Rated Highest Value of Routine Partial Sample Impulse Voltage Test
Voltage voltage for Uo for test Discharge Test Test for
equipment determination 15 minutes
of test
voltages
U Um Uo 3.5 Uo 1.5 Uo 4 Uo
kV kV kV kV KV KV kV kV
U Um Uo 2.5 Uo 1.5 Uo Uo 2 Uo
kV kV kV kV kV kV kV kV kV
45 to 47 52 26 65 39 26 52 250 52
60 to 69 72.5 36 90 54 36 72 325 72
110 to 115 123 64 160 96 64 128 550 128
132 to 138 145 76 190 114 76 152 650 132
150 to 161 170 87 218 131 87 174 750 150
1)
If the average thickness of insulation exceeds the nominal value by more than 5% but by not more than 15%, the test voltage shall be
adjusted to give an electrical stress at the conductor screen equal to that applying when the average thickness of insulation is equal to
the nominal value and the test voltages are the normal values specified for the rated voltage of the cable.
The cable length used for electrical type tests shall not have an average thickness exceeding the nominal value by more than 15%
1 2 3 4 5 6 7 8 9
Rated Highest Value of Uo for Voltage test Partial Heating Impulse Voltage test after Switching
impulse voltage test
Voltage voltage for discharge cycle voltage test impulse
equipment determination test voltage test Voltage
2Uo test
of test voltages
Volt-
U Um Dura- 1.5 Uo 2 Uo
Uo Age1) tion1)
kV kV kV kV min kV kV kV KV KV
Subject to agreement between manufacturer and purchaser, the voltage test of (4) may be replaced by a test at lower voltage
and longer duration even if the maximum stress in the insulation is lower than 30 MV/m. However, the voltage level shall not
be below 1.5 Uo and duration not longer than 10 h.