Drawing List
NR SD MCP A SC G000 FI Drawing List SD.MCP.A.SC.G000(FI) - Drawing List.pdf 29/11/2019

Group A - CABLE CAR STATION n20


SD MCP A PF -2 C001 2 FI Plan L-2_+1406 m - L-3_+1399.84 m SD.MCP.A.PF.L-2.C001.r2(FI) - Plan L-2_+1406 m - L-3_+1399.84 1 : 200 29/11/2019
m.pdf

NR SD MCP A SE C002 2 FI Section A-A' - Section B-B' SD.MCP.A.SE.C002.r2(FI) - Section A-A' - Section B-B'.pdf 1 : 200 29/11/2019

Group A - WINERY, RESTAURANT


NR SD MCP A AV W025 2 FI Axonometric view SD.MCP.A.AV.W025.r2(FI) - Axonometric view.pdf 1 : 100 29/11/2019

NR SD MCP A EL W007 2 FI North Elevation - West Elevation SD.MCP.A.EL.W007.r2(FI) - North Elevation - West Elevation.pdf 1 : 200 29/11/2019
NR SD MCP A EL W008 2 FI South Elevation - East Elevation SD.MCP.A.EL.W008.r2(FI) - South Elevation - East Elevation.pdf 1 : 200 29/11/2019

NR SD MCP A EX 2 W010 2 FI Restaurant SD.MCP.A.EX.L2.W010.r2(FI) - Restaurant.pdf 1 : 100 29/11/2019


NR SD MCP A EX 0 W011 2 FI Grape unloading area-cold room, SD.MCP.A.EX.L0.W011.r2(FI) - Grape unloading area-cold room, 1 : 100 29/11/2019
Steel vat room Steel vat room.pdf
NR SD MCP A EX 0 W012 2 FI Tasting Area (pipe) SD.MCP.A.EX.L0.W012.r2(FI) - Tasting Area (pipe).pdf 1 : 100 29/11/2019
NR SD MCP A EX -1 W013 2 FI Cask room, Barrique room SD.MCP.A.EX.L-1.W013.r2(FI) - Cask room, Barrique room.pdf 1 : 100 29/11/2019
NR SD MCP A EX -2 W014 2 FI Aging in bottle room, Bottling area SD.MCP.A.EX.L-2.W014.r2(FI) - Aging in bottle room, Bottling 1 : 100 29/11/2019
area.pdf
NR SD MCP A EX W015 2 FI Winery shop, Auditorium SD.MCP.A.EX.W015.r2(FI) - Winery shop, Auditorium.pdf 1 : 100 29/11/2019
NR SD MCP A EX -2 W016 2 FI Entrance cilinder SD.MCP.A.EX.L-2.W016.r2(FI) - Entrance cilinder.pdf 1 : 100 29/11/2019

NR SD MCP A MS 008 2 FI Masterplan SD.MCP.A.MS.008.r2(FI) - Masterplan.pdf 1 : 500 29/11/2019

SD MCP A PF 3 W001 2 FI Plan L3_+1433.71 m SD.MCP.A.PF.L3.W001.r2(FI) - Plan L3_+1433.71 m.pdf 1 : 200 29/11/2019
SD MCP A PF 2 W002 2 FI Plan L2_+1429.63 m SD.MCP.A.PF.L2.W002.r2(FI) - Plan L2_+1429.63 m.pdf 1 : 200 29/11/2019
SD MCP A PF 1 W003 2 FI Plan L1_+1425.38 m SD.MCP.A.PF.L1.W003.r2(FI) - Plan L1_+1425.38 m.pdf 1 : 200 29/11/2019
SD MCP A PF 0 W004 2 FI Plan L0_+1419.60 m SD.MCP.A.PF.L0.W004.r2(FI) - Plan L0_+1419.60 m.pdf 1 : 200 29/11/2019
SD MCP A PF -1 W005 2 FI Plan L-1_+1412.80 m SD.MCP.A.PF.L-1.W005.r2(FI) - Plan L-1_+1412.80 m.pdf 1 : 200 29/11/2019
SD MCP A PF -2 W006 2 FI Plan L-2_+1406 m SD.MCP.A.PF.L-2.W006.r2(FI) - Plan L-2_+1406 m.pdf 1 : 200 29/11/2019

NR SD MCP A SC 004 2 FI Area schedule SD.MCP.A.SC.004.r2(FI) - Area schedule.pdf 1 : 500 29/11/2019


NR SD MCP A SC 005 2 FI Area Tabulation - BOH/FOH SD.MCP.A.SC.005.r2(FI) - Area Tabulation - BOH/FOH.pdf 1 : 500 29/11/2019

NR SD MCP A SE W009 2 FI Sections A-A', B-B', C-C', D-D', E-E', SD.MCP.A.SE.W009.r2(FI) - Sections A-A', B-B', C-C', D-D', E-E', 1:200 29/11/2019
F-F' F-F'.pdf

Group C - TOPOGRAPHY, CONNECTIONS


NR SD MCP A T001 2 FI Site Plan / 3D Views / Sections SD.MCP.A.T001.r2(FI) - Site Plan / 3D Views / Sections 1 : 500 29/11/2019
1-1'_2-2'_3-3' 1-1'_2-2'_3-3'.pdf

JH200103: Information in drawings marked NR were used to review drawing nos. C001, W001-to-W006 and were not reviewed.
JH200103: Provide area tabulation and description of area.
Unable to compute occupant load because no area
tabulation for cable car station building was provided.

JH200103: Common path of travel


exceeds 6.3m for assembly occupancy.

Common path of travel exceeds 23m for


assembly occupancy with occupant load JH200103: L-3 does not appear to have any means of
not more than 50 persons egress. Provide at least one means of egress for L-3. NFPA
101, 2018, 4.5.3.1 requires "two means of egress, as a
minimum" but provides an exception in 7.13.2 for stories
JH200103: Dead-end corridor used exclusively for mechanical equipment if that story is not
exceeds 6.1m for assembly in excess of the common path of travel limitations in 7.13.1
occupancy (15m)

A A

11
3,
43
24

3
.1

m
5

m B B

+1406.00

C C

27
.0
2
D D
+1405.45

5
.3
45

60
3.
88
9.

+1396.50

5.
56
20
5.

+1400.64
BOARDING

6.
16
AREA
ARCHITECTURAL CONSULTANT STRUCTURAL AND STRUCTURAL AND
GEOTECHNICAL CONSULTANT MEP CONSULTANT
m
m
5,
56
0
MC&P
11
MC&P Marco Casamonti & Partners srl AEI PROGETTI srl GPA srl
10 10 Lungarno Benvenuto Cellini 13 Via Bolognese 48 via G. da S. Giovanni, 87
L3

L2

50125 Firenze – Italy 50139 Firenze – Italy 52027, San Giovanni Valdarno (AR)

G
0

OIN
L1

TG
.9
L3

OU
L2

G
14

OIN
tel: +39 055 6580127 tel: +39 055 470774 t: +39 055 468291
L1

TG
L3

14
OU
L2

G
OIN
L1

TG
marcocasamontiepartners@legalmail.it mail: mail@aieprogetti.it info@gpapartners.com

.9
OU
ING
UR

0
AS
ME
L
RA
web: www.aeiprogetti.net

NE
GE
L3

G
L2

IN M
L1

CO
L3

IN
L2

IN M
L1

CO
IN
9
LANDING ARCHITECT ENGINEER ENGINEER
AREA
27

Prof. Arch. Marco Casamonti Eng. Stefano Valentini Eng. Giovanni Cardinale
.0
3

T
A
E
5
LI L

STRUCTURAL AND
7 GEOTECHNICAL CONSULTANT
7
5
EL
LI
A
T

6 6 HYDEA S.p.A
T
A
EL
LI
5

Via del Rosso Fiorentino 2/g


50142 Firenze – Italy
tel: +39 055 719491
mail: mail@hydea.it
web: www.en.hydea.it
5 5
ENGINEER
Eng. Paolo Giustiniani

4 4 PROJECT NAME

Ba Na by Night
ADDRESS
3 3 Ba Na Hills
Da Nang, Vietnam
JH200103: Provide additional CLIENT
SUN GROUP
2
means of egress for L-2 that is 2
remote from the current means of SHEET CODE

egress. NFPA 101, 2018, 4.5.3.1 SD.MCP.A.PF.L-2.C001.r2(FI)


1 1
requires "two means of egress, as DESIGN PHASE . ORIGINATOR . DISCIPLINE . VIEW TYPE . LEVEL . SHEET NUMBER . REVISION (ISSUE TYPE)

SHEET NAME
a minimum" Plan L-2_+1406 m - L-3_+1399.84 m
DESIGN PHASE - DISCIPLINE
Rev Number Rev Date Rev Description
SCHEMATIC DESIGN 0 23/10/2019 FIRST ISSUE
Architecture 1 12/11/2019 SUBMISSION FOR AUTHORITY
2 29/11/2019 SD FINAL SUBMISSION
SCALE
As indicated

DATE
29/11/2019

RESERVED SPACE

(CC)A_FE_L-2 (C)A_F_L-3
1
A 2 3
4
B 5 6
C 7
8 9 11 12
D 10 13
1415
E 16
F 17
18
19
G
H

LEGEND

RESTAURANT

TECHNICAL AREA

JH200103
- The restaurant does not appear to have sufficient means of
A
1 egress. Provide at least three means of egress for L3. NFPA
6.25 2 101, 2018, 7.4.1.2 requires not less than 3 means of egress
3.50
3 for occupant load more than 500 but not more than 1000.
Based on the area tabulation provided, the total occupant
7.75 4
B load for L3 is 998 persons (restaurant: 996 persons;
7.75 5 technical areas: 2 persons)
C 6
3.50

7.75 7

7.75 8 11
9 12
3.50
D

7.75 10 13

7.75 14
15
3.50

E
7.75
16

F 7.75 17
+1429.63
3.25
18

9.25
19
G
6.05

7.00
H

8.30

+1434.22

JH201003: Spiral staircase is not specifically


+1433.20
permitted as means of egress in NFPA 101,
2018, chapter 12 for assembly occupancies

6.45
I

3.50
7.75
ARCHITECTURAL CONSULTANT STRUCTURAL AND STRUCTURAL AND
GEOTECHNICAL CONSULTANT MEP CONSULTANT

MC&P
MC&P Marco Casamonti & Partners srl AEI PROGETTI srl GPA srl

7.75
Lungarno Benvenuto Cellini 13 Via Bolognese 48 via G. da S. Giovanni, 87
50125 Firenze – Italy 50139 Firenze – Italy 52027, San Giovanni Valdarno (AR)
tel: +39 055 6580127 tel: +39 055 470774 t: +39 055 468291
marcocasamontiepartners@legalmail.it mail: mail@aieprogetti.it info@gpapartners.com
web: www.aeiprogetti.net

ARCHITECT ENGINEER ENGINEER

3.50
+1434.22 Prof. Arch. Marco Casamonti Eng. Stefano Valentini Eng. Giovanni Cardinale

STRUCTURAL AND
GEOTECHNICAL CONSULTANT

6.45
JH201003: Are these swing doors or sliding doors?
HYDEA S.p.A
Via del Rosso Fiorentino 2/g
50142 Firenze – Italy
NFPA 101, 2018 does not permit the use of sliding doors as means of tel: +39 055 719491
mail: mail@hydea.it

3.80
web: www.en.hydea.it
egress for this type of assembly occupancy.
ENGINEER
Eng. Paolo Giustiniani

If these doors are intended as means of egress, the doors are not
PROJECT NAME
sufficiently remote from one another. NFPA 101, 2018, 7.5.1.3.3 Ba Na by Night
requires that the min. separation of the two exits to be more than ADDRESS

one-third (1/3) max. overall diagonal of the space (diameter of the Ba Na Hills

0
15.3
Da Nang, Vietnam
circle) CLIENT
SUN GROUP

SHEET CODE

SD.MCP.A.PF.L3.W001.r2(FI)
DESIGN PHASE . ORIGINATOR . DISCIPLINE . VIEW TYPE . LEVEL . SHEET NUMBER . REVISION (ISSUE TYPE)

SHEET NAME

Plan L3_+1433.71 m
DESIGN PHASE - DISCIPLINE
Rev Number Rev Date Rev Description
JH201003: Provide at least 2 means of egress SCHEMATIC DESIGN 0 23/10/2019 FIRST ISSUE
Architecture 1 12/11/2019 SUBMISSION FOR AUTHORITY
from inner circular area. 2 29/11/2019 SD FINAL SUBMISSION
SCALE
1 : 200

DATE
29/11/2019

RESERVED SPACE
1
A 2 3
4
B 5 6
C 7
8 9 11 12
D 10 13
1415
E 16
F 17
18
19
G
H
JH200103: Door leaf width less than
810mm. NFPA 101, 2018,
I
7.2.1.2.3.2(1) requires one door leaf to
be not less than 810m when two door
leaves are provided

JH200103: No means of egress provided.


This space appears to be accessible for
equipment maintenance purposes but was
not included in legend and area tabulation.

At least two exits required to comply with


max. travel distance: 76m; max. common LEGEND
path of travel: 30m; and, max. dead-end
corridor:15m LOCKERS

RESTAURANT JH200103: Total area for


A
1
HORIZONTAL CONNECTIONS
technical areas is 1005.96
6.25 2 JH200103: Include this area into area m². This is different from
3.50
3
tabulation. What is the intended use of this SERVICES area tabulation in
space? Will it be sprinklered? SD.MCP.A.SC.004.r2(FI)
7.75 4 TECHNICAL AREA
B

2.60
7.75 5 VERTICAL CONNECTIONS
6
C
3.50

TECHNICAL AREAS - L2
7.75 7
JH201003: Are these Cod. Area Name

7.75 8 openings
11 in the floor slab 41 128.31 m² Technical Room Domestic Cold and Hot Water
42 50.99 m² Air Louvers
9
(sky lights)?
12

6.80
3.50 43 30.01 m² Air Louvers
D 7.00
41 44 189.65 m² Technical Room HVAC System

0
36.4 7.75 10 13 45 182.44 m² Air Louvers
101 46 198.68 m² Air Louvers
.30
47 139.47 m² Kitchen
7.75 14 48 39.72 m² Lockers

15
JH200103: The required 49 46.69 m² WC
1.00 3.50
means of egress from the

0
31.3
E
7.75
16 L2 restaurant and
7.00 staircase on GL/D-18 JH200103
F 7.75 17
appears to be through this - Provide name and area measurement for every
1.15
3.25
interior18 space but there area/space/room
20.7
0 0.85
9.25 does not appear to be any
G
42 unobstructed way of 19
travel
6.05
from this area to a public
46
H 2.10
7.00 7.00 way.
43
8.30

2.60
7.00
JH200103: Means of
45 2.60
egress from these exits is
20.9
0
through interior space that
21.1
0
does not appear to be any
unobstructed way of travel

9
11.3
to a public way.

6.45
mm
7.00
+1429.63

728
I
3.45

3.50
20.7
0

44

8.26
0.85

JH201003: Are these

7.75
structural elements for the

2.60
6.35

roof or openings in the slab?

2.60
+1429.63

7.75
ARCHITECTURAL CONSULTANT STRUCTURAL AND STRUCTURAL AND
GEOTECHNICAL CONSULTANT MEP CONSULTANT

MC&P
JH200103: No means of egress provided.
One means of egress is sufficient if MC&P Marco Casamonti & Partners srl AEI PROGETTI srl GPA srl

3.50
Lungarno Benvenuto Cellini 13 Via Bolognese 48 via G. da S. Giovanni, 87

common path of travel is less than 30m 50125 Firenze – Italy


tel: +39 055 6580127
50139 Firenze – Italy
tel: +39 055 470774
52027, San Giovanni Valdarno (AR)
t: +39 055 468291
marcocasamontiepartners@legalmail.it mail: mail@aieprogetti.it info@gpapartners.com
and occupant load is not more than 500 47
web: www.aeiprogetti.net

persons

6.45
ARCHITECT ENGINEER ENGINEER
Prof. Arch. Marco Casamonti Eng. Stefano Valentini Eng. Giovanni Cardinale

STRUCTURAL AND
GEOTECHNICAL CONSULTANT

3.80
49 HYDEA S.p.A
Via del Rosso Fiorentino 2/g
50142 Firenze – Italy
tel: +39 055 719491
mail: mail@hydea.it
web: www.en.hydea.it

48 ENGINEER

JH200103: All exit staircases Eng. Paolo Giustiniani

0
15.3
appear to discharge through PROJECT NAME

interior building area (roofed over Ba Na by Night


area). ADDRESS
Ba Na Hills
Da Nang, Vietnam
CLIENT
NFPA 101, 2018, 7.7.2 permits not SUN GROUP
more than 50 percent of the
SHEET CODE
required number of exits and 50
percent of the exit stair capacity to SD.MCP.A.PF.L2.W002.r2(FI)
DESIGN PHASE . ORIGINATOR . DISCIPLINE . VIEW TYPE . LEVEL . SHEET NUMBER . REVISION (ISSUE TYPE)

discharge through interior SHEET NAME

buildings; subject to other Plan L2_+1429.63 m


conditions DESIGN PHASE - DISCIPLINE
Rev Number Rev Date Rev Description
SCHEMATIC DESIGN 0 23/10/2019 FIRST ISSUE
Architecture 1 12/11/2019 SUBMISSION FOR AUTHORITY
2 29/11/2019 SD FINAL SUBMISSION
SCALE
1 : 200

DATE
29/11/2019

RESERVED SPACE
1
A 2 3
4
B 5 6
C 7
8 9 11 12
D 10 13
1415
E 16
F 17
18
19
G
H

LEGEND

JH201003: Common path of LOCKERS


travel exceeds limit of 30m for HORIZONTAL CONNECTIONS
industrial occupancy.
1 TECHNICAL AREA
A

6.25 2
3
3.50
12.0
0
7.75 4
B

5
10.2
38 5.50
7.75 5 TECHNICAL AREAS - L1

5.70
6
C Cod. Area Name
3.50
2.15 11.8
5
2.10 38 123.00 m² Technical Room-Electrical MV/LV + SPECIAL
7.75 7 SYSTEM
40
7.00
,37 39 41.00 m² Fire Fighting Station
7 m
7.00 40 123.00 m² Technical Room Fire Fighting Tank - 650 mc
m 7.75 8 11
7.00 9 12
3.50
D

5
10.8
2.70

21.1
0
7.75 10 13
JH200103
7.75 14
- Provide name and area measurement for every
15 area/space/room
1.00 3.50

0
22.0
3.15 7.00
E
7.75
7.00
16

5
F 7.75 17
10.8
7.55
20.7
0
3.25
39 1.15 18
5

2.15
10.2

4.00
40 2.25
0.85
9.25
19
5.25
G 7.00
7.50 6.05

7.00
5.70

2.15 8.35 7.00


5.50 2.10
H
2.60

8.35 3.20
7.00
8.30
12.3
11.8 3.00 0
JH200103: No means of egress provided. 5
7.00

One means of egress is sufficient if 40,363 mm 2.70


7.00
common path of travel is less than 30m
and occupant load is not more than 500 13.0
0

persons 88.2
5

6.45
21.1
0 4.90

2.40
7.00
I
2.60

3.50
7.00 4.50
85.3 7.55
0

0
11.2
1.15
2.15

7.10
2.25

mm
0.85

7.75
20.7

736
0 5.24

7.00

2.35
7.00

2.35

7.75
ARCHITECTURAL CONSULTANT STRUCTURAL AND STRUCTURAL AND
GEOTECHNICAL CONSULTANT MEP CONSULTANT

MC&P
MC&P Marco Casamonti & Partners srl AEI PROGETTI srl GPA srl

3.50
Lungarno Benvenuto Cellini 13 Via Bolognese 48 via G. da S. Giovanni, 87
50125 Firenze – Italy 50139 Firenze – Italy 52027, San Giovanni Valdarno (AR)
tel: +39 055 6580127 tel: +39 055 470774 t: +39 055 468291
marcocasamontiepartners@legalmail.it mail: mail@aieprogetti.it info@gpapartners.com
web: www.aeiprogetti.net

6.45
ARCHITECT ENGINEER ENGINEER
Prof. Arch. Marco Casamonti Eng. Stefano Valentini Eng. Giovanni Cardinale

STRUCTURAL AND
GEOTECHNICAL CONSULTANT

3.80
JH200103: Door leaves have width less than 810mm. HYDEA S.p.A
Via del Rosso Fiorentino 2/g
NFPA 101, 2018, 7.2.1.2.3.2(1) requires one door leaf to 50142 Firenze – Italy
tel: +39 055 719491
mail: mail@hydea.it
be not less than 810m when two door leaves are provided web: www.en.hydea.it

ENGINEER
Eng. Paolo Giustiniani

0
15.3
PROJECT NAME

Ba Na by Night
ADDRESS
Ba Na Hills
Da Nang, Vietnam
CLIENT
SUN GROUP

SHEET CODE

SD.MCP.A.PF.L1.W003.r2(FI)
DESIGN PHASE . ORIGINATOR . DISCIPLINE . VIEW TYPE . LEVEL . SHEET NUMBER . REVISION (ISSUE TYPE)

SHEET NAME

Plan L1_+1425.38 m
DESIGN PHASE - DISCIPLINE
Rev Number Rev Date Rev Description
SCHEMATIC DESIGN 0 23/10/2019 FIRST ISSUE
Architecture 1 12/11/2019 SUBMISSION FOR AUTHORITY
2 29/11/2019 SD FINAL SUBMISSION
SCALE
1 : 200

DATE
29/11/2019

RESERVED SPACE
1
A 2 3
4
JH200103: B 5 6
C 7
What is the volume of alcohol present in these rooms? Please provide engineering analysis 8 9 11 12
D
for smoke. 10 13
1415
E 16
F 17
18
The unenclosed floor openings from L-2 to L-1 to L0 create communicating spaces/atriums in G
19

these three cylinders. H

These spaces do not meet the requirements of NFPA 101, 2018 as a communicating space -- I

i.e. they must be treated as atriums -- because the lowest or next-to-lowest story within this
communicating space is NOT a street floor.

For atriums, NFPA 101, 2018 only allows low or ordinary hazard contents and requires
engineering analysis for smoke. The alcohol stored in this area does not have to be
considered high hazard content if the quantity is below 230L for sprinkler-protected buildings.

LEGEND

LOADING/UNLOADING AREA + GRAPE PRESS AREA

SCENIC PATH

1
A
HORIZONTAL CONNECTIONS

6.25 2 JH200103: Area for


STEEL VAT ROOM
3
tasting room is different

m
3.50

74 m
5 mm
4
TASTING ROOM from area tabulation in

22,6
7.75
+1419.60
SD.MCP.A.SC.004.r2(FI)

19,39
5.50
JH201003: Are these swing doors or sliding doors? B
SERVICES
7.75 5

NFPA 101, 2018 does not permit the use of sliding doors as means of C 34 9.85
3.50
6
TECHNICAL AREA
2.15 m
m mm
egress for this type of assembly occupancy. 2.10
7.75 7
,8
0 9 98
,6
5.00 7.00
20 23

2.60
1.70
2.73 7.75 8 11
7.00 9 12 FOH/ID NUMBER SCHEDULE - L0
5.50 3.50
D
2.70
Cod. Area Volume Medium Height Department
+1419.60 7.75 10 13
+1419.60 13.5 26 138.39 m² 1081.11 m³ 7.81 LOADING/UNLOADING AREA

0
5
+ GRAPE PRESS AREA

36.4
7.75 14 27 103.13 m² 845.74 m³ 8.2 STEEL VAT ROOM

0
34.4
28 55.48 m² 484.15 m³ 8.73 TASTING ROOM
7.00 15
+1419.60 1.00 3.50 29 65.79 m² 562.74 m³ 8.55 SCENIC PATH

0
22.0
3.15 30 8.43 m² 25.29 m³ 3 SERVICES
E +1412.80
35 7.00
7.75
16
31
32
14.43 m²
8.19 m²
43.29 m³
24.57 m³
3
3
SERVICES
SERVICES
33 31.35 m² 163.02 m³ 5.2 SERVICES
1.70
F +1419.60 16.7
0 7.75 17 34 31.35 m² 100.29 m³ 3.2 SERVICES
5.55 35 8.19 m² 24.57 m³ 3 SERVICES
+1412.80
28 36 1.15 3.25
36 14.43 m² 43.29 m³ 3 SERVICES
18 37 8.45 m² 25.35 m³ 3 SERVICES
29 +1419.60
+1405.50
2.15
2.25
0.85 9.25
7.00
3.25 19
G 2.20 37 1.70
6.05
JH200103
- Provide additional egress capacity or reduce front-of-house
2.95

7.00 8.35
2.15
5.70

H 33
5.50
2.10 +1405.50
+1419.60 27 3.20
7.00
areas. Occupant load on this floor exceeds total egress
5.00 8.35

1.70 8.30
capacity provided by the 7 exit stairs (OL: 1664 persons;
9.85
7.00
3.00
capacity: 1127 persons)
+1406.00 +1419.60
2.70

7.00
+1419.60 - Provide name and area measurement for every
14.7
area/space/room
5
+1419.60
88.0
26
JH200103: Dead-end 32 0

6.45
3.15

corridor exceeds 6.3m.

2.40
7.00

NFPA 101, 2018, 12.2.5.1.3


I 2.83 1.70
+1419.60
2.60

does not allow dead-end 31

3.50
4.50
85.3 7.00 5.55
0

0
11.2
corridors to exceed 6.3m for m
m 1.15
2.15
4.37
3
assembly occupancies. 49 2.25

7.10
24
, 0.86 30
m
m

3.24
56

7.75
16.7 1.70
0
,6
27

7.00 +1412.80
mm

2.35
23,651
26,875 mm

7.00

2.35

7.75
JH200103: Tasting rooms also +1419.60
+1419.60 ARCHITECTURAL CONSULTANT STRUCTURAL AND
GEOTECHNICAL CONSULTANT
STRUCTURAL AND
MEP CONSULTANT

require two exits remote from MC&P


one another because occupant
load for every room exceeds 50 MC&P Marco Casamonti & Partners srl AEI PROGETTI srl GPA srl

3.50
Lungarno Benvenuto Cellini 13 Via Bolognese 48 via G. da S. Giovanni, 87
50125 Firenze – Italy 50139 Firenze – Italy 52027, San Giovanni Valdarno (AR)
persons per room. tel: +39 055 6580127
marcocasamontiepartners@legalmail.it
tel: +39 055 470774
mail: mail@aieprogetti.it
t: +39 055 468291
info@gpapartners.com
web: www.aeiprogetti.net

6.45
ARCHITECT ENGINEER ENGINEER
Prof. Arch. Marco Casamonti Eng. Stefano Valentini Eng. Giovanni Cardinale
JH200103: Dead-end STRUCTURAL AND
corridor exceeds 6.3m. GEOTECHNICAL CONSULTANT

NFPA 101, 2018, 12.2.5.1.3

3.80
does not allow dead-end JH200103: Door leaves have width less than 810mm. HYDEA S.p.A

corridors to exceed 6.3m for NFPA 101, 2018, 7.2.1.2.3.2(1) requires one door leaf to
Via del Rosso Fiorentino 2/g
50142 Firenze – Italy
tel: +39 055 719491
assembly occupancies. be not less than 810m when two door leaves are provided mail: mail@hydea.it
web: www.en.hydea.it

ENGINEER
Eng. Paolo Giustiniani

0
15.3
PROJECT NAME

Ba Na by Night
ADDRESS
Ba Na Hills
Da Nang, Vietnam
CLIENT
SUN GROUP

SHEET CODE

SD.MCP.A.PF.L0.W004.r2(FI)
DESIGN PHASE . ORIGINATOR . DISCIPLINE . VIEW TYPE . LEVEL . SHEET NUMBER . REVISION (ISSUE TYPE)

SHEET NAME

Plan L0_+1419.60 m
DESIGN PHASE - DISCIPLINE
Rev Number Rev Date Rev Description
SCHEMATIC DESIGN 0 23/10/2019 FIRST ISSUE
Architecture 1 12/11/2019 SUBMISSION FOR AUTHORITY
2 29/11/2019 SD FINAL SUBMISSION
SCALE
1 : 200

DATE
29/11/2019

RESERVED SPACE
1
A 2 3
4
JH200103: B 5 6
C 7
What is the volume of alcohol present in these rooms? Please provide engineering analysis 8 9 11 12
D 10 13
for smoke. 1415
E 16
F 17
18
The unenclosed floor openings from L-2 to L-1 to L0 create communicating spaces/atriums in G
19

these three cylinders. H

These spaces do not meet the requirements of NFPA 101, 2018 as a communicating space -- I

i.e. they must be treated as atriums -- because the lowest or next-to-lowest story within this
communicating space is NOT a street floor.

For atriums, NFPA 101, 2018 only allows low or ordinary hazard contents and requires
engineering analysis for smoke. The alcohol stored in this area does not have to be
considered high hazard content if the quantity is below 250L for sprinkler-protected buildings.

LEGEND

JH200103: Provide additional AUDITORIUM


exit remote from existing exit.
BARRIQUE ROOM
Steel vat room require two exits
1
A remote from one another CASK ROOM
6.25 2 because occupant load 50
3
3.50 persons. LOCKERS

7.75 4 HORIZONTAL CONNECTIONS


B 5.50

JH200103: Change JH200103: Provide


7.75 5 STEEL VAT ROOM
doors
C
to swing in 9.85
6 seating plan for
direction of egress 2.15
3.50
further comments SERVICES
7.75 7

2.60
5.00
TECHNICAL AREA
1.70
16.7
0 7.75 8 11
JH200103: Dead-end corridor exceeds
7.00
3.50
9 12 6.1m. Eliminate corridor if possible
D
2.70

7.75 10 13
6.40
JH200103: Common path of travel

0
36.4
FOH/ID NUMBER SCHEDULE - L-1
+1412.80
22 1.70
16.7
0 7.75 14 exceeds 23m. Eliminate corridor if

0
34.4
4.85 Cod. Area Volume Medium Height Department
1.00
3.50
15 possible

0
3.15 13 162.61 m² 916.43 m³ 5.64 AUDITORIUM

22.0
E +1412.80 14 121.67 m² 452.64 m³ 3.72 STEEL VAT ROOM
23 7.00
7.75
16 15 138.19 m² 779.13 m³ 5.64 BARRIQUE ROOM
16 138.26 m² 795.19 m³ 5.75 CASK ROOM
1.70 17 8.43 m² 25.29 m³ 3 SERVICES
F 7.75 17
28,5 5.55 18 14.43 m² 43.29 m³ 3 SERVICES
5 3m
m
24 26.0
0 19 7.95 m² 23.86 m³ 3 SERVICES
16 +1412.80
+1412.80 1.15
2.15
3.25
18 20 15.44 m² 46.33 m³ 3 LOCKERS
+1405.50
2.25
21 16.35 m² 49.06 m³ 3 LOCKERS
0.85 9.25 22 16.35 m² 49.06 m³ 3 LOCKERS
5.25 19 23 8.19 m² 24.57 m³ 3 SERVICES
G 24 14.43 m² 43.29 m³ 3 SERVICES
+1412.80 25 6.05 25 13.65 m² 40.95 m³ 3 SERVICES
7.00 8.35

H
2.15
2.10
+1405.50
15 +1412.80 3.20
7.00
2.60

5.00
8.35
JH200103
8.30
1.70 28,6 - Provide additional egress capacity or reduce front-of-house
9.85 14 6 8m
m
3.00 12.3
0

2.85
7.00
+1406.00
areas. Occupant load on this floor exceeds total egress
2.70
capacity provided by the 7 exit stairs (OL: 1563 persons;
21
16.7
6.40 capacity: 1127 persons)
0 1.70
20 28,5

m
885 13

16 m
.03
6.05 0 mm - Provide name and area measurement for every

6.45
19

28,4
3.15
area/space/room

2.40
7.00 +1412.80
I 16.7 +1412.80
0 2.60
1.70
18

3.50
4.50
JH200103: 85.3
0 5.55

0
11.2
4.37
Common 1.15
2.15
2.25
path of travel

7.10
0.86
17
3.24

7.75
exceeds 16.7
0 1.70

23m. 7.00

Provide exit 2.35

at the top of 7.00

escalator 2.35

7.75
ARCHITECTURAL CONSULTANT STRUCTURAL AND STRUCTURAL AND
+1412.80 GEOTECHNICAL CONSULTANT MEP CONSULTANT

MC&P
MC&P Marco Casamonti & Partners srl AEI PROGETTI srl GPA srl

3.50
Lungarno Benvenuto Cellini 13 Via Bolognese 48 via G. da S. Giovanni, 87
50125 Firenze – Italy 50139 Firenze – Italy 52027, San Giovanni Valdarno (AR)
tel: +39 055 6580127 tel: +39 055 470774 t: +39 055 468291
marcocasamontiepartners@legalmail.it mail: mail@aieprogetti.it info@gpapartners.com
web: www.aeiprogetti.net

6.45
ARCHITECT ENGINEER ENGINEER
Prof. Arch. Marco Casamonti Eng. Stefano Valentini Eng. Giovanni Cardinale

STRUCTURAL AND
GEOTECHNICAL CONSULTANT
JH200103: Door leaves have width less than 810mm.

3.80
NFPA 101, 2018, 7.2.1.2.3.2(1) requires one door leaf to
be not less than 810m when two door leaves are provided HYDEA S.p.A
Via del Rosso Fiorentino 2/g
50142 Firenze – Italy
tel: +39 055 719491
mail: mail@hydea.it
web: www.en.hydea.it

ENGINEER
Eng. Paolo Giustiniani

0
15.3
PROJECT NAME

Ba Na by Night
ADDRESS
Ba Na Hills
JH200103: Da Nang, Vietnam
CLIENT
Change doors to SUN GROUP

swing in direction SHEET CODE


of egress
SD.MCP.A.PF.L-1.W005.r2(FI)
DESIGN PHASE . ORIGINATOR . DISCIPLINE . VIEW TYPE . LEVEL . SHEET NUMBER . REVISION (ISSUE TYPE)

SHEET NAME

Plan L-1_+1412.80 m
DESIGN PHASE - DISCIPLINE
Rev Number Rev Date Rev Description
SCHEMATIC DESIGN 0 23/10/2019 FIRST ISSUE
Architecture 1 12/11/2019 SUBMISSION FOR AUTHORITY
2 29/11/2019 SD FINAL SUBMISSION
SCALE
1 : 200

DATE
29/11/2019

RESERVED SPACE
JH200103:
1
What is the volume of alcohol present in these rooms? Please provide engineering analysis for smoke. A 2 3
4
B 5 6
C 7
The unenclosed floor openings from L-2 to L-1 to L0 create communicating spaces/atriums in these three cylinders. D
8 9 11 12
10 13
1415
E 16
These spaces do not meet the requirements of NFPA 101, 2018 as a communicating space -- i.e. they must be F 17
18
treated as atriums -- because the lowest or next-to-lowest story within this communicating space is NOT a street G
19
H
floor.

1 For atriums, NFPA 101, 2018 only allows low or ordinary hazard contents and requires engineering analysis for I

A
smoke. The alcohol stored in this area does not have to be considered high hazard content if the quantity is below
2
6.25
3
230L for sprinkler-protected buildings.
3.50

7.75 4
B 5.50

7.75 5
9.85
6

2.60
C
3.50
2.15
2.10
7.75 7 JH200103: Change

2.60
5.00

1.70
doors to swing in
16.7

7.00
0 7.75 8 11
direction of egress
9 12
3.50
D
2.70
0
6.40
7.75 10 13 LEGEND
36.4

1.70
16.7
0 7.75 14
0
34.4 4.85 SHOP
15
1.00
3.50

0
22.0
3.15
E +1406.00 BOTTLE AGING ROOM
8 7.00
7.75
16

1.70
BOTTLING AREA
F 16.7 17
0 7.75
4 5.55
WINE STORAGE
+1406.00 9 1.15
2.15
3.25
18
+1405.50
2.25
0.85 9.25 HORIZONTAL CONNECTIONS
7.00
3.25 19
G 1.70
10 6.05 SERVICES
7.00 8.35
2.15 3 +1406.00
2.60

+1405.50
2.10 3.02 3.20
7.00 TECHNICAL AREA
H
2.00
5.00
2.93
8.30 VERTICAL CONNECTIONS
2.60

1.70 12.3
9.85
2 11
3.00 0

2.85
7.00
+1406.00
2.70 +1406.00

6.40 FOH/ID NUMBER SCHEDULE - L-2


16.7
0 Cod. Area Volume Medium Height Department
1.70
1
6.05 88.0 138.15 m² 778.68 m³ 5.64 SHOP
0 1

6.45
2 138.15 m² 778.80 m³ 5.64 BOTTLE AGING ROOM
3.15
7 3 138.26 m² 795.16 m³ 5.75 BOTTLING AREA

2.40
4 173.08 m² 975.33 m³ 5.64 WINE STORAGE
7.00
5 8.43 m² 25.29 m³ 3 SERVICES
I 16.7 +1406.00
0 2.60 6 14.43 m² 43.29 m³ 3 SERVICES
1.70
6

3.50
4.50 7 7.95 m² 23.86 m³ 3 SERVICES
85.3 8.19 m² 24.57 m³ 3 SERVICES
0 8

0
11.2
1.15
4.37 9 14.43 m² 43.29 m³ 3 SERVICES
2.15 10 8.45 m² 25.35 m³ 3 SERVICES

7.10
2.25 11 20.79 m² 62.36 m³ 3 SERVICES
0.86
3.24 5 12 43.51 m² 131.18 m³ 3.01 SERVICES

7.75
16.7
0 1.70

7.00

2.35
JH200103
7.00 4.44 - Provide additional egress capacity or reduce front-of-house
2.35 areas. Occupant load on this floor exceeds total egress

7.75
capacity provided by the 7 exit stairs (OL: 2221 persons
+1406.00
[excl. cable car station]; capacity: 1127 persons). Cable car
station excluded because there is no area tabulation.

3.50
- Provide name and area measurement for every
12 area/space/room

6.45
JH200103: Door leaves have width less than 810mm.

3.80
NFPA 101, 2018, 7.2.1.2.3.2(1) requires one door leaf to
be not less than 810m when two door leaves are provided

0
15.3
ARCHITECTURAL CONSULTANT STRUCTURAL AND STRUCTURAL AND
GEOTECHNICAL CONSULTANT MEP CONSULTANT

MC&P
MC&P Marco Casamonti & Partners srl AEI PROGETTI srl GPA srl
Lungarno Benvenuto Cellini 13 Via Bolognese 48 via G. da S. Giovanni, 87
50125 Firenze – Italy 50139 Firenze – Italy 52027, San Giovanni Valdarno (AR)
tel: +39 055 6580127 tel: +39 055 470774 t: +39 055 468291
marcocasamontiepartners@legalmail.it mail: mail@aieprogetti.it info@gpapartners.com
web: www.aeiprogetti.net

+1406.00 ARCHITECT ENGINEER ENGINEER


Prof. Arch. Marco Casamonti Eng. Stefano Valentini Eng. Giovanni Cardinale

STRUCTURAL AND
GEOTECHNICAL CONSULTANT

HYDEA S.p.A
Via del Rosso Fiorentino 2/g
50142 Firenze – Italy
tel: +39 055 719491
5
.3 mail: mail@hydea.it
45
web: www.en.hydea.it
+1405.45
ENGINEER
Eng. Paolo Giustiniani

PROJECT NAME

Ba Na by Night
ADDRESS
Ba Na Hills
Da Nang, Vietnam
CLIENT
SUN GROUP

SHEET CODE

SD.MCP.A.PF.L-2.W006.r2(FI)
DESIGN PHASE . ORIGINATOR . DISCIPLINE . VIEW TYPE . LEVEL . SHEET NUMBER . REVISION (ISSUE TYPE)

SHEET NAME

Plan L-2_+1406 m

6.
22
DESIGN PHASE - DISCIPLINE
Rev Number Rev Date Rev Description
SCHEMATIC DESIGN
27

0 23/10/2019 FIRST ISSUE


.0

Architecture
4

1 12/11/2019 SUBMISSION FOR AUTHORITY


2 29/11/2019 SD FINAL SUBMISSION
SCALE
1 : 200

DATE
29/11/2019

RESERVED SPACE
MC&P – Marco Casamonti & Partners

The building is provided with a full Air Conditioning system (heat pumps), electrically
operated, to cool and heat properly the different areas maintaining the wine production
area with a controlled temperature in between 16-18° with a humidity factor of 85%.

In order to reduce the noise impact and to let the

Fresh air exchanges are granted with proper ducts running all along the building above
suspended ceilings..
JH201003: Do the winery building and cable car station building share the same sprinkler, hydrant
and fire hose system or does each building have an independent system?
A full sprinkler system + hydrants + fire hose is provided for the fire-fighting system.

Plumbing network will be made with insulate polyethylene pipes.

Discharge water pipelines will convey the sewages (black/grey/white) in to the existing
water and sewage management system at the Ba Na site.

All the production areas were machines are in function will be kept visible (with glass walls)
but separate from the visitors pathways.

Building B – Cable Car Station

The building B, is divided into two levels:

Basement (m.1399,84 a.s.l.) for technical systems and installations


Ground floor (at m.1406,0 a.s.l.) for the disembarking from the Cable Car.
The ground floor host the loading and unloading visitors area and the Doppelmayr control
cabin.

The basement floor will be used to allocate all the MEP services to serve the Station N°20 as:
emergency electric generators, transformation cabin, electric distribution cabin, diesel fuel
tank, fire fighting water tank

Structures
Building A (winery) will have a cellular foundation in reinforced concrete.
Main external, internal walls and slabs will be built in reinforced concrete.

MC&P Marco Casamonti & Partners – Firenze 50125 – Lungarno Benvenuto Cellini 13