Abstract – Harmonic currents, generated by non-linear wattmeter accuracy, will, in reality, produce an error of
electronic loads, produce ‘penalty losses’ in every element of ±1.5%,when measuring the efficiency of a transformer under
an electrical distribution system.[1] These harmonic-related linear or nonlinear loading. As a result, their claimed efficiency
losses reduce system efficiency, cause apparatus overheating, of 98%, for a 75kVA transformer, may, in fact, be only 96.5%.
and increase power and air conditioning costs.[2] Harmonic
II. TRANSFORMER LOSSES
currents effectively de-rate existing systems and, when
accommodated, add substantially to the capital cost of new Harmonic voltages and currents increase transformer losses.
distribution systems. The measurement and evaluation of More specifically, harmonic voltages increase losses in its
transformer losses under linear and non-linear load conditions magnetic core while harmonic currents increase losses in its
will be discussed. In addition, typical financial benefits that windings and structure. The effect of harmonic voltages is
result from the application of high efficiency harmonic relatively small since losses in the magnetic core are normally
mitigating distribution transformers, under non-linear loading, only 10% of the winding losses. A transformer’s penalty losses
will be calculated. are mainly due to harmonic currents. Unfortunately, harmonics
currents are typically much higher in 120/208-volt subsystems.
Index Terms – efficiency, harmonics, non-linear load, penalty
Transformers operating at these voltage levels require special
losses, transformer losses
consideration.
I. INTRODUCTION
IEEE STD 57.12.90 and IEEE STD 57.12.91 categorize
Existing Standards – The highest standards for transformer transformer losses as No-Load Losses (PNL) or Excitation
efficiency in North American are found in NEMA Standard Losses and Load Losses (PLL) or Impedance Losses. The sum
Publication TP1-2002,[3] CSA Publication C802.2-00 and of these losses is referred to as Total Losses (PLOSS):
EPA’s Energy Star requirements. The measurement and
calculation methods required by these standards accurately PLOSS PNL PLL (1)
determine a transformer’s losses and energy efficiency, when it Excitation Losses[4] are primarily losses in the magnetic
supplies linear resistive and/or inductive loads. core and are due to magnetic hysteresis and eddy currents.
The Non-Linear Load Reality – Modern electrical Load Losses are divided into I2R Losses and Stray Losses. I2R
distribution systems typically supply a high percentage of Losses can be obtained, as follows:
nonlinear electronic loads, particularly in 120/208-volt systems. h h max
I
2
As a result, transformer losses increase and energy efficiency I 2R h Rh (2)
decrease. The level of deterioration is a function of harmonic h 1
voltage magnitudes at a transformer’s primary terminals, load-
Eddy-currents, which produce stray electromagnetic flux in
generated harmonic current magnitudes at its secondary
the transformer’s windings, magnetic core, core clamps,
terminals and their phase relationships. There are,
enclosure and other structural parts, cause Stray Losses. With
unfortunately, no recognized standards for determining
high harmonic currents, the Eddy-Current Losses in the
transformer losses or efficiency under these nonlinear
windings are the most dominant losses in the transformer. Total
conditions.
Stray Losses (PS) are proportional to the product of
Misleading Claims – A number of high efficiency Fundamental Stray Losses (PS1) and the square of the product
distribution transformer manufacturers now claim efficiencies of the harmonic currents and their corresponding frequencies,
that meet or exceed the requirements of NEMA TP1-2002 and as follows:
CSA C802.2-00 under severe but unspecified nonlinear h hamx
loading. Several manufacturers have even published their
efficiency test methods. At best, these claims are misleading
PS PS 1 I
h 1
h
2
h2 (3)
2
*
1p i2/K i1 v = v1/K-v2 it is possible to separately measure the core and copper losses
2p
of the transformer. Measurement under nonlinear load
*
i = i1-i2 / K i2 conditions is also possible.
TRANSFORMER
v1 Kt = N1/N2 v2 v1/K To evaluate the new measuring method, using the proposed
connection diagram in Figure 4, we analyze the same example
evaluated with the conventional measuring approach, with
1p' 2p' standard Metering Class CTs and VTs, and specially design
differential CTs and VTs. The instrumentation is summarized
A Transformer as a Two-Port Network in Table 2.
Figure 3
Instruments Full Scale Full Scale Error
Average power for some period of time T can be expressed
by: VT1 480/120 0.360
1
T
1
T VT2 120/120 0.360
T 0
PLm (i1 i2 / K)v1dt (v1 / K v2 )i2dt Pm' Pm" (7) CT1 5/5 0.015
T0
CT2 225/5 0.015
Equation (6) is valid for any constant K . Based on this V1 120 0.120
formulation, a new measuring method is presented, with the
connection diagram shown in Figure 4. V2 120 0.120
A1 1 0.001
This method also requires two wattmeters, or two sets of
voltmeters and ammeters. One set for a full range of voltages A2 1 0.001
and small currents and the other set for small voltages and full Table 2
range of currents. Physical interpretation of this method can be
explained using Figure 4. Exciting current error is:
(i1 i 2' ) CT 1 A1
INPUT i1 i 2'
A2
OUTPUT
0.0016
A2 (i1 i 2' ) (i1 i 2' ) / 20
i1-i2' A1
Input Voltage is measured with the error:
CT 1 CT 2
v1 VT 1 V 1
i1
i2
0.0017
v1 v1
v1 TESTING
TRANSFORMER v2
v1 TRNASFORMER VT 2 The core losses are measured with the error:
VT 1 PFe v1 (i1 i2' )
0.0033
v2 PFe v1 (i1 i2' )
v1-v2' The series voltage drop is measured with the error:
Connection Diagram for a Single-Phase Transformer (v1 v 2 ) VT 2 V 2
0.0068
Figure 4 (v1 v 2' ) (v1 v 2' )
Based on the diagram as shown in Figure 4. Output current is measured with error:
i 2' CT 2 A 2
T T T 0.0079
1 1 1 '
i2 i2' / 20
P (i1 i2 / Kt )v1dt i0v1Adt i0vABdt
'
m (8)
T0 T0 T0 The copper losses are measured with the error:
PCu i2' (v1 v 2' )
The Pm' term corresponds to the losses due to the circulation ' 0.014
PCu i2 (v1 v 2' )
of magnetizing current in the primary added to magnetic core The core losses are measured with the error:
losses. That is equivalent to the transformer open circuit test.
PFe v1 (i1 i2' )
Second term Pm" is: 0.0033
PFe v1 (i1 i2' )
T T T
1 1 1 The total losses are measured with the error:
T 0
Pm" (v1 v 2 K t )i2 dt i21v1 A dt i21v AC dt (9)
T 0 T 0 PLoss Pcu PFe
0.013 1.3%
PLoss PLoss
Equation (9) represents the sum of the losses in the primary
and secondary of the transformer, due to load current, which is The efficiency measurement error is:
eff 0.033%
equivalent to a transformer short-circuit test. With this method,
3
IV. EVALUATION OF LOSSES AND MEASUREMENT
Based on the presented two measurement methods, we will plot
the losses and efficiency for both methods. Figures 5a and 5b -------------- V & C Difference ‘Plus’ & ‘Minus’ Error
present Losses (kW) vs. Load (pu) while Figures 6a and 6b
--------------- Power-In – Power-Out ‘Minus’ Error
present Efficiency (pu) vs. Load (pu).
4
[3] NEMA Standard Publication TP1-2002, ‘Guide for experience includes employment with ABB T&D, South
Determining Energy Efficiency for Distribution Transformers.’ Africa, Instrument Transformers, Inc., USA, and Phasetronics,
Inc., USA. Mr. Damnjanovic joined Power Quality
[4] IEEE Standard C57.12.91-1995, ‘Test Code for Dry-
International, Inc., USA, in 2002, as its Vice-President,
Type Distribution Power Transformers.’
Engineering. His research interests include electromagnetics,
[5] NEMA Standard Publication TP2-1998, ‘Standard Test power system modeling, analysis and design.
Method for Measuring the Energy Consumption of Distribution
Gregory Ferguson was born in Toronto, Canada in 1937. He
Transformers’
received a B.Sc. Degree in Engineering Technology from
[6] D. Lin, E.F. Fuchs, M. Doyle ‘Computer-Aided Testing Ryerson Polytechnic University, Toronto. His experience
of Electrical Apparatus Supplying Non-Linear Loads’, IEEE includes employment with the Ontario Hydro-Electric Power
Transactions on Power Systems, Vol.12, No.1, February 1997. Commission and Scarborough Public Utilities, Canada. He is
the founder of Ferguson Engineering Services, Inc., Canada,
VI. BIOGRAPHIES
Electrical Testing Instruments, Ltd., Canada, Power Quality
Aleksandar Damnjanovic was born in Yugoslavia in 1961. He International, Inc., USA and FES International, Inc., Canada &
received a B.S. Degree in Electrical Engineering from the USA. Mr. Ferguson is a Life Member in IEEE. His interests
University of St. Kiril and Methodij, Skopje, Yugoslavia, and a include electrical power system analysis, design, optimization
Master Degree and PhD in Electrical Engineering from Tswine and forensics.
University of Technology, Pretoria, South Africa. His