COPPER BUILDING WIRE TYPE TW

Applications
Used in installations where the
Copper
maximum conductor temperature does
PVC Insulation Conductor not exceed 75°C in dry and wet
locations, 600V. Used as machine tool
wire or appliance wire. Heat resistant
Specifications and flame retardant.
PNS 1207 onventional copper stranding
PNS 35 PVC Insulation

Features
Conventional copper stranding
PVC Insulation

PVC
Conductor Approximate
thickness
Cable Bending
Cross- ampacity radius
Singles Cond. Approx. Cond.
Size No. of sectional Average Any pt. Diameter
diameter diameter weight weight
strands area
mm / mm² mm mm mm² kg / km mm mm mm kg / km A* mm**
1.6 Solid 1.6 2.0 17.9 0.80 0.68 3.2 27 25+ 32
2.0 Solid 2.0 3.1 27.9 0.80 0.68 3.6 38 30+ 36
2.6 Solid 2.6 5.3 47.2 1.00 0.85 4.6 64 40+ 46
3.2 Solid 3.2 8.0 71.5 1.20 1.02 5.6 96 55 56
2.0 7 0.6 1.8 2.0 17.9 0.80 0.68 3.4 28 25+ 34
3.5 7 0.8 2.3 3.5 31.9 0.80 0.68 3.9 44 30+ 39
5.5 7 1 2.9 5.5 49.9 1.00 0.85 4.9 69 40+ 49
8.0 7 1.2 3.5 7.9 71.8 1.20 1.02 5.9 99 55 59
14 7 1.6 4.7 14.1 127.6 1.60 1.36 7.9 177 80 79
22 7 2 5.9 22.0 199.4 1.60 1.36 9.1 259 105 91
30 7 2.3 6.7 29.1 263.7 1.60 1.36 9.9 331 130 99
38 19 1.6 7.8 38.2 346.4 2.00 1.70 11.8 442 155 118
50 19 1.8 8.8 48.3 438.4 2.00 1.70 12.8 544 180 128
60 19 2 9.8 59.7 541.3 2.00 1.70 13.8 658 205 138
80 19 2.3 11.2 78.9 715.8 2.00 1.70 15.2 849 250 152
100 19 2.6 12.7 100.9 914.7 2.00 1.70 16.7 1,065 290 167
125 37 2.1 14.4 128.2 1162.1 2.40 2.04 19.2 1,362 335 192
150 37 2.3 15.7 153.7 1394.0 2.40 2.04 20.5 1,612 375 205
200 37 2.6 17.8 196.4 1781.3 2.40 2.04 22.6 2,028 440 226
250 37 2.9 19.8 244.4 2298.0 2.40 2.04 24.6 2,491 505 246
325 61 2.6 22.9 323.9 2936.8 2.80 2.38 28.5 3,314 600 285
400 61 2.9 25.5 402.9 3653.6 2.80 2.38 31.1 4,076 675 311
500 61 3.2 28.2 490.6 4448.6 2.80 2.38 33.8 4,918 770 338

*Ampacity based on PEC Table 3.10.1.17: Ampacities of Single Insulated Conductors, Rated 0 through 2000 Volts, In Free Air Based on Ambient Air Temperature of 30°C (86°F)
**Bending radius is based on PEC standards.
+Diagrams of cables are illustrative only and not necessarily to scale. PDP reserves the right to change or vary the construction of any of their products without notice.
While every care has been taken in the preparation of this data sheet, PDP accept no liability of any kind and are not responsible for the results of any actions taken on
the basis of this information or resulting from errors or omissions. This technical data sheet is intended as a guide only; any person using it must make reference to
the appropriate local standards or authorities.