Вы находитесь на странице: 1из 5

Zero Sequence Filtering in Differential Protection | Electrical Concepts https://electricalbaba.com/zero-sequence-filtering-in-differential-protec...

Zero sequence filtering is a concept used to eliminate zero sequence current component
from the secondary current of Current Transformer used in Differential Protection of
Transformer. This concept is useful in Transformer having earthed Star winding.

What is the Need for Zero Sequence Filtering?

Let us have a detailed discussion on this topic. For better understanding, let us consider a
Delta Star Transformer of voltage ratio 1:1 as shown in figure below. Voltage ratio of 1:1 has
been considered for the sake of simplicity.

Suppose a single line to ground fault take place in PN phase of Transformer. This ground
fault will obviously result in flow of fault current through the R phase which comprises of Zero
Sequence I0, positive sequence I1 and negative sequence current I2. Though Zero
Sequence current I0 will flow from the earthed Y side of Transformer, this component of
current will not flow in Delta side as Delta winding rather it will circulate in the delta winding.
Therefore in line current of delta side of Transformer, there will not be any zero sequence
current. This will create an imbalance in the differential current and may lead to actuation of
Differential Relay even in through fault condition. Note that Differential Protection is a unit

1 of 5 12/6/2019, 9:28 PM
Zero Sequence Filtering in Differential Protection | Electrical Concepts https://electricalbaba.com/zero-sequence-filtering-in-differential-protec...

protection and shall only operate if the fault is within the specified zone of protection. But
due to introduction of zero sequence current under fault condition, differential relay may
operate even in through fault condition which is definitely not desirable.

Let us understand the above expiation with some numeric data. Let the fault current be 100
A. This fault current will flow through ground and winding PN for star side of Transformer.

As we know that during single line to ground fault, the fault current has equal positive,
negative and zero sequence current component. Therefore, the fault current will have Zero
Sequence current I0 = 1/3(100+0+0) = 100/3 = x (say)

Since 100 A of current is flowing in winding PN of star side, therefore, the current in
corresponding delta side of winding AB will also be 100 A as voltage ratio is assumed unity.
This current in delta side is already having zero sequence current component of x A. This
current of magnitude x A will circulate around the delta loop.

Therefore, line current in AS = (100-x) A.

But the current in the star side of phase PN = 100 A

Thus a differential current of x A will be sensed by the relay and will cause the relay to
operate though the fault is not in the zone protected. Therefore in differential protection of
Delta Star or Star Delta Transformer, zero sequence filtering is required in star side to
make differential relay stable under through fault condition. In Star Star transformer
we may or may not need this filtering but it is recommended to enable this.

How Zero Sequence Filtering is achieved?

In earlier design, zero sequence filtering was achieved by proper selection of line CTs
connection. Let us discuss this aspect in detail. For better understanding, consider a DELTA
STAR Transformer as shown in figure below.

CTs in Delta side of Transformer are connected in STAR while that in STAR side, it is
connected in Delta. Why?

It’s quite easy. As zero sequence current cannot flow in Delta side, therefore line current IA –
IB will not have any zero sequence current components and hence line CTs secondary
currents I1, I2 and I3 won’t also have no zero sequence current component.

Next you might ask why we didn’t connect these CTs in delta? Actually in differential
protection of Transformer we need to correct the phase as there is a phase change of 30 °in
currents from Delta to Star, therefore to match the phase, we connected CTs in STAR
fashion.

Similarly in star side of Transformer, CTs are connected in DELTA to have phase correction.
This also have one more advantage. In case of single line to ground fault in STAR side, fault
current in line will contain zero sequence current component but due to DELTA connection of

2 of 5 12/6/2019, 9:28 PM
Zero Sequence Filtering in Differential Protection | Electrical Concepts https://electricalbaba.com/zero-sequence-filtering-in-differential-protec...

CTs, this zero sequence current will circulate around the DELTA loop. This will result in no
zero sequence current component in I’1, I’2 and I’3.

This is how zero sequence current is eliminated in differential protection of Transformer.

In modern Numerical Relays, this elimination of zero sequence current do not need such
connection of line CT secondary. We connect both Delta and Star side CTs in star and fed to
relay. What the numerical relay does is that it calculates the zero sequence current as

I0 = (Ia + Ib +Ic)/3

and subtracts this current I0 from the corrected phase current of CT input. If the CT input to
relay is Ia, then the input from differential calculation of relay will be (Ia – I0). The fault
current in the example was 100 A. Zero sequence current was x A. Therefore if filtering is
enabled, then relay input for differential calculation will be (100 – x) A in Star side of
Transformer and that in Delta side is (100 – x) A. This means no differential current and
hence relay is stable under through fault.

But mind that for relay to filter out zero sequence current, we need to enable this feature
provided in the numerical relay.

Hope you got what I meant to say throughout the post. But if you have anything to ask,
please write in comment. Thank you!

Epoxy insulators Sensitive Earth Fault Small electrical CT Matching Factor in


Protection transformer - High Transformer
frequency Differential Protection
transformer
Ad Biname insulators electricalbaba.com Ad transformer-shxy.com electricalbaba.com

Grounding Grid Restricted Earth Fault Broken Conductor Directional Earth


Design - Earthing/ Protection of Protection Fault Protection
grounding software Transformer

Ad voltsandbolts.com electricalbaba.com electricalbaba.com electricalbaba.com

Reply

3 of 5 12/6/2019, 9:28 PM
Zero Sequence Filtering in Differential Protection | Electrical Concepts https://electricalbaba.com/zero-sequence-filtering-in-differential-protec...

Reply

… …

Reply

Reply

Reply

4 of 5 12/6/2019, 9:28 PM
Zero Sequence Filtering in Differential Protection | Electrical Concepts https://electricalbaba.com/zero-sequence-filtering-in-differential-protec...

Post Comment

5 of 5 12/6/2019, 9:28 PM

Вам также может понравиться