Академический Документы
Профессиональный Документы
Культура Документы
TABLE OF CONTENTS
Warranty
Precautions
Part 1 About this Manual . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 1
Part 2 Description . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.1 Features . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
2.2 Hardware Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
2.3 Signal Processing, Load Outputs and Alarms . . . . . . . . . . . . . . . . . . . . . . . . . 4
2.4 Auxiliary Functions . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.1 Single Sensor Operation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.2 Auto Zero . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.3 Auto Calibration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.4 Wrap Angle Compensation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.5 Self Test . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.6 Reset . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 8
2.4.7 Lockout . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.5 Setup and Configuration . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.6 Diagnostics . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.7 Interfaces . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 9
2.7.1 Sensor Ports . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7.2 Auxiliary Analog Inputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7.3 Analog Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7.4 Fieldbus Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7.5 Serial Communications Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . 11
2.7.6 Front Panel Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
2.7.7 Logic Inputs and Outputs . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 12
Part 3 User Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.2 User Access Program . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 13
3.3 Front Panel Interface . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 14
3.3.1 Display and Keypad . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
3.3.2 Menus . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 15
Part 4 Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.1 Introduction . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 29
4.2 Cabinets . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.3 Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 30
4.3.1 AC Power Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.3.2 Sensor Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 32
4.3.3 Auxiliary Analog Input Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 35
4.3.4 Analog Output Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 37
4.3.5 Logic I/O Wiring . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 39
4.3.6 Serial Communications (SCI) Wiring . . . . . . . . . . . . . . . . . . . . . . . . 44
WARRANTY
The KELK Rollmax Digital Signal Processor, Model DSP2, is warranted against
defects in materials and workmanship for one year from the date of installation or
eighteen months from the date of shipment, whichever occurs first. This warranty
is independent of the KELK Rollmax Load Cell Five Year Conditional Warranty.
Should the equipment prove defective during the warranty period, KELK’s
obligation is limited to repair or replacement at our factory or, at our option, at the
premises of our designated local agent. Should the customer not wish to return
the product to the KELK factory or local agent for repair or replacement, KELK
will, if feasible, perform the necessary work at a suitable location in the
customer’s premises free of any charges for replaced materials or components
providing that he agrees to pay KELK’s standard hourly service rates for site and
travel time, plus transportation costs and living expenses at cost.
Products submitted for a warranty claim shall be shipped prepaid by the customer
to and from our factory where they will be inspected and repaired or replaced, at
our option.
PRECAUTIONS
Intended Use
The Rollmax Digital Signal Processor, Model DSP2, is intended for use only with
factory calibrated KELK strain gage sensors in load measuring systems. Do not
use the DSP2 in a manner not expressly described in this manual or approved by
authorized KELK personnel or their agents. The outputs and the alarms will be
unpredictable, both the DSP2 and the equipment to which it is connected may be
damaged and the protection provided by the DSP2 may be impaired.
Accessibility
The DSP2 enclosure is tool accessible and should only be opened by qualified
service personnel. Always disconnect the DSP2 from the power source before
removing the cover. Do not reconnect power until the cover has been replaced
and secured. The only permissible user service, the replacement of printed circuit
boards, does not require the application of power while the cover is removed.
The DSP2 is marked with IEC 61010 symbols to warn the user of items requiring
particular attention for safety reasons.
Electrostatic Damage
Information is provided for installing, operating and servicing the Rollmax Digital Signal
Processor, Model DSP2, as part of a KELK Roll Force, Pressure or Tension Measuring
System in metals rolling mills, or KELK Load Measuring System in metals and ore
processing applications.
Users of this manual must pay particular attention to the Precautions section at the front
of the manual and to all Warnings and Cautions contained herein.
If additional technical assistance is required, contact KELK at the address given on the
title page or our designated agent.
Translation of this manual into another language may result in loss of meaning and
content; in all cases, the content of the English version upon which the translation was
based prevails.
PART 2 DESCRIPTION
2.1 Features
The Rollmax Digital Signal Processor, Model DSP2, Figure 2.1, is a principal component
of KELK load measuring systems. It complements KELK strain gage sensors, providing
optimum performance in metal rolling, temper, and skin pass mills, metal and ore
processing, and other demanding industrial applications.
KELK measuring systems employ strain gage technology to ensure fast response,
excellent linearity and low hysteresis, and to permit the design and construction of very
robust sensors incorporating a one piece load sensing element.
Wrap Angle Compensation (WAC) for varying wrap angle tension measuring
applications
Menu driven setup and configuration. No manual hardware adjustments are required.
Continuous monitoring of the measuring system, including the DSP2 and the sensors
Load Simulation
A Signal Processor Board containing the digital signal processing electronics and
Logic I/O’s.
Two Strain Gage Interface Boards, providing sensor excitation and analog signal
processing, one for each sensor.
One Analog Output Boards, with two user configurable outputs.
A Power Supply.
A Front Panel User Interface Assembly.
One or two additional Analog Output Boards, for a maximum of six Analog Outputs.
A Fieldbus Card for the high speed transmission of digital data using Ethernet
(Modbus/TCP) or Profibus protocols.
An Auxiliary Analog Input Board for inputting analog wrap angle data in varying
wrap angle tension measuring applications.
The power switch, fuse and all connections are located on the rear panel.
Basic on-line signal processing for roll force, pressure, fixed wrap angle tension and load
measuring applications is shown in Figure 2.3. Signal processing for variable wrap angle
tension measuring applications is shown in Figure 2.4. Only one Analog Output and one
Load Alarm are shown - all Analog Outputs (up to six) and all Load Alarms (up to 4) can
be independently configured as the user pleases.
For roll force, pressure, fixed wrap angle tension and load measuring applications:
3. The sum (A+B) load and difference (A-B) load are calculated to complete the Load
Measurement Set. Only one Load Measurement Set is shown; however, there are
two. One includes user configurable signal filtering and is the source for the digital
and analog load outputs. The other, used for the alarms, does not include the filter.
through the Analog Outputs. Each output can be configured for load A, B, A+B
or A-B, for scaling factor and for voltage or current format.
5. The Load Alarms can be configured for load level or rate-of-change-of-load, for load
A, B, A+B or A-B, for threshold and for response time.
The zero offsets (Step 1) and gains (Step 2) are applied in two stages:
During analog signal processing - to coarse levels, set by the DSP2 during
Configuration to provide optimum resolution following A/D conversion.
(Configuration is performed during installation to calibrate the measuring system
and apply tare weight compensation.)
During subsequent digital signal processing - to fine tune the offsets and gains for
any adjustments introduced by Auto Calibration and Auto Zero.
The Load Measurement Set is also accessible, at a rate suitable for monitoring and data
logging purposes, through the Serial Communications Interface.
For tension applications, with varying wrap angles, signal processing is as described
above except that a scaling factor is applied following gain adjustment to compensate for
the changes in the angles. The scaling factor is calculated using lookup tables, entered
during setup, and sensor or manual inputs of wrap angle magnitude.
Sensor A Sensor B
Zero Offset A Calibration Calibration Zero Offset B
Target Load Target Load
Gain A Gain B
Channel A Channel B
Load Load
Single Sensor A
Operation Invoked
Channel A + Channel A -
Channel A Channel B
Channel B Channel B
Alarm
Load
Serial Analog Output
or
Communications A, B, A+B or A-B
Rate-of-Change-of-Load
Interface A,B, A+B or A-B
Figure 2.3 Basic Signal Processing - Roll Force, Pressure and Fixed Wrap Angle
Tension Measuring Applications
Sensor A Sensor B
Zero Offset A Calibration Calibration Zero Offset B
Target Load Target Load
Gain A Gain B
Channel A Channel B
Channel B Load Normal operation
Load Load
Single Sensor A
Operation Invoked
Channel A + Channel A -
Channel A Channel B
Channel B Channel B
Alarm
Load
Serial Analog Output
or
Communications A, B, A+B or A-B
Rate-of-Change-of-Load
Interface A,B, A+B or A-B
Figure 2.4 Basic Signal Processing - Variable Wrap Angle Tension Measuring
Applications
Single Sensor Operation, otherwise known as load doubling, connects both Channel A
and B registers in the Load Measurement Set to the same sensor channel. User initiated,
it provides an output on both channels in the unlikely event of a sensor or Strain Gage
Interface Board failure.
Auto Zero compensates for small changes in tare weight, without affecting other
measuring system settings. User initiated, it adjusts the fine offsets to set both channel
outputs to zero and indicates if a detected offset falls outside a range of ± 20% of the
defined channel input range.
Auto Calibration allows the user to ensure that the load measuring system has remained
in calibration. It fine tunes the zero offsets and gains to set the outputs of both channels
to zero and recalibrate the system.
If one or both strip wrap angles vary in tension measuring applications, an adjustment is
required. Wrap Angle Compensation (WAC) provides this adjustment by generating and
applying a scaling factor using wrap angle magnitude data.
The Self Test is performed automatically each time the DSP2 is turned on. It can also be
initiated manually. Temporarily freezing the Digital and Analog Outputs, it includes
more extensive testing than is possible during normal system operation but undertakes no
corrective actions.
2.4.6 Reset
When initiated, Reset has the same effect as turning on the system. The system is
initialized and normal operation commenced.
2.4.7 Lockout
Lockout prevents changes being made to the system setup and the use of Configuration,
Reset and Simulation. Single Sensor operation, Auto Zero and Auto Calibration and
Self Test are not locked out.
The DSP2 can be setup and configured with the User Access Program or through the
Front Panel Interface. No hardware adjustments are required. The interfaces are
described in Part 4. Setup and Configuration are described in Part 5.
2.6 Diagnostics
The DSP2 monitors measuring system performance, both continuously during on-line
operation and in response to Self Test and other auxiliary functions. System status is
annunciated:
For operational purposes, by Logic Outputs (Section 2.7.7) and through the user and
communications interfaces as described in Section 6.4.
For troubleshooting purposes, through the user and communications interfaces as
described in Section 7.1.
2.7 Interfaces
Function Interface
Input, Output, Control, Indicator
Serial Communications
Disabled by Lockout
Analog Outputs
Logic Outputs
Logic Inputs
Sensor Ports
Fieldbus
Inputs
Sensors x
Wrap Angle Input - On-line Mode x x
Load Outputs (For mill control) x x
Load Alarm Indication x x x x x
Operations
Load Monitoring and Display x x x x
Status Indication - Electronics Healthy x x
System Fault x x x
Channel A Fault x x x
Channel B Fault x x x
Single Sensor Op. x x x
Single Sensor Operation - Invoke x x x x x
- Revoke x x x
Auto Zero x x x x x
Auto Calibration x x x x x
Wrap Angle Input - Off-line Mode x x x x
Self Test x x x
Reset x x x
Lockout x x
Setup and Configuration x x x
Diagnostics
System Status x x x x
Calibration Data x x
Wrap Angle Compensation x x
Load Simulation x x x
Hardware and Firmware Data x
Gives access to the Load Measurement Set at a rate suitable for mill control.
Provides access for monitoring and controlling the DSP2.
Allows wrap angle data to be input.
The Ethernet (Modbus/TCP) and Profibus Interfaces are described in Appendices B and
C, respectively.
RS232 and RS485 modes are available. All DSP2’s employed in a mill can be connected
in RS485 mode to the mill computer.
The load data output over this interface are intended for data logging and monitoring purposes
only. For mill control, the higher output rate of the Fieldbus Interface is required.
The Front Panel Interface provides access for system setup, monitoring and control. It
comprises an alpha-numeric display, keypad, and status indicators. It is described in
Section 3.3.
Self Test.
Auto Calibration.
Auto Zero.
Single Sensor A Operation.
Single Sensor B Operation.
Lockout.
The functions are initiated by a user supplied voltage pulse or external contact closure.
3.1 Introduction
The user can setup, configure, monitor and control the measuring system:
The User Access Program (UAP) operates in a Windows environment and is menu
driven. It is supplied on a CD for installation on a user supplied PC or laptop.
Refer to Appendix E for details.
Two communication modes, RS232 or RS485, are available. Only one can be in use at
any time.
Load data output over this interface are intended for data logging and user monitoring
purposes only. For mill control, the higher output rate of the Fieldbus Interface is
required.
Title Page
Operations Panel
Setup
Input Channels
Analog Outputs
Load Alarms
Wrap Angle Compensation
Communications
Front Panel Displays
Diagnostics Status Screen
Configuration Data
Hardware Identification
Factory Calibration
Simulation
The Operations Panel displays the system operational condition and provides access to all
DSP2 control functions described in Part 6.
The Setup Summary Panel is the entry point for Setup and Configuration, described
in Part 5.
The Diagnostics Panel provides detailed fault identification for troubleshooting purposes,
load simulation and system test, described in Part 7.
ENTER
ZERO
In this manual, all references to keys are in upper case, e.g. ENTER and all displayed
menu items, parameters and functions are in bold print e.g. LoadDisp.
The display contains eight alpha-numeric characters.
The keypad contains nine keys:
ENTER To navigate the menu, edit a variable parameter and initiate a diagnostic process.
MENU To return to the menu entry point from any location in the menu.
3.3.2 Menus
The menu has a hierarchical structure. The complete menu is illustrated in Figure 3.2. It
comprises the Main Menu, illustrated in Figure 3.5, which leads to lower level menus,
Figures 3.6 to 3.15. Note: In this version of the manual, there are no figures
designated 3.3 and 3.4.
The Self Test, Configuration and Reset functions in the Main menu (Figure 3.5) and the
parameters in the Load Display menu (Figure 3.6) are discussed in Part 6, Operation.
The parameters in the Setup menus (Figures 3.7 to 3.13) are discussed in Part 5, Setup
and Configuration.
The parameters in the Diagnostics (Figure 3.14) and Calibration (Figure 3.15) menus are
discussed in Part 7, Troubleshooting.
When the signal processor is first switched on, BootDSP2, then Reset is displayed for
several seconds and is automatically followed by WAIT!!! which is then automatically
followed by KELKDSP2, the menu entry point. Then, if there is no user intervention
for a user selected time interval, a user selected default parameter, or series of parameters,
is displayed.
March 2008
Figure 3.2
16
Complete Menu
App_Tens Shnt100k AT099.99 BT099.99 Inp__2xA
Addr_254
App_Pres Shnt150k Inp__2xB
LEGEND
Addr_254
Shnt200k
MENU ORIGIN ( KELKDSP2 ) OR RETURN
MENU
Menus are navigated using the ENTER, ESC, ←, → and MENU keys.
ESC To undo the previous menu selection and return to the higher level in the
menu structure.
←→ To cycle between available items on the same level within the menu
structure.
MENU To return:
from the default display, to the last accessed point in the menu.
The variable parameters in the Setup menu are edited using the ENTER, ←, ↑, ↓, → and
ESC keys.
When a value is to be entered, set it within the prescribed range using the ← and
→ keys to cycle between the digits and the ↑ and ↓ keys to scroll the digits. Press
ENTER to enter it into memory. The display stops flashing. If the value is out of
range, it will not be accepted; the value must be set within the prescribed range
and the ENTER key pressed again.
If ESC is pressed during an edit, the edit is abandoned and the setting already in memory
is retained and displayed. The display stops flashing.
If MENU is pressed during an edit, the edit is abandoned and the setting already in
memory is retained. The display returns to the menu entry point, KELKDSP2, and stops
flashing.
Functions are initiated with the ENTER, ↑ and ↓ keys. To initiate a function:
4. Press ENTER to initiate the process. After completing the process, the “Y” reverts to
“N” and the display reverts to the normal illumination level.
ENTER
KELKDSP2 VER XXX Installed Software Version
ESC
Setup Menu
Setup
For entry of user selected parameters
Diagnostics Menu
Diagnose
For accessing diagnostics data
Bar Graphs
Σ/∆ ====
A+B & A-B
Channel A Load
A# XX.XX
User Designated Units
Channel B Load
B# XX.XX
User Designated Units
Channel A + Channel B
Σ# XX.XX
User Designated Units
Channel A - Channel B
∆# XX.XX
User Designated Units
Navigate between parameters
using left and right arrow keys.
ENTER
Setup InpChSet Input Channels
ESC
ComunSet Communications
ENTER Application
InpChSet AppForce
ESC Roll Force, Tension or Pressure
Filter
FiltrXXX
Range 001 to 999
Source
Inp A&B
A&B, 2xA or 2xB
To set - Press ENTER. Select from available options using up and down arrow keys.
Press ENTER.
To set - Press ENTER. Enter required value using left and right arrow keys to select
digit, and up and down arrow keys to increment digit. Press ENTER.
Mode
O1 V 10
± 10 V, 4 - 20mA, 0-20mA
AnaOut 2 to
Same as AnaOut 1
AnaOut 6
Threshold
R1TXXX.X
Range 001.0 to 150.0
Time
R1TimXXX
Range 001 to 999 ms
Relay 2 to
Same as Relay 1
Relay 4
To set - Press ENTER. Select from available options using up and down arrow keys.
Press ENTER.
To set - Press ENTER. Enter required value using left and right arrow keys to select
digit, and up and down arrow keys to increment digit. Press ENTER.
Address
Addr XXX
Range 001 to 254
Baud Rate
Baud9600
9600, 19K, 38k or 57k
ENTER Address
Fieldbus Addr XXX
ESC Range 001 to 254
To set - Press ENTER. Select from available options using up and down arrow keys.
Press ENTER.
To set - Press ENTER. Enter required value using left and right arrow keys to select
digit, and up and down arrow keys to increment digit. Press ENTER.
W1Table W1 Table
Table Entry # 1
11 TXXXX
Range 0000 to 9999
Table Entry # 2
12 TXXXX
Range 0000 to 9999
To set - Press ENTER key. Select from available options using up and down arrow keys.
Press ENTER Key.
To set - Press ENTER key. Enter required value using left and right arrow keys to select
digit, and up and down arrow keys to increment digit. Press ENTER Key.
Time Out
DMT XXXX
Range 0015 to 1800 Seconds
Display Time
DCT XX.X
Range 02.0 to 25.0 Seconds
To set - Press ENTER. Enter required value using left and right arrow keys to
select digit, and up and down arrow keys to increment digit. Press ENTER.
Scan to view parameters selected for automatic display using left and
right arrow keys.
To add a parameter for automatic display:
- navigate to the desired parameter at any location in the menu,
- press up arrow key,
- press down arrow key,
- press up arrow key.
To remove a parameter from automatic display:
- select parameter at this location using up and down arrow keys,
- press up arrow key,
- press down arrow key,
- press up arrow key.
ENTER
WAC W1inXXXX Wrap Angle Value W1
ESC
Navigate between functions using left and right arrow keys. Channel A
SimA XXX
To set - Press ENTER. Select from Range 000 to 150 %
available options using up and down arrow
keys. Press ENTER. Channel B
SimB XXX
Range 000 to 150 %
To set - Press ENTER. Enter required
value using left and right arrow keys to
select digit, and up and down arrow keys to
increment digit. Press ENTER.
ENTER ENTER
Cal Disp ChannelA Ahz XXXX Coarse (Hardware) Offset
ESC ESC
PART 4 INSTALLATION
4.1 Introduction
KELK load measuring systems are designed, and have been proven over many years, to
provide excellent performance in the demanding environments of the metals industry.
However, to achieve their full potential for high accuracy and long service life, they must
be properly installed.
Following installation, the system must be setup and configured before being placed in
on-line service, see Part 5.
Caution
! If the system is not properly setup and configured, the
Digital and Analog Outputs and the Load Alarms are
unpredictable and their use for mill control purposes
may cause the production of off-specification product
or mill damage.
So that the user has easy access to the power cord and switch.
The DSP2 and any cabinet in which it is installed, together with all connecting wiring
must be installed in compliance with all applicable codes, regulations and standards.
4.2 Cabinets
For rolling mills, grinding mils and other heavy industrial applications, the DSP2 should
be installed in a 19 inch rack mounting cabinet providing appropriate environmental
protection, such as the KELK floor standing and wall mounting models.
Use the lifting lugs provided on the top of the cabinet for ease of handling.
Provide sufficient clearance for the door to open. A standard KELK cabinet
requires 1450 to allow the rack to be fully opened for service.
Secure floor mounting cabinets to the floor or wall to prevent tipping. This is
particularly important for cabinets with swing out racks. KELK Floor Mounted
Cabinets are supplied with four holes in the base for M 12 or ½ in. bolts.
! Warning
4.3 Wiring
All connections to the DSP2 are on the rear panel, Figure 4.1.
Detailed drawings 43057 and 42945 (or a customer specific equivalent) are included at
the end of this manual to illustrate DSP2 cabinet installation and connection wiring.
All signal wiring connected to the DSP2 must be from SELV (Separated Extra Low
Voltage) sources in accordance with IEC 61010-1 annex H, Safety requirements for
electrical equipment for measurement, control and laboratory use.
Warning
All connections, except for the Fieldbus, are described in this section. The Fieldbus
connection is described in Appendices B and C.
If the DSP2 is installed in a cabinet, a power outlet should be provided in the cabinet and
all signal wiring should be connected via terminal blocks mounted in the cabinet.
The DSP2 must be connected to a power source with the characteristics specified in
Section 9.9. It adjusts automatically to the voltage range, typically 120 or 240 VAC, to
which it is connected. It must be properly grounded.
The DSP2 is supplied with a power cable and plug. The power cable connections are
shown in Figure 4.2.
For a new measuring system, recommended wiring practices and instructions are included
in the documentation supplied with the system.
For existing systems, it is strongly recommended that the sensor wiring be checked
against KELK recommendations and serviced, if necessary, to ensure optimum system
performance.
Sensor wiring must be rated at least 300V. Terminations must be clean so as not to
introduce contact resistance or leakage to ground. Cables must be run to avoid exposure
to power cables and other potential sources of electromagnetic interference. Good wiring
practices and a dry environment are essential. Typical sensor wiring is shown in
Figure 4.3. Connector pinouts are listed in Table 4.2.
1. The sensor cable hose assemblies must be free of damage and kinks.
The sensor cables should be terminated in a vapour proof junction box. The
junction box should be mounted on a vertical surface, with the sensor cable/hose
entries at the bottom, in a location that precludes the accumulation of mill fluids
and provides good accessibility, e.g. on top of the mill stand.
Open the junction box and inspect all connections. Replace all dirty and corroded
terminal blocks and lugs. Ensure that there are no frayed wires to cause
momentary shorts to ground.
Ensure that the box and all internal components are dry. If moisture is seen or
suspected, dry with alcohol.
DSP2 90348 Rev F2
March 2008
33
KELK Installation
Ensure that the cable shields are electrically isolated from the box ground.
Check the cable entry points; reseal, if necessary.
When replacing the junction box cover, ensure that the gasket is properly
positioned. Tighten the bolts sequentially, in two steps (snug, then tight) to
prevent distortion or damage of the cover and gasket.
A four conductor twisted (in pairs or all together) shielded cable, with insulating
jacket, is recommended.
The preferred routing is through metal conduit. However, the cable may, after
leaving the junction box in a conduit, be run in low signal cable trays. When run
parallel to heavy power cables, a minimum separation of 1 m (3.3 ft) is required
for runs of up to 30 m (100 ft). For longer runs, a minimum separation of 2 m
(6.6 ft) is required.
4. With the interconnecting cable not connected to the DSP2, check the sensor and
interconnecting cable wiring for:
Continuity. Using an Ohmmeter with a resolution of 0.1 Ohm, measure the input
resistance between the green and black conductors and the output resistance
between the red and white conductors. The measured values should be within
1 Ohm of those given on the Calibration Card supplied with the sensor, plus the
resistance of the interconnecting cable.
Leakage resistance. Measure leakage resistance between any conductor and the
cable shield, between any conductor and ground, and between the cable shield
and ground. The result should be greater than 100 megOhms in each case.
Caution
! Do not use an insulation tester with test voltages in
excess of 50V. Higher voltages may damage the sensor.
If any problems are encountered, test the interconnecting and sensor cables,
Sections 7.6.2 and 7.6.3.
Analog wrap angle sensor signals are input through the Auxiliary Analog Inputs. Wiring is
shown in Figure 4.4. Connector pinouts are listed in Table 4.2. Connecting cables must
be rated at least 300V. The following cables, or their equivalents, are recommended:
One cable for 2 channels - Belden 8723, 22 AWG. 2 twisted pairs, individually
shielded, or
Separate cables per channel - Belden 9451, 22 AWG. 1 twisted pair, shielded.
There are two analog outputs in each connector. Each output can be connected for
voltage or current, both are shown in Figure 4.5. An output must not be connected for
both current and voltage at the same time. Connector pinouts are listed in Table 4.3.
Connecting cables must be rated at least 300V. The following cables, or their
equivalents, are recommended:
Logic I/O wiring is shown in Figure 4.6. Connector pinouts are listed in Table 4.4.
Connecting cables must be rated at least 300V. The following cables, or their
equivalents, are recommended:
A user supplied voltage or contact closure can be used, see Figure 4.6b.
Before connecting to the Lockout logic input, remove the factory installed jumper.
A user supplied voltage is required, see Figure 4.6c. Do not use the DSP2
15 VDC supply; this might overload the supply.
The System Fault relay is de-energized for a fault condition.
5.1 Introduction
Before being placed into service, the measuring system must be setup and configured.
This must always be done when:
A) the system is initially installed
B) the DSP2 is changed
C) sensors are changed
D) the Calibration Target Load is changed.
Setup is the entering of sensor calibration data and the setting of all user selectable
options and parameters. The calibration data are taken into memory and are used by the
DSP2 to set system gain during Configuration. All other entries are immediately and
automatically used by the DSP2 in its operations.
Configuration is user initiated and applies data entered during Setup to calibrate the
measurement system. It must only be performed under static load conditions, i.e., with a
fixed tare load, and no active load, applied.
Configuration sets the load outputs to zero and calibrates the system. It first sets the
analog offsets and gains, then adjusts the digital offsets and gains for optimum system
accuracy.
The DSP2 is normally setup and configured through the User Access Program (UAP).
While the Front Panel Interface (FPI) can be used for this purpose, it is primarily intended
for ongoing system monitoring and service, including setup adjustments. Instructions for
using these interfaces are given in Part 3, User Interface.
It is recommended that the Pre Power-up checks given in 5.6 be carried out prior to
proceeding with Setup.
Caution
If the measuring system is not properly setup and configured, the
Digital and Analog Outputs and the Load Alarms are unpredictable
and use of the system for mill control purposes may cause the
production of off-specification product or mill damage.
5.2 Calibration
Each sensor is calibrated against a high precision, traceable standard at KELK. Sensor
output is measured from zero to full load (Sensor Capacity). Then, with no load applied,
a high accuracy Shunt Resistor is temporarily placed across one arm of the sensor’s strain
gage bridge to unbalance it. The signal produced by this resistor, expressed as a
percentage of Sensor Capacity, is the sensor’s Calibration Target Load. It is in the range
20.00 to 150.00 %.
In roll force, pressure and load measuring systems, the load is applied directly to the sensor,
as it is during factory calibration. Typically, such systems are calibrated such that Full
Scale Input (see Section 5.3) for each channel represents 100% of sensor capacity. The
sensor Calibration Target Load is used to directly calibrate the load measuring system.
In tension measuring systems, the magnitude of load applied to the sensor is dependent on
strip tension and the angles at which the strip approaches and leaves the tensiometer roll.
These wrap angles must be accurately known as they are factored into the calibration of
the system. KELK computes Calibration Target Loads for the tensiometer, based on the
mill and strip geometry defined by the user. They are listed in a Tensiometer Calibration
Data Sheet Form 855 supplied with each tensiometer; refer to Appendix F. Individual
sensor calibration cards are supplied also. Typically, such systems are calibrated such
that Full Scale Input for each channel represents 100% of rated tension (not sensor
capacity). Additional compensation is required in varying wrap angle applications, as
discussed in Section 5.5.
Caution
If a tensiometer is operated in a geometry different from that specified on the
Calibration Data Sheet, the Digital and Analog Outputs and the Load
Alarms will be unpredictable and use of the system for mill control purposes
may cause the production of off-specification product or mill damage.
The Shunt Resistor value and Calibration Target Loads (from the Calibration Cards for
roll force, pressure and load measuring applications, and from the Calibration Data Sheets
for tension measuring applications) are entered into the DSP2 during setup. Then, during
Configuration, the DSP2 computes and sets the analog and fine gains to be applied to the
sensor signals to provide a calibrated output.
The Calibration Target Loads given on Calibration Cards and Calibration Data Sheets are
determined with only the sensor cables connected directly to the calibrating electronics.
Installation in the mill normally involves the use of long interconnecting cables. Each
Calibration Target Load must be corrected to compensate for the effect of this additional
resistance.
Cf = 1 + 4 RL
RBR
Where:
RL is the resistance of one conductor of the interconnecting cable.
RBR is the sensor output resistance.
CTL1 = Cf xCTL
Where:
CTL is the output obtained from the calibration shunt resistor being applied
during factory calibration, expressed as a percentage of the full scale output
for force and pressure (found on the Calibration Card). For Tension
applications, it is the percentage of the full scale tension from the
Tensiometer Calibration Data Sheet;
and
CTL1 is the Calibration Target Load corrected for the interconnecting cable
resistance.
DSP2 90348 Rev F2
March 2008
48
KELK Setup and Configuration
Example:
For a sensor with an output resistance (RBR) of 240 Ohms connected to the signal
processor with 90 meters of 16 AWG (1.5 mm2) interconnecting cable:
Cf = 1 + 4 x 1.2 = 1.02
240
If the Calibration Card gives a Calibration Target Load of 79.73%, the new
Calibration Target Load is:
The input range for each channel is defined by Calibration (initially carried out during
Configuration). The Calibration routine involves the application of a known resistance to
force an output from the sensor which is applied to the DSP2 input. The value of the
Calibration Target Load entered for each channel defines this input as representing a
percentage of the intended ‘Full Scale Input’. Typically, for Roll force and Pressure
applications the Full Scale Input (FSI) is equivalent to the input corresponding to the
operation at rated capacity. For tension applications the FSI is normally the input
corresponding to the application of rated tension. During the Configuration routine the
DSP2 automatically adjusts the input stage gain to maximise the resolution of the input
stage to suit the Full Scale Input plus 20% zero allowance plus 50% over range allowance
plus 5% overhead. This adjustment sets the input saturation at a maximum level of 175%
of FSI; the actual limit is dependent upon the amount of zero allowance utilized at any
given time.
In operation, Sensor A and B outputs are amplified, digitized and adjusted to yield
Channel A and Channel B loads as percentages of the individual Full Scale Inputs. This
includes:
The application of zero offsets that were determined previously by the DSP2
during system setup and Configuration, and any subsequent Auto Zero or Auto
Calibration operation, with the desired tare load applied.
The application of gains determined previously by the DSP2 during system setup
and Configuration and any subsequent Auto Calibration, based on the sensor
calibration factors (Shunt Resistor value and Calibration Target Loads)
determined during factory calibration.
If the application is Tension Measurement there may be an additional gain
modification factor applied, see Section 5.5.
The Sum Load (Channel A Load + Channel B Load), expressed as a percentage of total
Full Scale Input, and the Difference Load (Channel A Load - Channel B Load), expressed
as a percentage of individual FSI, are computed to complete two Load Measurement Sets,
both comprising A, B, A+B, and A-B. One set includes user configurable signal filtering
and is the source for the digital and analog load outputs. The other is used for the alarms,
and has a separate filter and debounce algorithm.
Within each Load Measurement Set the scaling is fixed at 10000 equivalent to 100% of
the FSI.
The filtered Load Measurement Set is accessible through the Fieldbus Interface and the
Serial Communications Interface.
The user can select the form of Load display as either bar graph or numeric.
The bar graph displays loads, A and B, or A+B and A-B, each represented as a
percentage of FSI (or total FSI in the case of A+B).
For the numeric display the user can assign a scale factor in the range 1-9999 to define the
full scale value within the resolution of the Load Measurement set, or it can be formatted
to read as a percentage of the FSI. For examble, for a FSI representing 500 T, the display
can be configured to read 0500 (T) or 100.0(%).
Data is derived from the filtered Load Measurement Set, conversion and formatting is
applied, and the result fed to the display.
The Analog Outputs can be programmed to represent A, B, A+B or A-B and can be
scaled to represent any percentage of the FSI from 1 to 999%. This permits the user to set
these outputs to give the best resolution to meet their needs for example, high resolution
for differential load signals and lower resolution for overload detection. The scale factor,
which can be set from 1-999, indicates the percentage of FSI to be represented by the full
range (10V or 20 mA) of the Analog Outputs.
Examples:
For normal operation:
Scale factor 100 yields 10V equivalent to 100% FSI
The load, A, B, A+B or A-B, is read from the filtered Load Measurement Set. An
Output Scale Factor, entered during setup, is applied to yield the Analog Output Load
as a percentage of FSI.
A D/A conversion is executed and the Analog Output Load is output as a voltage or
current signal.
Four Logic Outputs can be programmed as Alarms to indicate that a specific load threshold
or rate of change of load threshold has been exceeded. The channel inputs saturate at 175%
of FSI of which 20 % is allocated for zero adjustment. The load threshold that can be
utilized is, therefore, restricted to the range 1-150% of FSI. The Threshold is expressed as
a percentage of: individual FSI for A, B and A-B, total FSI for A+B.
The load, A, B, A+B or A-B, is read from the internally unfiltered Load Measurement Set.
The load, or load change per millisecond, is compared with a Threshold, entered
during setup.
Alarm response time is user selectable. For Load Level Alarms, it is the time the
threshold must be crossed for the Alarm to change state, either to be asserted or
de-asserted. For Rate-of-Change-of-Load Alarms, it is the minimum time for which the
Alarm Logic Output relay is asserted.
Example:
Application:
Roll force.
Tare load - rolls and chocks.
Sensors
Sensor Capacity: 500 T.
Sensor A Calibration Target Load: 72.63%.
Sensor B Calibration Target Load: 73.18%.
Shunt Resistor: 150 kΩ.
1. Configuration sets the input gain using the value of shunt resistance and Calibration
Target Load for each sensor to yield a Full Scale Input equivalent to a load of 500T
(sensor capacity). Total FSI is 1000T.
2. Sensor A and B outputs are amplified, digitized, filtered and adjusted to yield
Channel A and Channel B loads. This includes:
The application of zero offsets that were determined previously by the DSP2
during system configuration, and any subsequent Auto Zero, with the desired
tare load applied.
The application of gains determined previously by the DSP2 during system
setup and configuration, based on the sensor calibration factors (Shunt
Resistor value and Calibration Target Loads) as listed above and entered
during setup and configuration.
3. The Sum (Channel A Load + Channel B Load) and Difference (Channel A Load -
Channel B Load) Loads are computed to yield the Load Measurement Sets, both
comprising A, B, A+B, and A-B.
4. The filtered Load Measurement Set is accessible through the Fieldbus Interface for
mill control purposes.
A and B are read from the filtered Load Measurement Set and their Output Scale
Factors are applied to yield Analog Output Loads as percentages of their Full
Scale Inputs, i.e. as percentages of 500 T. To achieve this, the same Output Scale
Factor of 080, the required Analog Output Full Load (400 T) as a percentage of
individual FSI ( in this case equal to sensor capacity 500 T), was entered for both
outputs during setup.
D/A conversions are executed and the loads are output as voltage or current
signals.
A+B is read from the filtered Load Measurement Set and the Output Scale Factor
is applied to yield the Analog Output Load as a percentage of total FSI, i.e. as a
percentage of 1000 T. To achieve this, an Output Scale Factor of 080, the
required Analog Output Full Load (800 T) as a percentage of total FSI (1000 T),
was entered during setup.
A D/A conversion is executed and the load is output as a voltage or current signal.
A-B is read from the filtered Load Measurement Set and the Output Scale Factor
is applied to yield the Analog Output Load as a percentage of individual FSI, i.e.
as a percentage of 500 T. To achieve this, an Output Scale Factor of 020, the
required Analog Output Full Load (100 T) as a percentage of individual FSI
(Sensor Capacity 500 T), was entered during setup.
A D/A conversion is executed and the load is output as a voltage or current signal.
A and B are read from the unfiltered Load Measurement Set and compared to their
Thresholds of 350 T. To achieve this, a Threshold of 070.0, (350 T) expressed as
a percentage of individual FSI (500 T), was entered for both Alarms during setup.
An Alarm is asserted if the Threshold is exceeded.
A-B is read from the unfiltered Load Measurement Set and compared to its
Threshold of 40 T. To achieve this, a Threshold of 008.0, the required Threshold
(40 T) expressed as a percentage of individual FSI (500 T), was entered during
setup.
The Alarm is asserted if the Threshold is exceeded.
The change in A+B per ms is calculated and compared to its Threshold of 100 T
per ms. To achieve this, a Threshold of 010.0, the required Threshold (100 T/ms)
expressed as a percentage of total FSI (1000 T/ms), was entered during setup.
The Alarm is asserted if the Threshold is exceeded.
The DSP2 applies the following fixed filtering to each channel to ensure signal quality:
input filters 50 kHz anti-aliasing and 3db filter with bandwidth on 2.8 kHz. Analog
output smoothing filter has a bandwidth of approximately 3.2 kHz.
A further filtering option is available to the user. This filter is applied after the signal is
transferred to the digital domain of the DSP2 Signal Processor. The input signal is
sampled at a rate of 50 kHz and processed at 10 kHz. A running average filter is available
to the user. The user may select a filter coefficient in the range 1-999. This coefficient
sets the number of samples to be averaged prior to the application of offset and gain
adjustments and subsequent formulation of values to be transferred to the Load
Measurement Set.
The following diagram shows a filter response with setting of the filter coefficients from
1 to 20. For default filter value N=1 with no filtering applied; actual value should be
chosen in accordance with the needs of the application.
10
1 2 3 4 5 6 7 8 9
0
0 0.25 0.5 0.75 1 1.25 1.5 1.75 2 2.25 2.5
Filter response [msec]
For the users guide a signal rise with the filter is presented by following formula:
This formula is valid for filter settings in the range of 6-999. For filter settings from 1-5 a
time of approximately 1 ms is required for filter to settle within 1% of full scale.
Note. The programmable logic outputs use a signal processed at 10kHz and is not
affected by the filter setting.
The Calibration Target Loads supplied with Tensiometer Load Cell Assemblies and
Monoblocs are for fixed strip entry and exit angles, as specified on their Calibration Data
Sheets. Compensation is required if one or both angles change.
For each angle that changes (entry, exit or both), a lookup table, containing a series of 21
coefficients equally spaced between the minimum and maximum values of a wrap angle
value, is entered during setup. During rolling, the DSP2 uses this table to determine the
appropriate Scaling Factor for the current wrap angle and adjusts the load signals to
output the correct strip tension.
During Setup the user selects the Wrap Angle input mode from the following list:
Fbs or AIN are used when the wrap angle is continuously changing during the process.
MAN would be used when changes are infrequent and can be processed by operator
intervention.
The lookup tables are generated by KELK, based on the rolling geometry (from which the
relationship between wrap angle and wrap angle sensor output or Wrap Angle Value may
be determined) specified by the user. Each table comprises 21 data points so that there
are 20 equal intervals between minimum and maximum wrap angle input. Using the
wrap angle inputs, the DSP2 interpolates linearly between table data points to determine
the corresponding coefficients, W1 and W2. These two coefficients are combined to
formulate the Compensation Factor applied to the sensor signal to maintain the correct
tension output.
The WAC Look-up Tables are supplied using Form 858, refer to Appendix F. KELK
uses the Application Wizard in the User Access Program, see Appendix C, to generate
these forms. In the event of changes to the system geopmetry, the user can generate their
own tables using this method.
Two Auxiliary Analog Inputs are provided. Input 1 is normally used for the strip entry
angle, and Input 2 for the exit angle. These can be reversed; however, it is essential that
the lookup tables and inputs always correspond.
The sensors and wiring are properly installed and connected to the correct Sensor
Ports.
If used, the wrap angle sensors and wiring are properly installed and connected to
the correct Auxiliary Analog Inputs.
All Analog Outputs, Logic I/O, J-7 Com 1 and Fieldbus cables are correctly
installed.
Any equipment that responds automatically to the outputs is not active.
Lockout is disabled. See Section 6.11.
Caution
Connect the PC or laptop serial port to DSP2 rear panel port J7 COM 1 and run the User
Access Program.
Select Setup to enter the setup menu (Figures 3.5 and 3.7).
Select InpChSet to enter the Input Channels Setup Menu, Figure 3.8. Set the variable
parameters.
Application - select AppForce for force measuring systems, App Tens for tension
measuring systems, App Press for pressure measuring systems.
Shunt Resistor - select the value corresponding to that on the sensor Calibration
Cards or Calibration Data Sheet, e.g. Shnt150K. This selection is utilized during
Configuration and must be correctly chosen to ensure correct measurement data.
Calibration Target Loads - set to the values on the sensor Calibration Cards or
tensiometer Calibration Data Sheets, as applicable, corrected for the resistance of the
interconnecting cables, e.g. AT081.32 for Sensor A Calibration Target Load of
81.32% and BT082.08 for Sensor B Calibration Target Load of 82.08%. See
Section 5.2 for additional information. The value must be in the range 20 to 150%.
This value is utilized during Configuration and must be correctly chosen to ensure
correct measurement data.
Filter - set filter in the range 1 to 999, e.g. Filtr020. See Section 5.4 for additional
information.
Source - select Inp A&B for Sensor A to be connected to Channel A and Sensor B
to Channel B, Inp 2xA for Sensor A to be connected to both Channels or Inp 2xB for
Sensor B to be connected to both Channels. Inp A&B is normally selected, the other
options invoke Single Sensor Operation and are intended for use if a sensor, or input
channel, has failed and a load signal is required on both channels.
Each of the installed Analog Outputs (maximum 6) can be setup to output A, B, A+B or
A-B from the Load Measurement Set in ± 10 V, 4 to 20 mA or 0 to 20 mA mode.
Select AnaChSet to enter the Analog Output Setup Menu, Figure 3.9. Set the variable
parameters. Output 1 is described. The other Outputs are setup in the same way.
Source - set Out1 A for A, Out1 B for B, Out1 A+B for A+B, Out1 A-B for A-B
or Out1 OFF to disable the output.
Output Scale Factor - set the Output Scale Factor, i.e. the load to be represented by
full scale (10 V or 20 mA) Analog Output, expressed as a percentage of:
Individual Full Scale Input for A, B and A-B,
Total Full Scale Input for A+B,
in the range 1 to 999 %. e.g. O1Scl100 for 100%. See Section 5.3 for additional
information.
Each of the four Load Alarms can be setup to indicate when a load level or
rate-of-change-of-load exceeds a threshold.
Select RelaySet to enter the Load Alarm Setup Menu, Figure 3.10. Set the variable
parameters. Load Alarm 1 is described. Load Alarms 2 to 4 are setup in the same way.
Source - Select the load from the Load Measurement Set. Set Rel1 A for A, Rel1 B
for B, Rel1 A+B for A+B, Rel1 A-B for A-B or Rel1 OFF to disable the alarm.
Mode - select R1md Ld for load level, R1md Rt+ for positive
rate-of-change-of-load or R1md Rt- for negative rate-of-change-of-load.
The parameters for Threshold and Time are different depending on the selection
of Load or Rate of change of load.
Threshold - set in the range 1.0 to 150.0 e.g. R1T010.0 for a load level to be
asserted at 10% or a rate-of-change-of-load to be asserted at 10%/ms. See Section
5.3 for additional information.
Load Threshold
Typically set in the range 1.0 to 150.0, e.g. R1T080.0 for a load level to be
asserted at 80%.
Time - set the response time in the range 1 to 999 ms, e.g. R1Tim025 for 25 ms.
Time parameter for Load alarm is the time for which the load must exceed the
threshold before the alarm is asserted and conversely, the time after the load has
fallen below the threshold, before the alarm is de-asserted.
- set the response time in the range 1 to 999 ms. e.g. R1Tim025 for 25 ms.
Time parameter for the Rate of Change Alarm is the duration of the alarm
condition after the rate of change of load threshold has been exceeded
- set the response time in the range 1 to 999 ms, e.g. R1Tim050 for 50 ms.
Refer to Table 5.1 and Figure 5.1 for examples of relay assertion and timing.
Relay 4
999 msec
Relay 3
Relay 2
50 msec 50 msec
Relay 1
100
75
Ch. 'A' % Load
50
25
0
0 1 2 3 4 5
Time [sec]
Figure 5.1 Example of Logic I/O Timing versus Mill Stand Load
Each of the Wrap Angle Compensation (WAC) Inputs can be setup to provide
compensation in varying wrap angle tension measuring applications. See Section 5.5 for
additional information. See Form 858 in Part A of the System manual for Look up table
entry information.
Select WAC to enter the WAC Setup Menu, Figure 3.11. Set the variable parameters.
WAC Input 1 as described. WAC Input 2 is setup in the same way.
Source - set the data source. If Wrap Angle Compensation is not required, select
W1Sc OFF and ignore the remaining parameters for the input. If Wrap Angle Values
are to be input through the UAP, FPI or SCI, select W1Sc Man. If Wrap Angle data
are to be input via the Auxiliary Analog Input select W1Sc Ain. Select W1Sc Fbs
for input Wrap Angle Values via the Fieldbus Interface.
Table Entries - a series of table entry points will be presented in the form
1NNTXXXX, where leading number 1 or 2 indicates WAC Input 1 or WAC Input 2,
NN is the point number and XXXX is the value for that point. Enter the table
supplied by KELK, e.g., to enter a value of 6731 for point 17, 117T6731.
W1 in XXXX is used to enter Wrap Angle Values manually in off-line wrap angle
input mode, see section 6.8.
5.8.5 Communications
Select ComunSet to enter the Communications Setup Menu, Figure 3.12. Set the
variable parameters.
Serial Interface:
Address - set the DSP2 address in the range 1 to 254, e.g. Addr 005.
For RS232 mode use address 254.
For RS485 select value from 1 to 254.
Baud Rate - select 9600, 19K, 38K or 57K baud, e.g. Baud 57K.
Fieldbus Interface:
Select User Int to enter the FPI Display Setup Menu, Figure 3.13. Set the variable
parameters:
Scale Factor - enter the Scale Factor, in the range 1 to 9999, to set the absolute load
values in the FPI display:
A and B absolute full scale loads equal the Scale Factor, e.g., for a Scale Factor of
600, A# 0600 and B# 0600 correspond to A%100.00 and B%100.00,
respectively.
Σ#XXXX =
A#XXXX+B#XXXX, the sum of the individual loads, for roll force
measuring systems
(A#XXXX+B#XXXX)/2, the average of the individual loads, for pressure
and tension measuring systems,
∆#XXXX = A#XXXX - B#XXXX, the difference between the individual loads.
e.g. enter SF#200.0 for a Scale Factor of 200.0.
Timeout - set the time, in the range 15 to 1800 seconds, the default display is to
remain inactive following user activity, e.g. DMT0300 for 300 s.
Display Time - set the time, in the range 2 to 25 seconds, each selected parameter is
to be displayed before being replaced by the next , e.g. DCT 10.0 for 10 s.
5.8.7 Configuration
After all necessary parameters have been entered in the Setup procedure, the
'Configuration' command must be invoked to apply the Calibration data and to zero each
channel before the DSP2 is placed on-line.
The procedure must also be invoked whenever changes are made to the Shunt Resistor
Value or the Calibration Target Load or a connected sensor has been replaced. It is also
recommended that, if the user applies a Self Test, Configuration is also invoked to fully
check the sensor calibration.
Caution
Press MENU. Select Config N (Figure 3.5). Set to Config Y. Press ENTER. Display
will show WAIT!!! while Configuration is in progress and revert automatically to Config
N on completion.
It is recommended that the setup be checked by running Simulation, Section 7.7, before
using the system on-line.
PART 6 OPERATION
6.1 Introduction
The Rollmax Digital Signal Processor, Model DSP2, provides the user with several
capabilities for system monitoring and control:
Load Displays.
Load Level and Rate-of-Change Alarms.
Single Sensor Operation.
Auto Zero.
Auto Calibration.
Self Test.
Reset.
Load Simulation.
Lockout.
Measured loads are displayed in the UAP Operations screen and the FPI alpha-numeric
display.
The FPI display normally cycles through the user selected Default Menu. A load can be
selected for continuous display - Press MENU, select LoadDisp, select load (Figure 3.6).
During normal operation (i.e. both Sensors A and B operational), the sum (Σ) and
difference (∆) loads in the FPI display are:
Σ% = (A% + B%)/2
∆% = A% - B%
Σ# = A# + B # for roll force measuring applications
= (A# + B#)/2 for pressure and tension measuring applications
∆# = A# - B #
During Single Sensor Operation (i.e. 2 x Sensor A or 2 x Sensor B), the sum (Σ) and
difference (∆) loads in the FPI display are:
Σ% = A% (or B%)
∆% = 0
Σ# = 2A# (or 2B#) for roll force measuring applications
= A# (or B#) for pressure and tension measuring applications
∆# = 0
Load alarm conditions (i.e. when a user set load levels, or rates-of-change are exceeded)
are annunciated:
The DSP2 continuously monitors the signal processing electronics, the sensor excitation
currents and signals, the Auxiliary Analog Inputs, the Fieldbus Interface and the internal
temperature. System status is annunciated:
Single Sensor Operation, otherwise known as load doubling, connects both Channel A
and B registers in the Load Measurement Set to the same sensor channel.
Through the FPI - Press MENU, select Setup, InpChSet, Inp 2xA or Inp 2xB
(Figure 3.8).
Through the UAP - Operations screen.
Through the SCI.
Through the Fieldbus Interface.
By contact closure at the Single Sensor A or the Single Sensor B Operation Logic
Input. Single Sensor Operation latches on, it is not revoked when the external
contacts are opened.
Note
When invoked:
The sum load (A+B) is twice the selected sensor load and the difference load
(A-B) is zero.
The front panel Single Sensor Indicator is illuminated.
The Single Sensor Operation Logic Output relay closes.
Through the FPI - Press MENU, select Setup, InpChSet, Inp A&B (Figure 3.8).
Through the UAP - Operations screen.
Through the SCI.
Auto Zero adjusts the fine offset of both channels to set their outputs to zero. It is
normally used to compensate for small changes in tare weight.
Configuration establishes a zero reference at the input stage. The Auto Zero command
will successfully zero the outputs provided the total offset detected at the input stage does
not exceed ±20% of the Full Scale Input also established during Configuration. This
limit serves to advise the user of the accumulation of small offsets successively corrected
and/or to alert the user to a single large change in offset.
It is recommended that in the event of a zero out of range error message that the cause be
investigated prior to further operation. To determine the actual magnitude of the offset
consult Section 7.6.1. To continue operation invoke Configuration to establish a new
zero reference.
Caution
If the new zero offset exceeds the allowable limit, a fault condition will be indicated. See
Section 7.1 for assistance with troubleshooting.
Auto Calibration allows the user to ensure that the measuring system has remained in
calibration. It zeroes both channels by adjusting their fine offsets, then, using the sensor
calibration data entered during setup, scales both channels by adjusting their fine gains.
Caution
If a new fine gain and/or zero offset exceeds the allowable limit of 2%, a fault condition
will be indicated. See Section 7.1 for assistance with troubleshooting.
If W1Sc Man was selected during setup, the Wrap Angle Value can be updated:
Through the FPI - Press MENU, select Setup, WAC - WAC 1, W1inXXXX
and/or WAC 2, W2inXXXX. Enter the Wrap Angle Value in the range 0 to 1000,
e.g., to enter a value of 0543 for W1, W1in0543.
Through the UAP - select the Operations screen and set the new values for W1in
and/or W2in.
Through the Serial Communications Interface, see Appendix A.
If W1Sc Fbs was selected during setup, the Wrap Angle Value must be updated through
the Fieldbus Interface, see Appendix B or C.
Through the FPI - Press MENU, select Self T N. Set to Self T Y. Press ENTER.
Display will show WAIT!!! while Self Test is in progress and revert
automatically to Self T N on completion (Figure 3.5).
Through the UAP - Operations screen.
By contact closure at the Self Test Logic Input.
Caution
If a fault condition is indicated, see Section 7.1 for assistance with troubleshooting.
To fully check the system the user is advised to invoke Configuration to check zero and
calibration are also within limits.
6.10 Reset
Reset has the same effect as turning on the system. The system is initialized and normal
operation commenced.
Through the FPI - Press MENU, select Reset N. Set to Reset Y. Press ENTER.
Display will show WAIT!!! while Reset is in progress and revert automatically to
Reset N on completion. (Figure 3.5)
Through the UAP - Operations screen.
Caution
6.11 Lockout
The Lockout condition is controlled primarily by a logic input at terminals J8-15 and
J8-33. When these terminals are open Lockout is asserted. When closed the user has full
access through all interfaces. Lockout can be overridden over the SCI, through the User
Access Program. This override will remain in effect until:
revoked through the SCI directly or through the User Access program,
automatically revoked by the DSP2 after no setup parameter has been changed or
Configuration, Self Test, Reset or Simulation has been activated, for a period of
1 hour.
PART 7 TROUBLESHOOTING
7.1 Introduction
Electronics Fault
A fault has been detected in the hardware or by the hardware. See Table 7.1
All DSP2 fault condition indications are volatile, that is, the fault indication is cancelled
as soon as the problem is corrected. To assist the user in the event that intermittent or
transient process or measurement system fault conditions occur the User Access Program
contains features for logging and reporting fault conditions, see section 7.8 for details.
A continuous routine monitors the status of the DSP2 hardware and signal processing. In
the event that a fault is detected, the ‘Electronics Healthy’ LED on the FPI goes out
indicating a fault condition. The user can access the error codes associated with the fault
through the FPI , the UAP over the SCI or via the Fieldbus option.
The following table, Table 7.1, lists the error codes displayed over the FPI or transmitted
over the SCI and Fieldbus in the event that a fault is detected in the hardware or the DSP2
signal processing. The table also includes a possible cause for the fault for the user to
investigate. For the case when multiple faults are detected the error code displayed or
transmitted will be the sum of the individual fault codes. An explanation of how to
determine the individual components of a combined error code together with an example
is given at the end of this section 7.1.
In the event that a fault occurs the appropriate Channel Fault LED on the FPI will be
illuminated and the corresponding logic output will be asserted. The user can access the
error codes associated with the fault through the FPI , the UAP over the SCI or via the
Fieldbus option.
The following table, Table 7.2, lists the error codes displayed over the FPI or transmitted
over the SCI and Fieldbus in the event that a fault is detected in either signal processing
channel. The table also includes a possible cause for the fault for the user to investigate.
For the case when multiple faults are detected the error code displayed or transmitted will
be the sum of the individual fault codes. An explanation of how to determine the
individual components of a combined error code together with an example is given at the
end of this section 7.1.
Subtract the largest fault number as identified by the FPI Hex Number in the tables
above, equal to or less than the displayed number, from the displayed number. That
fault is present.
Repeat the above, subtracting from the remainder, until the remainder is reduced to zero.
Note that the fault identifier is a number in hexadecimal format.
Examples:
For Electronics Status Message FltEl81
81 - 80 (Excessive internal temperature) = 01
01 - 01 (Signal processing error) = 0
For status messages transmitted over the SCI or the Fieldbus faults are
directly identified by bit position as indicated in the tables:
1 = fault detected, 0 = fault not detected
Other
In the case of a suspected Auxiliary Analog Input Board or Fieldbus Card fault, replace
the board, Section 8.3. Note that faults in these boards are not indicated by the DSP2
diagnostics.
Note. Printed circuit boards are not user serviceable. Defective boards should be
returned to KELK for evaluation and repair.
A low or zero excitation current can be caused by a poor sensor connection, a sensor
failure or an excitation supply failure. Note that the excitation circuit is short circuit
protected; it will automatically shut down when a short is detected. The DSP2 will
attempt an automatic restart if Configuration, Self Test or Reset is invoked. Test the
system, Section 7.6.1. Check for presence of excitation voltage, 10VDC. Follow with
the interconnecting cable (Section 7.6.2) and sensor (Section 7.6.3) tests, as required.
Tare offset and Fine Zero offset data are accessible via the FPI or the UAP.
The above values are relative to the value determined by Coarse Offset adjustment
during Configuration.
The total value of tare is the sum of Atar and Az or Btar and Bz.
For the above example:
For Channel A Total Tare = 55 - 15.3 = 39.7 % of FSI.
For Channel B Total Tare = -3 + 1.23 = - 1.77 % of FSI.
Tare offset information is available in the ±175% range. Tare applied outside that
range will saturate at ±175%.
The same information is available via the UAP - DIAGNOSTIC - Input Channel
Configuration Diagnostics, Calibration screen.
This data is valuable for tracking zero shifts that may occur.
A stable zero offset in the direction of the applied load, not caused by a tare load
or other mill operating condition, indicates that the sensor has been overloaded. If
the offset exceeds the available adjustment range, the sensor should be replaced.
A slow zero drift, not caused by a tare load or other mill operating condition,
indicates sensor fatigue. Fatigue manifests itself when a sensor reaches the end of
its life, which is typically after more than 10 million load cycles under proper
loading conditions. It will occur prematurely if a sensor is continuously locally
overloaded due to poor loading conditions. The drift is normally in a direction
opposite to the load direction. It progresses sufficiently slowly that Configuration
and Auto Zero will provide sufficient compensation to permit sensor replacement
to be planned and implemented on a relatively convenient schedule. If fatigue
occurs prematurely, thoroughly inspect the sensor installation for indications of
uneven loading and correct any problem before replacing it.
If load measurements or alarm levels deviate significantly from expected values and
cannot be attributed to a tare load or other mill operating condition, run Simulation
(Section 7.7) in Shunt mode:
First ensure that the system is off-line, apply Auto Zero to bring each channel to zero.
For roll force, pressure and load measuring systems, the DSP2 load displays should
correspond with the Sensor Calibration Target Loads (including interconnecting cable
corrections).
For fixed wrap angle tension measuring systems, the DSP2 load displays should
correspond with the Tensiometer Calibration Target Loads (including interconnecting
cable corrections).
For varying wrap angle tension measuring applications, the DSP2 load displays
should correspond with the Tensiometer Calibration Target Loads (including
interconnecting cable corrections) x the WAC Scale Factor. The Scale Factor is
accessible in the UAP Operations screen (Figure 3.1) and the FPI - Press MENU,
select Diagnose, WAC, Wf XXXX (Figure 3.14). If the displayed loads are correct,
erroneous wrap angle compensation may be causing the problem. Ensure that the
WAC lookup tables have been entered correctly and check the WAC sensor inputs.
If the displayed loads are incorrect, check that the Shunt Resistor value and Calibration
Target Loads were entered correctly during setup and apply Configuration. Any error
will affect the Digital and Analog Outputs, the Load Displays and the Load Alarms.
If the displayed loads are correct and an Analog Output is erroneous, check that the
correct Output Scale Factor has been entered. Any error will affect only the associated
Analog Output.
If the displayed loads are correct and a load level alarm is not asserted at the expected
level, run Simulation (Section 7.7) to determine the assertion point. If this differs from
the expected level, correct the Threshold setting. Any error will affect only the associated
Alarm.
If the problem cannot be attributed to any of the above causes, run Self Test, Section 6.9.
If an electronics fault is reported, see Section 7.2.
Several parameters in a new DSP2 are factory set at values outside of their acceptable
ranges so as to create an error message if the DSP2 is used before valid values have been
entered and Configuration has been run. If an invalid parameter message is displayed,
review the setup, ensuring that all required parameters have been entered, and run
Configuration.
7.6 Tests
Caution
1. Ensure the suspect channel is either not loaded or only tare loaded.
2. Switch off the DSP2. Disconnect the red and white interconnecting cable wires.
Switch on the DSP2.
3. With a DVM, measure the excitation voltage between the green (+) and black (-)
wires. This should be 10 VDC, ±0.5 VDC. A low reading indicates current leakage
in the cable or sensor, or an excitation supply problem.
4. With the DVM set to millivolts, measure between the red (+) and white (-) wires.
The reading will normally be less than 3 mV. Values above 15 mV are unusual. If
the value is high, it may be beyond the range of the zero control. A reading of ±5V
indicates sensor failure.
5. Switch off the DSP2, disconnect the green (+) and black (-) wires (this completely
disconnects the cable from the DSP2) and conduct the following tests in order:
(a) Input resistance: Using an Ohmmeter with a resolution of 0.1 Ohm, measure
between the green and black wires. The reading should be within 1 Ohm of the
resistance specified on the Calibration Card plus the resistance of the
interconnecting cable.
(b) Output resistance: Repeat (a) between the red and white wires.
High or low readings for tests (a) - (b) indicate cable problems or a damaged
sensor.
(c) Using a DVM set to millivolts, measure between any wire and ground. The
reading should be less than 5 mVDC.
(d) Repeat (c) between any wire and the internal cable shield.
(e) Repeat (c) between the internal cable shield and ground.
Any reading above 5 mVDC for tests (c) - (e) indicates moisture in the sensor or
cable which will result in unstable readings and, more noticeably, zero drift.
(f) Using a DVM or megometer with a test voltage of less than 50V, measure
bridge to ground resistance, i.e. any sensor wire to ground.
Caution
(g) Measure bridge to shield resistance by repeating (f) for any sensor wire to the
cable shield.
If all readings were normal for tests 4 and 5, the excitation supply is faulty. Replace the
Strain Gage Interface Board, Section 8.3.
If any readings were abnormal for tests 4 and 5, the problem is caused by the
interconnecting cable or the sensor.
3. If a problem is encountered it could be in either the sensor cable or the sensor itself.
Remove the sensor for a complete inspection, see the measuring system User’s
Manual.
4. Inspect the full length of the cable for damage, including crushing or kinking. If
damaged near its point of entry into the sensor, the sensor should be replaced. If
damaged at some point along its length, it can be repaired using KELK Splicing Kit
Part Number 20311. All necessary instructions are included in the kit. This is the
only recommended method.
5. If the cable is not damaged, the problem is probably in the sensor itself. Return the
sensor to KELK for evaluation and repair.
Load Simulation is provided to facilitate checking the DSP2 setup and the load output
(analog or digital) to mill control system interface.
Select Press MENU, select Diagnose, Load Sim (Figure 3.14). Press ENTER.
For application of the Shunt Resistors to the inputs - Select Sim SHNT, Press
ENTER, or
For Load Simulation at user selected levels - Select Sim USER. Press ENTER. The
levels of the data outputs will correspond to the levels set in SimA XXX and SimB
XXX. To change a level - select SimA XXX or SimB XXX, as required. Press
ENTER, set the required value. Press ENTER.
To return to normal operation, select Sim SHNT or Sim USER, as applicable. Press
ENTER. Select Sim OFF. Press ENTER.
To simulate a load using the UAP, press Simulation/Test in the Operations Screen to
expose the Simulation pop-up panel.
WARNING: Do not attempt to initiate Auto Calibration, Auto Zero, Self Test or Reset
when Load Simulation is active.
Load Simulation is automatically disabled if Auto Calibration, Auto Zero, Self Test or
Reset is initiated.
All DSP2 fault condition indications are volatile, that is the fault indication is cancelled
as soon as the problem is corrected. The User Access Program has features to assist the
user in the event that intermittent or transient process or measurement system fault
conditions occur.
When a successful connection is made to an operational DSP2 using the User Access
Program, a Fault logging file is automatically created using the same ‘Name’ as the
backup configuration file, for example, Test.log for a DSP2 backup configuration file
named Test.cfg. The Name.log file is in the same directory as the backup configuration
file, see Figure 7.1. System Status logging is intiated whenever the UAP connection is
made to the DSP2.
Important Note. If there are multiple DSP2s then each DSP2 must have its own Backup
Configuration file identified by ‘name’. An existing backup configuration file can be
used as a source for configuration data for any DSP2. Data can be read from file by the
UAP and applied to any DSP2 using the ‘Apply to DSP2’ button on the SETUP panel.
The user must assign a NAME to the DSP2, also via the SETUP panel before saving
using ‘Save to File’. The Save to File action will cause the ‘Name’.log file to be created
for that DSP2.
The following data, see Figure 7.2, is logged to the System Status logging file; reading
left to right
Date
Time
Fault code for input channel A
Fault code for input channel B
Comment.
The Start -Up Code and Counter windows are illustrated in Figure 7.3.
These Start-Up Code and Start-Up Counter features work in conjunction with each other.
There are two modes by which the DSP2 can be started.
1. External power ON/Off via the unit switch or external power supply failure or from a
user initiated Reset, code 0x080.
If either of these error conditions occurs then the appropriate error code is posted on the
UAP Diagnostics panel and the Start-Up counter incremented.
The Start-Up counter keeps count of the number of start-up occurences while
communication with the UAP is maintained. If the UAP connection is broken then the
counter returns to zero.
PART 8 MAINTENANCE
8.1 Introduction
The Rollmax Digital Signal Processor, Model DSP2, requires no routine maintenance,
other than occasional cleaning, if necessary, Section 8.4. Service is required only if a
failure occurs.
Both the line and the neutral are fused. To replace a fuse:
1. Disconnect the power supply and unplug the power cord from the rear of the DSP2,
see Figure 4.1.
2. Insert a screwdriver in the small notch in the fuse holder at the entrance to the power
socket and gently pry the fuse holder free.
4. Replace the fuser holder and power cord. Reconnect to the power supply.
The Strain Gage Interface Boards, Auxiliary Analog Input Board, Analog Output Boards,
and Fieldbus Card, may be replaced, or added, by the user.
Caution
To minimize the probability of electrostatic damage when handling printed circuit boards:
Wear a grounded wrist strap when handling boards not in protective packaging
Do not place boards on any surface other than a properly grounded static
dissipative mat.
Before installing or removing any board, ensure that the equipment is properly
grounded and ground the wrist strap to the equipment chassis.
Warning
4. If replacing a board, remove the two jack posts and the two screws holding the
connector plate, see Figure 7.2. Remove the connector plate. Using the tab at the
top rear corner of the board, carefully remove the board by pulling upwards until
it is just free of its socket, then sliding backwards.
If adding a new board, remove the two screws holding the cover plate. Remove
the cover plate.
5. Install the new board - center the connector in the rear panel opening and press
downwards to engage the socket on the Signal Processor Board. Install the
connector plate, screws and jack posts.
9. If a new board is being added, setup the new feature. See Part 5.
Caution
8.4 Cleaning
The DSP2 enclosure and front panel may be cleaned using a soft cloth dampened with
water and a mild detergent. Do not use harsh chemicals. Before cleaning, turn the power
off. Do not allow moisture to enter the DSP2.
PART 9 SPECIFICATIONS
Full Scale corresponds to the input or output level with the sensor loaded to rated capacity.
9.1 Performance
Analog Output
ROLLMAX DSP2 is for use with sensors with the following specifications:
Mode
Type
System Status
Load alarms
9.9 Power
9.10 Physical
Operating Environment
Storage Environment
Enclosure
Format CD
A.1 Introduction
The Serial Communications Interface (SCI) can be used to monitor and control the
Rollmax Digital Signal Processor, model DSP2.
Caution
Connect the DSP2 to the mill computer, Section 4.3.6. All DSP2’s employed in a mill
can be connected in parallel, in RS485 mode, to the computer.
Configure the DSP2 at the Front Panel Interface, Section 5.8.5. Set:
Any attempt to modify any of these parameters via the SCI will be ignored.
A.3 Processing
The SCI interface functions as a Modbus slave device. Once the SCI is configured, it
waits for a query (message) from a Modbus master. The DSP2 processes the request and,
if required, returns an appropriate response. While processing a query, the DSP2 ignores
any new query.
If RS485 mode has been selected, the DSP2 normally configures the port hardware for
receive, switching to the transmission configuration only when sending a response.
The DSP2 supports the remote terminal unit (RTU) serial transmission mode of the
Modbus protocol only.
The DSP2 always requires a “silent time” of at least 3.5 character times as an indication
of the end of a query. Characters received with less than this time separating them will be
deemed part of a single query.
Only queries containing 255 characters or less are supported. Any query longer than this
is ignored.
Characters that have a framing error are ignored. This will typically cause any associated
query to be rejected (as missing characters will normally cause the CRC validation check
to fail).
Write errors generally result in the return of an exception response. Since write errors are
tested per-register as a query is processed, some registers may be written even if an
exception response is returned.
Caution
Note
The following is an example of the use of the “read holding registers” function to read
Load and/or Load Alarm. Note that these parameters have been grouped in the memory
map (Section A.4.2) so that data for both sensors may be obtained with a single command.
The following is an example of the use of the “preset multiple registers” function to write
both Wrap Angle Value inputs.
A.4 Communications
A.4.1 Data Formats
The following table defines the formats of data that have been reconstructed after transmission.
For bitmapped formats, the condition is enabled (or “on”) when the bit is set and disabled
(or “off”) when the bit is clear, unless stated otherwise.
The nomenclature used for each format reflects the basic type and size (in eight-bit bytes)
of the format. The size of each format is always an integral multiple of one byte.
Regardless of their size, data are interpreted as “big-endian” (i.e., the least significant bit
is bit 0 and the most significant bit is the highest-numbered bit for the format).
For formats that do not use all of the available bits, the unused bits are ignored by the
format and are set to zero during transmission.
Enumerated Types
16E9 Source 0-A&B
1-2xA
2-2xB
16E12 No/Yes 0 - No
1 - Yes
16E13 Disable/Enable 0 - Disable
1 - Enable
16E14 Simulation 0 - Disable
1 - Simulate
2 - Shunt
Bitmapped Types
16B0 Logic Outputs (System Status Indicators and Bit 0 - System Fault
Load Alarms) Bit 1 - Channel A Fault
Bit 2 - Channel B Fault
Bit 3 - Single Sensor Operation
Bit 4 - Load Alarm 1
Bit 5 - Load Alarm 2
Bit 6 - Load Alarm 3
Bit 7 - Load Alarm 4
16B1 Electronics Status Bit 0 - Signal Processing
Bit 1 - Not assigned
Bit 2 - Not assigned
Bit 3 - Not used
Bit 4 - Not used
Bit 5 - Strain Gage Interface Board failed
Bit 6 - Not assiged
Bit 7 - Excessive internal temperature
16B2 Channel Status Bit 0 - Excitation current OFF
Bit 1 - Excitation undercurrent low
Bit 2 - Input Saturation ±
Bit 3 - Excitation current out of range
Bit 4 - No response to shunt resistor
Bit 5 - Coarse offset failure
Bit 6 - Coarse offset; no response
Bit 7 - No valid input
Bit 8 - Shunt resistor input too low
Bit 9 - Coarse gain fault
Bit 10 - Fine zero offset out of margin
Bit 11 - Fine gain out of margin
Bit 12 - Invalid parameter value
Bit 13 - Load Simulation active
Bit 14 - Internal routines active
Bit 15 - Signal Off (other channel doubled)
The following table lists the Modbus registers that may be accessed. Each register
contains a 16-bit value (i.e., consistent with the definition of a Modbus register).
Notes:
1. These registers are used to input Wrap Angle Values off-line wrap angle input mode,
see Sections 5.5 and 6.8 for additional information. The SCI should not be used to
input wrap angle sensor signals in on-line wrap angle input mode, the higher data rate
of the Fieldbus Interface is required.
2. The Auto Calibration (ref. Section 6.7) and Auto Zero (ref. Section 6.6) registers are
normally in the “No” state. A “Yes” instruction is required to initiate a function.
When the function is complete, the register is automatically reset to “No” by the DSP2.
3. If this register is set for Single Sensor Operation (1 for 2xA or 2 for 2xB), it can only
be changed to 0 for normal operation (A+B). See Section 6.5 for additional
information.
4. The effect of an instruction to the Lockout register is dependent on the status of the
Lockout Logic Input, see Section 6.11.
The SCI registers relate to the Status Indicators and Logic Outputs as shown in the
following table.
B.1 Introduction
The optional Fieldbus Interface provides the mill control computer with access to:
Load measurement data at the high rate necessary for mill control.
Input wrap angle data, for varying wrap angle tension measuring applications.
Monitor and control the DSP2.
Note: the switches on the rear of the unit are not used.
B.2.1 Connections
B.2.2 Terminations
This module is for use with twisted pair cables; no external terminator is required.
Configure the DSP2 either at the Front Panel Interface, Section 5.8.5, or via the User
Access Program. Set:
• Address (1-254)
Note: the IP address default is 10.0.0.254; it is the last field that is set via the FGI or the
UAP.
B.2.4 Indicators
This module is equipped with four bi-color status and indication LED’s at the front of the
unit. They indicate as follows:
Number Color Frequency Indication
1 Green Steady Connection Status
2 Green Steady Module Status
3 Green Flashes Network Status
4 Green Flashes Transmission Activity
B.3 Processing
Because the DSP2 Fieldbus interface is implemented as two sections of dual port RAM,
one Read and the other Write, it is not possible to implement Read/Write registers
directly on the fieldbus and a work-around is used. All registers that are written by the
host are mirrored in the space read by the host.
The DSP2 cannot determine exactly which variable has been updated by the host in the
dual port memory so it operates by identifying changes in variable values sent by the host.
Normally, this is completely transparent to the host but there are two cases where care
must be exercised:
At startup the current value buffer, used to identify changes, is set to 0. If the host
tries to write a zero to a DSP2 variable, no action will be taken and the DSP2
variable will remain at its default power-on value.
If the host tries to write the same value twice to a DSP2 variable, no action will be
taken and the DSP2 variable will remain unchanged. This is only a problem if the
variable has been changed by the UAP or FPI between the first and second writes.
Functions such as Auto Calibrate and Auto Zero, that are initiated by changing a register
value from 0 to 1 and indicate completion by the DSP2 changing the value back to zero
must be handled as follows:
B.4 Communications
The following table defines the formats of data that have been reconstructed after transmission.
For bitmapped formats, the condition is enabled (or “on”) when the bit is set and disabled
(or “off”) when the bit is clear, unless stated otherwise.
The nomenclature used for each format reflects the basic type and size (in eight-bit bytes)
of the format. The size of each format is always an integral multiple of one byte.
Regardless of their size, data are interpreted as “big-endian” (i.e., the least significant bit
is bit 0 and the most significant bit is the highest-numbered bit for the format).
For formats that do not use all of the available bits, the unused bits are ignored by the
format and are set to zero during transmission.
Enumerated Types
16E9 Source 0-A&B
1-2xA
2-2xB
16E12 No/Yes 0 - No
1 - Yes
16E13 Disable/Enable 0 - Disable
1 - Enable
Bitmapped Types
16B0 Logic Outputs (System Status Indicators and Bit 0 - System Fault
Load Alarms) Bit 1 - Channel A Fault
Bit 2 - Channel B Fault
Bit 3 - Single Sensor Operation
Bit 4 - Load Alarm 1
Bit 5 - Load Alarm 2
Bit 6 - Load Alarm 3
Bit 7 - Load Alarm 4
16B1 Electronics Status Bit 0 - Signal Processing error
Bit 1 - Not assigned
Bit 2 - Not assigned
Bit 3 - Not used
Bit 4 - Not used
Bit 5 - Strain Gage Interface Board failed
Bit 6 - Not assigned
Bit 7 - Excessive internal temperature
16B2 Channel Status Bit 0 - Excitation current OFF
Bit 1 - Excitation undercurrent low
Bit 2 - Input Saturation ±
Bit 3 - Excitation current out of range
Bit 4 - No response to shunt resistor
Bit 5 - Coarse offset correction failure
Bit 6 - Coarse offset; no response
Bit 7 - No valid input
Bit 8 - Shunt resistor input too low
Bit 9 - Coarse gain fault
Bit 10 - Fine zero offset out of margin
DSP2 90348 Rev F2
March 2008
107
KELK Ethernet
The following table defines the data that may be accessed via the Fieldbus interface. The
grouping of the data reflects the manner in which it is treated by the DSP2. Process
variables are updated from the DSP2 to the Fieldbus memory at 500Hz, other variables
are updated at approximately 45Hz.
Host Read Host Write Name Format Units Min Max Default Notes
Address Address Value Value Value
(Hex) (Hex)
Process Variables (Read-Only, Volatile)
0000 Input A Load 16I2 % -327.68 327.67 - 1
0001 Input B Load 16I2 % -327.68 327.67 - 1
0002 Relay Outputs 16B0 - - - - 1
0003 Input Sum A+B 16I2 % -327.67 327.67 - 1
0004 Input Difference A-B 16I2 % -327.67 327.67 - 1
System Status Data (Read-Only, Volatile)
000C Electronics Status 16B1 - - - 0 2
000D Channel A Status 16B2 - - - 0 2
000E Channel B Status 16B2 - - - 0 2
000F Electronics Temperature 16U1 °C -55.0 125.0 - 2
Operational Parameters (Read-Write, Volatile)
0020 0420 WAC Input W1 16U0 - 0 1000 0 2
0021 0421 WAC Input W2 16U0 - 0 1000 0 2
0022 0422 AutoCalibrate 16E12 - - - 0 2,3
0023 0423 AutoZero 16E12 - - - 0 2,3
Configuration Parameters (Read-Write, Non-Volatile)
0041 0441 Sensor Input Configuration 16E9 - - - 0 2,4
Notes:
1. These variables are updated by the DSP2 at 500Hz.
2. These variables are updated by the DSP2 one at a time sequentially every 2ms.
(about 45Hz).
3. Refer to B.3 above for operation of this function request register.
4. Sensor Input Configuration is for invoking Single Sensor Operation (Load
Doubling). The field bus interface can change this parameter from 0 (normal) to 1
(double A) or 2 (double B), however, it cannot change this value if it is already
non-zero. Only the FPI or SCI bus can clear it.
C.1 Introduction
The optional Fieldbus Interface provides the mill control computer with access to:
Load measurement data at the high rate necessary for mill control.
Input wrap angle data, for varying wrap angle tension measuring applications.
Monitor and control the DSP2.
C.2.1 Connections
* +5V BUS and GND BUS are used for bus termination. Some devices, like optical transceivers
(RS485 to fibre optics) might require external power supply from these pins. RTS is used in
some equipment to determine the direction of transmission. In normal applications only A-Line,
B-Line and Shield are used.
C.2.2 Termination
The end nodes in a Profibus-DP network has to be terminated to avoid reflections on the
bus line. The AnyBus-S Profibus-DP module is equipped with a termination switch to
accomplish this in an easy way. If the module is used as the first or last module in a
network the termination switch has to be in ON position. Otherwise, the switch has to be
in OFF position.
PLEASE NOTE: If an external termination connector is used the switch must be in OFF
position.
On the rear of the Fieldbus card are two rotary switches. These are for the purpose of
manually setting the address. The switch setting is not used by DSP2 and, therefore, both
switches must be set to zero
Configure the DSP2 either at the Front Panel Interface, Section 5.8.5 or via the User
Access Program. Set:
Address (1-125) DSP2 accepts values up to 254, the card, however, is limited to a
maximum of 125.
C.2.4 Indications
The module is equipped with four LED's mounted at the front panel and one LED on the
board, used for debugging purposes. The front LED's can be mounted in two ways, either
top mounted or angle mounted. The function of the LED's are described in the table and
figure below.
1. Not used
2. On-Line
3. Off-Line
4. Fieldbus diagnostics
There is also one additional Bicolour Watchdog LED on the AnyBus-S module. The
functionality of this LED is the same for all AnyBus-S modules, and is specified in the
AnyBus-S Design Guide.
C.3 Processing
Because the DSP2 Fieldbus interface is implemented as two sections of dual port RAM,
one Read and the other Write, it is not possible to implement Read/Write registers
directly on the fieldbus and a work-around is used. All registers that are written by the
host are mirrored in the space read by the host.
The DSP2 cannot determine exactly which variable has been updated by the host in the
dual port memory so it operates by identifying changes in variable values sent by the host.
Normally, this is completely transparent to the host but there are two cases where care
must be exercised:
At startup the current value buffer, used to identify changes, is set to 0. If the host
tries to write a zero to a DSP2 variable, no action will be taken and the DSP2
variable will remain at its default power-on value.
If the host tries to write the same value twice to a DSP2 variable, no action will be
taken and the DSP2 variable will remain unchanged. This is only a problem if the
variable has been changed by the UAP or FPI between the first and second writes.
Functions such as Auto Calibrate and Auto Zero, that are initiated by changing a register
value from 0 to 1 and indicate completion by the DSP2 changing the value back to zero,
must be handled as follows:
At startup, the value of the host write register will be 0.
The host must write 1 to the host write register, changing it from 0 to 1 to request a
function.
While the function is in progress, the host will read 1 from the mirrored read
register.
When the function is completed, the host will read 0 from the mirrored read
register.
The host must write 0 to the host write register to enable a subsequent function
request to change value from 0 to 1.
C.4 Communications
The following table defines the formats of data that have been reconstructed after transmission.
For bitmapped formats, the condition is enabled (or “on”) when the bit is set and disabled
(or “off”) when the bit is clear, unless stated otherwise.
The nomenclature used for each format reflects the basic type and size (in eight-bit bytes)
of the format. The size of each format is always an integral multiple of one byte.
Regardless of their size, data are interpreted as “big-endian” (i.e., the least significant bit
is bit 0 and the most significant bit is the highest-numbered bit for the format).
For formats that do not use all of the available bits, the unused bits are ignored by the
format and are set to zero during transmission.
Enumerated Types
16E9 Source 0-A&B
1-2xA
2-2xB
16E12 No/Yes 0 - No
1 - Yes
16E13 Disable/Enable 0 - Disable
1 - Enable
Bitmapped Types
16B0 Logic Outputs (System Status Indicators and Bit 0 - System Fault
Load Alarms) Bit 1 - Channel A Fault
Bit 2 - Channel B Fault
Bit 3 - Single Sensor Operation
Bit 4 - Load Alarm 1
Bit 5 - Load Alarm 2
Bit 6 - Load Alarm 3
Bit 7 - Load Alarm 4
16B1 Electronics Status Bit 0 - Signal Processing error
Bit 1 - Not assigned
Bit 2 - Not assigned
Bit 3 - Not used
Bit 4 - Not used
Bit 5 - Strain Gage Interface Board failed
Bit 6 - Not assigned
Bit 7 - Excessive internal temperature
16B2 Channel Status Bit 0 - Excitation current OFF
Bit 1 - Excitation undercurrent low
Bit 2 - Input Saturation ±
Bit 3 - Excitation current out of range
Bit 4 - No response to shunt resistor
Bit 5 - Coarse offset correction failure
Bit 6 - Coarse offset; no response
Bit 7 - No valid input
Bit 8 - Shunt resistor input too low
Bit 9 - Coarse gain fault
Bit 10 - Fine zero offset out of margin
Bit 11 - Fine gain out of margin
Bit 12 - Invalid parameter value
Bit 13 - Load Simulation active
Bit 14 - Internal routines active
Bit 15 - Signal Off (other channel doubled)
The following table defines the data that may be accessed via the Fieldbus interface. The
grouping of the data reflects the manner in which it is treated by the DSP2. Process
variables are updated from the DSP2 to the Fieldbus memory at 500Hz, other variables
are updated at approximately 45Hz.
Byte based addressing is used.
Each DSP2 variable occupies two bytes (MSB:LSB)
Host Read Host Write Name Format Units Min Max Default Notes
Address Address Value Value Value
(Hex) (Hex)
Process Variables (Read-Only, Volatile)
0000:1 Input A Load 16I2 % -327.68 327.67 - 1
0002:3 Input B Load 16I2 % -327.68 327.67 - 1
0004:5 Relay Outputs 16B0 - - - - 1
0006:7 Input Sum A+B 16I2 % -327.67 327.67 - 1
0008:9 Input Difference A-B 16I2 % -327.67 327.67 - 1
System Status Data (Read-Only, Volatile)
0010:11 Electronics Status 16B1 - - - 0 2
0012:13 Channel A Status 16B2 - - - 0 2
0014:15 Channel B Status 16B2 - - - 0 2
0016:17 Electronics Temperature 16U1 °C -55.0 125.0 - 2
Operational Parameters (Read-Write, Volatile)
0020:21 0000:1 WAC Input W1 16U0 - 0 1000 0 2
0022:23 0002:3 WAC Input W2 16U0 - 0 1000 0 2
0024:25 0004:5 AutoCalibrate 16E12 - - - 0 2,3
0026:27 0006:7 AutoZero 16E12 - - - 0 2,3
Configuration Parameters (Read-Write, Non-Volatile)
0030:31 0010:11 Sensor Input Configuration 16E9 - - - 0 2,4
Notes:
1. These variables are updated by the DSP2 at 500Hz.
2. These variables are updated by the DSP2 one at a time sequentially every 2ms.
(about 45Hz).
3. Refer to the paragraph C.3 above for operation of this function request register.
4. Sensor Input Configuration is for invoking Single Sensor Operation (Load
Doubling). The field bus interface can change this parameter from 0 (normal) to 1
(double A) or 2 (double B), however, it cannot change this value if it is already
non-zero. Only the FPI or SCI bus can clear it.
Below are lists of DSP2 options and spares. They may be used with any Rollmax DSP2
electronics system. Refer to KELK drawing 41990, provided at the end of this appendix, for the
DSP2 product structure and the availability of spares.
Note: If the user intends to expand an existing system by including an above analog input or
output option, the corresponding cable assembly for that option must be ordered
separately, see Individual Input/Output Cable Assemblies section below.
Harnesses are manufactured to a fixed length with 1.2 metres of connecting cable between the
DSP2 frame and the start of the terminal block assembly, as required for installation in KELK
cabinets. An optional, extended harness length of 2.0 metres is available.
PL044673-YYZL.L
The extension YYZ is added to denote included options in the same way as the DSP2 unit. The
extension L.L provides the harness length. A further explanation is as follows:
YY represents: No. of Analog Output Boards -1A, -2A, or -3A. (the number of
actual boards, with “A” denoting
“Analog”
Z represents: Auxiliary Analog Input Board -X (left blank if option not selected)
The following individual cable assemblies can be ordered apart from the Basic DSP2 harness. As
described above, if an optional analog input or output board is purchased for an existing system,
the respective cable assembly must also be ordered from the list below.
The Twin Strain Gage Input and Logic I/O cable assemblies (that are used in the Basic DSP2
Wiring Harness) can be ordered as spares. As can be seen below, the part numbers for these
assemblies have only a length extension. The first number is the standard length, while the value
in parentheses is the optional, longer length.
NOTE: Length of each cable assembly specified below is the full length, measured from the exit
point of the DSP2 to the respective terminal block.
Note that Profibus, Ethernet and Serial connections are provided directly on the DSP2 unit and
do not require a separate cable assembly.
Power Cord
E.1 Introduction
The DSP2 is designed to function with a large range of strain gage sensor types and in a
range of applications. The DSP2 offers many features and options and can operate in a
number of distinct modes depending on the specific application. It is necessary, therefore,
that before the unit is placed into operation the user must define and set various parameters
and optional features. A menu driven Front Panel Interface is provided for this purpose.
The Front Panel Interface is limited in that it can only display one parameter at a time. The
User Access Program has been developed to provide the user with a more friendly and
more comprehensive tools by which to setup and monitor the DSP2.
The User Access Program (UAP) is supplied on CD together with a copy of the DSP2
Manual in pdf format. The program is designed for use with any PC operating in a
Windows environment; connection to the DSP2 is through the serial port. Connection is
made at J7-COM1 on the back of the DSP2.
E.2 Features
The UAP completely replicates the Front Panel Interface (FPI) for the setup of:
a) Input Channels
b) Wrap angle Compensation
c) Output Channels
d) Relays and Load Alarms
e) Communications
f) Front Panel Display
A full screen to monitor the load outputs from each channel and to determine the
status of the system.
A full diagnostics screen to provide the user with instant readout of the system status
plus an indication of any faults detected.
The program uses standard conventions and menu structure for its operation. Each
screen is self explanatory. Areas on any screen not available to the user are shown in
gray.
The UAP, when connected to the DSP2, automatically assesses the hardware
configuration of the DSP2.
An existing operation configuration can be read back from a DSP2.
A new or revised operation configuration can be downloaded to the DSP2.
Password protection can be applied to any file.
The UAP provides additional user access to the DSP2 not provided by the FPI.
a) Calculation of Cable Correction factors for installations with very long cable runs.
b) Calculation of wrap angle from known Tension system geometries.
c) Calculation of Look Up Table entries for Wrap Angle Compensation.
d) Internal configuration data.
DSP2 90348 Rev F2
March 2008
119
KELK USER ACCESS PROGRAM
E.3 Installation
For use with Windows 98, ME, 2000, or XP. Refer to Section 9.11 for minimum
computer requirements.
Insert the CD in the drive and follow 'NEXT' prompts to complete installation of the
program.
If the CD does not automatically start the installation process, open the CD icon and
double click on SETUP.EXE.
If there is already an earlier version of the program installed on the PC, the install
program will prompt you before uninstalling it. When the uninstall is complete,
remove and re-insert the CD to start the install process.
Connect the computer to the DSP2 via the serial link at connection J7-COM1 at the rear
of the DSP2.
Refer to Section 4.3.6.
Start UAP
Under ‘File’ there is a menu item ‘Communications Setup’.
Selection of this item yields a panel that displays the Communication Setting List of
previously and currently connected DSP2 and a window for the entry of a new
Communications Setup. An active setting in the Communication Setting List will be
indicated by a ‘check’ in the second column; inactive settings are indicated by a red ‘X’.
Selection of any Setting on the list causes the details of that setting to be displayed in the
Communications Setup window. This display can be partially cleared by selecting ‘Add’
permitting the user to define a new setting. In this window:
The ‘COM port’ is the host computer COM port.
The Protocol and Address entries must match the target DSP2 protocol and address.
The DSP2 Name is user definable.
When the required setup has been defined click ‘Connect’ to add it to the Communications
Setting List. If a unit is detected to which this setup can be applied, a succesful connection
will be indicated, otherwise, the new entry will be marked with a red ‘X’.
The UAP program can be accessed without connection to a DSP2. This mode allows the
user to view or edit backup configuration files and familiarize themselves with the
program and its navigation.
Upon start up the UAP will search for a connected DSP2 and attempt to establish
communication.
The program has a Default file ‘Default.cfg.’ available or the user may select from their
own previously saved files.
Selection of the default or a backup file will result in the display of the ‘Rollmax DSP2
Navigation Panel’.
Ensure that the computer is connected to the DSP2 and that the DSP2 communications
parameters have been defined as in E.4. above.
Upon start up the UAP will search for a DSP2 specified by Communication Setting List
and attempt to establish communication. If no unit is found then the user is prompted to
a) Open a Configuration File. The program has a Default file ‘Default.cfg.’ available to
the user or, the user may select from their own previously saved backup configuration
files or,
b) Search for an Attached device. This option presents the user with a Communications
Setup panel from which an existing connection can be accessed or a new connection
defined.
When a DSP2 is successfully detected, its configuration is automatically read back into
the UAP and the operating condition of that DSP2 is displayed.
Selection of any read option will result in the display of the ‘Rollmax DSP2 Operation
Panel’ for either the file or the connected DSP2.
Data entry into any data field in any panel will result in the background of that field
changing colour to yellow to indicate that the field has been edited. The field background
will remain yellow until the data is applied to the DSP2 using the Apply command on the
DSP2 Setup panel or cancelled by selecting ‘Cancel Changes’. Data entered via the Input
Channel panel (see below) can only be applied to the DSP2 using the Configuration
command on the DSP2 Setup Panel.
Data as entered into the UAP fields is applied to the DSP2 by the ‘Apply to DSP2’
command on the DSP2 Setup Panel. Data can be applied at anytime the UAP is in use.
See also ‘Configuration via the UAP’.
Data directly related to the sensor and to the sensor /DSP2 system setup (refer to section
5.2) can only be applied to DSP2 using the ‘Configuration’ command on the DSP2 Setup
Panel. When this command is invoked DSP2 verifies that the parameter values applied
(in E.5.3 and E.5.4 above, for example) are valid and then configures the internal gain
settings to provide the required system gain.
The user is advised to double check this data prior to invoking the ‘Apply to DSP2’ and
‘Configuration’ commands.
A feature is available from the ‘File’ menu for the purpose of printing the following:
‘Save File’ and ‘Save as’ buttons are provided on the DSP2 Setup Panel. Customer can
define the directory and save as ‘Name’.cfg.
This Screen is divided into two panels. The left panel is the Navigation Panel; this contains
menu systems for both connected DSP2 and any selected DSP2 configuration files. The
right hand panel is user selected from the menus listed on the Navigation Panel.
The Navigation panel displays DSP2 file menus represented in three main sections
DSP2; ‘Name’ displays the current Operational status of a connected DSP2.
SETUP
DIAGNOSTICS
SETUP and DIAGNOSTICS contain sub-menus of related panels that can be selected and
accessed by the user.
The right hand panels that can be accessed via the Navigation panel are briefly described below.
Selection of either ‘DSP2 (name)’ or ‘Operations’ will display the DSP2 Operations
panel, Figure E1.
‘Name’ is user applied for a connected DSP2, otherwise the FILE ‘name’ field indicates
that backup ‘name’ file is accessed.
A series of buttons is available for the user to access any one of seven operations.
Activation of any button changes the dialogue box to reference the chosen operation and
displays another button for the user to invoke the chosen operation.
Operations:
1) Status
2) Single Sensor Operation; see Section 6.5
3) Calibration; see section 6.7
4) Zero; see section 6.6
5) Self-Test; see section 6.9
6) Reset; see section 6.10
7) WAC Input; see section 6.8
This panel, Figure E2, shows the current status of each parameter module. Any changes
made over the UAP will cause the appropriate box to change colour to yellow. This
indicates that changes have been made to the UAP file but have not yet been applied to a
DSP2 or saved to file.
Any parameter module can be selected from the SETUP sub-menu at the left of the panel.
This panel shows the Wrap Angle Compensation Tables and allows the user to select the
mode of WAC input to the DSP2. Table data can be entered manually or by using the
Application Wizard. The data for entry is fully described in the panel notes. See also
section 5.5 of the manual.
Application Wizard
The Application Wizard may be accessed through the Input Channels Panel and Wrap
Angle Compensation Panel. The Application Wizard provides the means for the user to
select the type of tensiometer system in place, strip configurations, mounting
configurations, fixed or variable angles and to specify the system geometry. The
Wizard calculates wrap angles, system formulae, maximum loads and Utilization
factors for each defined system. Using the ‘Show Section View’ button, the user can
visually verify that the data input does correctly define the basic system configuration.
In the case of variable angle systems the Wrap Angle Coefficients are calculated and
can be applied directly to the DSP2. These coefficients can be further verified using the
‘View’ and ‘Check’ buttons on the Wrap Angle Compensation panel.
Communication Panel
This panel is for the setting of the Fieldbus communication parameters. See section 5.8.5.
Note the Serial communication parameters can only be changed or set at the DSP2 FPI.
To set the mode and format of the front panel load display, refer to section 5.8.6.
E.6.6 Diagnostics
This panel, Figure E3, illustrates the current status of the DSP2.
The DSP2 Internal temperature, Start Up Code and Start Up Counter are also displayed
on this panel.
See Part 7 Troubleshooting for a full explanation of all displayed fault conditions and
Start Up Codes and Counter.
This panel displays the internal settings of the DSP2 for each input channel. The user has
no access to these settings; they are for information only.
Identification Panel
This panel displays DSP2 serial number and identification details for all boards installed
in the subject DSP2. This is for information only.
This panel displays factory set calibration parameters for Auxiliary Analog Input and
Analog Output boards installed in the subject DSP2.
The user has no access to these parameters; they are for information only.
This panel allows the user to simulate loads on each input channel either to some selected
level or by applying a shunt resistor directly to the sensor. The simulation is indicated at
the analog outputs and, if applicable, at the Relays. Refer to Section 7.7.
E.7 Example of DSP2 Setup and Configuration Summary Printout (see following pages)
IDENTIFICATION
Rollmax DSP2
Serial Number: 133 Firmware Version: 01.12
Fieldbus Card
N/A
SETUP
Input Channels
Load Cell Calibration Card Information Channel 'A' Channel 'B'
Model No. D1335 D1335
Serial No. 11 12
Capacity (C) [N] 2500.00 2500.0
Sensitivity (S) [mV/N] 1.6567 1.6541
Shunt Resistor at Calibration [✗✡] 250 250
Output with Calibration Shunt Resistor [Oc] [%] 42.29 42.39
Output Briidge Resistance ✡ 700.00 700.00
Interconnection Cable
Measured Single lead resistance: 1.70 [ohm]
Calibration Target Load Correction
Cable Correction Factor (Cf) 1.0097 1.0097
Utilization Factor (Uf) 1.2120 1.2120
Application Data and DSP2 Setting
Load Cell Sensitivity at Rated Load (Sr) [mV/V] — —
Application Shunt Resistor [✗✡] 100
Output with Application Shunt Resistor (Os) [%] 105.7 105.97
Calibration Target Load [%] A:86.25 B:100.20
DSP2 Inputs
Application Tension
Filter Length 999 Corner Frequency 5 [Hz]
SETUP
Communication
CALIBRATION DATA
Channel 'A' Channel 'B’
Input Channel Configuration Parameters
Hardware Settings
Zero DAC 0 -31
Gain DAC 4095 1347
Excitation DAC 4095 541
Software Settings
Fine Zero Adjustment -19550 -19445
Fine Gain Adjustment 60000 60000
Tare Load (Zero Offset)
Tare Zero Offset [ % ] -195 -194
Input Channel Settings
Zero Correction Limit [ % ] 20 20
Maximum Input [ % ] 325.00 325.00
APPENDIX F
F.1 Introduction
KELK load cells can be used to measure force or tension. Each load cell is factory
calibrated to determine its full load sensitivity (output at its rated capacity). Following
this, a precision resistor of known value (calibration shunt resistor) is placed across one
arm of the load cell bridge to force a fixed and repeatable output. The forced output is
expressed as a percentage of the full scale output for force, pressure or tension, depending
on the application. This provides a precise transfer reference that allows the system to be
calibrated on-site, effectively removing the need to use dead weight or auxiliary
calibration equipment that may be difficult to apply in the actual installation.
Each KELK load cell is supplied with a calibration card giving details of the model and
serial number, its full load sensitivity and the value of transfer reference and the value of
shunt resistor applied to create it. An example of a calibration card is given in Figure F1.
Load cell systems that require outputs in terms of force or load can be calibrated directly
using the information given on the calibration card. In the cases of systems designed to
measure tension, however, additional information is required to assist the user to calibrate
the system.
In tension measurement systems, the load cells measure load directly proportional to
tension. The constant of proportionality is related to the overall system geometry and the
wrap angles of the strip over the tensiometer roll. The accuracy of the system depends on
the precise knowledge of the system geometry and the wrap angles.
With each tension measurement system, KELK provides a ‘Tensiometer Application Data
Sheet’, Form 858 or 859, and a Tensiometer Calibration Data Sheet, Form 855.
Copies of this form corresponding to each application can be found in Section A of the
Tension Measurement System manual. The form is generated by KELK by inputting
application wrap angles and specific system parameters, as given on the system
installation drawing, into the DSP2 User Access Program (UAP) supplied with the
system. An example is given in Figure F2.
This feature of the UAP can be accessed by activating the ‘Application Wizard’ button in
the ‘Input Channels’ screen.
Note: the ‘Application Wizard’ button is only active if the ‘Tension’ application and
‘Extended Entry’ selections are chosen.
Refer to Appendix E for full details.
The above information is all displayed, and can be readily interpreted, using the
comprehensive legend.
Refer to Sections 5.8.4 and 6.8 for full details of Wrap Angle Compensation.
Compensation is achieved using values from look-up tables to calculate system gain
compensation factors. The UAP Application Wizard can generate the look-up tables
based on user input. Figure F3 illustrates the look-up tables for a system with one
variable angle and one fixed angle. Figure F4 illustrates the case for two variable angles.
Figure F3. Form 859 with WAC Tables for One Variable Angle Case
Figure F4. Form 859 with WAC Tables for Two Variable Angles Case
KELK generates Form 859 using the user-supplied data. In the event of system changes, the
user can utilize the UAP feature to update the system information and generate new data.
This form, supplied for each application, uses the data derived using Form 858 and load
cell calibration cards to determine the Calibration Target Load to be entered into the
DSP2 to correctly calibrate each sensor channel. As a result, the DSP2 outputs a signal
directly representing tension.
Note: For applications involving variable wrap angles, the Calibration Target Load is
determined using the system geometry that results in the largest force on the
sensor.
1 Location Interstand 1-2 Interstand 2-3 0 0 0 0
Information
Application
2 Position OS DS OS DS 0 0 0 0 0 0 0 0
6 Serial No. 11 12 13 14 0 0 0 0 0 0 0 0
8 Sensitivity (S) mV/V 1.5600 1.5499 1.5600 1.5678 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Shunt Resistor
9 κΩ 200 200 0 0 0 0
at Calibration
Output with Calibration
10 mV/V 0.8599 0.8450 0.8599 0.8862 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Shunt Resistor (Oc)
Output Bridge
11 Ω 700 700 0 0 0 0
Resistance
Corrections
Cable Correction
12 1 1 0 0 0 0
Factor (Cf)1
2
13 Utilization Factor (Uf) 2.1393 2.0890 0.0000 0.0000 0.0000 0.0000
Application
15 κΩ 250 250 0 0 0 0
Shunt Resistor
Output with application
16 mV/V 0.6879 0.6760 0.6879 0.7090 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000 0.0000
Shunt Resistor (Os)
Calibration Target Load
17
CTL=100*(Os/Sr)
% 94.34 93.31 92.12 94.47 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
18 CTL * Cf % 1 1 1 1 0 0 0 0 0 0 0 0
Customer Name
1
. To determine the Cable Correction Factor Cf, see System Manual under 'Calibration', DSP2 Manual section Mill Type
5.2 or use the DSP2 UAP.
2
. Utilization Factor Uf - the ratio of load cell capacity to force on the load cell at full rated tension; from Form 858. TENSIOMETER CALIBRATION DATA SHEET
INQUIRY: REV. DATE: DRAWN:
ZZ-YYYY 21-Feb-06
For full description of this form and its use, refer to Appendix F of DSP2 manual. JOB No.: DATE: CHK/APP:
JT-xxxx 09-Apr-08
855
SHEET 1 of 1
The form also includes information to assist the user in the setup of each input channel as
follows:
Application information
Row 1. Location in mill
2. Sensor position; for example, Drive or Operator side
3. Rated tension for the application
4. KELK reference information (installation drawing number)
DSP2 90348 Rev F2
March 2008
138
KELK Tensiometer Calibration
Information Sheets
Important Note.
The content of Forms 855 and 858, as supplied with the manual, is derived from the information
given on the installation drawing and/or supplied by the customer. This data should be checked
against the ‘as built’ or ‘as installed’ situation at the time of system calibration. If the data on the
forms do not correspond to the ‘as installed’ situation, new forms should be created. This can
either be done by KELK or by the customer using the UAP Input Channel screen and the
Application Wizard. Software to create Form 855 is included on the UAP CD.