Вы находитесь на странице: 1из 1

CompactLogix 5370 Controllers Overview Chapter 5

Controller Functionality Table 3 describes functionality available with CompactLogix 5370 controllers.
Table 3 - CompactLogix 5370 Controller Functionality
Cat. No. Controller Tasks Programs Internal Energy EtherNet/IP Power Supply On-board User Local I/O Module
Supported Supported Per Storage Solution Network Distance Rating Memory Size Support
Task Topology
Support
1769-L16ER-BB1B As many as six
384 KB 1734 POINT I/O
modules(2)
NA
1769-L18ER-BB1B As many as eight
512 KB 1734 POINT I/O
1769-L18ERM-BB1B modules(2)
1769-L24ER-QB1B
Support the 768 KB As many as four
1769-L24ER-QBFC1B following See footnote(1) Compact I/O
topologies: modules
1769-L27ERM-QBFC1B Yes - Eliminating 1 MB
32 1000 the need for a • Device-level
1769-L30ER battery ring (DLR)
As many as eight
1769-L30ER-NSE • Linear 1 MB Compact I/O
• Traditional star modules
1769-L30ERM
1769-L33ER 4 As many as 16
2 MB Compact I/O
1769-L33ERM modules
1769-L36ERM As many as 30
3 MB Compact I/O
modules
(1) CompactLogix 5370 L2 controllers have an embedded power supply. Therefore, you do not need to consider power supply distance rating when installing the controller. The Compact I/O modules that
are used as local expansion modules in a CompactLogix 5370 L2 control systems operate on a CompactBus and do have a power supply distance rating you must consider when installing those modules.
For more information on power supply distance rating regarding using Compact I/O modules in a CompactLogix 5370 L2 control system, see page 147 and page 226.
(2) IMPORTANT: You can use up to the maximum number of 1734 POINT I/O modules with the CompactLogix 5370 L1 controllers that are listed in Table 1, as long as the total current drawn by the modules
does not exceed the available POINTBus backplane current of 1 A. If you must use more local expansion modules than the POINTBus backplane current supports, you can install a 1734-EP24DC POINT I/
O expansion power supply between local expansion modules to increase the POINTBus backplane power and meet your system requirements.

Rockwell Automation Publication 1769-UM021F-EN-P - April 2015 119