Вы находитесь на странице: 1из 4

Project: Rating Program: LTC v1_187.

idd
Unit Tag: Software Version: YW 19.03a
Engineer: Date: 08/13/19 14:59:45
Customer:

Warnings / Errors
WARNING LAST DATA LINE IS PARTLOAD OPERATING LIMIT WITH PRE-ROTATION VANES (1).

Page 1 of 4
Project: Rating Program: LTC v1_187.idd
Unit Tag: Software Version: YW 19.03a
Engineer: Date: 08/13/19 14:59:45
Customer:
SALES REPORT

Unit Specifications
Model YKMDMPH95EQG Gear Code RL(CALC)
Rated Net Capacity (Tons) 800.0 Specified Net Capacity (Tons) 800.0
Heat Rejection Capacity (MBtu/h) 11.04
NPLV.IP (kW/Ton.R) 0.4614 Refrigerant Type/Charge (lb) R-134a/2252
Full Load (kW/Ton.R) 0.5514 A-Weighted SPL (dBA) 82
Input Power (kW) 441.1 Max Motor Load (kW) 447.0
Voltage / Hz (Input) 415 / 50.0 Oil Cooler Refrig clr
Condenser Gas Inlet Type Baffle
Job FLA (Amps) 711 OptiSound Control Y
Isolation Valve N
LRA (Amps) 4480 Variable Orifice VALVE:3
Solid State - LV Unit
Min Circuit Ampacity 889 Starter Type
Mounted
Max Circuit Breaker Amps 1200 Starter Model 26LBK-50

Evaporator Condenser
Fluid Water* Water*
Tube MTI No. 321 260 / 260
Passes 2* 2*
Fouling Factor (hr-ft²-°F/Btu) 0.000100* 0.000250*
Entering Fluid Temp (°F) 54.00* 87.00*
Leaving Fluid Temp (°F) 44.00* 96.24
Fluid Flow (gpm) 1914 2400*
Fluid Pressure Drop (ft H2O) 9.50 21.8
(*) Designates User Specified Input

Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-
Heating Packages Using Vapor Compression Cycle Certification Program, which is based on
AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in
the AHRI Directory at www.ahridirectory.org.
Compliant with ASHRAE 90.1 - 2004.
Compliant with ASHRAE 90.1 - 2007.
Compliant with ASHRAE 90.1 - 2010.
Compliant with ASHRAE 90.1 - 2013.
Compliant with ASHRAE 90.1 - 2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant
Management Credit (EAc4).
Materials and construction per mechanical specifications - Form 160.75-EG1.
Auxiliary components included in total KW - oil pump & heater, chiller controls.

Page 2 of 4
Project: Rating Program: LTC v1_187.idd
Unit Tag: Software Version: YW 19.03a
Engineer: Date: 08/13/19 14:59:45
Customer:

Partload Data (CEFT constant)


Net Capacity Input Power EEFT ELFT CEFT CLFT
% Load % Power kW/Ton.R
(Tons) (kW) (°F) (°F) (°F) (°F)
100 800.0 100 441.1 54.00 44.00 87.00 96.24 0.5514
90 720.0 90 396.6 53.00 44.00 87.00 95.32 0.5509
80 640.0 81 355.6 52.00 44.00 87.00 94.40 0.5557
70 560.0 72 316.9 51.00 44.00 87.00 93.50 0.5659
60 480.0 63 279.9 50.00 44.00 87.00 92.59 0.5831
50 400.0 54 237.2 49.00 44.00 87.00 91.66 0.5929
40 320.0 45 199.2 48.00 44.00 87.00 90.75 0.6225
30 240.0 37 161.8 47.00 44.00 87.00 89.84 0.6741
20 160.0 28 123.0 46.00 44.00 87.00 88.93 0.7689
15 120.3 23 102.3 45.50 44.00 87.00 88.47 0.8504

Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-
Heating Packages Using Vapor Compression Cycle Certification Program, which is based on
AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in
the AHRI Directory at www.ahridirectory.org.
Compliant with ASHRAE 90.1 - 2004.
Compliant with ASHRAE 90.1 - 2007.
Compliant with ASHRAE 90.1 - 2010.
Compliant with ASHRAE 90.1 - 2013.
Compliant with ASHRAE 90.1 - 2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant
Management Credit (EAc4).
Materials and construction per mechanical specifications - Form 160.75-EG1.
Auxiliary components included in total KW - oil pump & heater, chiller controls.

Page 3 of 4
Project: Rating Program: LTC v1_187.idd
Unit Tag: Software Version: YW 19.03a
Engineer: Date: 08/13/19 14:59:45
Customer:

Certified in accordance with the AHRI Water-Cooled Water Chilling and Heat Pump Water-
Heating Packages Using Vapor Compression Cycle Certification Program, which is based on
AHRI Standard 550/590 (I-P) and AHRI Standard 551/591 (SI). Certified units may be found in
the AHRI Directory at www.ahridirectory.org.
Compliant with ASHRAE 90.1 - 2004.
Compliant with ASHRAE 90.1 - 2007.
Compliant with ASHRAE 90.1 - 2010.
Compliant with ASHRAE 90.1 - 2013.
Compliant with ASHRAE 90.1 - 2016.
Compliant with the requirements of the LEED Energy and Atmosphere Enhanced Refrigerant
Management Credit (EAc4).
Materials and construction per mechanical specifications - Form 160.75-EG1.
Auxiliary components included in total KW - oil pump & heater, chiller controls.

Page 4 of 4