1 2 3 4

Mini type VFD of CV20 series Item Description Operation Button Description Faults and actions
Display setting frequency, output frequency, output voltage, Fault Fault
Thank you for using CV20 series Variable Frequency Drive made by Kinco Automation. LED Display Button Description Possible reasons for fault Actions
Operation output current and so on, about 20 parameters. code categories
CV20 satisfies the high performance requirements by using a unique control method to achieve high
panel Keys lock and function Lock part of keys or all the keys. Increase the value or function
torque, high accuracy and wide speed-adjusting range. Its anti-tripping function and capabilities of Acc time is too short Prolong the Acc time
selection Define the function of part of keys Decrease the value or function
adapting to severe power network, temperature, humidity and dusty environment exceed those of Parameters of motor are wrong Auto-tune the parameters of motor
Open phase protection (optional), overcurrent protection,
similar product made by other companies, which improves the product’s reliability MENU Enter or Exit the programming status Over-current Coded disc breaks down, when PG is Check the coded disc and the
Protection function overvoltage protection, under-voltage protection, overheat E001 during running connection
noticeably;Without PG connector, strong speed control, flexible input/output terminal, pulse
protection, over-load protection and so on. In panel operation mode, run the VFD by the first pressing; acceleration
frequency setting, saving parameters at power outage and stop, frequency setting channel, master and RUN/STOP Drive power is too small Select a higher power drive
slave frequency control and so on, all these satisfy various of high accuracy and complex drive Indoor, installed in the environment free from directsunlight, stop VFD by the second pressing. In VFD error status, reset the error by pressing
Operating site Check and adjust V/F curve, adjust
dust, corrosive gas, combustible gas, oil mist, steam and drip. V/F curve is not suitable
command, at the same time we provide the OEM customer high integration total solution, it values Short pressing to shift data or function code. Hold pressing(more than 1s) to enter torque boost
highly in system cost saving and improving the system reliability. Derated above 1000m, the rated output current SHIFT/ENTER Deceleration time is too short Prolong the Dec time
Altitude
CV20 can satisfy the customers’ requirements on low noise and EMI by using optimized PWM shall be decreased by 10% for every rise of 1000m function code or save the changed value
Environment The load generates energy or the load
technology and EMC design. Ambienttemperature -10℃~40℃, derated at 40℃~ 50℃ Over-current Connect suitable braking kit
Wiring: inertial is too big
This manual provides information on installation, wiring, parameters setting, trouble-shooting, Humidity 5%~95%RH, non-condensing E002 during
Coded disc breaks down, when PG is Check the coded disc and the
and daily maintenance. To ensure the correct installation and operation of CV20, please read this deceleration
Vibration Less than 5.9m/s2 (0.6g) running connection
manual carefully before starting the drive and keep it in a proper place and to the right person. Storage temperature -40℃~+70℃ Danger Drive power is too small Select a higher power drive
Unpacking Inspection Note Protection class IP20 Acceleration /Deceleration time is too Prolong Acceleration/ Deceleration
Structure -Wiring can only be done after the drive’s AC power is disconnected, all the LEDs on the operation
Upon unpacking, please check for: Cooling method Air cooling, with fan control. short time
panel are off and waiting for at least 5 minutes. Then, you can remove the panel. Over-current
 Any damage occurred during transportation; Installation method Wall-mounted Sudden change of load or Abnormal load Check the load
-Wiring job can only be done after confirming the charge indicator on the right bottom is off and the In constant
 Check whether the rated values on the nameplate of the drive are in accordance with your order. Efficiency ≥90% E003 Low AC supply voltage Check the AC supply voltage
voltage between main circuit power terminals + and - is below DC36V. speed
Our product is manufactured and packed at factory with great care. If there is any error, please contact Coded disc breaks down, when PG is Check the coded disc and the
Introduction of CV20 series: -Wire connections can only be done by trained and authorized person operation
us or distributors.The user manual is subject to change without notifying the customers due to the running connection
continuous process of product improvements Rated capacity Rated input Rated output Motor power -Check the wiring carefully before connecting emergency stop or safety circuits. Drive power is too small Select a higher power drive
Model of VFD -Check the drive’s voltage level before supplying power to it, otherwise human injuries or equipment
You can scan the QR code below to get the latest electronic version of the official website. (kVA) current(A) current(A) (kW) Over voltage Abnormal AC supply voltage Check the power supply
CV20-1S-0002G 0.6 6.0 1.3 0.2 damage may happen. E004 during
Too short acceleration time Prolong acceleration time
CV20-1S-0004G 1.0 9.0 2.5 0.4 acceleration
CV20-1S-0007G 1.5 18.0 4.0 0.75 ! Attention Over voltage
Too short Deceleration time (with
reference to generated energy)
Prolong the deceleration time
CV20-2S-0004G 1.0 5.3 2.5 0.4 E005 during
CV20-2S-0007G 1.5 8.2 4.0 0.75 -Check whether the Variable Speed Drive’s rated input voltage is in compliant with the AC supply The load generates energy or the load
deceleration Connect suitable braking kit
CV20-2S-0015G 3.0 14.0 7.5 1.5 voltage before using. inertial is too big
CV20-4T-0007G 1.5 3.4 2.3 0.75 -Dielectric strength test of the drive has been done in factory, so you do not need to do it again. Wrong ASR parameters, when drive run
Refer to A5. ASR parameter setting
-Refer to chapter 2 on connected braking resistor or braking kit. Over voltage in the vector control mode
CV20-4T-0015G 3.0 5.0 3.7 1.5
in Acceleration /Deceleration time is too Prolong Acceleration/ Deceleration
VFD model rule CV20-4T-0022G 4.0 5.8 5.5 2.2 -It is prohibited to connect the AC supply cables to the drive’s terminals U, V and W.
E006 constant-speed short time
-Grounding cables should be copper cables with section area bigger than 3.5mm2, and the grounding
CV20 – 4T– 0015G–A–037 External dimension: operating Abnormal AC supply voltage Check the power supply
resistance should be less than 10Ω.
VFD code Custom software:
process Abnormal change of input voltage Install input reactor
-There is leakage current inside the drive. The total leakage current is greater than 3.5mA, depending
CV: Mini type No.37 Too big load inertia Connect suitable braking kit
on the usage conditions. To ensure safety, both the drive and the motor should be grounded, and a
Drive’s control
leakage current protector (RCD) should be installed. It is recommended to choose B type RCD and Check the AC supply voltage or seek
Communication port: E007 power supply Abnormal AC supply voltage
The second generation None: Standard RS485 set the leakage current at 300mA. service
over voltage
A: CAN
-The drive should be connected to the AC supply via a circuit breaker or fuse to provide convenience Input phase Any of phase R, S and T cannot be Check the wiring and installation
00: Standard model E008
…..other models to input over-current protection and maintenance. loss detected Check the AC supply voltage
G: Constant torque Output phase Any of Phase U, V and W cannot be Check the drive’s output wiring
E009
Power supply L: Constant power Top of single-phase/3-phase loss detected Check the cable and the motor
1:100V R/L1 S/L2 T/L3
Short-circuit among 3-phase output or Rewiring, please make sure the
2:200V
4:400V Power
line-to-ground short circuit insulation of motor is good
Bottom U/L1 V/L2 W/L3
0002: 200w Instantaneous over-current Refer to E001~E003
0004: 400w
S: 400V
Single phase 0015: 1.5kw
Vent is obstructed or fan does not work Clean the vent or replace the fan
4:
T: Three-phase …… Terminal name Function description Over-temperature Lower the ambient temperature
R/L1、S/L2、T/L3 Single-phase 220V(R/L1, S/L2) or 3-phase 380VAC input terminal Wires or connectors of control board
Protections of Check and rewiring
Production introduction: CV20-2S-0004G~ CV20-2S-0015G/ CV20-1S-0002G~ CV20-1S-0007G E010 are loose
U/T1、V/T2、W/T3 3-phase AC output terminal IGBT act
Current waveform distorted due to
General specifications Check the wiring
Shield terminal output phase loss
Item Description
Auxiliary power supply is damaged or
4T:3-phase,380V~440V AC; 50Hz/60Hz Seek service
Rated voltage and IGBT driving voltage is too low
2S:Single-phase,200V~240V;50Hz/60Hz
frequency Braker
Short-circuit of IGBT bridge Seek service
Input 1S:Single-phase, 100~120V; 50/60HZ
R/L1 U/T1 Control board is abnormal Seek service
4T: 320V~460V AC;2S:180V~260V; 1S: 90~132V 3-Phase AC power S/L2 V/T2 M
Allowable voltage range Ambient over-temperature Lower the ambient temperature
Voltage tolerance<3%; Frequency: ±5% T/L3 W/T3 IGBT module’s
PE Vent is obstructed Clean the vent
Rated voltage 4T:0~440V;2S:0~240V;1S:0~240V Main loop PE for motor E011 heatsink
Fan does not work Replace the fan
Frequency 0Hz~300Hz (0~800HZ customizable) overheat
Output Multi-function input 1 Control loop IGBT module is abnormal Seek service
G type: 150% rated current for 1 minute, 180% rated current X1
Multi-function input 2
Overload capacity X2 Rectifier’s Ambient over-temperature Lower the ambient temperature
for 10 seconds; Multi-function input 3 X3 Modbus rtu
Multi-function input 4 RS485 E012 heatsink Vent is obstructed Clean the vent
Control mode V/F control X4
2:+5v overheat Fan does not work Replace the fan
3:485+
Modulation mode Space vector PWM modulation COM 4:485- Parameters of motor are wrong Auto-tune the parameters of motor

3
Starting torque 1 Hz 150%rated torque 5:GND

1
+10V I
Too heavy load Select the drive with bigger power
Digital setting: Max frequency ×±0.01%; CV20-4T-0007G~CV20-4T-0022G Analog input AI1 Ra
Frequency accuracy AI V Reduce the DC injection braking
Analog setting: Max. frequency ×±0.2% COM Programable relay output
Rc DC injection braking current is too big current and prolong the braking
Digital setting: 0.01Hz; Mechanical parameters PE Drive
Frequency resolution × E013 time
Control Analog setting: Max frequency×0.1% VFD model External dimension and (mm) √ overload
Too short acceleration time Prolong acceleration time
Characteris Torque boost Manual torque boost :0%~30.0% (G: Constant torque load; Installa- Weight
Note: DIP Low AC supply voltage Check the AC supply voltage
tics L: Draught fan and water W H D W1 H1 D1 T1 tion (kg) switch setting
4 patterns: 1 V/F curve mode set by user and Adjust V/F curve or torque boost
pump load) hole(d) Improper V/F curve
V/F pattern 3 kinds of torque-derating modes (2.0 order, 1.7 order, and 1.2 value
order) CV20-1S-0002G
Improper motor’s overload protection Modify the motor’s overload
Linear acceleration/deceleration, CV20-1S-0004G Arrangement of control circuit terminals is as follows:
Acc/Dec curve threshold protection threshold.
Four kinds of acceleration/deceleration time CV20-1S-0007G
68 132 131 56 120 - 12 5 0.8 Motor is locked or load suddenly become
Limit current during the operation automatically CV20-2S-0004G RS-485 Check the load
Auto current limit RA RC +10V A1 X1 X2 X3 X4 COM too big
to prevent frequent overcurrent trip CV20-2S-0007G
Motor Use a special motor if the motor
Operation Panel, Terminal, CommunicationControl, CV20-2S-0015G E014 Common motor has operated with
Operation Command over-load is required to operate for a long
Supportswitching between these control channesl. CV20-4T-0007G It lists the possible faults of CV20. The fault code varies from E001 to E027. Once a fault occurs, you heavy load at low speed for a long time.
Operation time.
Function Frequency Setting Digital, Analog Voltage/current setting. CV20-4T-0015G 100 151 128 89 140 - 9 5 1.0 may check it against the table and record the detailed phenomena before seeking service from your Low AC supply voltage Check the AC supply voltage
Auxiliary frequency Support main and auxiliary setting(“+”,”-”, “min”, “max”) CV20-4T-0022G supplier. Set V/F curve and torque boost
Improper V/F curve
value correctly
5 6 7 8

Fault Fault Function Factory Setting Function Factory Setting Function Factory Setting
Possible reasons for fault Actions Name Descriptions Unit Modif Name Descriptions Unit Modif Name Descriptions Unit Modif
code categories code setting range code setting range code setting range
external A1.03 DC injection 0.0%~100.0% drive’s rated 0.1% 0.0% ○ 0~1000 A3.04 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000 A4.22 ACC/DEC time 0.00~300.00Hz 0.01Hz 0.00Hz × 0~30000
Terminal used for stopping the drive in Disconnect the terminal if the braking current at current Corresponding to 1/2 switch freq. Select ACC/DEC time 2
E015 equipment
emergent status is closed external fault is cleared start the Min reference when output freq. is less
fails
A1.04 DC injection 0.00(No action) 0.01s 0.00s ○ 0~3000 of curve 1 than A4.22
EEPROM R/W Press STOP/RST to reset, seek braking time at 0.01~30.00s A3.05 Max reference of A3.07~110.00% 0.01% 100.00% ○ 0~11000 A4.23~ Reserved Reserved 1 0 ○ 0~65535
E016 R/W fault of control parameters
fault service start curve 2 A4.40
Communication Set b3.02 to 0, it means do not A1.05 Stopping mode 0: Dec-to-stop 1 0 × 0~2 A3.06 Actual value The same as A3.02 0.01% 100.00% ○ 0~10000 Group A5:reserved
E017 The setting time is too shot
timeout detection 1: Coast-to-stop corresponding to Group A6:Control terminals parameters
Low AC supply voltage Check the AC supply voltage 2: Dec-to-stop+DC the Max reference A6.00~ Multi-function 0: No function1:Forward 1 0 × 0~54
injection braking of curve 2 A6.03 terminal X1~X4 2: Reverse
Replace the contactor in main
Contactor damaged A1.06 DC injection 0.00~60.00Hz 0.01Hz 0.00Hz ○ 0~6000 A3.07 Min reference of 0.0%~A3.05 0.01% 0.00% ○ 0~11000 3: Forward jog operation
circuit and seek service
Contactor not braking initial curve 2 4: Reverse jog operation
E018 Replace the soft start resistor and frequency at stop A3.08 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000 5: 3-wire operation control
closed Soft start resistor is damaged
seek service A1.07 Injection braking 0.00~10.00s 0.01s 0.00s ○ 0~1000 Corresponding to 6: External RESET signal
Control circuit is damaged Seek service waiting time at the Min reference input
Input phase loss Check the wiring of R, S, T. stop of curve 2 7: External fault signal
Wires or connectors of control board are A1.08 DC injection 0.0%~100.0% drive’s rated 0.1% 0.0% ○ 0~1000 A3.09 Max reference of A3.11~110.00% 0.01% 100.00% ○ 0~11000 input
Check and re-wire braking current at current curve 3 8: External interrupt signal
Current loose
stop A3.10 Actual value The same as A3.02 0.01% 100.00% ○ 0~10000 input
E019 detection Auxiliary power supply is damaged Seek service
A1.09 DC injection 0.0(No action) 0.01s 0.00s ○ 0~3000 Corresponding to 9: Drive operation prohibit
circuit fails Hall sensor is damaged Seek service braking time at 0.01~30.00s the Max reference 10: External stop command
Amplifying circuit is abnormal Seek service stop of curve 3 11: DC injection braking
Press STOP/RSTkey to reset or A1.10 Restart after power 0:Disable 1 0 × 0~1 A3.11 Min reference of 0.0%~A3.09 0.01% 0.00% ○ 0~11000 command
Terrible interference add、a power filter in front of failure 1:Enable curve 3 12: Coast to stop
System A1.11 Delay time for 0.0~10.0s 0.1s 0.0s ○ 0~100 A3.12 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000 13: Frequency ramp up
E020 power supply input
interference restart after power corresponding to (UP)
DSP in control board read / write by Press STOP/RST key or seek 14: Frequency ramp down
failure the Min reference
mistake service. (DN)
A1.12 Anti-reverse 0: Disabled 1 0 × 0~1 of curve 3
Update the panel’s parameters and running function 1: Enabled(It will operate A3.13 Max reference of A3.15~110.00% 0.01% 100.00% ○ 0~11000 15: Switch to panel control
Panel’s parameters are not complete or version again. First set b4.04 to 1 at zero frequency when curve 4 16: Switch to terminal
Parameter the version of the parameters are not the to upload the parameters and then input a reverse command) A3.14 Actual value The same as A3.02 0.01% 100.00% ○ 0~10000 control
E023 17: Switch to
copy error same as that of the main control board set b4.04 to 2 or 3 to download A1.13 Delay time of run 0.00~360.00s 0.01s 0.00s ○ 0~36000 corresponding to
reverse/forward the Max reference communication control
the parameters.
of curve 4 mode
Panel’s EEPROM is damaged Seek service A1.14 Switch mode of 0: Switch when pass 0Hz 1 0 × 0~1
18: Main reference
run reverse/ 1: Switch when pass A3.15 Reference of A3.17~A3.13 0.01% 100.00% ○ 0~11000
Improper settings of parameters on the Set the parameters correctly frequency via AI
forward (Reserved) starting frequency inflection point 2
nameplate according to the nameplate 27: Preset frequency 1
A1.15 Detecting 0.00~150.00Hz 0.01Hz 0.10Hz × 0~15000 of curve 4
Prohibiting contra Auto-turning during 28: Preset frequency 2
Cancel prohibiting rollback frequency of stop A3.16 Actual value The same as A3.02 0.01% 100.00% ○ 0~10000
Auto-tuning rollback 29: Preset frequency 3
E024 A1.16 Reserved corresponding to
30: Preset frequency 4
fault Check the motor’s wiring Group A2:Frequency setting the Min reference
31: Acc/Dec time 1
Check the set value of A0.10(upper A2.00 Auxiliary reference 0: No auxiliary reference 1 0 ○ 0~5 of inflection point
Overtime of auto-tuning 32: Acc/Dec time 2
limiting frequency), make sure if it is frequency selector frequency 2 of curve 4
33: Multiple close-loop
lower than the rated frequency or not 1: AI A3.17 Reference of A3.19~A3.15 0.01% 0.00% ○ 0~11000
reference selection 1
5: Output by PID process inflection point 1
The load of 34: Multiple close-loop
E026 The load is lost or reduced Check the situation of the load A2.01 Main and auxiliary 0: + 1 0 ○ 0~3 of curve 4
drive is lost reference selection 2
reference 1: - A3.18 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000 35: Multiple close-loop
Brake unit frequency 2: MAX(Main reference, corresponding to
E027 Brake tube is broken Seek service reference selection 3
fault calculation Auxiliary reference) the Min reference 36: Multiple close-loop
3: MIN(Main reference, of inflection point reference selection 4
List of Parameters: Auxiliary reference) 1 of curve 4 37: Forward prohibit
A2.02 UP/DN rate 0.01~99.99Hz/s 0.01 1.00 ○ 1~9999 A3.19 Min reference of 0.0%~A3.17 0.01% 0.00% ○ 0~11000 38: Reverse prohibit
Function Factory Setting curve 4
Name Descriptions Unit Modif A2.03 UP/DN regulating Unit’s place of LED: 1 00 ○ 0~11H 39: Acc/Dec prohibit
code setting range
control 0:Save reference frequency A3.20 Actual value The same as A3.02 0.01% 0.00% ○ 0~10000 40: Process close-loop
Group A0:Basic operating parameters corresponding to
upon power outage prohibit
A0.00 User password 0: No password protection. 1 0 ○ 0~FFFF the Min reference
1:Not save reference 42: Main frequency switch
Others: Password of curve 4
frequency upon power to digital setting
protection. Group A4:Acc/Dec parameters
outage. 43: PLC pause
A0.01 Control mode 0~1: reserved 1 0 × 0~2 Ten’s place of LED: A4.00 Acc/Dec mode 0: Linear Acc/Dec 1 0 × 0~1 44: PLC prohibit
2: V/F control 0:Hold reference frequency 1: S Curve 45: PLC stop memory clear
A0.02 Main reference 0: Digital setting in A0.03 1 3 ○ 0~5 at stop A4.01 Acc time 2 0.0~6000.0 0.1s 20.0s ○ 0~60000 46: Swing input
frequency selector 1: AI 1:Clear reference A4.02 Dec time 2 0.0~6000.0 0.1s 20.0s ○ 0~60000 47: Swing reset
2: Reserved frequency at stop A4.03 Acc time 3 0.0~6000.0 0.1s 20.0s ○ 0~60000 48~49:Reserved
3:Potentiometer Hundred’s place of LED: A4.04 Dec time 3 0.0~6000.0 0.1s 20.0s ○ 0~60000 50: Timer 1 start
A0.03 Set the operating A0.11~A0.10 0.01Hz 50.00 ○ 0~3000 0:UP/DN integral time valid 51: Timer 2 start
A4.05 Acc time 4 0.0~6000.0 0.1s 20.0s ○ 0~60000
frequency in digital 1:UP/DN speed value 53: Counter input
mode A4.06 Dec time 4 0.0~6000.0 0.1s 20.0s ○ 0~60000
A2.04 Jog operating 0.10~50.00Hz 0.01Hz 5.00 ○ 10~5000 A4.07 S curve 10.0%~50.0%(Acc time) 0.1% 20.0% ○ 100~500 54: Counter clear
A0.04 Methods of input 0: Panel control 1 0 ○ 0~2 frequency Others: Reserved
ting operating 1: Terminal control acceleration A4.07+ A4.08≤90%
A2.05 Interval of Jog 0.0~100.0s 0.1s 0.0 ○ 0~1000 starting time A6.04 reserved
commands 2: Communication control operation A6.05
A0.05 Set running 0: Forward 1 0 ○ 0~1 A4.08 S curve 10.0%~70.0%(Acc time) 0.1% 20.0% ○ 100~800
A2.06 Skip frequency 1 0.00~300.00Hz 0.01Hz 0.00 × 0~30000 acceleration ending A4.07+ A4.08≤90% A6.08 Terminal filter 0~500ms 1 10 ○ 0~500
direction 1: Reverse A2.07 Range of skip 0.00~30.00Hz 0.01Hz 0.00 × 0~3000 time A6.09 Terminal control 0:2-wire operating mode 1 1 0 × 0~3
A0.06 Acc time 1 0.0~6000.0 0.1s 6.0s ○ 0~60000 frequency 1 mode selection 1:2-wire operating mode 2
A4.09 S curve deceleration 10.0%~50.0%(Dec time) 0.1% 20.0% ○ 100~500
A0.07 Dec time 1 0.0~6000.0 0.1s 6.0s ○ 0~60000 A2.08 Skip frequency 2 0.00~300.00Hz 0.01Hz 0.00 × 0~30000 2:3-wire operating mode 1
starting time A4.09+ A4.10≤90%
A0.08 Max. output 50Hz~ 300.00Hz 0.01Hz 50.00 × 0~30000 A2.09 Range of skip 0.00~30.00Hz 0.01Hz 0.00 × 0~3000 3:3-wire operation mode 2
A4.10 S curve 10.0%~70.0%(Dec time) 0.1% 20.0% ○ 100~800
frequency frequency 4:2-wire operation mode 3
deceleration A4.09+ A4.10≤90%
A0.09 Max. output 0~480 1V VFD’s × 0~480 A2.10 Skip frequency 3 0.00~300.00Hz 0.01Hz 0.00 × 0~30000 A6.10 reserved
ending time
voltage rated A2.11 Range of skip 0.00~30.00Hz 0.01Hz 0.00 × 0~3000 A6.11
A4.11 Quick start-stop 0: Disable 1 2 × 0~3
values frequency 3 A6.12
selector 1: Quick start, normal stop
A0.10 Upper limit of A0.11~A0.08 0.01Hz 50.00 ○ 0~30000 Group A3:Setting curve A6.13 Input terminal’s Binary setting 1 00 ○ 0~FFH
2: Normal start, quick stop
frequency positive and 0: Positive logic:
A3.00 Reference LED unit’s place: 1 3330 ○ 0~3333H 3: Quick start, quick stop
A0.11 Lower limit of 0.00~A0.10 0.01Hz 0.00 ○ 0~30000 negative logic Terminal Xi is enabled if it
frequency AI curve selection A4.12 Start ACR-P 0.1~200.0 0.1 20.0 ○ 1~2000
frequency curve selection 0: Curve 1 is connected to
A4.13 Start ACR-I 0.000~10.000s 0.001s 0.200s ○ 0~10000
A0.12 Basic operating 0.00~300.00Hz 0.01Hz 50.00 ○ 0~30000 1: Curve 2 corresponding common
A4.14 Start AVR-P 0.1~200.0 0.1 20.0 ○ 1~2000
frequency 2: Curve 3 terminal, and disabled if it
A4.15 Start AVR-I 0.000~10.000s 0.001s 0.200s ○ 0~10000
A0.13 Torque boost 0.0%(Auto),0.1%~30.0% 0.1% 0.0% ○ 0~300 3: Curve 4 is disconnected.
A4.16 Stop ACR-P 0.1~200.0 0.1 20.0 ○ 1~2000
Group A1: Start and stop parameters A3.01 Max reference of A3.03~110.00% 0.01% 100.00% ○ 0~11000 1: Negative logic:
A4.17 Stop ACR-I 0.000~10.000s 0.001s 0.200s ○ 0~10000 Terminal Xi is disabled if it
A1.00 Starting mode 0: Start from the starting 1 0 × 0~2 curve 1
frequency A4.18 Stop AVR-P 0.1~200.0 0.1 20.0 ○ 1~2000 is connected to
A3.02 Actual value Reference frequency: 0.01% 100.00% ○ 0~10000
1: Brake first and then start A4.19 Stop AVR-I 0.000~10.000s 0.001s 0.200s ○ 0~10000 corresponding common
Corresponding to 0.0~100.00%Fmax
2: Reserved A4.20 Over commutation 0: disable 1 0 × 0~1 terminal, and enabled if it
the Max reference Torque: 0.0~300.00%Te
A1.01 Starting frequency 0.00~60.00Hz 0.01Hz 0.00Hz ○ 0~6000 Stop 1:enable is disconnected.
of curve1
A1.02 Holding time of 0.00~10.00s 0.01s 0.00s ○ 0~1000 A3.03 Min reference of 0.0%~A3.01 0.01% 0.00% ○ 0~11000
A4.21 ACC/DEC time 0:ACC/DEC time × 1 1 0 × 0~1 Unit’s place of LED:
starting frequency coefficient 1: ACC/DEC time × 0.1 BIT0~BIT3: X1~X4
curve 1
9 10 11 12

Function Factory Setting Function Factory Setting Function Factory Setting Function Factory Setting
Name Descriptions Unit Modif Name Descriptions Unit Modif Name Descriptions Unit Modif Name Descriptions Unit Modif
code setting range code setting range code setting range code setting range
A6.14 reserved 1 0 × 0~50 Hundred’s place of LED: Group b1:V/F parameters 0:1-8-2-N format, RTU
A6.15 Selection for fault locked b1.00 V/F curve setting 0: V/F curve is defined by 1 0 × 0~3 1:1-8-1-E format, RTU
A6.16 Output functions of 0: Running signal(RUN) 1 15 × 0~50 function. user 2:1-8-1-O format, RTU
relay R1 1: frequency arriving 0:Disable; 1: 2-order curve Hundred’s place of LED:
signal(FAR) 1: Enable 2: 1.7-order curve wiring mode
2: frequency detection Thousand’s place of LED: 3: 1.2-order curve 0:Direct connection via
threshold (FDT1) Reserved b1.01 V/F frequency B1.03~A0.08 0.01Hz 0.00Hz × 0~30000 cable (RS232/485)
3: frequency detection A8.01 Fault masking Unit’s place of LED: 1 2000 × 0~2222H value F3 1: MODEM (RS232)
threshold (FDT2) selection 1 Communication fault b1.02 V/F voltage value B1.04~100.0% 0.1% 0.0% × 0~1000 b3.01 Local address 0~127,0 is the broadcasting 1 5 × 0~127
4: overload signal(OL) masking selection V3 address
5: low voltage signal (LU) Ten’s place of LED: b1.03 V/F frequency B1.05 ~B1.01 0.01Hz 0.00Hz × 0~30000 b3.02 Time threshold for 0.0~1000.0s 0.1 0.0s × 0~10000
6: external fault signal Relay fault masking value F2 judging the
(EXT) selection b1.04 V/F voltage value B1.06~B1.02 0.1% 0.0% × 0~1000 communication
7: frequency high limit Hundred’s place of LED: V2 status
(FHL) EEPROM fault masking b1.05 V/F frequency 0.00~B1.03 0.01Hz 0.00Hz × 0~30000 b3.03 Delay for 0~1000ms 1 5ms × 0~1000
8: frequency low limit selection value F1 responding to
(FLL) Thousand’s place of LED: b1.06 V/F voltage value 0~B1.04 0.1% 0.0% × 0~1000 control PC
9: zero-speed running Reserved V1 Group b4:Keyboard parameters
10~11: Reserved 0:Disable.Stop when fault b4.00 Key-lock function 0: The keys on the 1 0 ○
b1.07 Cut-off point used 0.0%~50.0% 0.1% 10.0% ○ 0~500 0~4
12: PLC running step happen selection operation panel are not
for manual torque (Corresponding to A0.12)
complete signal 1:Disable.Continue locked, and all the keys are
boost
13: PLC running cycle operating when fault usable.
b1.08 AVR function 0: Disable 1 2 × 0~2
complete signal happen 1: The keys on the
1: Enable all the time
14: Swing limit 2:Enable operation panel are locked,
2: Disabled in Dec process
15: Drive ready (RDY) A8.02 Fault masking Unit’s place of LED: 1 00 × 0~22H and all the keys are
b1.09 VF Output voltage 0: no function 1 0 × 0~3
16: Drive fault selection 2 Open phase fault masking unusable.
selection 1: AI
17: Switching signal of selection for input 2: All the keys except for
b1.10 VF Output voltage 0: no function 1 0 × 0~3
host Ten’s place of LED: the multi-functional key
19: Torque limiting offset selection 1: AI
Open phase fault masking are unusable.
20: Drive running selection for output Group b2:Enhanced parameters
3: All the keys except for
forward/reverse A8.03 Motor overload 0: Disabled 1 1 × 0~2 b2.00 Carrier wave 2.0~6..0KHz 0.1 6.0 ○ 20~150
the SHIFT key are
21: Timer 1 reach protection mode 1:Common mode(with low frequency
unusable.
22: Timer 2 reach selection speed compensation) b2.01 Auto adjusting of 0: Disable 1 1 ○ 0~1
4: All the keys except for
23: Preset counter reach 2: Variable frequency CWF 1: Enable
the RUN AND STOP keys
24: Intermediate counter motor (without low speed b2.02 Voltage adjustment Unit’s place of LED: 1 001 × 0~111H are unusable.
reach compensation) selection Over-voltage at stall
b4.01 Multi-function key Reserved 1 4 ○ 0~5
Others: Reserved A8.04 Auto reset times 0: No function 1 0 × 0~100 Selection
definition
A6.18 Output terminal’s Binary setting: 1 0 ○ 0~1FH 1~100: Auto reset times 0: Disable(When install
b4.02 Parameter 0: All parameters are 1 1 ○ 0~2
positive and 0: Terminal is enabled if it Note: brake resistor)
protection allowed modifying;
negative logic is connected to correspond The IGBT protection 1: Enable
1: Only A0.03 and b4.02
common terminal, and (E010) and external Ten’s place of LED:
can be modified;
disabled if it is equipment fault (E015) Not stop when
2: Only b4.02 can be
disconnected. cannot be reset instantaneous stop function
modified.
1: Terminal is disabled if it automatically. selection
b4.03 Parameter 0: No operation 1 0 × 0~2
is connected to A8.05 Reset interval 2.0~20.0s/time 0.1s 5.0s × 20~200 0: Disable
initialization 1: Clear fault information
corresponding common 1: Enable(Low voltage
A8.06 Fault locking 0:Disable. 1 0 × 0~1 in memory
terminal, and enable if it is compensation)
function selection. 1: Enable. 2: Restore to factory
disconnected. Hundred’s place of LED:
Group b0:Motor parameters settings
Unit’s place of LED: Over modulation selection
b0.00 Rated power 0.4~999.9KW 0.1 0 × 4~9999 b4.04 Parameter copy 0: No action 1 0 × 0~3
BIT2:R1 0: Disable
b0.01 Rated voltage 0~ rated voltage of drive 1 0 × 0~999 1: Enable 1: parameters upload
Ten’s place of LED:
b0.02 Rated current 0.1~999.9A 0.1A Depend × 1~9999 2: parameters download
Reserved b2.03 Overvoltage point 120.0%~150.0%Udce 0.1% 140.0% × 1200~1500
on 3: parameters download
A6.19 Frequency arriving 0.00~300.00Hz 0.01Hz 2.50Hz ○ 0~30000 at stall
drive’s (except the parameters
signal (FAR) b2.04 Droop control 0: Disable 0.01~10.00Hz 0.01 0.00Hz ○ 0~1000
model related to drive type)
A6.20 FDT1 level 0.00~300.00Hz 0.01Hz 50.00Hz ○ 0~30000 b2.05 Auto current 20.0%~200.0%Ie 0.1% 150.0% × 200~2000
Note:
b0.03 Rated frequency 1.00~300.00Hz 0.01Hz Depend × 100~
A6.21 FDT1 lag 0.00~300.00Hz 0.01Hz 1.00Hz ○ 0~30000 limiting threshold
on 30000 Not to upload/ download
A6.22 FDT2 level 0.00~300.00Hz 0.01Hz 25.00Hz ○ 0~30000 b2.06 Frequency 0.00~99.99Hz/s 0.01 10.00 ○ 0~9999 drive’s parameters.
drive’s
A6.23 FDT2 lag 0.00~300.00Hz 0.01Hz 1.00Hz ○ 0~30000 decrease rate when Hz/s Hz/s
model b4.05 Display parameters Binary setting: 1 1007H ○ 0~7FFFH
A6.24 Virtual terminal Binary setting 1 00 ○ 0~FFH current limiting
b0.04 Number of 2~24 1 4 × 2~24 selection BIT1:Operating
setting 0: Disable; b2.07 Auto current 0:Invalid at constant speed 1 1 × 0~1 0: No display
polarities of motor
1: Enable limiting 1:Valid at constant speed 1: Display
b0.05 Rated speed 0~60000RPM 1RPM 1440 × 0~60000
Unit’s place of LED: selection Note: Unit’s place of LED:
RPM
BIT0~BIT3: X1~X4 It is valid all the time at BIT0: Output frequency
b0.06 Resistance of 0.00%~50.00% 0.01% Depend × 0~5000 Acc/Dec
Ten’s place of LED: stator %R1 on (No display at stop.Display
Reserved b2.08 Gain of Slip 0.0~300.0% 0.1% 100.0% ○ 0~3000 power frequency at energy
drive’s
A6.28~ reserved compensation feedback mode)
model
A6.43 b2.09 Slip compensation 0.0~250.0% 0.1% 200.0% ○ 0~2500 BIT1:Setting frequency
b0.07 Leakage 0.00%~50.00% 0.01% Depend × 0~5000
A6.44 Setting value of 0.0~10.0s 0.1s 0.0 ○ 1~100 limit (Flicking.No display at
inductance %Xl on
timer 1 b2.10 Slip compensation 0.1~25.0s 0.1s 2.0s ○ 0~250 energy feedback mode)
drive’s
A6.45 Setting value of 0~100s 1s 0 ○ 1~100 time constant BIT2:Output current
model
timer 2 b2.11 auto energy-saving 0: Disable 1 0 × 0~1 (No display at stop.Display
b0.08 Resistance of 0.00%~50.00% 0.01% Depend × 0~5000
A6.46 Target value of 0~65535 1 100 ○ 0~65535 function 1: Enable power frequency at energy
rotor %R2 on
counter b2.12 Frequency decrease 0.00~99.99Hz/s 0.01 10.00 ○ 0~9999 feedback mode)
drive’s
A6.47 Intermediate value 0~65535 1 50 ○ 0~65535 rate at voltage Hz/s Hz/s BIT3:Output voltage
model
of counter compensation (No display at stop.Display
b0.09 Exciting 0.0%~2000.0% 0.1% Depend × 0~20000
A6.48~ Reserved Reserved 1 50 ○ 0~65535 b2.13 Zero-frequency 0.00~300.00Hz 0.01Hz 0.50Hz ○ 0~30000 power frequency at energy
inductance %Xm on
A6.49 Operation threshold feedback mode)
drive’s
A6.50 Multi-speed terminal 0~500 1 300 ○ 0~65535 b2.14 Zero-frequency 0.00~300.00Hz 0.01Hz 0.00Hz ○ 0~30000 Ten’s place of LED:
model
switching time Hysteresis BIT0: AI
b0.10 Current without 0.1~999.9A 0.1A Depend × 1~9999
A6.51~ Reserved - 1 0 ○ 0~65535 (Reserved) BIT3: DI terminal status
load I0 on
b2.15 Fan control 0: Auto operation mode 1 0 × 0~1 Hundred’s place of LED:
A6.60 drive’s
1:Fan operate continuously BIT0:Output power
Group A8:Fault parameters model
when power is on (No display at stop and
A8.00 Protective action of Unit’s place of LED: 1 0000 × 0~1111H b0.11 Auto-tuning 0: Auto-tuning is disabled 1 0 × 0~3
Note: energy feedback mode)
relay Action selection for 1: Stationary auto-tuning
1.Continue to operate for 3 BIT1:Output torque
under-voltage fault (Start auto-tuning to a
minutes (No display at stop and
indication. standstill motor)
Group b3:Communication parameter energy feedback mode)
0:Disable; 2: Rotating auto-tuning
b3.00 Communication Unit’s place of LED: 1 001 × 0~155H BIT2:Analog close-loop
1: Enable b0.12 Motor’s overload 20.0%~110.0% 0.1% 100.0% × 200~1100 feedback(%)
Ten’s place of LED: Protection configuration Baud rate selection
0:4800BPS (No display at feedback
Action selection for auto coefficient
1:9600BPS mode)
reset interval fault b0.13 Oscillation 0~255 1 10 ○ 0~255
2:19200BPS BIT3:Analog close-loop
indication. inhibition
Ten’s place of LED: setting(%)(Flicking, no
0:Disable coefficient
Data format display at feedback mode)
1: Enable
13 14 15 16

Function Factory Setting Function Factory Setting Function Factory Setting Function Factory Setting
Name Descriptions Unit Modif Name Descriptions Unit Modif Name Descriptions Unit Modif Name Descriptions Unit Modif
code setting range code setting range code setting range code setting range
Thousand’s place of LED: C2: Simple PLC d0.05 Output voltage 0~480V 1V 0 * 0~480 Group U0:Factory parameters
BIT0:Bus voltage C2.00 Simple PLC Unit’s place of LED: 1 0000 × 0~1123H d0.06 Output current 0.0~3Ie 0.1A 0.0 * 0~65535 U0.00 Factory password **** 1 Factory - 0~FFFF
BIT1:Speed(R/MIN) operation mode PLC operation mode d0.07 Torque current -300.0~+300.0% 0.1% 0.0% * 0~6000 Note: setting
(No display at feedback selector 0: No function d0.08 Magnetic flux 0~+100.0% 0.1% 0.0% * 0~1000 Other parameters in this
mode) 1: Stop after single cycle current group can’t display until
BIT2:Setting speed 2: Keep final states after d0.09 Motor power 0.0~200.0(Corresponding 0.1% 0.0% * 0~2000 entering the right
(R/MIN)(Flicking, no single cycle to the motor’s rated power) password.
display at feedback mode) 3: Continuous cycle d0.10 Motor estimated -300.00~300.00Hz 0.01 0.00 * 0~60000 Group P0:Factory parameters
Note: Ten’s place of LED: frequency P0.00 Reserved Reserved 1 Factory * 0~65535
If all the BITs are 0, the Start mode d0.11 Motor actual -300.00~300.00Hz 0.01 0.00 * 0~60000 setting
drive will display setting 0: Start from first step frequency
frequency at stop, display Note:
1: Start from the step d0.12 Bus voltage 0~800V 1V 0 * 0~800
output frequency at before stop (or alarm). ○:Can be modified during operation;
d0.13 Drive operation 0~FFFH 1 0 * 0~FFFFH
operating and display bus 2: Start from the step and
status bit0: Run/Stop ×:Cannot be modified during operating;
voltage at energy feedback frequency before stop(or *:Actually detected and cannot be revised;
bit1: Reverse/Forward
mode. alarm) -:Defaulted by factory and cannot be modified.
bit2: Operating at zero
b4.06 Linear speed ratio 0.00~99.99 0.01 1.00 ○ 0~9999 Hundred’s place of LED:
frequency
b4.07 Speed ratio 0.000~30.000 0.001 1.000 ○ 0~30000 Storage after power off
bit3: Accelerating
b4.08~ Reserved Reserved 1 0 ○ 0~65535 0: Disable Application
bit4: Decelerating
b4.09 1: Save the segment
bit5: Operating at constant 1. Terminal control starting, analog input as reference frequency.
b4.10 Customer 0~65535 1 0 × 0~65535 frequency when power off
speed In many cases, inverter is generally started by external terminals. The frequency is usually adjusted
parameter 0:Not valid Thousand’s place of LED:
bit6: Pre-commutation
initialization Time unit selector for each by the potentiometer or external 0/4~20mA analog input to adjust the inverter running frequency.
bit7: Tuning
b4.11~ Reserved Reserved 1 0 ○ 0~65535 step Parameters settings and wiring diagram as follows:
bit8: Over-current limiting
b4.15 0: Second
bit9: DC over-voltage 1) Parameter settings:
b4.16 Standard/high 0: Standard(0-300HZ) 0 0 × 0~1 1: Minute
limiting First of all, set parameters of group b0 according to the motor parameters on the motor
frequency 1: high frequency C2.01 Step 1 setting Unit’s of LED: 1 000 ○ 0~323H bit10: Torque limiting
switching (0-3000HZ) 0: Multiple frequency N nameplate. Then do auto-tuning. Then set the following parameters:
bit11: Speed limiting
b4.17~ Reserved Reserved (N: corresponding to bit12: Drive fault A0.02=1 AI1 as reference frequency. Select analog voltage or current signal by the jumper in
b4.20 current step) bit13: Speed control control board.
Group C0:Multi-section parameters 1: Defined by A0.02 bit14: Torque control
2: Multiple closed-loop A0.04=1 Operating commands are given by terminal.
C0.00~ Multi-speed from Lower limit of frequency~ 0.01Hz 5.00Hz ○ 0~30000 d0.14 Input terminals 0~FFH, 1 00 * 0~FFH
reference N A1.12=0 Reverse running is allowable.
C0.14 1~15 upper limit of frequency status 0: OFF; 1: ON
(N: corresponding to A6.00=01 Motor running forward when X1 is valid.
Group C1:Process PID parameters d0.15 Output terminals 0~1FH, 1 0 * 0~1FH
current step)
C1.00 Close-loop control 0: Disable1: Enable 1 0 × 0~1 status 0: OFF; 1: ON A6.01=02 Motor running reverse when X2 is valid.
3: Defined by C1.01
function d0.16 AI input -10.00~10.00V 0.01V 0.00 * 0~2000 2) Wiring:
Ten’s place of LED:
C1.01 Reference channel 0: Digital input 1 1 ○ 0~3 0: Forward d0.19 Percentage of AI -100.00%~110.00% 0.01% 0.00 * 0~20000
selection 1: AI 1: Reverse after regulation
C1.02 Feedback channel 0: AI 1 0 ○ 0 2: Defined by operation d0.24 Process close-loop -100.0~100.0% 0.1% 0.0% * 0~2000
selection command reference (Ratio of the full range)
C1.03 Digital setting of -10.00V~10.00V 0.01 0.00 ○ 0~2000 Hundred’s place of LED: d0.25 Process close-loop -100.0~100.0% 0.1% 0.05% * 0~2000
reference 0: Acc/Dec time 1 feedback (Ratio of the full range)
C1.05 Min reference 0.0%~(C1.07) 0.1% 0.0% ○ 0~1000 1: Acc/Dec time 2 d0.26 Process close-loop -100.0~100.0% 0.1% 0.0% * 0~2000
(Ratio of Min reference to 2: Acc/Dec time 3 error (Ratio of the full range)
base value of10V/20mA) 3: Acc/Dec time 4 d0.27 Process close-loop -100.0~100.0% 0.1% 0.0% * 0~2000
C1.06 Feedback value 0.0~100.0% 0.1% 0.0% ○ 0~1000 C2.02 Step 1 operating 0.0~6500.0 0.1 20.0 ○ 0~65000 (Ratio of the full range)
corresponding to (Ratio of Min reference to time d0.28 Temperature of 0.0~150.0℃ 0.1℃ 0.0 * 0~1500
the Min reference base value of 10V/20mA) C2.03~ Step N setting and Step N setting is same as 1 000 ○ 0~323H heat sink 1
C1.07 Max reference (C1.05)~100.0% 0.1% 100.0% ○ 0~1000 C2.30 Step N operating C2.01 0.1 20.0 ○ 0~65000 d0.29 Temperature of 0.0~150.0℃ 0.1℃ 0.0 * 0~1500
(Ratio of Max reference to time Step N operating time same heat sink 2
base value of 10V/20mA) as C2.02 d0.30 Total conduction 0~65535 hours 1 hours 0 * 0~65535
C1.08 Feedback value 0.0~100% 0.1% 100.0% ○ 0~1000 Group C3: Swing parameters time
corresponding to (Ratio of Max reference to C3.00 Swing function 0: Disable 1 0 × 0~1 d0.31 Total operating 0~65535 hours 1 hours 0 * 0~65535
the Max reference base value of 10V/20mA) selector 1: Enable time 2. Terminal control starting, multi-speed operation.
C1.09 Proportional gain 0.000~10.000 0.001 2.000 ○ 0~10000 C3.01 Swing Operation Unit’s place of LED: 1 0000 × 0~1111H d0.32 Total fan’s 0~ 65535 hours 1 hours 0 * 0~65535 Control VFD starting via terminal, set VFD running at 10HZ, 30HZ, 50HZ. Switch frequency by X
KP mode Startup method operating time terminals.
C1.10 Integral gain Ki 0.000~10.000 0.001 0.100 ○ 0~10000 0: Auto mode1: d0.33 ASR controller -300.0~300.0% 0.1% 0.0% * 0~6000
○ First of all, set parameters of group b0 according to the motor parameters on the motor nameplate. Then
C1.11 Differential gain 0.000~10.000 0.001 0.100 0~10000 By terminal output (Corresponding to drive’s
Kd Ten’s place of LED: Swing rated torque) do auto-tuning. Then set the following parameters:
C1.12 Sampling cycle T 0.01~50.00s 0.01s 0.50s ○ 1~5000 control d0.34~ Reserved Reserved 1 0 * 0~65535 1) Parameter settings:
C1.13 Output filter 0.01~10.00s 0.01s 0.05 ○ 1~1000 0: Reference centre d0.56 A0.02=0 Main frequency is set by A0.03.
C1.14 Error limit 0.0~20.0% 0.1% 2.0% ○ 0~200 frequency Group d1:Fault record
A0.03=10 When X2/X3 are invalid, main frequency is 10HZ.
(Corresponding to 1: Reference max. d1.00 Fault record 1 0~55 1 0 * 0~50
close-loop reference) frequency A0.04=1 Operating commands are given by terminals.
d1.01 Bus voltage of the 0~999V 1V 0V * 0~999
C1.15 Close-loop 0: Positive 1 0 × 0~1 Hundred’s place of LED: latest failure A6.00=01 When X1 is valid, motor run forward.
regulation 1: Negative Swing states storage d1.02 Actual current of 0.0~999.9A 0.1A 0.0A * 0~9999 A6.01=27 When X2 is valid, preset frequency 1 as main frequency.
characteristic 0: Save after stop the latest failure A6.02=28 When X3 is valid, preset frequency 2 as main frequency.
C1.16 Integral regulation 0: Stop integral regulation 1 0 × 0~1 1: Not save after stop d1.03 Operation 0.00Hz~300.00Hz 0.01Hz 0.00Hz * 0~30000
Thousand’s place of LED: C0.00=30 Set preset frequency 1=30HZ.
selection when the frequency frequency of the
reaches the upper and Swing states latest failure C0.01=50 Set preset frequency 2=50HZ.
lower limits storage after power failure d1.04 Operation status of 0~FFFFH 1 0000 * 0~FFFFH 2) Wiring:
1: Continue the integral 0: Save the latest failure
regulation when the 1: Not save
d1.05 Fault record 2 0~55 1 0 * 0~50
frequency reaches the C3.02 Preset swing 0.00Hz~Max. frequency 0.01Hz 0.00Hz ○ 0~
d1.06 Fault record 3 0~55 1 0 * 0~50
upper and lower limits frequency 100000
Group d2:Product Identity Parameters
C1.17 Preset close-loop 0.00~300.00Hz 0.01Hz 0.00Hz ○ 0~30000 C3.03 Waiting time for 0.0~3600.0s 0.1s 0.0s ○ 0~36000
d2.00 Serial number 0~FFFF 1 100 * 0~65535
frequency preset swing
d2.01 Software version 0.00~99.99 1 1.00 * 0~9999
C1.18 Holding time of 0.0~3600.0s 0.1s 0.0s × 0~36000 frequency
number
preset close-loop C3.04 Swing amplitude 0.0%~50.0% 0.1% 0.0% ○ 0~500
d2.02 Custom-made 0~9999 1 0 * 0~9999
frequency C3.05 Jump frequency 0.0%~50.0% 0.1% 0.0% ○ 0~500
version number
C1.19~ Preset close-loop -10.00V ~10.00V 0.01V 0.00V ○ 0~2000 C3.06 Swing cycle 0.1~999.9s 0.1s 10.0s ○ 1~9999
d2.03 Load type selection 0: Heavy load G 1 0 × 0~9
C1.33 reference 1~15 C3.07 Triangle wave 0.0%~100.0% 0.1% 50.0% ○ 0~1000
1: Light load L
C1.34 Close-loop output 0: The close-loop output is 1 0 ○ 0~1 rising time (Swing cycle)
2~9: Reserved
reversal selection negative, the drive will Group d0:Status display
d2.04 Rated voltage Output power,0~999.9KvA 0.1KVA Factory * 0~9999
operate at zero frequency. d0.00 Main reference -300.00~300.00Hz 0.01Hz 0.00 * 0~60000 (Dependent on drive’s setting
1: The close-loop output is frequency model)
negative and the drive d0.01 Auxiliary reference -300.00~300.00Hz 0.01Hz 0.00 * 0~60000 d2.05 Rated current 0~999.9A 1V Factory * 0~999
operate reverse. frequency (Dependent on drive’s setting
C1.35 Sleep function 0: Disable 1 0 ○ 0~1 d0.02 Preset frequency -300.00~300.00Hz 0.01Hz 0.00 * 0~60000 model)
selection 1: Enable. d0.03 Frequency after -300.00~300.00Hz 0.01Hz 0.00 * 0~60000 d2.06 Rated current 0~999.9A 0.1A Factory * 0~9999
C1.36 Sleep level 0.0~100.0% 0.1% 50.0% ○ 0~1000 Acc/Dec (Dependent on drive’s setting
C1.37 Sleep latency 0.0~6000.0s 0.1s 30.0s ○ 0~60000 d0.04 Output frequency -300.00~300.00Hz 0.01Hz 0.00 * 0~60000 model)
C1.38 Wake-up level 0.0~100.0% 0.1% 50.0% ○ 0~1000