lose or misplace.
B. Preparation
2. Installation
Eccentric Reducer
Suction Pipe
Foot Valve
Concentric Reducer
Gate Valve
3. Field Alignment
6. POINTS TO NOTE
8. REFERENCES
Installation and operation manual centrifugal Pumps by Weinman.
Installation and operating manual for fire pumps by Armstrong.
NFPA-20 Standard for the installation of stationary Pumps for Fire Protection.
Fire Pump System in NFPA 20 Standard - ETNA
https://maker.pro/custom/tutorial/the-basic-mechanical-tools-you-need-for-your-workshop