Service Entrance Computation

General Lighting Load and general use receptacle

150 sq.m X 24 W/sq.m = 3,600 W

Air Conditioning Load

{ [ (10 X 7) + 6.10] + (0.25 X 10) } X 230 = 18,078 W

Range Load

One 5 kW range at 80% DF = 5,000 X 0.8 = 4,000 W

Other Loads

One 9 kW Refrigerator = 900 W

Applying demand Factor (DF) for other loads

900 W X 40% DF = 900 X 0.4 = 360 W

Total Computed Load

18,078 + 4,000 + 900 + 360 = 23,338 W

Total Computed Current

23,338 W/ 230 V = 101.47 A

Service entrance conductor

Use 3.5 mm2 THW in 20 mm diameter PVC

Service Equipment

A. Maximum Current Rating of Protective Device, with

1. Non-Time Delay Fuse

[18,078 + 1785 +360 + 300%(10X230) + (10 X 230)] / 230 = 111.29 A

2. Inverse-Time Circuit Breaker

[18,078 + 1785 + 360 + 250%(10X230) + (10 X 230)] / 230 = 132.58 A

B. Service Equipment Rating in case of undergrounded service

1. Use one 50 AT,2PST, 250 V safety switch with two 100 A renewable fuses or

2. Use one 30 AT, 2 poles, 240 V, molded case circuit breaker


Branch Circuit Computation
`
Branch Circuit no. 1
 Type of Load: Lightings
 No. of Outlets: 13
 Wattage: 1300 W
 Branch Current: 1300W/230V=5.65A
 Size of wire:2-3.5 mm2 THW
 Size of Conduct: 20mm diameter PVC
 Size of Overprotective Device: Use 20 A circuit breaker
Branch Circuit no. 2
 Type of Load: Lightings
 No. of Outlets: 12
 Wattage: 1200 W
 Branch Current: 1200W/230V= 5.22A
 Size of wire: 2-3.5mm2 THW
 Size of Conduct: 20mm diameter PVC
 Size of Overprotective Device: Use 20 A circuit breaker
Branch Circuit no. 3
 Type of Load: Convenience Outlet
 No. of Outlets: 9
 Wattage: 1620W
 Branch Current: 1620W/230V= 7.04 A
 Size of wire: 2-3.5 mm2 THW
 Size of Conduct: 20mm PVC
 Size of Overprotective Device: Use 20 A circuit breaker
Branch Circuit no. 4
 Type of Load: Convenience Outlet
 No. of Outlets: 9
 Wattage: 1620W
 Branch Current: 1620W/230V=7.04A
 Size of wire:2-3.5 mm2 THW
 Size of Conduct: 20mm PVC
 Size of Overprotective Device: Use 30 A circuit breaker

Branch Circuit no. 5


 Type of Load: Refrigerator
 No. of Outlets:1
 Wattage:1500W
 Branch Current: 1500W/230V=6.52A
 Size of wire:2-3.5 mm2 THW
 Size of Conduct:20mm diameter PVC
 Size of Overprotective Device: Use 20 A circuit breaker
Branch Circuit no. 6
 Type of Load: Range
 No. of Outlets: 1
 Wattage: 8000W
 Branch Current: 8000W/230V=34.78A
 Size of wire: 2-8.0mm2 THW
 Size of Conduct: 25 mm diameter PVC
 Size of Overprotective Device: Use 50 A circuit breaker
Branch Circuit no. 7
 Type of Load: Aircon 1HP
 No. of Outlets: 1
 Wattage: 1840W
 Branch Current: 1840W/230V=8A
 Size of wire: 2-3.5mm2THW
 Size of Conduct: 20 mm diameter PVC
 Size of Overprotective Device: Use 20 A circuit breaker
Branch Circuit no. 8
 Type of Load: Aircon 1HP
 No. of Outlets: 1
 Wattage: 1840W
 Branch Current: 1840W/230V=8A
 Size of wire: 2-3.5mm2 THW
 Size of Conduct: 20 mm diameter PVC
 Size of Overprotective Device: Use 20 A circuit breaker
Branch Circuit no. 9
 Type of Load: Aircon 1HP
 No. of Outlets: 1
 Wattage: 1840W
 Branch Current: 1840W/230V=8A
 Size of wire: 2-3.5mm2 THW
 Size of Conduct: 20 mm diameter PVC
 Size of Overprotective Device: Use 20 A circuit breaker
Branch Circuit no. 10
 Type of Load: Aircon 1HP
 No. of Outlets: 1
 Wattage: 1840W
 Branch Current: 1840W/230V=8A
 Size of wire: 2-3.5mm2 THW
 Size of Conduct: 20 mm diameter PVC
 Size of Overprotective Device: Use 20 A circuit breaker
MAPUA UNIVERSITY
SCHOOL OF ELECTRICAL, ELECTRONICS
and COMPUTER ENGINEERING
EE DEPARTMENT

EE24-E17
RESIDENTIAL ELECTRICAL SYSTEMS DESIGN

TOLENTINO, Paul Diony S.


January 24, 2020
Rating