GUARANTEED TECHNICAL PARTICULARS PORTABLE LT/HT ACCUCHECK AGAINST

TN-2434

Sr. Technical Specification Requirements Bidder’s Offer


No.

1. a)Makers name Please specify manufacturer ‘ZERA’ .Made in Germany.


and country & name & works address Zera India Private Limited
works address. A-47 Sector 25 , GDIC
Electronic Estate,
Gandhinagar , Gujrat.

b) GST 24AAACZ3469K1ZZ
registration No.

2. Type of Meter Please specify model MT310 Working Standard


number and attach product Meter. Product brochure
literature/ brochure. attached.

3. Accuracy Class Class 0.1 Direct Mode and Class 0.1S for Direct mode
0.2S with Clamp-On Mode and 0.2S for clamp-on mode.
(split core error However 0.5S suitable
compensated current additional clamp on CTs is
transformer) for Active, also provided as per Spec CL
Reactive and Apparent 3.13 (b).
Energy

4. Voltage Range To be defied 100mV-300V

5. Current Range To be defied for both 1 mA-12A Direct mode


measuring mode
10mA-120A Clamp-on mode

6. Current rating of Please specify the rating of 10mA-120 A


Clamp On CT clamp on CT

7. Parameters  Instantaneous
Displayed– Parameters
1. Real Time & Date 1. Real Time & Date
2. Instantaneous Voltage of 2. Instantaneous Voltage of
each phase for 4 wire and each phase for 4 wire and
line voltage for 3 wire line voltage for 3 wire
3. Instantaneous Line 3. Instantaneous Line current
current of each phase of each phase
4. Instantaneous active and 4. Instantaneous active and
reactive current of each reactive current of each
phase phase
5. Instantaneous Power 5. Instantaneous Power Factor
Factor of each phase & of each phase & total power
total power factor. factor.
6. Instantaneous Frequency 6. Instantaneous Frequency
7. Simultaneous display of 7. Simultaneous display of
Active, Reactive and Active, Reactive and
Apparent Load Apparent Load
8. Phase Sequence 8. Phase Sequence
9. Active, Reactive (Lag & 9. Active, Reactive (Lag &
Lead) and Apparent Lead) and Apparent
Energies Energies .
10. Continuous update of 10. Continuous update of
Active, Reactive (Lag & Active, Reactive (Lag &
Lead) and Apparent Lead) and Apparent
Energies on display. Energies on display.

 Incremental values of  Incremental values of


energies during test energies during test
1. Active Energy 4. Active Energy
2. Reactive Energy (lag / 5. Reactive Energy (lag / lead)
lead) Apparent Energy
3. Apparent Energy

8. Display 1. Voltage - 0.00 Volt 4 digit resolution after decimal


Resolution-
2. Current - 0.00 Amp 4 digit resolution after decimal

3. Frequency - 0.00 Hz 3 digit after decimal

4. Individual Power Factor - 4 digit resolution after decimal


0.000 for all ranges

5. Average 3- phase Power 4 digit after decimal


Factor - 0.000 for all
ranges

6. Instantaneous Load (kW/ 4 digit after decimal


kVAr/ kVA) - 0.000

7. Energy Wh/ VArh/ VAh -


6 digit after decimal
0.000 for all ranges

8. % Error Resolution - 0.00 5 digit after decimal


Connection check 1. Missing Current Through vector diag &
9. instantaneous values.
2. Missing Potential Through vector diag &
instantaneous values.
3. Reverse Current if any Reverse current indication by
current is reverse PF & vector representation.
4. Accidental connection of Through vector diag &
both types of instantaneous values.
measurement modes.
5. Phase Association Through vector diag &
instantaneous values.
6. Phase Sequence (Forward Through vector diag &
or Reverse) instantaneous values.

7. Over Voltage Overload indication on display


8. Over Current Overload indication on display
10. Type of Display Graphical Display LCD graphical display

11. Interfaces 1. USB/ RS232 connector


for connecting to the PC. 1. RS232 connector
provided.
2. Scanning Head switch to 2. Scanning Head switch
count pulses. to count pulses/mark
on rotor.
3. Remote snap switch to
count pulses. 3. Remote snap switch
provided.
12. Memory Minimum 400 test results Could not be verified.

13. Parameters to be 1. Date & Time stamp Verified for all given
logged in 2. Serial Number of the parameters. Annexure
memory during MUT enclosed.
3. Consumer Identification
each test.
4. Meter Constant of the Annexure -3 Pg no. 8.
MUT
5. No. of Test Revolutions /
Pulses for which test is
being carried out
6. PT Ratio (as the case
may be)
7. CT Ratio (as the case
may be)
8. Instantaneous voltage of
each phase.
9. Instantaneous line
current of each phase.
10. Instantaneous
Frequency
11. Instantaneous Power
Factor of individual
phases & total P. F.
12. Energy logged by
equipment (Active,
Reactive & Apparent)
13. Instantaneous Load in
KW, KVA & KVAr
14. Test Duration
15. Percentage Error of
Active, Reactive (Lag/
Lead), Apparent Energy

14. Scanning head Common for rotor mark & Provided.


LED/LCD pulses To sense
pulses up to 200 Hz.

15. Snap Switch Snap Switch to operate Provided.


equipment remotely

16. Dial Test Facility Relay Output for dial test. Provided.

17. Key Board Alphanumeric key pad Provided.

18. Type Test Type Test report from To be verified by purchaser.


recognized lab shall be
submitted. With type test
reports tender shall be
rejected.

19. Measurement of Measurement up to 30th Verified upto 40th harmonics.


Harmonics Harmonic (minimum) with
display of effective active,
reactive and apparent
power due to each harmonic

20. Accessories Whether all accessories as All accessories provided as per


per clause 18 of the sheet enclosed.
specification are provided?
Please furnish details.
21. Carrying Case Shall be packed in Aluminum carrying case
Aluminum casing. provided.

---------------------------