MVA 1000 kV A
Mvar 1000 kV A
pu 1
kVA kV A
kvar kVA
Variable Declarations
Generator voltage,
VGEN 13.8 kV
line-line
System frequency f 60 Hz
1/3
Calculations
Total capacitance per phase CT CGEN CGSU CUAT CBUS CSURGE CVT CT 0.6531 μF
Capacitive reactance
1
per phase Xco Xco 4062 Ω
2 π f CT
The NGR must be less than or equal to the capacitive reactance seen at the neutral,
Xcg
Neutral grounding resistor RNGR RNGR 0.5415 Ω
initial value 2
N
RNGR
Neutral grounding resistor RNGR
RTC RNGR 0.4513 Ω
final value 1
VGLN
Neutral grounding transformer Ir_s Ir_s 353 A
secondary current N RNGR
Is the resistance component of the ground-fault current greater than the capacitive current?
Ir_s
Icheck I3co Icheck 1
N
2/3
Is the resistor power loss greater than the capacitive reactive power?
SNGT 15 kVA
Choose next larger standard distribution transformer rating:
3/3