Академический Документы
Профессиональный Документы
Культура Документы
4 ent
1 05 - d o cum
4J 0 u
0_6 ité d
2 5 142 a v alid
50
tion
,l sion
l i s a e d ver
uti at
ant upd
i e r , av n l y if
if
Vér C U12/10/2016 se o IBERTO GUYNET PEIRANO UPDATE
B 23/09/2016 IBERTO GUYNET PEIRANO UPDATE
A 22/043/2016 SOURIAU DISPENSA PEIRANO FIRST ISSUE
Rev Date Written Checked Approved Subject
PROJECT:
K3 CHP Facility
Kemsley Mill, Sittingbourne, Kent
CUSTOMER:
ED
EPC CONTRACTOR:
PT
E
CE
SUBCONTRACTOR:
BP
AC
TITLE OF DOCUMENT:
an
PIPING CLASS
d
we
vie
This document is property of CNIM. It cannot be used reproduced, transmitted and/or disclosed without the prior written permission of CNIM
N° document :
Page Issue:
Re
A - First issue
B - Update (design conditions)
C C1.2:
- Modification of class LAA C.1.2-2 (T=300°C instead of 250°C)
- Modification of class LBD C.1.2-2 (T=250°C instead of 170°C)
- Creation of class LBS C1.2-2 (0,5 bars / 250°C)
- Creation of class LBA C1.2-2 (4 bars / 400°C)
C3.1:
- Modification of class LBA C.3.1-2 (P=20 bars instead of 15 bars)
- Suppression of class LCC C3.1-2
C6.1:
- Modification of class LBA C.6.1-1 (T=425°C instead of 370°C)
- Modification of class LBA C.6.1-2 (T=370°C instead of 425°C)
C9.1:
- Modification of class LAB C.9.1-2 (P=97 bars instead of 91 bars)
- Modification of class LBA C.9.1-1 (T=305°C instead of 310°C)
50251420_64J0105-C-PIPING CLASS
Revisions
Designation Class / PN Pipe material TAG INDEX Typical Fluid P bar(g) T °C
CLASS C1.1 PN 16 P265GH EGD 1 Diesel oil 15 40
GAC 1 Raw Water 15 40
GCK 1 Demineralised Water 10 70
GKB 1 Town Water 10 40
GTA 1 Water recovery from waste water 10 90
GMA 1 Industrial Used Water 10 90
HLW 1 Sweeping Air 0,5 250
PGB 1 Component cooling water 10 100
SGA 1 Fire Extinction Water 15 40
CLASS C1.2 150 P265GH LAA 1 Feed water tank 0,5 145
LAA 2 Feed water tank 6 300
LAB 1 Feed water 0,5 165
LAB 2 Feed water 7 165
LBA 1 High pressure steam piping system 10 20
LBA 2 High pressure steam piping system 4 400
LBD 1 Medium pressure steam piping system 10 300
LBD 2 Medium pressure steam piping system 0,5 250
LBD 3 Medium pressure steam piping system 6 300
LBD 4 Medium pressure steam piping system 6 200
LBD 5 Medium pressure steam piping system 1 150
LBD 6 Medium pressure steam piping system 2,5 210
LBD 7 Medium pressure steam piping system 0,5 150
LBS 1 Low pressure steam piping system 0,5 150
LBS 2 Low pressure steam piping system 0,5 250
LBE 1 Vacuum Steam 0,5 150
LCA 1 Condensate 0,5 150
LCA 2 Condensate 1,5 150
LCN 1 Auxiliary steam condensate 0,5 150
LCN 2 Auxiliary steam condensate 1 150
LCN 3 Auxiliary steam condensate 10 300
LCN 4 Auxiliary steam condensate 10 185
LCN 5 Auxiliary steam condensate 10 200
LCN 6 Auxiliary steam condensate 6 200
LCN 7 Auxiliary steam condensate 0,5 300
LFC 1 Drains 0,5 100
LFC 2 Drains 0,5 400
LFC 3 Drains 0,5 150
LFC 4 Drains 3 150
LFC 5 Drains 6 165
MAJ 1 Air removal system 0,5 150
MAJ 2 Air removal system 0,5 420
CLASS C1.4 PN 16 TP316L EGD 1 Diesel oil 15 40
GAC 1 Raw Water 15 40
GBE 1 Oxygen reducer 7 40
GBE 2 Oxygen reducer 7 165
GCK 1 Demineralised Water 10 70
GKB 1 Town Water 10 40
GMA 1 Industrial Used Water 10 90
GTA 1 Water recovery from waste water 10 90
QEB 1 Service Air 10 50
QFB 1 Instrument Air 10 50
PGB 1 Component cooling water 10 100
SGA 1 Fire Extinction Water 15 40
CLASS C3.1 300 P265GH EGD 1 Diesel oil 25 40
LBD 1 Medium pressure steam piping system 25 300
LBD 2 Medium pressure steam piping system 10 400
LBD 3 Medium pressure steam piping system 12 270
LBD 4 Medium pressure steam piping system 25 400
LCA 1 Condensate 30 150
LCA 2 Condensate 30 210
LBA 1 High pressure steam piping system 25 230
LBA 2 High pressure steam piping system 20 425
LCC 1 Main condensate heating system 30 150
LFC 1 Drains 10 400
CLASS C3.2 300 TP316L EGD 1 Diesel oil 25 40
LCA 1 Condensate 30 150
CLASS C6.1 600 P265GH LAB 1 Feed water 50 165
LBA 1 High pressure steam piping system 44 425
LBA 2 High pressure steam piping system 44 370
CLASS C6.3 600 16Mo3 LBA 2 High pressure steam piping system 55 440
CLASS C9.1 900 P265GH GBE 1 Phosphate 97 40
GBE 2 Phosphate 97 310
LAB 1 Feed water 118 165
LAB 2 Feed water 97 310
LBA 1 High pressure steam piping system 91 305
LBA 2 High pressure steam piping system 97 310
LBD 1 Medium pressure steam piping system 97 310
CLASS C9.3 900 16Mo3 LBA 1 High pressure steam piping system 89,5 450
CLASS C9.4 PN 160 13CrMo4-5 LBA 1 High pressure steam piping system 90 480
CLASS C15.2 1500 TP316L LAB 1 Feed water 118 165
LAB 2 Feed water 97 310
LBA 1 High pressure steam piping system 91 450
LBA 2 High pressure steam piping system 97 310
GBE 1 Phosphate 97 40
GBE 2 Phosphate 97 310
50251420_64J0105-C-PIPING CLASS
Recap
Fluid tag/ Codes fluide Denomination
(HSJ) Ammonia water
(HTK) Lime Slurry
(NDA) District heating
EGD Diesel oil
GAC Raw Water
GBE Oxygen reducer
GBE Hydrochloric acid
GBE Trisodium phosphate
GBE Chlorohydric acid
GBE Trisodic Phosphate
GBE Oxygen reductor
GCK Demineralised Water
GCK Softened water
GKB Town Water
GMA Industrial Used Water
HLW Sweeping Air
LAA Feed water tank
LAB Feed water
LBA High pressure steam piping system
LBD Medium pressure steam piping system
LBE Vacuum Steam
LBS Low pressure steam piping system
LCA Condensate
LCC Main condensate heating system
LCN Auxiliary steam condensate
LCN Auxiliary steam condensate
LFC Drains
MAG Condensing system
PAB Cooling Water
PGB Component cooling water
QEA Compressed Air Production
QEB Service Air
QFB Instrument Air
QFC Service Air
SDA Central vacuum system
SGA Fire Extinction Water
MAJ Air removal system
GTA Water recovery from waste water
50251420_64J0105-C-PIPING CLASS
Codes Fluides
STANDARD FOR FLANGES / NORME BRIDES : EN 1759
DN OD THICKNESS / EPAISSEURS
50251420_64J0105-C-PIPING CLASS
Standards-Ep
CLASS C1.1
PN PN 16
Pipe material/ Matériau P265GH
Group of material/ Groupe de matériau ISO 15608 1.1
Seamless/
Type sans soudure
Standard EN10216-2
Corrosion allowance/ Surépaisseur de corrosion [mm] 1,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 410 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 252 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 265 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 171 [N/mm2]
Maxi. design temp. with yield stress/ Temp. maxi de calcul en limite élastique 450 [°C]
Mini. design temp. with hot flow (10000 h)/ Temp. mini de calcul avec fluage (10000 h) 400 [°C]
Maxi. design temp. with hot flow (10000 h)/ Temp. maxi de calcul avec fluage(10000 h) 500 [°C]
Mini. yield stress Rp0,2 at design temp. (°C)/ Limite d'élasticité Rp0,2 (Mpa) à la temp. de (°C)
Temp. 50 100 150 200 250 300 350 400 450 --- --- ---
Rp0,2T 265 226 213 192 171 154 141 134 128 --- --- ---
Creep rupture strength / Résistance à la rupture par fluage pour 10000 h (MPa) (11)
Temp. 400 410 420 430 440 450 460 470 480 490 500 --- --- --- --- --- --- ---
RmT 182 166 151 138 125 112 100 88 77 67 58 --- --- --- --- --- --- ---
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if other
materials than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la norme
EN13480-5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3 -or
submitted to a flexibility analysis. According
to § 8.2.1 of EN13480-5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le § 12.2.10.1
de la norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée, l'étendue des
contrôles NDE peut être réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTE 4 : Allowable stress is indicated NA when the allowable stress is the one without creep and stress rupture.
La contrainte de calcul correspondant aux conditions de fluage est notée NA lorsque la contrainte prépondérante est celle sans fluage.
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTE 6 Piping used in the creep range, are classified in category III for NDE extend determination.
Dans le domaine du fluage , les tuyauteries sont classées en categorie III pour la determination des contrôles (article 8.2.1 norme EN 13480)
50251420_64J0105-C-PIPING CLASS
C11a
NOTE 7 All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between CNIM and
the Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles fera
l'objet d'un accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In this
case the concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées, p. ex.
les échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
NOTE 10 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5.
Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 11 : For pipings with design temp. T>413 °C a counting system will be provided to control time of exceeding of the service temp. limit of 413°C. According to §5.2 of EN13480-3 security factor of 1,25 is
applied to hot flow design stress corresponding to 10000 h life time.
Pour les cas de fonctionnement avec T>413°C, un système de suivi de la durée de dépassement de 413°C sera prévu. Par conséquent, conformément au §5.2 de la EN13480-3, un coéf. de
sécurité de 1,25 est appliqué à la valeur de la contrainte de rupture par fluage pour une durée de 10000 h.
NOTE 12 : (**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle NDE
Fluid Tag/ Code fluide
Insulation thickness/
Design at design temp. Sealing
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Design Soudures circ. Soudures SW
Conditions de
Groupe fluide
calcul Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 11,78 16,84 6,9 NA 0 yes/ oui 0 0 0 0 2 0
20 0 12,37 17,69 7,2 NA 0 yes/ oui 0 0 0 0 2 0
25 0 13,29 19,01 7,8 NA 0 yes/ oui 0 0 0 0 2 0
40 0 16,10 23,02 9,4 NA 0 yes/ oui 0 10 0 10 2 0
50 0 17,34 24,80 10,2 NA 0 yes/ oui 0 10 0 10 2 0
80 0 21,95 31,39 12,8 NA 0 yes/ oui 0 10 0 10 2 0
28,43 40,66 16,6 0 10 0 10 2 0
Diesel oil
50251420_64J0105-C-PIPING CLASS
C11a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle NDE
Insulation thickness/
Design at design temp. Sealing
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Design Soudures circ. Soudures SW
Conditions de
Groupe fluide
calcul Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 11,78 16,84 6,9 NA 0 yes/ oui 0 0 0 0 2 0
20 0 12,37 17,69 7,2 NA 0 yes/ oui 0 0 0 0 2 0
25 0 13,29 19,01 7,8 NA 0 yes/ oui 0 0 0 0 2 0
40 0 16,10 23,02 9,4 NA 0 yes/ oui 0 0 0 0 2 0
50 0 17,34 24,80 10,2 NA 0 yes/ oui 0 0 0 0 2 0
80 0 21,95 31,39 12,8 NA 0 yes/ oui 0 0 0 0 2 0
Raw Water
50251420_64J0105-C-PIPING CLASS
C11a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle NDE
Insulation thickness/
Design at design temp. Sealing
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Design Soudures circ. Soudures SW
Conditions de
Groupe fluide
calcul Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 11,78
7,85 16,84
11,23 6,9
4,6 NA 0 yes/ oui 0 0 0 0 2 0
20 0 8,25 11,79 4,8 NA 0 yes/ oui 0 0 0 0 2 0
25 0 8,86 12,67 5,2 NA 0 yes/ oui 0 0 0 0 2 0
40 0 10,73 15,35 6,3 NA 0 yes/ oui 0 0 0 0 2 0
50 0 11,56 16,53 6,8 NA 0 yes/ oui 0 0 0 0 2 0
80 0 14,63 20,92 8,6 NA 0 yes/ oui 0 0 0 0 2 0
Town Water
50251420_64J0105-C-PIPING CLASS
C11a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle NDE
Insulation thickness/
Design at design temp. Sealing
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Design Soudures circ. Soudures SW
Conditions de
Groupe fluide
calcul Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 11,78
7,85 16,84
11,23 6,9
5,1 NA 30 ---- 0 0 0 0 2 0
20 0 8,25 11,79 5,4 NA 30 ---- 0 0 0 0 2 0
25 0 8,86 12,67 5,8 NA 30 ---- 0 0 0 0 2 0
40 0 10,73 15,35 7,0 NA 40 ---- 0 0 0 0 2 0
Industrial Used Water
50251420_64J0105-C-PIPING CLASS
C11a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle NDE
Insulation thickness/
Design at design temp. Sealing
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Design Soudures circ. Soudures SW
Conditions de
Groupe fluide
calcul Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 11,78
7,85 16,84
11,23 6,9
5,2 NA 30 ---- 0 0 0 0 2 0
20 0 8,25 11,79 5,5 NA 30 ---- 0 0 0 0 2 0
25 0 8,86 12,67 5,9 NA 30 ---- 0 0 0 0 2 0
Component cooling water
50251420_64J0105-C-PIPING CLASS
C11a
CLASS C1.1
DIMENSIONS :
P265GH SA 234 WPB
Design Thk/ Actual Thk / Design Thk/ Fittings Observations/
DN OD / Diam. ext.
Ep. calculée Ep. réelle Ep. calculée Thk/ Ep Comments
in mm mm mm mm mm
mm
FLANGES/ BRIDES :
FITTINGS/RACCORDS :
DN [mm] Ends / ASME Class / Thk /
Material/ Matériau Standard / Norme
-> <- Embouts Epaisseur
(*) - machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3 and general
requirements of EN 13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les exigences générales
spécifiées dans EN13480-4 s'appliquent au processus de cintrage.
(**) - BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be submited for CNIM approval.
(**) - Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de réf. choisies par le Fournisseur seront
soumises à CNIM pour accord .
Thread/
Material/ Matériaux Type
BOLTING/BOULONNERIE : Filetage
Stud bolts/ Tiges
filetées
42CrMo4 EN10269 --------- In compliance with/ Suivant EN 1515
Métric
Nuts / Ecrous C45E EN10269 Heavy hex
Note:
Low strength bolting shall be used (yield stress < 240 MPa) where steel flanges are bolted to cast iron flanges.
Pour les jonctions comprenant au moins une bride en fonte grise , il est recommandé d'utiliser de la boulonnerie dont la limite élastique ne dépasse pas
240 N/mm2.
50251420_64J0105-C-PIPING CLASS
C11b
GASKETS/JOINTS :
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves that may be
installed on pipings of this class. In some specific cases depending on design conditions and actual valve position the valve description may be
different than the one given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et aider le
concepteur dans la définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des conditions de design et de
fonctionnement le type de robinet peut être différent de la liste ci dessous.
Valves herebelow are valid for utility circuits. For carbon steel valve (Steam, Condensates, Feed water) , valve type are similar to C1.2 class.
Robinetterie ci dessous valide pour les utilités. Pour la robinetterie acier ( Vapeur, Condensats, Eau alimentaire) , le type de robinet sera similaire à la
classe C1.2 .
800 monobloc
Manual/
Manuelle Flexible wedge/ Coin Flanges/
80 400 16 EN 1092 Cast iron/ Fonte (**) 1423/64E0002
flexible Brides
classe Carbon steel/ Acier
15 50 SW EN12760 1423/64E0001
Automatic/ 800 Parallel slide/ Sièges au carbone
Motorisée parallèles Flanges/
80 400 16 EN 1092 Cast iron/ Fonte (**) 1423/64E0002
Brides
Globe/ Rob. Manual/ classe Loose dic/ Soupape
15 50 GAZ ISO 228-1 Copper alloy/ laiton 1423/64E0001
à soupape Manuelle 800 mobile
40 150 1 piece stem and
Manual/ Wafer type/ Steel or cast iron/
16 butterfly-EPDM 1423/64E0001-0002
Manuelle 200 600 A inserer Acier ou fonte
Butterfly/ sleeve /
EN 1092
Papillon (*) Papillon et axe
40 150
Automatic/ monobloc-Manchette Wafer type/ Steel or cast iron/
16 1423/64E0001-0002
Motorisée 200 600 EPDM A inserer Acier ou fonte
50251420_64J0105-C-PIPING CLASS
C11b
CLASS C1.2
Class 150
Pipe material/ Matériau P265GH
Group of material/ Groupe de matériau ISO 15608 1.1
Seamless/
Type sans soudure
Standard EN10216-2
Corrosion allowance/ Surépaisseur de corrosion [mm] 1,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 410 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 252 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 265 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 171 [N/mm2]
Maxi. design temp. with yield stress/ Temp. maxi de calcul en limite élastique 450 [°C]
Mini. design temp. with hot flow (10000 h)/ Temp. mini de calcul avec fluage (10000 h) 400 [°C]
Maxi. design temp. with hot flow (10000 h)/ Temp. maxi de calcul avec fluage(10000 h) 500 [°C]
Mini. yield stress Rp0,2 at design temp. (°C)/ Limite d'élasticité Rp0,2 (Mpa) à la temp. de (°C)
Temp. 50 100 150 200 250 300 350 400 450 --- --- ---
Rp0,2T 265 226 213 192 171 154 141 134 128 --- --- ---
Creep rupture strength / Résistance à la rupture par fluage pour 10000 h (MPa) (11)
Temp. 400 410 420 430 440 450 460 470 480 490 500 --- --- --- --- --- --- ---
RmT 182 166 151 138 125 112 100 88 77 67 58 --- --- --- --- --- --- ---
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if
other materials than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la
norme EN13480-5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3
-or submitted to a flexibility analysis.
According to § 8.2.1 of EN13480-5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le §
12.2.10.1 de la norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée,
l'étendue des contrôles NDE peut être réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTE 4 : Allowable stress is indicated NA when the allowable stress is the one without creep and stress rupture.
La contrainte de calcul correspondant aux conditions de fluage est notée NA lorsque la contrainte prépondérante est celle sans fluage.
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTE 6 Piping used in the creep range, are classified in category III for NDE extend determination.
Dans le domaine du fluage , les tuyauteries sont classées en categorie III pour la determination des contrôles (article 8.2.1 norme EN 13480)
50251420_64J0105-C-PIPING CLASS
C12a
NOTE 7 All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between
CNIM and the Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des
contrôles fera l'objet d'un accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In
this case the concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas
calorifugées, p. ex. les échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
NOTE 10 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5.
Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 11 : For pipings with design temp. T>413 °C a counting system will be provided to control time of exceeding of the service temp. limit of 413°C. According to §5.2 of EN13480-3 security factor
of 1,25 is applied to hot flow design stress corresponding to 100000 h life time.
Pour les cas de fonctionnement avec T>413°C, un système de suivi de la durée de dépassement de 413°C sera prévu. Par conséquent, conformément au §5.2 de la EN13480-3, un coéf.
de sécurité de 1,25 est appliqué à la valeur de la contrainte de rupture par fluage pour une durée de 100000 h.
NOTE 12 : (**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 NS 0,39 0,59 0,3 NA 30 ---- 0 0 0 0 2 0
20 NS 0,42 0,63 0,3 NA 30 ---- 0 0 0 0 2 0
25 NS 0,44 0,66 0,3 NA 30 ---- 0 0 0 0 2 0
40 NS 0,54 0,80 0,4 NA 40 ---- 0 0 0 0 2 0
50 NS 0,60 0,89 0,4 NA 40 ---- 0 0 0 0 2 0
Feed water tank
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 NS
0 0,39
4,71 0,59
9,80 0,3
4,6 NA 30
60 ---- 0 0 0 0 2 0
20 0 5,04 10,48 4,9 NA 60 ---- 0 0 0 0 2 0
25 0 5,32 11,06 5,2 NA 60 ---- 0 0 0 0 2 0
40 0 6,44 13,39 6,3 NA 60 ---- 0 0 0 0 2 0
50 0 7,17 14,92 7,0 NA 60 ---- 0 0 0 0 2 0
Feed water tank
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 NS
0 0,39
5,50 0,59
8,52 0,3
4,0 NA 30 ---- 0 0 0 0 2 0
20 0 5,88 9,11 4,3 NA 30 ---- 0 0 0 0 2 0
25 0 6,20 9,61 4,5 NA 30 ---- 0 0 0 0 2 0
40 0 7,51 11,64 5,5 NA 40 ---- 0 0 0 0 2 0
50 0 8,37 12,97 6,1 NA 40 ---- 0 0 0 0 2 0
80 0 10,24 15,87 7,4 ? 60 ---- 0 0 0 0 2 0
Feed water
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
High pressure steam piping system 15 NS
0 0,39
3,14 0,59
7,51 0,3
3,5 NA 30
60 ---- 0 0 0 0 2 0
20 0 3,36 8,03 3,8 NA 60 ---- 0 0 0 0 2 0
25 0 3,54 8,47 4,0 NA 60 ---- 0 0 0 0 2 0
40 0 4,29 10,26 4,8 NA 80 ---- 0 0 0 0 2 0
50 0 4,78 11,43 5,4 NA 80 ---- 0 0 0 0 2 0
80 0 5,85 13,99 6,6 ? 100 ---- 0 0 0 0 2 0
100 0 7,58 18,12 8,5 ? 100 ---- 0 0 0 0 2 0
150 0 11,26 26,91 12,6 ? 120 ---- yes/ 0 0 0 0 2 0
LBA 2 4 400 89,3 145,6 G2 0,96
200 0 9,51 22,73 10,6 ? 120 ---- oui 0 0 0 0 2 0
250 0 11,90 28,45 13,3 ? 120 ---- 0 0 0 0 2 0
300 I 12,23 29,23 13,7 ? 120 ---- 0 10 0 0 2 0
350 I 11,65 27,86 13,0 ? 120 ---- 0 10 0 0 2 0
400 I 11,93 28,52 13,4 ? 150 ---- 0 10 0 0 2 0
450 I 12,27 29,33 13,7 ? 150 ---- 0 10 0 0 2 0
500 I 13,66 32,65 15,3 ? 150 ---- 0 10 0 0 2 0
600 I 12,08 28,87 13,5 ? 150 ---- 0 10 0 0 2 0
Medium pressure steam piping system
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
Medium pressure steam piping system Medium pressure steam piping system 15 NS 0,39 0,59
0,74 0,3 NA 30
50 ---- 0 0 0 0 2 0
20 NS 0,42 0,79 0,4 NA 50 ---- 0 0 0 0 2 0
25 NS 0,44 0,83 0,4 NA 50 ---- 0 0 0 0 2 0
40 NS 0,54 1,01 0,5 NA 60 ---- 0 0 0 0 2 0
50 NS 0,60 1,12 0,5 NA 60 ---- 0 0 0 0 2 0
80 NS 0,73 1,37 0,6 ? 80 ---- 0 0 0 0 2 0
100 NS 0,95 1,78 0,8 ? 80 ---- 0 0 0 0 2 0
150 NS 1,41 2,64 1,2 ? 80 ---- yes/ 0 0 0 0 2 0
LBD 2 0,5 250 114,0 NA G2 0,09
200 NS 1,19 2,23 1,0 ? 100 ---- oui 0 0 0 0 2 0
250 NS 1,49 2,79 1,3 ? 100 ---- 0 0 0 0 2 0
300 NS 1,53 2,86 1,3 ? 100 ---- 0 0 0 0 2 0
350 NS 1,46 2,73 1,3 ? 100 ---- 0 0 0 0 2 0
400 NS 1,49 2,79 1,3 ? 120 ---- 0 0 0 0 2 0
450 NS 1,53 2,87 1,3 ? 120 ---- 0 0 0 0 2 0
500 NS 1,71 3,20 1,5 ? 120 ---- 0 0 0 0 2 0
600 NS 1,51 2,83 1,3 ? 120 ---- 0 0 0 0 2 0
15 0 4,71 9,80 4,6 NA 60 ---- 0 0 0 0 2 0
20 0 5,04 10,48 4,9 NA 60 ---- 0 0 0 0 2 0
25 0 5,32 11,06 5,2 NA 60 ---- 0 0 0 0 2 0
40 0 6,44 13,39 6,3 NA 60 ---- 0 0 0 0 2 0
50 0 7,17 14,92 7,0 NA 60 ---- 0 0 0 0 2 0
80 0 8,78 18,26 8,6 ? 80 ---- 0 0 0 0 2 0
100 0 11,37 23,66 11,1 ? 80 ---- 0 0 0 0 2 0
150 0 16,89 35,13 16,4 ? 100 ---- yes/ 0 0 0 0 2 0
LBD 3 6 300 102,7 NA G2 1,25
200 I 14,27 29,67 13,9 ? 100 ---- oui 0 10 0 0 2 0
250 I 17,85 37,13 17,4 ? 100 ---- 0 10 0 0 2 0
300 I 18,34 38,15 17,9 ? 100 ---- 0 10 0 0 2 0
350 I 17,48 36,36 17,0 ? 100 ---- 0 10 0 0 2 0
400 I 17,90 37,22 17,4 ? 120 ---- 0 10 0 0 2 0
450 I 18,40 38,28 17,9 ? 120 ---- 0 10 0 0 2 0
500 I 20,49 42,62 20,0 ? 120 ---- 0 10 0 0 2 0
600 II 18,12 37,68 17,6 ? 120 ---- 0 10 0 0 2 0
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
Medium pressure steam piping system Medium pressure steam piping system 15 NS
0 0,39
4,71 0,59
7,86 0,3
3,7 NA 30
40 ---- 0 0 0 0 2 0
20 0 5,04 8,41 3,9 NA 40 ---- 0 0 0 0 2 0
25 0 5,32 8,87 4,2 NA 40 ---- 0 0 0 0 2 0
40 0 6,44 10,74 5,0 NA 50 ---- 0 0 0 0 2 0
50 0 7,17 11,96 5,6 NA 50 ---- 0 0 0 0 2 0
80 0 8,78 14,65 6,9 ? 60 ---- 0 0 0 0 2 0
100 0 11,37 18,97 8,9 ? 60 ---- 0 0 0 0 2 0
150 0 16,89 28,17 13,2 ? 60 ---- yes/ 0 0 0 0 2 0
LBD 4 6 200 128,0 NA G2 1,00
200 I 14,27 23,80 11,1 ? 80 ---- oui 0 10 0 0 2 0
250 I 17,85 29,78 13,9 ? 80 ---- 0 10 0 0 2 0
300 I 18,34 30,60 14,3 ? 80 ---- 0 10 0 0 2 0
350 I 17,48 29,16 13,7 ? 80 ---- 0 10 0 0 2 0
400 I 17,90 29,86 14,0 ? 80 ---- 0 10 0 0 2 0
450 I 18,40 30,70 14,4 ? 80 ---- 0 10 0 0 2 0
500 I 20,49 34,19 16,0 ? 80 ---- 0 10 0 0 2 0
600 II 18,12 30,22 14,2 ? 80 ---- 0 10 0 0 2 0
15 0 0,79 1,18 0,6 NA 40 ---- 0 0 0 0 2 0
20 0 0,84 1,26 0,6 NA 40 ---- 0 0 0 0 2 0
25 0 0,89 1,33 0,6 NA 40 ---- 0 0 0 0 2 0
40 0 1,07 1,61 0,8 NA 50 ---- 0 0 0 0 2 0
50 0 1,20 1,80 0,8 NA 50 ---- 0 0 0 0 2 0
80 0 1,46 2,20 1,0 ? 60 ---- 0 0 0 0 2 0
100 0 1,90 2,85 1,3 ? 60 ---- 0 0 0 0 2 0
150 0 2,81 4,23 2,0 ? 60 ---- yes/ 0 0 0 0 2 0
LBD 5 1 150 142 NA G2 0,15
200 0 2,38 3,58 1,7 ? 80 ---- oui 0 0 0 0 2 0
250 0 2,97 4,47 2,1 ? 80 ---- 0 0 0 0 2 0
300 0 3,06 4,60 2,2 ? 80 ---- 0 0 0 0 2 0
350 0 2,91 4,38 2,1 ? 80 ---- 0 0 0 0 2 0
400 0 2,98 4,49 2,1 ? 80 ---- 0 0 0 0 2 0
450 I 3,07 4,61 2,2 ? 80 ---- 0 10 0 0 2 0
500 I 3,42 5,14 2,4 ? 80 ---- 0 10 0 0 2 0
600 I 3,02 4,54 2,1 ? 80 ---- 0 10 0 0 2 0
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
Medium pressure steam piping system Medium pressure steam piping system 15 NS
0 0,39
1,96 0,59
3,35 0,3
1,6 NA 30
40 ---- 0 0 0 0 2 0
20 0 2,10 3,58 1,7 NA 40 ---- 0 0 0 0 2 0
25 0 2,22 3,78 1,8 NA 40 ---- 0 0 0 0 2 0
40 0 2,68 4,58 2,1 NA 50 ---- 0 0 0 0 2 0
50 0 2,99 5,10 2,4 NA 50 ---- 0 0 0 0 2 0
80 0 3,66 6,24 2,9 ? 60 ---- 0 0 0 0 2 0
100 0 4,74 8,08 3,8 ? 60 ---- 0 0 0 0 2 0
150 0 7,04 12,00 5,6 ? 60 ---- yes/ 0 0 0 0 2 0
LBD 6 2,5 210 125 NA G2 0,43
200 0 5,94 10,14 4,7 ? 80 ---- oui 0 0 0 0 2 0
250 0 7,44 12,69 5,9 ? 80 ---- 0 0 0 0 2 0
300 0 7,64 13,03 6,1 ? 80 ---- 0 0 0 0 2 0
350 0 7,28 12,42 5,8 ? 80 ---- 0 0 0 0 2 0
400 0 7,46 12,72 6,0 ? 80 ---- 0 0 0 0 2 0
450 I 7,67 13,08 6,1 ? 80 ---- 0 10 0 0 2 0
500 I 8,54 14,56 6,8 ? 80 ---- 0 10 0 0 2 0
600 I 7,55 12,87 6,0 ? 80 ---- 0 10 0 0 2 0
15 NS 0,39 0,59 0,3 NA 30 ---- 0 0 0 0 2 0
20 NS 0,42 0,63 0,3 NA 30 ---- 0 0 0 0 2 0
25 NS 0,44 0,67 0,3 NA 30 ---- 0 0 0 0 2 0
40 NS 0,54 0,81 0,4 NA 40 ---- 0 0 0 0 2 0
50 NS 0,60 0,90 0,4 NA 40 ---- 0 0 0 0 2 0
80 NS 0,73 1,10 0,5 ? 60 ---- 0 0 0 0 2 0
100 NS 0,95 1,43 0,7 ? 60 ---- 0 0 0 0 2 0
150 NS 1,41 2,12 1,0 ? 60 ---- yes/ 0 0 0 0 2 0
LBD 7 0,5 150 142 NA G2 0,08
200 NS 1,19 1,79 0,8 ? 60 ---- oui 0 0 0 0 2 0
250 NS 1,49 2,24 1,0 ? 80 ---- 0 0 0 0 2 0
300 NS 1,53 2,30 1,1 ? 80 ---- 0 0 0 0 2 0
350 NS 1,46 2,19 1,0 ? 80 ---- 0 0 0 0 2 0
400 NS 1,49 2,24 1,1 ? 80 ---- 0 0 0 0 2 0
450 NS 1,53 2,31 1,1 ? 80 ---- 0 0 0 0 2 0
500 NS 1,71 2,57 1,2 ? 80 ---- 0 0 0 0 2 0
600 NS 1,51 2,27 1,1 ? 80 ---- 0 0 0 0 2 0
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
Low pressure steam piping system 15 NS 0,39 0,59 0,3 NA 30 ---- 0 0 0 0 2 0
20 NS 0,42 0,63 0,3 NA 30 ---- 0 0 0 0 2 0
25 NS 0,44 0,67 0,3 NA 30 ---- 0 0 0 0 2 0
40 NS 0,54 0,81 0,4 NA 40 ---- 0 0 0 0 2 0
50 NS 0,60 0,90 0,4 NA 40 ---- 0 0 0 0 2 0
80 NS 0,73 1,10 0,5 ? 60 ---- 0 0 0 0 2 0
100 NS 0,95 1,43 0,7 ? 60 ---- 0 0 0 0 2 0
150 NS 1,41 2,12 1,0 ? 60 ---- yes/ 0 0 0 0 2 0
LBS 1 0,5 150 142,0 NA G2 0,08
200 NS 1,19 1,79 0,8 ? 60 ---- oui 0 0 0 0 2 0
250 NS 1,49 2,24 1,0 ? 80 ---- 0 0 0 0 2 0
300 NS 1,53 2,30 1,1 ? 80 ---- 0 0 0 0 2 0
350 NS 1,46 2,19 1,0 ? 80 ---- 0 0 0 0 2 0
400 NS 1,49 2,24 1,1 ? 80 ---- 0 0 0 0 2 0
450 NS 1,53 2,31 1,1 ? 80 ---- 0 0 0 0 2 0
500 NS 1,71 2,57 1,2 ? 80 ---- 0 0 0 0 2 0
600 NS 1,51 2,27 1,1 ? 80 ---- 0 0 0 0 2 0
15 NS 0,39 0,74 0,3 NA 50 ---- 0 0 0 0 2 0
Low pressure steam piping system
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 NS 0,39 0,59 0,3 NA 30 ---- 0 0 0 0 2 0
20 NS 0,42 0,63 0,3 NA 30 ---- 0 0 0 0 2 0
25 NS 0,44 0,67 0,3 NA 30 ---- 0 0 0 0 2 0
40 NS 0,54 0,81 0,4 NA 40 ---- 0 0 0 0 2 0
50 NS 0,60 0,90 0,4 NA 40 ---- 0 0 0 0 2 0
Vacuum Steam
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 NS
0 0,39
1,18 0,59
1,77 0,3
0,8 NA 30 ---- 0 0 0 0 2 0
20 0 1,26 1,89 0,9 NA 30 ---- 0 0 0 0 2 0
25 0 1,33 2,00 0,9 NA 30 ---- 0 0 0 0 2 0
40 0 1,61 2,42 1,1 NA 40 ---- 0 0 0 0 2 0
50 0 1,79 2,70 1,3 NA 40 ---- 0 0 0 0 2 0
80 0 2,19 3,30 1,5 ? 60 ---- 0 0 0 0 2 0
Condensate
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15
15 NS
0 0,39
0,79 0,59
1,18 0,3
0,6 NA
30
40 ----
---- 0
0 0
0 0
0 0
0 2
2 0
0
20 0 0,84 1,26 0,6 NA 40 ---- 0 0 0 0 2 0
25 0 0,89 1,33 0,6 NA 40 ---- 0 0 0 0 2 0
Auxiliary steam condensate
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 NS
0 0,39
7,85 0,59
12,68 0,3
5,9 NA 30
40 ---- 0 0 0 0 2 0
20 0 8,40 13,57 6,4 NA 40 ---- 0 0 0 0 2 0
25 0 8,86 14,31 6,7 NA 40 ---- 0 0 0 0 2 0
Auxiliary steam condensate
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 NS
0 0,39
4,71 0,59
7,86 0,3
3,7 NA 30
40 ---- 0 0 0 0 2 0
20 0 5,04 8,41 3,9 NA 40 ---- 0 0 0 0 2 0
25 0 5,32 8,87 4,2 NA 40 ---- 0 0 0 0 2 0
Auxiliary steam condensate
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 NS 0,39 0,59
0,56 0,3 NA 30 ---- 0 0 0 0 2 0
20 NS 0,42 0,60 0,3 NA 30 ---- 0 0 0 0 2 0
25 NS 0,44 0,63 0,3 NA 30 ---- 0 0 0 0 2 0
40 NS 0,54 0,77 0,4 NA 40 ---- 0 0 0 0 2 0
50 NS 0,60 0,85 0,4 NA 40 ---- 0 0 0 0 2 0
80 NS 0,73 1,05 0,5 NA 40 ---- 0 0 0 0 2 0
100 NS 0,95 1,36 0,6 NA 50 ---- 0 0 0 0 2 0
Drains
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15
15 NS
NS 0,39
0,39 0,59
0,59 0,3
0,3 NA
30
30 ----
---- 0
0 0
0 0
0 0
0 2
2 0
0
20 NS 0,42 0,63 0,3 NA 30 ---- 0 0 0 0 2 0
25 NS 0,44 0,67 0,3 NA 30 ---- 0 0 0 0 2 0
40 NS 0,54 0,81 0,4 NA 40 ---- 0 0 0 0 2 0
50 NS 0,60 0,90 0,4 NA 40 ---- 0 0 0 0 2 0
80 NS 0,73 1,10 0,5 ? 60 ---- 0 0 0 0 2 0
100 NS 0,95 1,43 0,7 ? 60 ---- 0 0 0 0 2 0
Drains
150 NS 1,41 2,12 1,0 ? 60 ---- yes/ 0 0 0 0 2 0
LFC 3 0,5 150 142,0 NA G2 0,08
200 NS 1,19 1,79 0,8 ? 60 ---- oui 0 0 0 0 2 0
250 NS 1,49 2,24 1,0 ? 80 ---- 0 0 0 0 2 0
300 NS 1,53 2,30 1,1 ? 80 ---- 0 0 0 0 2 0
350 NS 1,46 2,19 1,0 ? 80 ---- 0 0 0 0 2 0
400 NS 1,49 2,24 1,1 ? 80 ---- 0 0 0 0 2 0
450 NS 1,53 2,31 1,1 ? 80 ---- 0 0 0 0 2 0
500 NS 1,71 2,57 1,2 ? 80 ---- 0 0 0 0 2 0
600 NS 1,51 2,27 1,1 ? 80 ---- 0 0 0 0 2 0
15 0 2,36 3,54 1,7 NA 30 ---- 0 0 0 0 2 0
20 I 2,52 3,79 1,8 NA 30 ---- 0 10 0 0 2 0
25 0 2,66 4,00 1,9 NA 30 ---- 0 0 0 0 2 0
40 0 3,22 4,84 2,3 NA 40 ---- 0 0 0 0 2 0
50 0 3,59 5,39 2,5 NA 40 ---- 0 0 0 0 2 0
80 0 4,39 6,60 3,1 ? 60 ---- 0 0 0 0 2 0
100 0 5,69 8,55 4,0 ? 60 ---- 0 0 0 0 2 0
Drains
50251420_64J0105-C-PIPING CLASS
C12a
Actual stresses/ NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
Design design temp.
Coating/ Peinture
Sealing
Denomination
Pression d'épreuve
(Actual stress Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure / allowable
les soudures
Design Soudures circ. Soudures SW
Groupe fluide
Conditions de Soudure
fluide
calcul
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
calcul conditions/ d'étanch.
conditions/ contr. réelle /
Stress
Conditions Surface Surface
Sans Conditions contr. Volume Volume Surface Surface
rupture (4) de calcul NDE NDE
fluage d'épreuve admissible) NDE NDE NDE NDE
P T 10000h (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 NS 0,39 0,59 0,3 NA 30 ---- 0 0 0 0 2 0
20 NS 0,42 0,63 0,3 NA 30 ---- 0 0 0 0 2 0
25 NS 0,44 0,67 0,3 NA 30 ---- 0 0 0 0 2 0
40 NS 0,54 0,81 0,4 NA 40 ---- 0 0 0 0 2 0
Air removal system
50251420_64J0105-C-PIPING CLASS
C12a
CLASS C1.2
DIMENSIONS :
P265GH SA 234 WPB
Design Thk/ Pipes Thk/ Design Thk/ Fittings Thk/ Observations/
DN OD/ Diam. ext.
Ep. calculée Ep tuyauteries Ep. calculée Ep raccords Comments
in mm mm mm mm mm mm
Note : Connecting piping with machining or reducing, see sheet "FITTINGS WELDING DETAILS"
Voir les raccordements par usinage ou par délardage sur la feuille "SOUDURE DES RACCORDS"
FLANGES/ BRIDES :
FITTINGS/RACCORDS :
DN [mm] Material/ Ends / ASME Class / Thk /
Standard / Norme
-> <- Matériau Embouts Epaisseur
(*) - Machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3 and general requirements
of EN 13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les exigences générales spécifiées
dans EN13480-4 s'appliquent au processus de cintrage.
(**) : EN10253-2 type A fittings not accepted. BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be
submited for CNIM approval.
(**) Raccords selon EN10253-2 type A non admis. Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de réf.
choisies par le Fournisseur seront soumises à CNIM pour accord .
Thread/
Material/ Matériaux Type
BOLTING/BOULONNERIE : Filetage
Stud bolts/ 42CrMo4 / A193B7
Tiges filetées EN10269
--------- In compliance with/ Suivant EN 1515
Métric
C45E/ A194 2H
Nuts / Ecrous Heavy hex
EN10269
50251420_64J0105-C-PIPING CLASS
C12b
GASKETS/JOINTS :
spiral wound st. steel, graphite filler, with inner and outer protection rings (anti-corrosion treated)/
Type
spiralé inox/graphite avec anneaux de protection (int. et ext.) traités anti-corrosion
Standard EN 12560-2 / type C/I
Class 150
Dimensions EN 12560-2
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves that may be installed on
pipings of this class. In some specific cases depending on design conditions and actual valve position the valve description may be different than the one
given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et aider le concepteur dans la
définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des conditions de design et de fonctionnement le type de robinet
peut être différent de la liste ci dessous.
40 150 Wafer
Manual/ Steel or cast iron/ Acier
150 1 piece stem and type/ A 1423/64E0002
Manuelle ou fonte
Butterfly/ 200 600 butterfly-EPDM sleeve inserer
/ Papillon et axe EN 1759
Papillon (*) 40 150 monobloc-Manchette Wafer
Automatic/ Steel or cast iron/ Acier
150 EPDM type/ A 1423/64E0002
Motorisée ou fonte
200 600 inserer
15 50 Carbon steel-Stainless
Manual/
150 steel/ Acier au carbone- 1424/64E0001-0002
Manuelle inox.
Ball/ 80 Floating ball/ Boisseau
Boisseau flottant GAZ ISO 228-1
(*) 15 50 (2 pieces) Carbon steel-Stainless
Automatic/
150 steel/ Acier au carbone- 1424/64E0001-0002
Motorisée inox.
80
Class Carbon steel/ Acier au
15 50 SW EN12760 1423/64E0001
Strainer/ 800 carbone
---------- type "Y"
Flanges/
Filtre Carbon steel/ Acier au
80 600 150 EN 1759 1423/64E0002
Brides carbone
Class Globe+ spring/ Carbon steel/ Acier au
Check/ 15 50 SW EN12760 1423/64E0001
800 Soupape+ressort carbone
Clapet de ----------
Flanges/ Carbon steel/ Acier au
non-retour 80 600 150 Swing valve/ A battant EN 1759 1423/64E0002
Brides carbone
Control/ Automatic/ Piston or 1/4 turn/ Flanges/ Carbon steel/ Acier au
15 600 150 EN 1759 1424/64E0001
Régul. Motorisée Soupape ou 1/4tour Brides carbone
50251420_64J0105-C-PIPING CLASS
C12b
CLASS C1.4
PN PN 16
Pipe material/ Matériau TP316L
Group of material/ Groupe de matériau ISO 15608 8.1
Seamless/ sans
Type soudure
Standard ASME
Corrosion allowance/ Surépaisseur de corrosion [mm] 0,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 485 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 163 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 108 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 172 [N/mm2]
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if
other materials than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la norme
EN13480-5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3 -or
submitted to a flexibility analysis.
According to § 8.2.1 of EN13480-5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le §
12.2.10.1 de la norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée,
l'étendue des contrôles NDE peut être réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTA 4 : For stainless steel piping pressure test , halogen concentration within the water have to be controlled and must not exceed 50x10-6 ppm
Pour les essais hydrostatiques de réseaux de tuyauterie en acier inoxydable austénitiques, la concentration en halogène dans l'eau doit être contrôlée et ne doit pas dépasser 50x10-6 ppm .
NOTE 5 : The actual stress values given in the columns below takes into account the internal pressure only.
Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTA 6 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5. Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 7 : All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
(**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between CNIM
and the Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles
fera l'objet d'un accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In this
case the concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées, p.
ex. les échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
50251420_64J0105-C-PIPING CLASS
C14a
Allowable stress / Contrainte de calcul (N/mm2)
Temp. 50 100 150 200 250 300 350 400 450 --- --- ---
Sigma 15,70
108 13,13
90,5 11,90
82,1 10,89
75,1 10,14
69,9 9,57
66 63,1
9,15 60,7
8,80 58,1
8,43 --- --- ---
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
calorifuge (9)
flexibilité (2), (3)
conditions/ welds/
Pressure test/
/Contrainte de Pressure / allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
Index
soudures
Fluid group/
calcul DN test stress BW (6) tubulures (6) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 10,31 14,74 9,5 NA 0 NA 0 0 0 0 2 0
20 0 13,24 18,93 12,3 NA 0 NA 0 0 0 0 2 0
Diesel oil
50251420_64J0105-C-PIPING CLASS
C14a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
calorifuge (9)
flexibilité (2), (3)
conditions/ welds/
Pressure test/
/Contrainte de Pressure / allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
Index
soudures
Fluid group/
calcul DN test stress BW (6) tubulures (6) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15
15 0
FAUX 10,31
6,87 14,74
9,83 9,5
7,2 NA
0
30 NA
NA 0
0 0
0 0
10 0
0 2
10 0
10
Demineralised
50251420_64J0105-C-PIPING CLASS
C14a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Allowable EN 13480-1
réelle (5) NDE [%] selon EN 13480-5 (1), (7), (8)
stress at Stress ratio
Design Sealing
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
calorifuge (9)
flexibilité (2), (3)
conditions/ welds/
Pressure test/
/Contrainte de Pressure / allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
Index
soudures
Fluid group/
calcul DN test stress BW (6) tubulures (6) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 10,31
6,87 14,74
9,83 9,5
6,4 NA 0 NA 0 0 0 0 2 0
20 0 8,82 12,62 8,2 NA 0 NA 0 0 0 0 2 0
Service Air
50251420_64J0105-C-PIPING CLASS
C14a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Allowable EN 13480-1
réelle (5) NDE [%] selon EN 13480-5 (1), (7), (8)
stress at Stress ratio
Design Sealing
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
calorifuge (9)
flexibilité (2), (3)
conditions/ welds/
Pressure test/
/Contrainte de Pressure / allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
Index
soudures
Fluid group/
calcul DN test stress BW (6) tubulures (6) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 10,31
6,87 14,74
10,25 9,5
7,6 NA 0
30 NA 0 0 0 0 2 0
8,82 13,16 9,8 0 0 0 0 2 0
cooling water
20 0 NA 30 NA
Component
50251420_64J0105-C-PIPING CLASS
C14a
CLASS C1.4
DIMENSIONS :
FLANGES/ BRIDES :
Standard/ Norme EN 1092-1
PN 16
Material/ Matériau A182 F316L
Type Welding neck/ A collerette - Type 11
Facing RF / Face de joint surélevée (type B)
FITTINGS/RACCORDS :
DN [mm] Material/ Ends / Standard / ASME Class / Thk /
-> <- Matériau Embouts Norme Epaisseur
(*) - Machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3
and general requirements of EN 13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les
exigences générales spécifiées dans EN13480-4 s'appliquent au processus de cintrage.
Material/ Thread/
Type
BOLTING/BOULONNERIE : Matériaux Filetage
Stud bolts/ Tiges X5CrNi 18-10
---------
filetées EN10269 (AT+C) In compliance with/ Suivant EN 1515
Métric
X5CrNi 18-10
Nuts / Ecrous Heavy hex
EN10269
50251420_64J0105-C-PIPING CLASS
C14b
GASKETS/JOINTS :
ROBINETTERIE
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves
that may be installed on pipings of this class. In some specific cases depending on design conditions and actual valve position the
valve description may be different than the one given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et
aider le concepteur dans la définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des
conditions de design et de fonctionnement le type de robinet peut être différent de la liste ci dessous.
50251420_64J0105-C-PIPING CLASS
C14b
CLASS C3.1
Class 300
Pipe material/ Matériau P265GH
Group of material/ Groupe de matériau ISO 15608 1.1
Seamless/
Type sans soudure
Standard EN10216-2
Corrosion allowance/ Surépaisseur de corrosion [mm] 1,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 410 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 252 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 265 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 171 [N/mm2]
Maxi. design temp. with yield stress/ Temp. maxi de calcul en limite élastique 450 [°C]
Mini. design temp. with hot flow (10000 h)/ Temp. mini de calcul avec fluage (10000 h) 400 [°C]
Maxi. design temp. with hot flow (10000 h)/ Temp. maxi de calcul avec fluage(10000 h) 500 [°C]
Mini. yield stress Rp0,2 at design temp. (°C)/ Limite d'élasticité Rp0,2 (Mpa) à la temp. de (°C)
Temp. 50 100 150 200 250 300 350 400 450 --- --- ---
Rp0,2T 265 226 213 192 171 154 141 134 128 --- --- ---
Creep rupture strength / Résistance à la rupture par fluage pour 10000 h (MPa) (11)
Temp. 400 410 420 430 440 450 460 470 480 490 500 --- --- --- --- --- --- ---
RmT 182 166 151 138 125 112 100 88 77 67 58 --- --- --- --- --- --- ---
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if
other materials than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la
norme EN13480-5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3 -or
submitted to a flexibility analysis.
According to § 8.2.1 of EN13480-5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le §
12.2.10.1 de la norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée,
l'étendue des contrôles NDE peut être réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTE 4 : Allowable stress is indicated NA when the allowable stress is the one without creep and stress rupture.
La contrainte de calcul correspondant aux conditions de fluage est notée NA lorsque la contrainte prépondérante est celle sans fluage.
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTE 6 Piping used in the creep range, are classified in category III for NDE extend determination.
Dans le domaine du fluage , les tuyauteries sont classées en categorie III pour la determination des contrôles (article 8.2.1 norme EN 13480)
50251420_64J0105-C-PIPING CLASS
C31a
NOTE 7 All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between
CNIM and the Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles
fera l'objet d'un accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In
this case the concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées,
p. ex. les échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
NOTE 10 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5.
Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 11 : For pipings with design temp. T>413 °C a counting system will be provided to control time of exceeding of the service temp. limit of 413°C. According to §5.2 of EN13480-3 security factor of
1,25 is applied to hot flow design stress corresponding to 100000 h life time.
Pour les cas de fonctionnement avec T>413°C, un système de suivi de la durée de dépassement de 413°C sera prévu. Par conséquent, conformément au §5.2 de la EN13480-3, un coéf. de
sécurité de 1,25 est appliqué à la valeur de la contrainte de rupture par fluage pour une durée de 100000 h.
NOTE 12 : (**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Allowable EN 13480-1
réelle (5) NDE [%] selon EN 13480-5 (1), (7), (8)
stress at design Stress ratio
Design
Coating/ Peinture
(Actual stress /
Denomination
temp.
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
Catergory/ Categorie
Pressure test/
/Contrainte de Pressure allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
soudures
Index
Fluid group/
calcul DN test stress BW (6) (12) tubulures (6)(12) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 19,63 28,07 11,5 NA 0 yes/ oui 0 0 0 0 2 0
20 0 21,00 30,03 12,3 NA 0 yes/ oui 0 0 0 0 2 0
25 0 22,15 31,68 13,0 NA 0 yes/ oui 0 0 0 0 2 0
40 0 26,83 38,37 15,7 NA 0 yes/ oui 0 10 0 0 2 0
50 0 29,88 42,73 17,5 NA 0 yes/ oui 0 10 0 0 2 0
80 0 36,58 52,31 21,4 NA 0 yes/ oui 0 10 0 0 2 0
47,39 67,77 27,7 0 10 0 0 2 0
Diesel oil
50251420_64J0105-C-PIPING CLASS
C31a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Coating/ Peinture
(Actual stress /
Denomination
temp.
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
Catergory/ Categorie
Pressure test/
/Contrainte de Pressure allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
soudures
Index
Fluid group/
calcul DN test stress BW (6) (12) tubulures (6)(12) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
fluage (4) d'épreuve admissible) NDE NDE
NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 19,63 28,07
40,83 11,5
19,1 NA 0
60 yes/
----oui 0 0 0 0 2 0
Medium pressure steam piping system
20 0 21,00 43,68 20,5 NA 60 ---- 0 0 0 0 2 0
25 0 22,15 46,08 21,6 NA 60 ---- 0 0 0 0 2 0
40 0 26,83 55,81 26,1 NA 60 ---- 0 0 0 0 2 0
50 I 29,88 62,15 29,1 NA 60 ---- 0 10 0 0 2 0
80 I 36,58 76,08 35,6 ? 80 ---- 0 10 0 0 2 0
100 I 47,39 98,57 46,2 ? 80 ---- 0 10 0 0 2 0
150 II 70,37 146,36 68,5 ? 100 ---- yes/ 0 10 0 0 2 0
LBD 1 25 300 102,7 NA G2 5,20
200 II 59,44 123,64 57,9 ? 100 ---- oui 0 10 0 0 2 0
250 II 74,37 154,69 72,4 ? 100 ---- 0 10 0 0 2 0
300 III 76,42 158,96 74,4 ? 100 ---- 0 10 10 0 10 10
350 III 72,83 151,49 70,9 ? 100 ---- 0 10 10 0 10 10
400 III 74,57 155,10 72,6 ? 120 ---- 0 10 10 0 10 10
450 III 76,68 159,50 74,7 ? 120 ---- 0 10 10 0 10 10
500 III 72,37 150,53 70,5 ? 120 ---- 0 10 10 0 10 10
600 III 75,48 156,99 73,5 ? 120 ---- 0 10 10 0 10 10
15 0 7,85 18,77 8,8 NA 60 ---- 0 0 0 0 2 0
Medium pressure steam piping system
50251420_64J0105-C-PIPING CLASS
C31a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Coating/ Peinture
(Actual stress /
Denomination
temp.
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
Catergory/ Categorie
Pressure test/
/Contrainte de Pressure allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
soudures
Index
Fluid group/
calcul DN test stress BW (6) (12) tubulures (6)(12) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
fluage (4) d'épreuve admissible) NDE NDE
NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 19,63
9,42 28,07
18,38 11,5
8,6 NA 0
50 yes/
----oui 0 0 0 0 2 0
Medium pressure steam piping system
20 0 10,08 19,66 9,2 NA 50 ---- 0 0 0 0 2 0
25 0 10,63 20,74 9,7 NA 50 ---- 0 0 0 0 2 0
40 0 12,88 25,12 11,8 NA 60 ---- 0 0 0 0 2 0
50 0 14,34 27,98 13,1 NA 60 ---- 0 0 0 0 2 0
80 0 17,56 34,25 16,0 ? 80 ---- 0 0 0 0 2 0
100 I 22,75 44,37 20,8 ? 80 ---- 0 10 0 0 2 0
150 I 33,78 65,89 30,9 ? 80 ---- yes/ 0 10 0 0 2 0
LBD 3 12 270 109,5 NA G2 2,34
200 I 28,53 55,66 26,1 ? 100 ---- oui 0 10 0 0 2 0
250 I 35,70 69,64 32,6 ? 100 ---- 0 10 0 0 2 0
300 II 36,68 71,56 33,5 ? 100 ---- 0 10 0 0 2 0
350 II 34,96 68,20 31,9 ? 100 ---- 0 10 0 0 2 0
400 II 35,79 69,83 32,7 ? 120 ---- 0 10 0 0 2 0
450 III 36,81 71,80 33,6 ? 120 ---- 0 10 10 0 10 10
500 III 34,74 67,77 31,7 ? 120 ---- 0 10 10 0 10 10
600 III 36,23 70,68 33,1 ? 120 ---- 0 10 10 0 10 10
15 0 19,63 46,93 22,0 NA 60 ---- 0 0 0 0 2 0
Medium pressure steam piping system
50251420_64J0105-C-PIPING CLASS
C31a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Coating/ Peinture
(Actual stress /
Denomination
temp.
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
Catergory/ Categorie
Pressure test/
/Contrainte de Pressure allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
soudures
Index
Fluid group/
calcul DN test stress BW (6) (12) tubulures (6)(12) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 19,63
23,56 28,07
35,43 11,5
16,6 NA 0
30 yes/
----oui 0 0 0 0 2 0
20 0 25,20 37,90 17,7 NA 30 ---- 0 0 0 0 2 0
25 0 26,58 39,98 18,7 NA 30 ---- 0 0 0 0 2 0
40 I 32,20 48,42 22,7 NA 40 ---- 0 10 0 0 2 0
50 I 35,86 53,92 25,3 NA 40 ---- 0 10 0 0 2 0
80 I 43,90 66,01 30,9 ? 60 ---- 0 10 0 0 2 0
Condensate
50251420_64J0105-C-PIPING CLASS
C31a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Coating/ Peinture
(Actual stress /
Denomination
temp.
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
Catergory/ Categorie
Pressure test/
/Contrainte de Pressure allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
soudures
Index
Fluid group/
calcul DN test stress BW (6) (12) tubulures (6)(12) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
fluage (4) d'épreuve admissible) NDE NDE
NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15
15 0
0 19,63
19,63 28,07
35,05 11,5
16,4 NA
0
50 yes/
----oui 0
0 0
0 0
0 0
0 2
2 0
0
21,00 37,49 17,6 0 0 0 0 2 0
High pressure steam piping system
20 0 NA 50 ----
25 0 22,15 39,55 18,5 NA 50 ---- 0 0 0 0 2 0
40 0 26,83 47,91 22,4 NA 60 ---- 0 0 0 0 2 0
50 I 29,88 53,35 25,0 NA 60 ---- 0 10 0 0 2 0
80 I 36,58 65,31 30,6 ? 80 ---- 0 10 0 0 2 0
100 I 47,39 84,61 39,6 ? 80 ---- 0 10 0 0 2 0
150 II 70,37 125,64 58,8 ? 80 ---- yes/ 0 10 0 0 2 0
LBA 1 25 230 119,6 NA G2 4,46
200 II 59,44 106,13 49,7 ? 100 ---- oui 0 10 0 0 2 0
250 II 74,37 132,79 62,2 ? 100 ---- 0 10 0 0 2 0
300 III 76,42 136,45 63,9 ? 100 ---- 0 10 10 0 10 10
350 III 72,83 130,04 60,9 ? 100 ---- 0 10 10 0 10 10
400 III 74,57 133,14 62,4 ? 120 ---- 0 10 10 0 10 10
450 III 76,68 136,92 64,1 ? 120 ---- 0 10 10 0 10 10
500 III 72,37 129,22 60,5 ? 120 ---- 0 10 10 0 10 10
600 III 75,48 134,77 63,1 ? 120 ---- 0 10 10 0 10 10
15 0 15,71 38,40 18,0 NA 60 ---- 0 0 0 0 2 0
16,80 41,08 19,2 0 0 0 0 2 0
High pressure steam piping system
20 0 NA 60 ----
25 0 17,72 43,33 20,3 NA 60 ---- 0 0 0 0 2 0
40 0 21,47 52,49 24,6 NA 80 ---- 0 0 0 0 2 0
50 0 23,90 58,45 27,4 NA 80 ---- 0 0 0 0 2 0
80 I 29,26 71,55 33,5 ? 100 ---- 0 10 0 0 2 0
100 I 37,91 92,70 43,4 ? 100 ---- 0 10 0 0 2 0
150 I 56,29 137,65 64,5 ? 120 ---- yes/ 0 10 0 0 2 0
LBA 2 20 425 87,3 115,6 G2 4,89
200 III 47,55 116,28 54,5 ? 120 ---- oui 0 10 10 0 10 10
250 III 59,50 145,48 68,1 ? 120 ---- 0 10 10 0 10 10
300 III 61,14 149,49 70,0 ? 120 ---- 0 10 10 0 10 10
350 III 58,27 142,47 66,7 ? 120 ---- 0 10 10 0 10 10
400 III 59,66 145,87 68,3 ? 150 ---- 0 10 10 0 10 10
450 III 61,35 150,00 70,2 ? 150 ---- 0 10 10 0 10 10
500 III 57,90 141,57 66,3 ? 150 ---- 0 10 10 0 10 10
600 III 60,38 147,65 69,1 ? 150 ---- 0 10 10 0 10 10
50251420_64J0105-C-PIPING CLASS
C31a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Coating/ Peinture
(Actual stress /
Denomination
temp.
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
Catergory/ Categorie
Pressure test/
/Contrainte de Pressure allowable Soudures circ. Soudures SW
Conditions de Design Soudure
Groupe fluide
soudures
Index
Fluid group/
calcul DN test stress BW (6) (12) tubulures (6)(12) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
fluage (4) d'épreuve admissible) NDE
NDE
NDE
NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 19,63
23,56 28,07
35,43 11,5
16,6 NA 0
30 yes/
----oui 0 0 0 0 2 0
20 0 25,20 37,90 17,7 NA 30 ---- 0 0 0 0 2 0
Main condensate heating system
50251420_64J0105-C-PIPING CLASS
C31a
CLASS C3.1
DIMENSIONS :
P265GH SA 234 WPB
Design Thk/ Pipes Thk/ Design Thk/ Fittings Thk/ Observations/
DN OD/ Diam. ext.
Ep. calculée Ep tuyauteries Ep. calculée Ep raccords Comments
in mm mm mm mm mm mm kg/m
Note : Connecting piping with machining or reducing, see sheet "FITTINGS WELDING DETAILS"
Voir les raccordements par usinage ou par délardage sur la feuille "SOUDURE DES RACCORDS"
FLANGES/ BRIDES :
Piping Thk /
Weldolets 50 500 A105 BW ASME B16.9 Epaisseur tuyauterie
(*) - machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3 and general
requirements of EN 13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les exigences générales
spécifiées dans EN13480-4 s'appliquent au processus de cintrage.
(**) : EN10253-2 type A fittings not accepted. BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be
submited for CNIM approval.
(**) Raccords selon EN10253-2 type A non admis. Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de
réf. choisies par le Fournisseur seront soumises à CNIM pour accord .
50251420_64J0105-C-PIPING CLASS
C31b
BOLTING/BOULONNERIE :
Material/ Thread/
Matériaux
Type Filetage
Stud bolts/ 42CrMo4 / A193B7
---------
Tiges filetées EN10269 In compliance with/ Suivant EN 1515
Métric
C45E/ A194 2H
Nuts / Ecrous Heavy hex
EN10269
GASKETS/JOINTS :
spiral wound st. steel, graphite filler, with inner and outer protection rings (anti-corrosion treated)/
Type
spiralé inox/graphite avec anneaux de protection (int. et ext.) traités anti-corrosion
Standard EN 12560-2 / type C/I
Class 300
Dimensions EN 12560-2
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves that may be installed on
pipings of this class. In some specific cases depending on design conditions and actual valve position the valve description may be different than the one
given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et aider le concepteur dans
la définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des conditions de design et de fonctionnement le type de
robinet peut être différent de la liste ci dessous.
50251420_64J0105-C-PIPING CLASS
C31b
CLASS C3.2
Class 300
Pipe material/ Matériau TP316L
Group of material/ Groupe de matériau ISO 15608 8.1
Seamless/
Type sans soudure
Standard ASME
Corrosion allowance/ Surépaisseur de corrosion [mm] 0,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 485 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 163 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 108 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 172 [N/mm2]
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if
other materials than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la
norme EN13480-5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3
-or submitted to a flexibility analysis.
According to § 8.2.1 of EN13480-5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le §
12.2.10.1 de la norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée,
l'étendue des contrôles NDE peut être réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTA 4 : For stainless steel piping pressure test , halogen concentration within the water have to be controlled and must not exceed 50x10-6 ppm
Pour les essais hydrostatiques de réseaux de tuyauterie en acier inoxydable austénitiques, la concentration en halogène dans l'eau doit être contrôlée et ne doit pas dépasser 50x10-6 ppm .
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
: Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTA 6 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5. Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 7 : All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
(**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
50251420_64J0105-C-PIPING CLASS
C32a
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between
CNIM and the Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles
fera l'objet d'un accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In
this case the concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées,
p. ex. les échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
Allowable EN 13480-1
stress at réelle (5) Stress ratio [%] selon EN 13480-5 (1), (7), (8)
Design
Coating/ Peinture
Denomination
(Actual stress /
Pression d'épreuve
design temp. Circ. Welds/ Branch weld/
calorifuge (9)
flexibilité (2), (3)
Sealing welds/
Catergory/ Categorie
Pressure test/
/Contrainte de Pressure
les soudures
Conditions de Design Soudures circ. Soudures SW Soudure
Groupe fluide
Index
DN stress
Fluid group/
calcul test BW (6) tubulures (6) d'étanch.
calcul conditions/
conditions/ contr. réelle /
Stress Conditions contr.
Sans rupture
Conditions Surface
Volume
Surface
Volume Surface
de calcul admissible) NDE NDE Surface NDE
fluage (4) d'épreuve NDE NDE NDE
P T 10000h
(**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 17,18 24,57 15,9 NA 0 NA 0 0 0 0 2 0
20 0 22,06 31,55 20,4 NA 0 NA 0 0 0 0 2 0
27,95 39,98 25,8 0 0 0 0 2 0
Diesel oil
25 0 NA 0 NA
40 0 40,61 58,07 37,5 NA 0 NA yes/ 0 10 0 10 2 0
EGD 1 25 40 108,3 L1 3,58
50 0 51,01 72,94 47,1 NA 0 NA oui 0 10 0 10 2 0
80 0 58,99 84,36 54,5 NA 0 NA 0 10 0 10 2 0
100 II 52,32 74,82 48,3 NA 0 NA 0 10 0 10 2 0
150 II 32,56 46,56 30,1 NA 0 NA 0 10 0 10 2 0
15 0 20,616 33,90 25,1 NA 30 NA 0 0 0 0 2 0
20 0 26,47 43,53 32,2 NA 30 NA 0 0 0 0 2 0
Condensate
50251420_64J0105-C-PIPING CLASS
C32a
CLASS C3.2
DIMENSIONS :
FLANGES/ BRIDES :
Standard/ Norme ASME B16.5/EN 1759
Class 300
Material/ Matériau A182 F316L
Type Welding neck/ A collerette - Type 11
Facing RF / Face de joint surélevée (type B)
FITTINGS/RACCORDS :
DN [mm] Material/ Ends / Standard / ASME Class / Thk /
-> <- Matériau Embouts Norme Epaisseur
Tees , elbows (*) , reducers , caps / 8 40 A182 F316L SW ASME B16.11 3000
Piping Thk /
Tés, coudes (*), réductions, fonds 50 150 A403WP316L BW ASME B16.9 Epaisseur tuyauterie
Piping Thk /
Weldolets 50 150 A182 F316L BW ASME B16.9 Epaisseur tuyauterie
(*) - machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in
EN 13480-3 and general requirements of EN 13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et
les exigences générales spécifiées dans EN13480-4 s'appliquent au processus de cintrage.
NOTE : BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be
submited for CNIM approval.
NOTE : Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de réf.
choisies par le Fournisseur seront soumises à CNIM pour accord .
Material/ Thread/
BOLTING/BOULONNERIE : Matériaux
Type Filetage
Stud bolts/ X5CrNi 18-10
Tiges filetées EN10269 (AT+C)
---------
Métric
X5CrNi 18-10
Nuts / Ecrous Heavy hex
EN10269
50251420_64J0105-C-PIPING CLASS
C32b
GASKETS/JOINTS :
spiral wound st. steel, graphite filler, with inner and outer protection rings (anti-corrosion treated)/
Type
spiralé inox/graphite avec anneaux de protection (int. et ext.) traités anti-corrosion
Standard ASME B16.20 / EN 12560-2 / type C/I
Class 300
Dimensions ASME B16.20 / EN 12560-2
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of
valves that may be installed on pipings of this class. In some specific cases depending on design conditions and actual
valve position the valve description may be different than the one given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide
général et aider le concepteur dans la définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en
fonction des conditions de design et de fonctionnement le type de robinet peut être différent de la liste ci dessous.
Manual/
Flange
Manuelle Flexible wedge/ Stainless steel/
80 200 300 s/ EN 1759 1423/64E0006
Coin flexible Acier inox.
Brides
Classe Stainless steel/
8 50 SW EN 12760 1423/64E0006
Automatic/ 800 Parallel slide/ Acier inox.
Motorisée Sièges parallèles Flange Stainless steel/
80 200 300 s/ EN 1759 1423/64E0006
Acier inox.
Brides
Globe/ Rob. Manual/ Loose dic/ Stainless steel/
8 50 300 GAZ ISO 228-1 1423/64E0006
à soupape Manuelle Soupape mobile Acier inox.
Stainless steel/
8 50 GAZ ISO 228-1
Manual/ Acier inox.
Flange 1423/64E0006
Manuelle Stainless steel/
80 200 Floating ball/ s/ EN 1759
Ball/ Acier inox.
300 Boisseau flottant Brides
Boisseau (2 pieces) Stainless steel/
8 50 GAZ ISO 228-1
Automatic/ Acier inox.
Flange 1424/64E0006
Motorisée Stainless steel/
80 200 s/ EN 1092
Acier inox.
Brides
Stainless steel/
8 50 GAZ ISO 228-1 1423/64E0006
Strainer/ Acier inox.
---------- 300 type "Y" Flange
Filtre Stainless steel/
80 200 s/ EN 1759 1423/64E0006
Acier inox.
Brides
Globe+ spring/ Stainless steel/
Check/ 8 50 GAZ ISO 228-1 1423/64E0006
Soupape+ressort Acier inox.
Clapet de ---------- 300 Flange
non-retour Swing valve/ A Stainless steel/
80 200 s/ EN 1759 1423/64E0006
battant Acier inox.
Brides
50251420_64J0105-C-PIPING CLASS
C32b
CLASS C6.1
Class 600
Pipe material/ Matériau P265GH
Group of material/ Groupe de matériau ISO 15608 1.1
Seamless/
Type sans soudure
Standard EN10216-2
Corrosion allowance/ Surépaisseur de corrosion [mm] 1,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 410 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 252 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 265 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 171 [N/mm2]
Maxi. design temp. with yield stress/ Temp. maxi de calcul en limite élastique 450 [°C]
Mini. design temp. with hot flow (10000 h)/ Temp. mini de calcul avec fluage (10000 h) 400 [°C]
Maxi. design temp. with hot flow (10000 h)/ Temp. maxi de calcul avec fluage(10000 h) 500 [°C]
Mini. yield stress Rp0,2 at design temp. (°C)/ Limite d'élasticité Rp0,2 (Mpa) à la temp. de (°C)
Temp. 50 100 150 200 250 300 350 400 450 --- --- ---
Rp0,2T 265 226 213 192 171 154 141 134 128 --- --- ---
Creep rupture strength / Résistance à la rupture par fluage pour 10000 h (MPa) (11)
Temp. 400 410 420 430 440 450 460 470 480 490 500 --- --- --- --- --- --- ---
RmT 182 166 151 138 125 112 100 88 77 67 58 --- --- --- --- --- --- ---
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if
other materials than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la
norme EN13480-5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3 -
or submitted to a flexibility analysis.
According to § 8.2.1 of EN13480-5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le §
12.2.10.1 de la norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée,
l'étendue des contrôles NDE peut être réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTE 4 : Allowable stress is indicated NA when the allowable stress is the one without creep and stress rupture.
La contrainte de calcul correspondant aux conditions de fluage est notée NA lorsque la contrainte prépondérante est celle sans fluage.
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTE 6 Piping used in the creep range, are classified in category III for NDE extend determination.
Dans le domaine du fluage , les tuyauteries sont classées en categorie III pour la determination des contrôles (article 8.2.1 norme EN 13480)
50251420_64J0105-C-PIPING CLASS
C61a
NOTE 7 All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between CNIM
and the Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles
fera l'objet d'un accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In
this case the concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées,
p. ex. les échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
NOTE 10 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5.
Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 11 : For pipings with design temp. T>413 °C a counting system will be provided to control time of exceeding of the service temp. limit of 413°C. According to §5.2 of EN13480-3 security factor of
1,25 is applied to hot flow design stress corresponding to 100000 h life time.
Pour les cas de fonctionnement avec T>413°C, un système de suivi de la durée de dépassement de 413°C sera prévu. Par conséquent, conformément au §5.2 de la EN13480-3, un coéf. de
sécurité de 1,25 est appliqué à la valeur de la contrainte de rupture par fluage pour une durée de 100000 h.
NOTE 12 : (**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Allowable stress réelle (5) NDE [%] selon EN 13480-5 (1), (7), (8)
Stress ratio
Design at design temp. Sealing
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
flexibilité (2), (3)
Catergory/ Categorie
conditions/ /Contrainte de welds/
/ allowable
Pressure test/
Conditions de calcul Pressure Soudures circ. Soudures SW
Design Soudure
Groupe fluide
soudures
Index
DN stress
Fluid group/
calcul test BW (6) (12) tubulures (6)(12) d'étanch.
conditions/
conditions/ contr. réelle /
Stress Conditions contr.
Conditions Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 39,26 60,85 28,5 NA 30 ---- 0 0 0 0 2 0
20 0 42,00 65,08 30,5 NA 30 ---- 0 0 0 0 2 0
25 0 44,31 68,66 32,2 NA 30 ---- 0 0 0 0 2 0
40 I 53,66 83,16 38,9 NA 40 ---- 0 10 0 0 2 0
50 I 59,76 92,61 43,4 NA 40 ---- 0 10 0 0 2 0
80 I 73,16 113,37 53,1 ? 60 ---- 0 10 0 0 2 0
Feed water
50251420_64J0105-C-PIPING CLASS
C61a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Denomination
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
flexibilité (2), (3)
Catergory/ Categorie
conditions/ /Contrainte de welds/
/ allowable
Pressure test/
Conditions de calcul Pressure Soudures circ. Soudures SW
Design Soudure
Groupe fluide
soudures
Index
DN stress
Fluid group/
calcul test BW (6) (12) tubulures (6)(12) d'étanch.
conditions/
conditions/ contr. réelle /
Stress Conditions contr.
Conditions Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 39,26
34,55 60,85
84,49 28,5
39,6 NA 30
60 ---- 0 0 0 0 2 0
High pressure steam piping system
50251420_64J0105-C-PIPING CLASS
C61a
CLASS C6.1
DIMENSIONS :
P265GH SA 234 WPB
Design Thk/ Pipes Thk/ Design Thk/ Fittings Thk/ Observations/
DN OD/ Diam. ext.
Ep. calculée Ep tuyauteries Ep. calculée Ep raccords Comments
in mm mm mm mm mm mm kg/m
Note : Connecting piping with machining or reducing, see sheet "FITTINGS WELDING DETAILS"
Voir les raccordements par usinage ou par délardage sur la feuille "SOUDURE DES RACCORDS"
FLANGES/ BRIDES :
Piping Thk /
Weldolets 50 500 A105 BW ASME B16.9 Epaisseur tuyauterie
(*) - machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3 and general
requirements of EN 13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les exigences générales
spécifiées dans EN13480-4 s'appliquent au processus de cintrage.
(**) : EN10253-2 type A fittings not accepted. BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be
submited for CNIM approval.
(**) Raccords selon EN10253-2 type A non admis. Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de
réf. choisies par le Fournisseur seront soumises à CNIM pour accord .
50251420_64J0105-C-PIPING CLASS
C61b
BOLTING/BOULONNERIE :
Thread/
Material/ Matériaux Type Filetage
Stud bolts/ 42CrMo4 / A193B7
Tiges filetées EN10269
--------- In compliance with/ Suivant EN 1515
Métric
C45E/ A194 2H
Nuts / Ecrous Heavy hex
EN10269
GASKETS/JOINTS :
spiral wound st. steel, graphite filler, with inner and outer protection rings (anti-corrosion treated)/
Type
spiralé inox/graphite avec anneaux de protection (int. et ext.) traités anti-corrosion
Standard EN 12560-2 / type C/I
Class 600
Dimensions EN 12560-2
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves that may be installed on
pipings of this class. In some specific cases depending on design conditions and actual valve position the valve description may be different than the one
given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et aider le concepteur dans
la définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des conditions de design et de fonctionnement le type de
robinet peut être différent de la liste ci dessous.
50251420_64J0105-C-PIPING CLASS
C61b
CLASS C6.3
Class 600
Pipe material/ Matériau 16Mo3
Group of material/ Groupe de matériau ISO 15608 1.2
Seamless/
Type sans soudure
Standard EN 10216-2
Corrosion allowance/ Surépaisseur de corrosion [mm] 1,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 450 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 266 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 280 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 187 [N/mm2]
Maxi. design temp. without hot flow/ Temp. maxi de calcul sans fluage 500 [°C]
Mini. design temp. with hot flow (10000 h)/ Temp. mini de calcul avec fluage (10000 h) 500 [°C]
Maxi. design temp. with hot flow (10000 h)/ Temp. maxi de calcul avec fluage(10000 h) 500 [°C]
Mini. yield stress Rp0,2 at design temp. (°C)/ Limite d'élasticité Rp0,2 (Mpa) à la temp. de (°C)
Temp. 50 100 150 200 250 300 350 400 450 500 --- ---
Rp0,2T 280 243 237 224 205 173 159 156 150 146 --- ---
Creep rupture strength / Résistance à la rupture par fluage pour 10000 h (MPa) (11)
Temp. 450 460 470 480 490 500 510 520 530 540 550 --- --- --- --- --- --- ---
RmT 298 273 247 221 196 171 148 125 104 84 64 --- --- --- --- --- --- ---
The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if other
NOTE 1 : materials than those mentioned
La colonne "Etendue de contrôlehere
NDEabove are used.
[%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la norme
EN13480-5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
Les tuyauterieswith
-in compliance qui ne remplissent
§ 12.2.10.1 of aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le § 12.2.10.1-or
EN 13480-3 de la
norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée, l'étendue des contrôles NDE
NOTE 4 : Allowable stress is indicated NA when the allowable stress is the one without creep and stress rupture.
La contrainte de calcul correspondant aux conditions de fluage est notée NA lorsque la contrainte prépondérante est celle sans fluage.
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTE 6 Piping used in the creep range, are classified in category III for NDE extend determination.
Dans le domaine du fluage , les tuyauteries sont classées en categorie III pour la determination des contrôles (article 8.2.1 norme EN 13480)
50251420_64J0105-C-PIPING CLASS
C63a
NOTE 7 All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between CNIM and the
NOTE 8 : Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles fera l'objet
d'un accord
Insulation entre la values
thickness Sté CNIMareet son Client.
defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In this case the
NOTE 9 : concerned piping
Les épaisseurs dewill be painted
l'isolation or, if necessary,
thérmique will
en fonction dehave a 30
P,T et DNmm thick
sont insulation
définies to provideaux
conformément selfrègles
security protection.
internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées, p. ex. les
échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
NOTE 10 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5.
Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
For pipings with high service temperature, a counting system may be provided to control time of exceeding the limit temperature for creep rupture situation. According to §5.2 of EN13480-3 security
NOTE 11 : factorles
of 1,25 is applied to hot flow design stress corresponding to life
Pour cas de fonctionnement à temperature élevée, un système de time
suivibelow 100000h.
de la durée de dépassement de temperature seuil fluage peut être prévu. Par conséquent, conformément au §5.2 de la
EN13480-3, un coéf. de sécurité de 1,25 est appliqué à la valeur de la contrainte de rupture par fluage pour une durée inférieure à 100000 h.
NOTE 12 : (**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
#####
Allowable stress Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
EN 13480-1 Stress ratio
Flexibility analysis/
Denomination
Coating/ Peinture
at design temp. réelle (5) NDEWelds/
Circ. [%] selon Branch
EN 13480-5
weld/(1), (7), (8)
thickness/
Epaisseur
Insulation
Design conditions/
Analyse de
Design
Toutes les
Groupe fluide
All welds/
/Contrainte de
soudures
Pressure
Pression
Soudures circ. Soudures SW welds/
Fluid group/
test allowable
Catergory/
Index
Categorie
Conditions de calcul DN conditions/
test/
calcul conditions/ stress BW (6) (12) tubulures (6)(12) Soudure
Stress Conditions Surface Surface
Sans Conditions contr. réelle / Volume Volume Surface Surface
rupture de calcul NDE NDE
P T fluage contr. NDE NDE NDE NDE
(4) d'épreuve (**) (**)
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 43,19 99,98 42,8 NA 60 ---- 0 0 0 0 2 0
High pressure steam piping system
50251420_64J0105-C-PIPING CLASS
C63a
CLASS C6.3
DIMENSIONS :
16Mo3 16Mo3
Design Thk/ Pipes Thk/ Design Thk/ Fittings Thk/ Ep Observations/
DN OD/ Diam. ext.
Ep. calculée Ep tuyauteries Ep. calculée raccords Comments
in mm mm mm mm mm mm kg/m
Note : Connecting piping with machining or reducing, see sheet "FITTINGS WELDING DETAILS"
Voir les raccordements par usinage ou par délardage sur la feuille "SOUDURE DES RACCORDS"
FLANGES/ BRIDES :
Piping Thk /
Weldolets 50 500 16Mo3 BW ASME B16.9 Epaisseur tuyauterie
(*) - machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3 and general requirements of EN
13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les exigences générales spécifiées dans
EN13480-4 s'appliquent au processus de cintrage.
(**) : EN10253-2 type A fittings not accepted. BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be submited for
CNIM approval.
(**) Raccords selon EN10253-2 type A non admis. Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de réf.
choisies par le Fournisseur seront soumises à CNIM pour accord .
50251420_64J0105-C-PIPING CLASS
C63b
BOLTING/BOULONNERIE :
Thread/
Material/ Matériaux Type Filetage
Stud bolts/ 42CrMo5-6
Tiges filetées EN10269
--------- In compliance with/ Suivant EN 1515
Métric
42CRMo4
Nuts / Ecrous Heavy hex
EN10269
GASKETS/JOINTS :
spiral wound st. steel, graphite filler, with inner and outer protection rings (anti-corrosion treated)/ spiralé
Type
inox/graphite avec anneaux de protection (int. et ext.) traités anti-corrosion
Standard EN 12560-2 / type C/I
Class 600 / 800 (DN <= 50)
Dimensions EN 12560-2
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves that may be installed on pipings
of this class. In some specific cases depending on design conditions and actual valve position the valve description may be different than the one given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et aider le concepteur dans la
définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des conditions de design et de fonctionnement le type de robinet
peut être différent de la liste ci dessous.
Manual/ monobloc
Manuelle Parallel slide/ Sièges
80 600 600 BW EN12627 16Mo3 1423/64E0002
parallèles
Note : Valves DN<=50 cl. 800 if suitable with the piping design conditions
Robinetterie DN<=50 en cl. 800 si les cond. de calcul des lignes correspondantes le permettent
50251420_64J0105-C-PIPING CLASS
C63b
CLASS C9.1
Class 900
Pipe material/ Matériau P265GH
Group of material/ Groupe de matériau ISO 15608 1.1
Seamless/
Type sans soudure
Standard EN10216-2
Corrosion allowance/ Surépaisseur de corrosion [mm] 1,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 410 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 252 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 265 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 171 [N/mm2]
Maxi. design temp. with yield stress/ Temp. maxi de calcul en limite élastique 450 [°C]
Mini. design temp. with hot flow (10000 h)/ Temp. mini de calcul avec fluage (10000 h) 400 [°C]
Maxi. design temp. with hot flow (10000 h)/ Temp. maxi de calcul avec fluage(10000 h) 500 [°C]
Mini. yield stress Rp0,2 at design temp. (°C)/ Limite d'élasticité Rp0,2 (Mpa) à la temp. de (°C)
Temp. 50 100 150 200 250 300 350 400 450 --- --- ---
Rp0,2T 265 226 213 192 171 154 141 134 128 --- --- ---
Creep rupture strength for the considered time/ Résistance à la rupture par fluage pour la durée considérée (MPa)
Temp. 400 410 420 430 440 450 460 470 480 490 500 --- --- --- --- --- --- ---
RmT 182 166 151 138 125 112 100 88 77 67 58 --- --- --- --- --- --- ---
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if other materials
than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la norme EN13480-5
doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3 -or submitted to
a flexibility analysis. According to § 8.2.1 of EN13480-
5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le § 12.2.10.1 de la norme
EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée, l'étendue des contrôles NDE peut être
réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTE 4 : Allowable stress is indicated NA when the allowable stress is the one without creep and stress rupture.
La contrainte de calcul correspondant aux conditions de fluage est notée NA lorsque la contrainte prépondérante est celle sans fluage.
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTE 6 Piping used in the creep range, are classified in category III for NDE extend determination.
Dans le domaine du fluage , les tuyauteries sont classées en categorie III pour la determination des contrôles (article 8.2.1 norme EN 13480)
50251420_64J0105-C-PIPING CLASS
C91a
NOTE 7 All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between CNIM and the
Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles fera l'objet d'un
accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In this case the
concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées, p. ex. les
échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
NOTE 10 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5.
Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 11 : For pipings with high service temperature, a counting system may be provided to control time of exceeding the limit temperature for creep rupture situation. According to §5.2 of EN13480-3 security factor of
1,25 is applied to hot flow design stress corresponding to life time below 100000h.
Pour les cas de fonctionnement à temperature élevée, un système de suivi de la durée de dépassement de temperature seuil fluage peut être prévu. Par conséquent, conformément au §5.2 de la EN13480-3,
un coéf. de sécurité de 1,25 est appliqué à la valeur de la contrainte de rupture par fluage pour une durée inférieure à 100000 h.
NOTE 12 : (**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
#####
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Fluid Tag/ Code fluide
Insulation thickness/
at design temp.
Sealing
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Conditions de calcul Design Soudures circ. Soudures SW
calcul
Groupe fluide
Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 76,17 108,93 44,6 NA 0 yes/ oui 0 0 0 0 2 0
20 0 81,48 116,52 47,7 NA 0 yes/ oui 0 0 0 0 2 0
25 0 85,95 122,91 50,3 NA 0 yes/ oui 0 0 0 0 2 0
40 II 100,67 143,96 58,9 NA 0 yes/ oui 0 10 0 10 2 0
50 II 115,94 165,79 67,9 NA 0 yes/ oui 0 10 0 10 2 0
80 II 108,50 155,16 63,5 NA 0 yes/ oui 0 10 0 10 2 0
Phosphate
50251420_64J0105-C-PIPING CLASS
C91a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
at design temp.
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Conditions de calcul Design Soudures circ. Soudures SW
calcul
Groupe fluide
Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 76,17 108,93
161,16 44,6
75,5 NA 60 ---- 0 0 0 0 2 0
20 0 81,48 172,38 80,7 NA 60 ---- 0 0 0 0 2 0
25 0 85,95 181,85 85,2 NA 60 ---- 0 0 0 0 2 0
40 II 100,67 212,99 99,7 NA 60 ---- 0 10 0 10 2 0
50 II 115,94 245,28 114,9 NA 60 ---- 0 10 0 10 2 0
80 II 108,50 229,56 107,5 ? 80 ---- 0 10 0 10 2 0
Phosphate
50251420_64J0105-C-PIPING CLASS
C91a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
at design temp.
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Conditions de calcul Design Soudures circ. Soudures SW
calcul
Groupe fluide
Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 76,17 108,93
161,16 44,6
75,5 NA 60 ---- 0 0 0 0 2 0
20 0 81,48 172,38 80,7 NA 60 ---- 0 0 0 0 2 0
25 0 85,95 181,85 85,2 NA 60 ---- 0 0 0 0 2 0
40 I 100,67 212,99 99,7 NA 60 ---- 0 10 0 0 2 0
50 I 115,94 245,28 114,9 NA 60 ---- 0 10 0 0 2 0
80 I 108,50 229,56 107,5 ? 80 ---- 0 10 0 0 2 0
Feed water
50251420_64J0105-C-PIPING CLASS
C91a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Insulation thickness/
at design temp.
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Conditions de calcul Design Soudures circ. Soudures SW
calcul
Groupe fluide
Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 76,17 108,93
161,16 44,6
75,5 NA 60 ---- 0 0 0 0 2 0
High pressure steam piping system
50251420_64J0105-C-PIPING CLASS
C91a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Fluid Tag/ Code fluide
Insulation thickness/
at design temp.
Sealing
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Conditions de calcul Design Soudures circ. Soudures SW
calcul
Groupe fluide
Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 76,17 108,93
89,47 44,6
75,5 NA 60 ---- 0 0 0 0 2 0
20 0 81,48 95,70 80,7 NA 60 ---- 0 0 0 0 2 0
25 0 85,95 100,95 85,2 NA 60 ---- 0 0 0 0 2 0
Auxiliary steam condensate
50251420_64J0105-C-PIPING CLASS
C91a
CLASS C9.1
DIMENSIONS :
P265GH SA 234 WPB
Design Thk/ Pipes Thk/ Design Thk/ Fittings Thk/ Ep Observations/
DN OD/ Diam. ext.
Ep. calculée Ep tuyauteries Ep. calculée raccords Comments
in mm mm mm mm mm mm kg/m
Note : Connecting piping with machining or reducing, see sheet "FITTINGS WELDING DETAILS"
Voir les raccordements par usinage ou par délardage sur la feuille "SOUDURE DES RACCORDS"
FLANGES/ BRIDES :
Piping Thk /
Weldolets 50 500 A105 BW ASME B16.9 Epaisseur tuyauterie
(*) - machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3 and general requirements of EN
13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les exigences générales spécifiées dans
EN13480-4 s'appliquent au processus de cintrage.
(**) : EN10253-2 type A fittings not accepted. BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be submited for
CNIM approval.
(**) Raccords selon EN10253-2 type A non admis. Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de réf.
choisies par le Fournisseur seront soumises à CNIM pour accord .
BOLTING/BOULONNERIE :
Thread/
Material/ Matériaux Type Filetage
Stud bolts/ 42CrMo4 / A193B7
Tiges filetées EN10269
--------- In compliance with/ Suivant EN 1515
Métric
C45E/ A194 2H
Nuts / Ecrous Heavy hex
EN10269
50251420_64J0105-C-PIPING CLASS
C91b
GASKETS/JOINTS :
spiral wound st. steel, graphite filler, with inner and outer protection rings (anti-corrosion treated)/ spiralé
Type
inox/graphite avec anneaux de protection (int. et ext.) traités anti-corrosion
Standard EN 12560-2 / type C/I
Class 900
Dimensions EN 12560-2
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves that may be installed on pipings
of this class. In some specific cases depending on design conditions and actual valve position the valve description may be different than the one given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et aider le concepteur dans la
définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des conditions de design et de fonctionnement le type de robinet
peut être différent de la liste ci dessous.
Note : Valves DN<=50 cl. 800 if suitable with the piping design conditions
Robinetterie DN<=50 en cl. 800 si les cond. de calcul des lignes correspondantes le permettent
50251420_64J0105-C-PIPING CLASS
C91b
CLASS C9.3
Class 900
Pipe material/ Matériau 16Mo3
Group of material/ Groupe de matériau ISO 15608 1.2
Seamless/
Type sans soudure
Standard EN 10216-2
Corrosion allowance/ Surépaisseur de corrosion [mm] 1,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 450 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 266 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 280 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 187 [N/mm2]
Maxi. design temp. without hot flow/ Temp. maxi de calcul sans fluage 500 [°C]
Mini. design temp. with hot flow (10000 h)/ Temp. mini de calcul avec fluage (10000 h) 500 [°C]
Maxi. design temp. with hot flow (10000 h)/ Temp. maxi de calcul avec fluage(10000 h) 500 [°C]
Mini. yield stress Rp0,2 at design temp. (°C)/ Limite d'élasticité Rp0,2 (Mpa) à la temp. de (°C)
Temp. 50 100 150 200 250 300 350 400 450 500 --- ---
Rp0,2T 280 243 237 224 205 173 159 156 150 146 --- ---
Creep rupture strength / Résistance à la rupture par fluage pour 10000 h (MPa) (11)
Temp. 450 460 470 480 490 500 510 520 530 540 550 --- --- --- --- --- --- ---
RmT 298 273 247 221 196 171 148 125 104 84 64 --- --- --- --- --- --- ---
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if other materials
than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la norme EN13480-
5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3 -or submitted
to a flexibility analysis. According to § 8.2.1 of
EN13480-5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le § 12.2.10.1 de la
norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée, l'étendue des contrôles NDE peut
être réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTE 4 : Allowable stress is indicated NA when the allowable stress is the one without creep and stress rupture.
La contrainte de calcul correspondant aux conditions de fluage est notée NA lorsque la contrainte prépondérante est celle sans fluage.
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTE 6 Piping used in the creep range, are classified in category III for NDE extend determination.
Dans le domaine du fluage , les tuyauteries sont classées en categorie III pour la determination des contrôles (article 8.2.1 norme EN 13480)
50251420_64J0105-C-PIPING CLASS
C93a
NOTE 7 All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between CNIM and the
Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles fera l'objet
d'un accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In this case the
concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées, p. ex. les
échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
NOTE 10 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5.
Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 11 : For pipings with high service temperature, a counting system may be provided to control time of exceeding the limit temperature for creep rupture situation. According to §5.2 of EN13480-3 security factor
of 1,25 is applied to hot flow design stress corresponding to life time below 100000h.
Pour les cas de fonctionnement à temperature élevée, un système de suivi de la durée de dépassement de temperature seuil fluage peut être prévu. Par conséquent, conformément au §5.2 de la EN13480-
3, un coéf. de sécurité de 1,25 est appliqué à la valeur de la contrainte de rupture par fluage pour une durée inférieure à 100000 h.
NOTE 12 : (**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
#####
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Fluid Tag/ Code fluide
Insulation thickness/
at design temp.
Sealing
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Conditions de calcul Design Soudures circ. Soudures SW
calcul
Groupe fluide
Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 70,28 164,00 70,3 NA 60 ---- 0 0 0 0 2 0
High pressure steam piping system
50251420_64J0105-C-PIPING CLASS
C93a
CLASS C9.3
DIMENSIONS :
16Mo3 16Mo3
Design Thk/ Pipes Thk/ Design Thk/ Fittings Thk/ Ep Observations/
DN OD/ Diam. ext.
Ep. calculée Ep tuyauteries Ep. calculée raccords Comments
in mm mm mm mm mm mm kg/m
Note : Connecting piping with machining or reducing, see sheet "FITTINGS WELDING DETAILS"
Voir les raccordements par usinage ou par délardage sur la feuille "SOUDURE DES RACCORDS"
FLANGES/ BRIDES :
Piping Thk /
Weldolets 50 500 16Mo3 BW ASME B16.9 Epaisseur tuyauterie
(*) - machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3 and general requirements of EN
13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les exigences générales spécifiées dans
EN13480-4 s'appliquent au processus de cintrage.
(**) : EN10253-2 type A fittings not accepted. BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be submited for
CNIM approval.
(**) Raccords selon EN10253-2 type A non admis. Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de réf.
choisies par le Fournisseur seront soumises à CNIM pour accord .
BOLTING/BOULONNERIE :
Thread/
Material/ Matériaux Type Filetage
Stud bolts/ 42CrMo5-6
Tiges filetées EN10269
--------- In compliance with/ Suivant EN 1515
Métric
42CRMo4
Nuts / Ecrous Heavy hex
EN10269
50251420_64J0105-C-PIPING CLASS
C93b
GASKETS/JOINTS :
spiral wound st. steel, graphite filler, with inner and outer protection rings (anti-corrosion treated)/ spiralé
Type
inox/graphite avec anneaux de protection (int. et ext.) traités anti-corrosion
Standard EN 12560-2 / type C/I
Class 900
Dimensions EN 12560-2
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves that may be installed on pipings
of this class. In some specific cases depending on design conditions and actual valve position the valve description may be different than the one given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et aider le concepteur dans la
définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des conditions de design et de fonctionnement le type de robinet
peut être différent de la liste ci dessous.
Manual/ monobloc
Manuelle Parallel slide/ Sièges
80 600 900 BW EN12627 16Mo3 1423/64E0002
parallèles
Note : Valves DN<=50 cl. 800 if suitable with the piping design conditions
Robinetterie DN<=50 en cl. 800 si les cond. de calcul des lignes correspondantes le permettent
50251420_64J0105-C-PIPING CLASS
C93b
CLASS C9.4
PN PN 160
Pipe material/ Matériau 13CrMo4-5
Group of material/ Groupe de matériau ISO 15608
Seamless/
Type sans soudure
Standard EN 10216-2
Corrosion allowance/ Surépaisseur de corrosion [mm] 1,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 440 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 276 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 290 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 183 [N/mm2]
Maxi. design temp. without hot flow/ Temp. maxi de calcul sans fluage 500 [°C]
Mini. design temp. with hot flow (10000 h)/ Temp. mini de calcul avec fluage (10000 h) 500 [°C]
Maxi. design temp. with hot flow (10000 h)/ Temp. maxi de calcul avec fluage(10000 h) 550 [°C]
Mini. yield stress Rp0,2 at design temp. (°C)/ Limite d'élasticité Rp0,2 (Mpa) à la temp. de (°C)
Temp. 50 100 150 200 250 300 350 400 450 500 --- ---
Rp0,2T 290 264 253 245 236 192 182 174 168 166 --- ---
Creep rupture strength / Résistance à la rupture par fluage pour 10000 h (MPa) (11)
Temp. 450 460 470 480 490 500 510 520 530 540 550 560 570 580 590 600 --- ---
RmT 377 347 319 292 264 238 209 181 155 131 109 90 74 60 50 41 --- ---
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if other
materials than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la norme
EN13480-5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3 -or
submitted to a flexibility analysis. According to §
8.2.1 of EN13480-5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le § 12.2.10.1 de la
norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée, l'étendue des contrôles NDE
peut être réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTE 4 : Allowable stress is indicated NA when the allowable stress is the one without creep and stress rupture.
La contrainte de calcul correspondant aux conditions de fluage est notée NA lorsque la contrainte prépondérante est celle sans fluage.
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTE 6 Piping used in the creep range, are classified in category III for NDE extend determination.
Dans le domaine du fluage , les tuyauteries sont classées en categorie III pour la determination des contrôles (article 8.2.1 norme EN 13480)
50251420_64J0105-C-PIPING CLASS
C94a
NOTE 7 All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between CNIM and the
Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles fera l'objet
d'un accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In this case the
concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées, p. ex. les
échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
NOTE 10 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5.
Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 11 : For pipings with high service temperature, a counting system may be provided to control time of exceeding the limit temperature for creep rupture situation. According to §5.2 of EN13480-3 security factor
of 1,25 is applied to hot flow design stress corresponding to life time below 100000h.
Pour les cas de fonctionnement à temperature élevée, un système de suivi de la durée de dépassement de temperature seuil fluage peut être prévu. Par conséquent, conformément au §5.2 de la
EN13480-3, un coéf. de sécurité de 1,25 est appliqué à la valeur de la contrainte de rupture par fluage pour une durée inférieure à 100000 h.
NOTE 12 : (**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
#####
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Fluid Tag/ Code fluide
Insulation thickness/
at design temp.
Sealing
Coating/ Peinture
(Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
Catergory/ Categorie
Pressure test/
Pressure allowable
les soudures
Conditions de calcul Design Soudures circ. Soudures SW
calcul
Groupe fluide
Soudure
Index
Fluid group/
DN test stress BW (6) (12) tubulures (6)(12)
conditions/ d'étanch.
conditions/ contr. réelle /
Stress Conditions
Conditions contr. Surface Surface
Sans rupture de calcul Volume Volume Surface Surface
d'épreuve admissible) NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 70,68 139,60 63,6 NA 60 ---- 0 0 0 0 2 0
High pressure steam piping system
50251420_64J0105-C-PIPING CLASS
C94a
CLASS C9.4
DIMENSIONS :
13CrMo4-5 13CrMo4-5
Design Thk/ Pipes Thk/ Design Thk/ Fittings Thk/ Ep Observations/
DN OD/ Diam. ext.
Ep. calculée Ep tuyauteries Ep. calculée raccords Comments
in mm mm mm mm mm mm kg/m
Note : Connecting piping with machining or reducing, see sheet "FITTINGS WELDING DETAILS"
Voir les raccordements par usinage ou par délardage sur la feuille "SOUDURE DES RACCORDS"
FLANGES/ BRIDES :
Piping Thk /
Weldolets 50 500 13CrMo4-5 BW EN 10222 Epaisseur tuyauterie
(*) - machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3 and general requirements of EN
13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les exigences générales spécifiées dans
EN13480-4 s'appliquent au processus de cintrage.
(**) - BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be submited for CNIM approval.
(**) - Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de réf. choisies par le Fournisseur seront soumises à CNIM
pour accord .
BOLTING/BOULONNERIE :
Thread/
Material/ Matériaux Type Filetage
Stud bolts/ 42CrMo5-6
Tiges filetées EN10269
--------- In compliance with/ Suivant EN 1515
Métric
42CRMo4
Nuts / Ecrous Heavy hex
EN10269
50251420_64J0105-C-PIPING CLASS
C94b
GASKETS/JOINTS :
spiral wound st. steel, graphite filler, with inner and outer protection rings (anti-corrosion treated)/ spiralé
Type
inox/graphite avec anneaux de protection (int. et ext.) traités anti-corrosion
Standard EN 12560-2 / type C/I
Class 160
Dimensions EN 12560-2
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves that may be installed on pipings
of this class. In some specific cases depending on design conditions and actual valve position the valve description may be different than the one given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et aider le concepteur dans la
définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des conditions de design et de fonctionnement le type de robinet
peut être différent de la liste ci dessous.
Manual/ monobloc
Manuelle Parallel slide/ Sièges
80 600 160 BW EN12627 13CrMo4-5 1423/64E002
parallèles
Note : Valves DN<=50 cl. 800 if suitable with the piping design conditions
Robinetterie DN<=50 en cl. 800 si les cond. de calcul des lignes correspondantes le permettent
50251420_64J0105-C-PIPING CLASS
C94b
CLASS C15.2
Class 1500
Pipe material/ Matériau TP316L
Group of material/ Groupe de matériau ISO 15608 8.1
Seamless/ sans
Type soudure
Standard EN 10216-5
Corrosion allowance/ Surépaisseur de corrosion [mm] 0,0 [mm]
Mini. tensile stress Rm at room temp./ Résistance à la traction Rm (temp. ambiante). 485 [N/mm2]
Allowable stress test conditions(room temp.)/ Contrainte de calcul situation d'essai 163 [N/mm2]
Allowable design stress at room temp./ Contrainte de calcul à la temp. ambiante 108 [N/mm2]
Mini. yield stress Rp0,2 at room temp./ Limite d'élasticité Rp0,2 à la temp. ambiante 172 [N/mm2]
NOTE 1 : The "NDE extent [%] per type of weld acc. to EN 13480-5" column contains values corresponding to materials of group 1.1, 1.2 and 8.1. The rules of § 8.2.1 of EN13480-5 shall be applied if other
materials than those mentioned here above are used.
La colonne "Etendue de contrôle NDE [%] selon EN 13480-5" contient les pourcentages de contrôle correspondant aux groupes des matériaux 1.1, 1.2 et 8.1. Les valeurs du § 8.2.1 de la norme
EN13480-5 doivent être appliquées en cas d'utilisation des matériaux autres que ceux mentionnés ci-dessus.
NOTE 2 : A flexibility examination is required when both following conditions are met: - design temperature T>=100 °C - nominal diameter DN>= 80
In other cases, it is under supplier's responsibility whether to perform such an analysis or not.
L'étude de flexibilité est requise pour les tuyauteries remplissant les deux conditions suivantes : - temperature de calcul T>=100 °C - diamètre nominal DN >= 80
Dans les autres cas , la réalisation ou non de l'analyse est de la responsabilité du fournisseur .
NOTE 3 : Pipings that do not comply with conditions specified in NOTE 2 here above (identified by "?" in "Flexibility analysis" column) shall be :
-in compliance with § 12.2.10.1 of EN 13480-3 -or
submitted to a flexibility analysis.
According to § 8.2.1 of EN13480-5 and depending on real calculated stress value, the extent of Non Destructive Examination (NDE) given in the table below may be reduced of 50%.
Les tuyauteries qui ne remplissent aucune des deux conditions évoquées en NOTE 2 ci-dessus (identifiées par "?" dans la colonne "Analyse de flexibilité" ), ni celles définies dans le §
12.2.10.1 de la norme EN 13480-3 doivent être soumises aux calculs de flexibilité. Conformément au § 8.2.1 de la EN13480-5 et en fonction de la valeur de la contrainte réelle calculée,
l'étendue des contrôles NDE peut être réduite de 50% par rapport aux valeurs données dans le tableau ci-dessous.
NOTA 4 : For stainless steel piping pressure test , halogen concentration within the water have to be controlled and must not exceed 50x10-6 ppm
Pour les essais hydrostatiques de réseaux de tuyauterie en acier inoxydable austénitiques, la concentration en halogène dans l'eau doit être contrôlée et ne doit pas dépasser 50x10-6 ppm .
NOTE 5 The actual stress values given in the columns below takes into account the internal pressure only.
: Les contraintes réelles données dans le tableau ci-dessous tiennent compte uniquement de la pression de design (pression interne dans la tuyauterie).
NOTA 6 : Abbreviations : NA - not applicable ; NS - not submitted ; MT, PT, RT,UT - see EN 13480-5. Abréviations : NA - non applicable ; NS - non soumis ; MT, PT, RT, UT, VT - voir EN 13480-5.
NOTE 7 : All welds that, for any reason, can not be submitted to hydraulic testing, shall be controlled by an appropriate NDE method complying with § 9 of EN 13480-5 standard.
(**) A 100% liquid penetrant examination (PT) is required if a hydraulic test is not carried out.
Les soudures des tuyauteries qui ne peuvent pas être soumises à l'épreuve hydraulique seront testées par une methode NDE appropriée en accord avec le § 9 de la EN 13480-5.
(**) En l'absence d'épreuve hydraulique un contrôle PT 100% est requis
50251420_64J0105-C-PIPING CLASS
C152a
NOTE 8 : Pipings having design pressure <= 0,5 bars g (i.e. not submitted to DESP 97/23) will be tested according to the appropriate technical widely recognized rules of conduct agreed between CNIM
and the Customer.
Les tuyauteries ayant la pression de design P <= 0,5 bars eff. (c.à.d. non soumises à la DESP 97/23) seront contrôlées conformément aux règles de bonne pratique ; l'étendue des contrôles fera
l'objet d'un accord entre la Sté CNIM et son Client.
NOTE 9 : Insulation thickness values are defined complying to CNIM rules. Some pipings will not be insulated in accordance with the table below, ex. safety valves discharge vent pipes and vents. In this
case the concerned piping will be painted or, if necessary, will have a 30 mm thick insulation to provide self security protection.
Les épaisseurs de l'isolation thérmique en fonction de P,T et DN sont définies conformément aux règles internes de conception de la CNIM. Certaines tuyauteries ne seront pas calorifugées, p.
ex. les échapp. soupapes. Dans ce cas les tuyauterie concernées seront peintes ou, éventuellement, revêtues d'une protection dite personnel de 30 mm d'ép.
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Coating/ Peinture
design temp. (Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
flexibilité (2), (3)
Catergory/ Categorie
conditions/ welds/
/Contrainte de allowable
Pressure test/
Conditions de Pressure Soudures circ. Soudures SW
Design Soudure
Groupe fluide
Index
soudures
calcul DN stress
Fluid group/
calcul test BW (6) tubulures (6) d'étanch.
conditions/ contr. réelle /
conditions/
Stress Conditions contr.
Conditions Surface Surface
Sans rupture de calcul admissible) Volume Volume Surface Surface
d'épreuve NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 75,20 126,90 94,0 NA 30 NA 0 0 0 0 2 0
20 0 76,04 128,32 95,0 NA 30 NA 0 0 0 0 2 0
Feed water
50251420_64J0105-C-PIPING CLASS
C152a
Actual stresses/ Contr. NDE [%] extend acc. to EN 13480-5/ Etendue contrôle
Allowable EN 13480-1 réelle (5) NDE [%] selon EN 13480-5 (1), (7), (8)
stress at Stress ratio
Design
Coating/ Peinture
design temp. (Actual stress /
Pression d'épreuve
Circ. Welds/ Branch weld/
calorifuge (9)
flexibilité (2), (3)
Catergory/ Categorie
conditions/ welds/
/Contrainte de allowable
Pressure test/
Conditions de Pressure Soudures circ. Soudures SW
Design Soudure
Groupe fluide
Index
soudures
calcul DN stress
Fluid group/
calcul test BW (6) tubulures (6) d'étanch.
conditions/ contr. réelle /
conditions/
Stress Conditions contr.
Conditions Surface Surface
Sans rupture de calcul admissible) Volume Volume Surface Surface
d'épreuve NDE NDE
fluage (4) NDE NDE NDE NDE
P T (**) (**)
10000h
barg °C N/mm2 [mm] MPa N/mm2 [%] [mm] VT MT/PT RT/UT MT/PT RT/UT MT/PT MT/PT
15 0 75,20
61,82 126,90
88,40 94,0
57,2 NA 0 NA 0 0 0 0 2 0
20 0 62,51 89,38 57,9 NA 0 NA 0 0 0 0 2 0
Phosphate
50251420_64J0105-C-PIPING CLASS
C152a
CLASS C15.2
DIMENSIONS :
X6CrNiNb18-10
Design Thk/
DN OD
Ep. calculée Schedule.
in mm mm mm
1 25 33,4 2,76 10 S
2 50 60,3 5,01 80 S
3 80 88,9 7,38 80 S
FLANGES/ BRIDES :
Standard/ Norme ASME B16.5/EN 1759
Class 1500
FITTINGS/RACCORDS :
DN [mm] Material/ Ends / Standard / ASME Class / Thk /
-> <- Matériau Embouts Norme Epaisseur
Tees , elbows (*) , reducers , caps / 8 40 A182 F316L SW ASME B16.11 3000
Piping Thk /
Tés, coudes (*), réductions, fonds 50 150 A403WP316L BW ASME B16.9 Epaisseur tuyauterie
Piping Thk /
Weldolets 50 150 A182 F316L BW ASME B16.9 Epaisseur tuyauterie
(*) - machine bending R=5D is preferable for DN<=40 instead of forged elbows ; the design thickness requirements specified in EN 13480-3
and general requirements of EN 13480-4 apply to all bend process.
(*) - Cintrage machine de préférence pour DN <= 40, rayon 5*D ; les préscriptions de la EN13480-3 concernant les épaisseurs et les
exigences générales spécifiées dans EN13480-4 s'appliquent au processus de cintrage.
NOTE : BW ends shall be in accordance with equivalent pipe thickness. Fitting specification chosen by the supplier shall be submited for
CNIM approval.
NOTE : Les dim. des embouts BW doivent être en accord avec les ép. des tuyauteries correspondantes ; les normes de réf. choisies par le
Fournisseur seront soumises à CNIM pour accord .
50251420_64J0105-C-PIPING CLASS
C152b
Material/ Thread/
BOLTING/BOULONNERIE : Matériaux
Type Filetage
Stud bolts/
Tiges filetées
21CrMoV5-7 ---------
Métric
Nuts / Ecrous 21CrMoV5-7 Heavy hex
spiral wound st. steel, graphite filler, with inner and outer protection rings (anti-corrosion treated)/
Type
spiralé inox/graphite avec anneaux de protection (int. et ext.) traités anti-corrosion
Standard ASME B16.20 / EN 12560-2 / type C/I
Class 1500
Dimensions ASME B16.20 / EN 12560-2
ROBINETTERIE :
Informations given in table below shall be considered as a guide representig general rules applied in choice and design of valves
that may be installed on pipings of this class. In some specific cases depending on design conditions and actual valve position the
valve description may be different than the one given below.
Les informations contenues dans le tableau ci-dessous sont données à titre indicatif. Elles doivent servir comme guide général et
aider le concepteur dans la définition du marériel appartenant à cette classe. Dans certains cas spécifiques, en fonction des
conditions de design et de fonctionnement le type de robinet peut être différent de la liste ci dessous.
50251420_64J0105-C-PIPING CLASS
C152b
CONNECTIONS/BRANCHEMENTS
CLASS C1.1 :
Branch size DN/ DN ligne
secondaire [mm]
DN 8 15 20 25 40 50 80 100 150 200 250 300 350 400 450 500 550 600
600
550
500
450
400 D
Main pipe size DN/
DN ligne principale
350
300
[mm]
250
200
150
100
80
50
40 A
B
25 A
20 A
15 A
8 A
CLASS C1.2 :
Branch size DN/ DN ligne
secondaire [mm]
DN 8 15 20 25 40 50 80 100 150 200 250 300 350 400 450 500 550 600
600
550
500
450
400 D
Main pipe size DN/
DN ligne principale
350
300 C
[mm]
250
200
150
100
80
50
40 A
B
25 A
20 A
15 A
8 A
50251420_64J0105-C-PIPING CLASS
Branch conn. Page 81
CONNECTIONS/BRANCHEMENTS
CLASS C1.3 :
Branch size DN/ DN ligne
secondaire [mm]
DN 8 15 20 25 40 50 80 100
100 E
Main pipe size DN/
DN ligne principale
80 E
50 F E
[mm]
40 E
25 E
20 E
15 E
8 E
CLASS C1.4 :
Branch size DN/ DN ligne
secondaire [mm]
DN 8 15 20 25 40 50 80 100 150 200 250 300 350 400 450 500 550 600
600
550
500
450
400
Main pipe size DN/
DN ligne principale
350 J
300
[mm]
250
200
150
100
80
50
40 G
H
25 G
20 G G - Straight tee BW
15 G H - Reducing outlet tee BW
8 G J - Branch on pipe without reinforcement
G - Té égal BW
H - Té réduit BW
J - Piquage tube sur tube sans renfort
50251420_64J0105-C-PIPING CLASS
Branch conn. Page 82
CONNECTIONS/BRANCHEMENTS
350 M
300 N M
[mm]
250 M
200 M
150 M
100 M
80 M
50 M L - Straight tee SW
40 L M - Straight tee BW
R
25 L N - Half coupling
20 L P - Weldolet or straight tee + reducer
15 L R - Straight tee SW + half coupling
8 L
L - Té égal SW
M - Té égal BW
N - Demi manchon
P - Raccord type WELDOLET ou Té+reduction au choix
R - Té égal SW + Réduction M/F(SW)
Note : If welded branches are used instead of WELDOLETS, the supplier will have to issue a
calculation note acc. to EN 13480-3.
Si les piquages avec anneaux renforts sont réalisés au lieu de WELDOLETS, le Fournisseur
devra présenter une note de calcul en accord avec EN 13480-3.
50251420_64J0105-C-PIPING CLASS
Branch conn. Page 83