Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 3
FOREWORD
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 4
PREFACE
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 5
CONTENTS
1 Introduction 01
4 Construction 08
5 Operation of AC system 12
6 Control of AC system 17
8 Trouble shooting 31
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 1
1. INTRODUCTION
RMPU type
AC coaches
SG EOG SG EOG
AC 1st 2T 3T AC 2T 3T
Chair AC AC AC Chair AC AC
car car
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 2
Antiskid protection
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 3
Externally ventilated.
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 4
Figure 1.1
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 5
3
2
2 4
1
1
Figure 1.3
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 6
Cable connection
Battery box
3.1.6 Disconnecting and earthing device
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 7
Figure 1.5
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 8
Bolt fixing
Cable connection
Fuse box
Cable connection
Bolt fixing
Earthing
Figure 1.6 cable
4. CONSTRUCTION
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 9
Figure 1.7
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 10
Vehicle body
Figure 1.8
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 11
Figure 1.9
Exhaust Air Unit
Exhaust Air Fan
4.3 Fresh Air Screens
The fresh air screens are installed parallel to the
air conditioning unit. These screens are fitted with
exchangeable air filters.
Figure 1.10
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 12
5 OPERATION OF AC SYSTEM
5.1 Operating Mode
(a) Preheating and Cooling Operation
In this mode the outside air dampers are
closed to facilitate rapid heating up or cooling
down of the coach.
(b) Normal Operation
In this mode, the dampers are set to
ensure the envisaged fresh air volume of 21
m3/h per person.
(c) Emergency Operation
When AC system fails due to failure of
power supply, the adjusting dampers of the
circulating air duct close so that the system is
operated exclusively with outside air.
5.2 Switch Panel Operation
To make system ready for controlled operation,
ensure 24V supply on the switch panel and “400V ok”
signal on input BA011 = 1L. Switch ON the HVAC
system by means of switch S1U4S1 (61-S2), (BA
001=1L) provided on the switch panel. The system may
be turned OFF by putting this switch on position ‘O’.
Switch S1U4S1 (61-S2) when set to position ‘0’
turns the system off.
Figure 1.11
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 13
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 14
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 15
5.6 Dehumidification
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 16
Figure 1.12
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 17
6. CONTROL OF AC SYSTEM
All controlling and regulating functions are
performed by digital controller FPC 20/2 software/
operating modes.
The control of the air conditioning system is
divided into the following operating modes.
Test mode
Emergency mode
Control mode
6.1 Test Mode
This mode only support test run. The PC is
connected to the a/c computer via serial port.
6.2 Emergency Mode
If a measuring sensor fails, the system continues
in emergency mode. This mode consists of the two
steps.
Outdoor temperature Step 1: Evaluation is taken over by
sensor defective the sensor of the other
system.
Step 2: Fixed value of 20°C.
Duct air temperature Control together with room
sensor defective temperature.
Room air temperature Step 1: Evaluation is taken over by
sensor defective the sensor of other system.
Step 2: Control according to duct
temperature and outdoor
temperature.
Set point generator Control to fixed value of “Mid”
defective
Room and duct Turns OFF heating and cooling,
sensors defective ventilation remains possible.
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 18
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 19
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 20
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 21
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 22
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 23
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 24
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 25
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 26
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 27
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 28
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 29
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 30
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 31
8. TROUBLE SHOOTING
The common troubles are listed below alonwith
their probable causes and remedial action to be taken:
1. Plant is switched on but does not start
Probable Cause Remedial action
No voltage Check voltage at input device and
fuses.
2. Condenser fan does not start
No voltage applied to Check fuses thermal relays.
motor.
Condenser motor defective By pass defective unit.
3. Compressor does not start even though
indoor temperature is high
No voltage applied to Reset HP, if already tripped.
compressor. Check fuses thermal relays.
Compressor motor By pass defective unit.
defective.
4. Compressor starts and stops but preset
temperature is not reached
Suction pressure Check rotation of fan.
low Air filter clogged. Clean as much as
possible.
Refrigerant shortage. Record in
logbook.
High pressure Check fuses, thermal relays
goes high Condenser contaminated, clean it.
Condenser defective/ extra
refrigerant.
Control pressure Check rotation of fan.
switch doesn’t Replace high-pressure cut out.
come on
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 32
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 33
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 34
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 35
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 36
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 37
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 38
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006
CAMTECH/2005/E/LHB-RMPU/1.0 39
OUR OBJECTIVE
Trouble Shooting directory for LHB type RMPU EOG AC Coaches February, 2006