BUSBAR
Technology and Solutions
Protection and Substation Automation
PROTECTION
APPLICATION
BASICS 1
BBP_basics_1 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 1

ABB
Topic Objectives
Objectives

r Measurement
- Differential Current Measurement
- Stabilized Differential Current Measurement
r Intertripping
r Differential Current Supervision
BBP_basics_1 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 2

ABB
© ABB Switzerland Ltd. - 3
BBP_basics_1 / 2002-03-15 / RW

Measuring Principle

Who knows
Mr. Kirchhoff ?

ABB
Measuring Principle
Kirchhoffs 1st Law: Node Rule

The summe of all


currents must be zero

I1 + I2 + I3 = S I = 0
BBP_basics_1 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 4

ABB
Measuring Principle
Kirchhoffs 1st Law: Node Rule

I1 + I2 + I3 = S I

¹
0
Þ Fault on the busbar
BBP_basics_1 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 5

Þ Trip circuit breaker

ABB
Measuring Principle
Differential current measurement

S I = I1 + I2 + I3

If
S I > differential current setting
Þ Trip Busbar Protection
BBP_basics_1 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 6

ABB
Measuring Principle
Stabilised differential current measurement
Differential current Idiff= | S I |

k= 1
k= 0,85
ult
f a
a l
rn
nte
i

no fault
Ikmin
BBP_basics_1 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 7

0
Restraint current IRest = S | I |
ABB
Measuring Principle
Stabilised differential current measurement

Advantage:

as more (load / fault) current is flowing on


the busbar
as more differential current is required to
generate a tripping signal
Þ system is very stable in case of
BBP_basics_1 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 8

CT failure
CT saturation
ABB
Intertripping
Tripping flow chart

Measurement Intertripping
system system
TRIP CB

TRIP BBP
trip all CBs TRIP CB

zone x connected TRIP CB


to zone x
BBP_basics_1 / 2002-03-15 / RW
© ABB Switzerland Ltd. - 9

ABB
How is it possible to detect
failures in the CT circuits
???
© ABB Switzerland Ltd. - 10
BBP_basics_1 / 2002-03-15 / RW

ABB
Differential Current Supervision
Þ Differential Current Alarm

A differential current for a longer time is


the consequence of a failure in the
system (intern / extern)

Þ Differential current alarm


Þ Option to block the system
© ABB Switzerland Ltd. - 11
BBP_basics_1 / 2002-03-15 / RW

ABB
Differential Current Supervision

Which failures in the CT circuits


can the Differential current
supervision detect
???
© ABB Switzerland Ltd. - 12
BBP_basics_1 / 2002-03-15 / RW

ABB
Differential Current Supervision

The differential current


supervision can detect

Þ a missing CT input (e.g. CT circuit


not connected to the system)
Þ a wrong CT ratio
© ABB Switzerland Ltd. - 13
BBP_basics_1 / 2002-03-15 / RW

Þ a wrong current direction

ABB
Differential Current Supervision

Þ the “differential current supervision” is able


to detect a missing / wrong CT input
Þ therefore the “differential current alarm” is
very important and must not be ignored by the
operating personal
If not, there is a risk of maloperation !!!