Generator Electrical Specification Transformer Electrical Specification

Voltage 480 Hz 60 Primary Voltage, V 480 Hz 60

Phase 3 PF 0.8 (min.) Secondary Voltage, V 13800 Phase 3

DG Set 1 2 3 4 5 DG Set 1 2 3 4 5
Gen. Capacity, Rated kW 500 100 100 111 112 Gen. kVA @ nom. P.F 625 125 125 138.75 140
Gen. Rated FLC 751.76 150.35 150.35 166.89 168.39 Std. Transformer Size, kVA 1500 50 150 0 0
:Breaker Sizing: Impedance, % 5 5 5 5 5
110% of Gen. Rated FLC 826.93 165.39 165.39 183.58 185.23 :Transformer Configuration:
Std. Circuit Breaker Size 175 175 200 0 0 Primary Delta Delta Delta Delta Delta
Circuit Breaker Type MCCB MCCB MCCB n/a n/a Secondary Wye Wye Wye Wye Wye
:CT Selection: :Voltage:
Gen. Rated FLC 751.76 150.35 150.35 166.89 168.39 Primary Voltage, L-L 480 480 480 480 480
Std. CT Ratio 1000 100 200 n/a n/a Primary Voltage, L-N 480 480 480 480 480
CT Type MR MR MR MR MR Secondary Voltage, L-L 13800 13800 13800 13800 13800
Secondary Voltage, L-N 7967 7967 7967 7967 7967
:Current of Selected Std. Transformer Size:
Primary Current, L-L 1804.22 60.14 180.42 0.00 0.00
Primary Current, L-N 1041.67 34.72 104.17 0.00 0.00
Secondary Current, L-L 62.76 2.09 6.28 0.00 0.00
Secondary Current, L-N 62.76 2.09 6.28 0.00 0.00
:FDS with LA (Branch):
Std. FDS rating 2 2 7 0 0
:FDS with LA (Main) / Disconnect Switch:
Std. FDS rating 0
Std. DS rating 200

:Bus Conductor:
Conductor Size 2/0
Ampacity 270
Type ACSR
TYPICAL CALCULATION FOR SMALL & MEDIUM SIZE DIESEL POWER GENERATION

Generator Technical Details Generator Transformer Detail

Voltage 480 Frequency 60 High Voltage 13800 No. Of Phase

No. Of Phase 3 Power Factor 0.8 Low Voltage 480 Frequency

:CALCULATIONS:

DIESEL GENERATOR: GENERATOR TRANSFORMER:


Diesel Generator Set 1 2 3 4 5 Transformer Set 1 2 3
Capacity, kW 300 500 0 0 0 Generator kVA 375 625 0
Rated Current, A 451.05 751.76 0.00 0.00 0.00 Transformer Impedance 0.00 0 0
BREAKER SIZING: Configurations:
+10% of Rated Current 496.16 826.93 0.00 0.00 0.00 Primary Delta Delta Delta
Breaker Size 500 600 200 250 150 Secondary Wye Wye Wye
Breaker Type n/a n/a n/a n/a n/a VOLTAGES:
CABLE SIZING: Primary Voltage, (L-L) 480 480 480
+15% of Rated Current 518.71 864.52 0.00 0.00 0.00 Primary Voltage, (L-N) 480 480 480
Cable Size, mm² 0 0 0 0 0 Secondary Voltage, (L-L) 13800 13800 13800
Cable Type n/a n/a n/a n/a n/a Secondary Voltage, (L-N) 7967 7967 7967
CT SELECTION: CURRENTS:
Generator Rated Current 451.05 751.76 0.00 0.00 0.00 Primary Current, (L-L) 451.05 751.76 0.00
Generator CT ratio 800 1000 n/a n/a n/a Primary Current, (L-N) 260.42 434.03 0.00
CT Type MR MR MR MR MR Secondary Current, (L-L) 15.69 26.15 0.00
VOLTAGE DROP CALCULATION (3-PHASE): Secondary Current, (L-N) 15.69 26.15 0.00
Generator to Panel CT SELECTION:
Length, (meter) 30 30 0 0 0 Transformer Primary CT 800 300 n/a
Resistance, R (Ω/m) 0.000164 0.000295 0.000000 0.000000 0.000000 Transformer Secondary CT n/a n/a n/a
Reactance, X (Ω/m) 0.000256 0.002295 0.000000 0.000000 0.000000 CT Type MR MR MR
Impedance, Z (Ω/m) 0.000000 0.000000 0.000000 0.000000 0.000000 FDS SECTION (BRANCH):
Voltage Drop (L-N) 6.670 63.012 0.000 0.000 0.000 Voltage Level, V 13800 13800 13800
Voltage at Control Panel 473.33 416.99 480.00 480.00 480.00 X' Former Secondary FLC 15.69 26.15 0.00
Voltage Drop, % 1.39 13.13 0.00 0.00 0.00 Size of Fuse Link 25 20 3
Result Good No Good Good Good Good FDS SECTION (MAIN):
Voltage Level, V 13800
Panel to Transformer X' Former Total FLC 41.84
Length, (meter) 40 50 0 0 0 Size of Fuse Link 7
Resistance, R (Ω/m) 0.000115 0.002557 0.000000 0.000000 0.000000 Size of Disconnect Switch N/A
Reactance, X (Ω/m) 0.000754 0.000164 0.000000 0.000000 0.000000 BUS CONDUCTOR SELECTION:
Impedance, Z (Ω/m) 0.000000 0.000000 0.000000 0.000000 0.000000 Voltage Level, V 13800
Voltage Drop 29.764 223.360 0.000 0.000 0.000 X' Former Total FLC 41.84
Voltage at Transformer 450.24 256.64 480.00 480.00 480.00 Size of Conductor 1/0
Voltage Drop, % 6.61 87.03 0.00 0.00 0.00 Ampacity 230
Result No Good No Good Good Good Good Type of Conductor ACSR
TRANSFORMER SIZE SELECTION:
Note: Generator Output, kVA 375 625 0
Allowable VD is <5%
:Transformer Size:

Transformer, kVA 400 0 0


(In Market)

Prepared By:

Sr. Engineer, EEICD


MEDIUM SIZE DIESEL POWER GENERATION

Generator Transformer Detail

60

CULATIONS:

GENERATOR TRANSFORMER:
4 5
0 0
0 0

Delta Delta
Wye Wye
VOLTAGES:
480 480
480 480
13800 13800
7967 7967
CURRENTS:
0.00 0.00
0.00 0.00
0.00 0.00
0.00 0.00
CT SELECTION:
n/a n/a
n/a n/a
MR MR
FDS SECTION (BRANCH):
13800 13800
0.00 0.00
3 2
FDS SECTION (MAIN):

BUS CONDUCTOR SELECTION:

TRANSFORMER SIZE SELECTION:


0 0

:Transformer Size:

0 0
TYPICAL CALCULATIONS FOR POWER GENERATIONS

Diesel Generator Details


"General Specifications"
Primary Voltage, L-L 480 Note:
Power Factor 0.8
Frequency 60
Number Of Phase 3

Diesel Generator Set Set No. 1 Set No. 2 Set No. 3 Set No. 4 Set No. 5 Set No. 6

Voltage 480 480 480 480 480 480


Capacity, kW 500 500 500 500 500 500
Rated Current 752 752 752 752 752 752
"Breaker Sizing"
+ 115% of Rated Current 865 865 865 865 865 865
Breaker Size 1000 1000 1000 1000 1000 1000 <<< - - -
Type ACB ACB ACB ACB ACB ACB <<< - - -
"Cable Sizing"
Generator to Transformer
+ 125% of Rated Current 940 940 940 940 940 940 <<< - - -
Cable Size 3-200mm² 3-200mm² 3-200mm² 3-200mm² 3-200mm² 3-200mm² <<< - - -
Type THHN THHN THHN THHN THHN THHN <<< - - -
Transformer to FDS
+ 125% of Rated Current 39 39 39 39 39 39
Cable Size 3C-8mm² 3C-8mm² 3C-8mm² 3C-8mm² 3C-8mm² 3C-8mm² <<< - - -
Type 15 kV XLPE 15 kV XLPE 15 kV XLPE 15 kV XLPE 15 kV XLPE 15 kV XLPE <<< - - -
"Transformer Selection"
Low Voltage, V 480 480 480 480 480 480
High Voltage, kV 13.8 13.8 13.8 13.8 13.8 13.8
Primary Current, A 902 902 902 902 902 902
Secondary Current, A 31 31 31 31 31 31
Impedance, % 0 0 0 0 0 0 <<< - - -
Calculated Capacity, kVA 625 625 625 625 625 625
Approved Capacity, kVA 750 750 750 750 750 750 <<< - - -
"CT Selection"
Generator Side 940 940 940 940 940 940
Generator Neutral 543 543 543 543 543 543
Transformer Neutral 18.116 18.116 18.116 18.116 18.116 18.116
Generator Primary CT Ratio 1000 500 300 1000 1000 1000 <<< - - -
Generator Neutral CT Ratio 250 300 200 700 700 700 <<< - - -
Transformer CT Ratio 10 10 6 20 20 20 <<< - - -
Secondary CT Ratio 1A 1A 1A 1A 1A 1A <<< - - -
"FDS Selection-Branch"
Voltage Level, kV 13.8 13.8 13.8 13.8 13.8 13.8
X'Former Secondary Current, A 31.38 31.38 31.38 31.38 31.38 31.38
Fuse Link, A 12 15 10 35 35 35
"FDS Selection-Main"
Voltage Level, kV 13.8 13.8 13.8 13.8 13.8 13.8
Sum of Full Load Current 188.27 188.27 188.27 188.27 188.27 188.27
Fuse Link, A 80 80 80 80 80 80
Disconnect Switch, A 80 80 80 80 80 80
Automatic Recloser <<< - - - See Approved Standard Rating
"Main Bus Conductor"
Voltage Level, kV 13.8
Conductor Size 2/0 ACSR
Ampacity 270
"Voltage Drop Calculation"
Generator to Transformer
Length, m 50 100 100 100 100 100 <<< - - -
Allowable VD < 5%
Resistance, R (Ω/m) 0.000092 0.000164 0.000164 0.000164 0.000164 0.000164 <<< - - -
Reactance, X (Ω/m) 0.000128 0.000131 0.000131 0.000131 0.000131 0.000131 <<< - - -
Impedance, Z (Ω) 0.000157 0.000210 0.000210 0.000210 0.000210 0.000210
Voltage Drop, V 5.916758 15.778045 15.778045 15.778045 15.778045 15.778045
Voltage at Transformer, V 474 464 464 464 464 464
Voltage Drop, % 1.2 3.4 3.4 3.4 3.4 3.4
Good Good Good Good Good Good
NS FOR POWER GENERATIONS

Filled-Up Only the required


No. Of Generator Sets

Remarks

Insert Size of CB
Insert Type of CB

See PEC Table


Insert Size of Cable
Insert Type of Cable

Not Included in the Contract


Insert Size of Cable Not Included in the Contract
Insert Type of Cable Not Included in the Contract

If Unknown leave it Blank

Insert Approved Size of X' former

Select as per Std. CT Ratio


Select as per Std. CT Ratio
Select as per Std. CT Ratio
Select as per Std. CT Ratio

Not Included in the Contract


Not Included in the Contract
Not Included in the Contract

Considering a Maximum of Not Included in the Contract


Two(2) Outgoing Feeder Not Included in the Contract
Not Included in the Contract
Designer choice if he/she Not Included in the Contract
will use FDS or DS Not Included in the Contract

Not Included in the Contract


Not Included in the Contract
Not Included in the Contract

Approximate Distance

Insert Resistance Value


Insert Reactance Value
Fuse link CT Ratio Bus Conductor Ampacity Configuration Std. 3-Phase Transformer, kVA Std. CB Rating
0 n/a 0 0 kVA
1 600:1A 1/0 230 Delta 1 1 PV
2 600 2/0 270 Wye 3 3 Phase
3 500 3/0 300 6 6 FLC
4 450 4/0 340 9 10
5 400 15 15 Secondary
6 300 2/0 270 25 20 SV
7 250 1/0 230 30 25 FLC
8 200 37.5 30
10 150 45 35
12 100 50 40
15 50 75 45
20 1200:1A 112.5 50
25 1200 150 60
30 1000 225 70
35 900 250 80
40 800 300 90
45 600 350 100
50 500 400 110
50 400 500 125
65 300 750 150
75 200 1000 175
80 100 1500 200
100 2000:1A 2000 225
140 2000 2500 250
150 1600 3750 300
200 1500 5000 350
1200 7500 400
1100 10000 450
800 12000 500
500 15000 600
400 20000 700
300 25000 800
3000:1A 30000 1000
3000 37500 1200
2500 50000 1600
2200 60000 2000
2000 75000 2500
1500 100000 3000
1200 4000
1000 5000
800 6000
500
300
4000:1A
4000
3500
3000
2500
2000
1500
1000
500
5000:1A
5000
4000
3500
3000
2500
2000
1500
1000
500
Generator Full Load Current Power Factor
375 625 0 0 0 36.87 36.87 36.87 36.87 36.87
480 480 480 480 480 0.80 0.80 0.80 0.80 0.80
3 3 3 3 3 0.60 0.60 0.60 0.60 0.60
451.05 751.76 0.00 0.00 0.00 0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
13800 13800 13800 13800 13800
15.69 26.15 0.00 0.00 0.00 36.87 36.87 36.87 36.87 36.87
0.80 0.80 0.80 0.80 0.80
0.60 0.60 0.60 0.60 0.60
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
0.00 0.00 0.00 0.00 0.00
Breaker Type Cable Type drop down Wire (For.) Cable Type Cable Size (mm²) THW THHN
Angle MCCB XLPE 125 265 THHN 2.0 20 25
cosØ ACB THHN 80 205 THHN 3.5 25 30
sinØ VCB THW 80 205 THHN 5.5 35 40
RcosØ OCB THWN 80 205 THHN 8.0 50 55
XsinØ n/a n/a 60 170 THHN 14 65 70
RcosØ+XsinØ 22 85 90
30 110 115
Angle 38 125 130
cosØ 50 145 150
sinØ 60 160 170
RcosØ 80 195 205
XsinØ 100 220 225
RcosØ+XsinØ 125 255 265
150 280 295
175 305 345
200 330 355
250 375 400
Allowable Ampacities of Insulated Copper Conductors Rated 0-2000 V, 60°C 325 435 470
to 90°C (Not More Than three Conductors in Raceways or Cable) COPPER 375 470 530
400 485 515
Temperature Rating of Conductors 500 540 580
Size
60°C 75°C 90°C
Types Types Types
TW RHW TBS, SIS 1 125
UF THHW SA, FEP 2 80
THW FEPB, MI 3 80
mm² THWN RHH, RHW-2 4 80
XHHN THHN, THHW 5 60
USE THW-2
ZX THWN-2
USE-2
XHH
XHHW
XHHW-2
ZW-2
2.0 20 20 25
3.5 25 25 30
5.5 30 35 40
8.0 40 50 55
14 55 65 70
22 70 85 90
30 90 110 115
38 100 125 130
50 120 145 150
60 135 160 170
80 160 195 205
100 185 220 225
125 210 255 265
150 240 280 295
175 260 305 345
200 280 330 355
250 315 375 400
325 370 435 470
375 395 470 530
400 405 485 515
500 445 540 580

Correction Factors (Copper)


Ambient
For Ambient Temp. Other than 30°C
Temp. (C°)
21-25 1.08 1.05 1.04
26-30 1.00 1.00 1.00
31-35 0.91 0.94 0.96
36-40 0.82 0.88 0.91
41-45 0.71 0.82 0.87
46-50 0.58 0.75 0.82
51-55 0.41 0.67 0.76
56-60 - 0.58 0.71
61-70 - 0.33 0.58
71-80 - - 0.41
1 2 3 4 5 Correction Factor THW THHN 1 2 3 4 5 DD
25 25 25 25 25 21-25 1.05 1.04 1.04 1.04 1.04 1.04 1.04 36-40
30 30 30 30 30 26-30 1.00 1.00 1.0 1.0 1.0 1.0 1.0
40 40 40 40 40 31-35 0.94 0.96 0.96 0.96 0.96 0.96 0.96
55 55 55 55 55 36-40 0.88 0.91 0.91 0.91 0.91 0.91 0.91
70 70 70 70 70 41-45 0.82 0.87 0.87 0.87 0.87 0.87 0.87
90 90 90 90 90 46-50 0.75 0.82 0.82 0.82 0.82 0.82 0.82
115 115 115 115 115 51-55 0.67 0.76 0.76 0.76 0.76 0.76 0.76
130 130 130 130 130 56-60 0.58 0.71 0.71 0.71 0.71 0.71 0.71
150 150 150 150 150 61-70 0.33 0.58 0.58 0.58 0.58 0.58 0.58
170 170 170 170 170 71-80 - 0.41 0.41 0.41 0.41 0.41 0.41
205 205 205 205 205
225 225 225 225 225
265 265 265 265 265
295 295 295 295 295
345 345 345 345 345
355 355 355 355 355
400 400 400 400 400
470 470 470 470 470
530 530 530 530 530
515 515 515 515 515
580 580 580 580 580

THHN 125 225 265 295


THHN 80 170 205 225
THHN 80 170 205 225
THHN 80 170 205 225
THHN 60 150 170 205

1 225 1205.75 295 1037.43 G


2 170 186.55 225 172.90
3 170 186.55 225 172.90
4 170 186.55 225 172.90
5 150 154.70 205 172.90
df % Derating
0.91 1-3 1 1-3
0.91 4-6
0.91 7-9
0.91 10-20
0.91 21-30
31-40
41 & Above
SIZING OF STATION SERVICE TRANSFORMER
Connected Load to Transformer Transformer Detail
Load No. Of Total DF Total DF kVA Load 361.51
Description Watts Voltage P.F Qty. D.F, % Total VA
No. Phase VA
1 Load Schedule 17422 230 1 3 2 100 34844 34844 Primary Voltage (L-L) 13800 V
2 17422 230 0.8 1 1 100 21777.5 21777.5 Secondary Voltage (L-L) 480 V
3 17422 230 0.8 1 1 100 21777.5 21777.5 Number of Phase 3
4 17422 230 0.8 1 1 100 21777.5 21777.5 Frequency 60 Hz
5 17422 230 0.8 1 1 100 21777.5 21777.5 Impedance 4 %
6 17422 230 0.8 1 1 100 21777.5 21777.5 Transformer Configuration
7 17422 230 0.8 1 1 100 21777.5 21777.5 "Primary" Delta
8 17422 230 0.8 1 1 100 21777.5 21777.5 "Secondary" Wye
9 17422 230 0.8 1 1 100 21777.5 21777.5
10 17422 230 0.8 1 1 100 21777.5 21777.5 "Calculation"
11 17422 230 0.8 1 1 100 21777.5 21777.5 Primary Voltage (L-L) 13800
12 17422 230 0.8 1 1 100 21777.5 21777.5 Primary Voltage (L-N) 13800
13 17422 230 0.8 1 1 100 21777.5 21777.5 Secondary Voltage (L-L) 480
14 17422 230 0.8 1 1 100 21777.5 21777.5 Secondary Voltage (L-N) 277
15 17422 230 0.8 1 1 100 21777.5 21777.5
16 17422 230 0.8 1 1 100 21777.5 21777.5 Primary Current (L-L) 15.12
17 0 230 0.8 1 1 100 0 0 Primary Current (L-N) 8.73
18 0 230 0.8 1 1 100 0 0 Secondary Current (L-L) 434.82
19 0 230 0.8 1 1 100 0 0 Secondary Current (L-N) 434.82
20 0 230 0.8 1 1 100 0 0
21 0 230 0.8 1 1 100 0 0 "Size of CB" As per PEC 2009 ART 4.50 Table 4.50.1.3(a)
22 0 230 0.8 1 1 100 0 0 Transformer Primary Side 90.75 90 << - -
23 0 230 0.8 1 1 100 0 0 Transformer Secondary Side 543.53 500 << - -
24 0 230 0.8 1 1 100 0 0
25 0 230 0.8 1 1 100 0 0 "Size of Transformer"
26 0 230 0.8 1 1 100 0 0 Total Connected Load 434.82
27 0 230 0.8 1 1 100 0 0
28 0 230 0.8 1 1 100 0 0
Total Connected Load should be less than 75% of Transformer FLC
29 0 230 0.8 1 1 100 0 0
30 0 230 0.8 1 1 100 0 0
31 0 230 0.8 1 1 100 0 0 Calculated Transformer FLC 579.77
32 0 230 0.8 1 1 100 0 0 Calculated Size of Transformer, kVA 482.01
33 0 230 0.8 1 1 100 0 0
34 0 230 0.8 1 1 100 0 0
35 0 230 0.8 1 1 100 0 0
Size of Transformer, kVA: 500
36 0 230 0.8 1 1 100 0 0
37 0 230 0.8 1 1 100 0 0
38 0 230 0.8 1 1 100 0 0
39 0 230 0.8 1 1 100 0 0
40 0 230 0.8 1 1 100 0 0 Prepared By:
41 0 230 0.8 1 1 100 0 0
42 0 230 0.8 1 1 100 0 0 M. J. J. FEDERICO
43 0 230 0.8 1 1 100 0 0 Sr. Engineer, EEICD

Total DF kVA Load 361.51


TATION SERVICE TRANSFORMER
Transformer Detail

As per PEC 2009 ART 4.50 Table 4.50.1.3(a)


Approved Size of CB
Approved Size of CB

Total Connected Load should be less than 75% of Transformer FLC


5 MW JOLO DISEL POWER PLANT PROJECT
Electical Engineering, Instrumentation & Control Division

Item Rating Rated Multiplier Size of


Paricular V Hz No. Of Ø X"d PF Conductor
No. kW HP Current @ 250% Breaker

A. Gensets Ventilation Fan

Genset No. 1 (Ventilation Fan No. 1) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Genset No. 1 (Ventilation Fan No. 2) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Genset No. 2 (Ventilation Fan No. 1) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Genset No. 2 (Ventilation Fan No. 2) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Genset No. 3 (Ventilation Fan No. 1) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Genset No. 3 (Ventilation Fan No. 2) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Genset No. 4 (Ventilation Fan No. 1) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Genset No. 4 (Ventilation Fan No. 2) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Genset No. 5 (Ventilation Fan No. 1) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Genset No. 5 (Ventilation Fan No. 2) 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

B. Radiator

Radiator No. 1 480 60 3 10% 0.80 22.5 - 33.83 84.58 90AT 14.0mm² THW

Radiator No. 2 480 60 3 10% 0.80 22.5 - 33.83 84.58 90AT 14.0mm² THW
5 MW JOLO DISEL POWER PLANT PROJECT
Electical Engineering, Instrumentation & Control Division

Item Rating Rated Multiplier Size of


Paricular V Hz No. Of Ø X"d PF Conductor
No. kW HP Current @ 250% Breaker

Radiator No. 3 480 60 3 10% 0.80 22.5 - 33.83 84.58 90AT 14.0mm² THW

Radiator No. 4 480 60 3 10% 0.80 22.5 - 33.83 84.58 90AT 14.0mm² THW

Radiator No. 5 480 60 3 10% 0.80 22.5 - 33.83 84.58 90AT 14.0mm² THW

C. Common Auxiliary Load

C.1 Pumps

Fuel Oil Transfer Pump No. 1 480 60 3 5% 0.80 - 5 7.60 19.00 20AT 5.5mm² THW

Fuel Oil Transfer Pump No. 2 480 60 3 5% 0.80 - 5 7.60 19.00 20AT 5.5mm² THW

Fuel Oil Unloading Pump 480 60 3 5% 0.80 - 10 14.0 35.00 35AT 8.0mm² THW

Lube Oil Transfer Pump No. 1 480 60 3 5% 0.80 - 7.5 11.0 27.50 30AT 8.0mm² THW

Lube Oil Transfer Pump No. 2 480 60 3 5% 0.80 - 7.5 11.0 27.50 30AT 8.0mm² THW

Waste Oil Transfer Pump No. 1 480 60 3 5% 0.80 - 7.5 11.0 27.50 30AT 8.0mm² THW

Waste Oil Transfer Pump No. 2 480 60 3 5% 0.80 - 7.5 11.0 27.50 30AT 8.0mm² THW

Fire Pump (Motor driven) 480 60 3 5% 0.80 - 6.5 9.64 24.10 25AT 5.5mm² THW

Fire Pump (Jockey driven) 480 60 3 5% 0.80 - 1.0 1.80 4.50 15AT 5.5mm² THW

Deepwell Pump 480 60 3 5% 0.80 - 6.7 10.0 25.00 25AT 5.5mm² THW

C.2 Air Starting System


5 MW JOLO DISEL POWER PLANT PROJECT
Electical Engineering, Instrumentation & Control Division

Item Rating Rated Multiplier Size of


Paricular V Hz No. Of Ø X"d PF Conductor
No. kW HP Current @ 250% Breaker

Air Compressor No. 1 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW

Air Compressor No. 2 480 60 3 5% 0.80 3.7 - 5.56 13.91 20AT 5.5mm² THW
W JOLO DISEL POWER PLANT PROJECT
Engineering, Instrumentation & Control Division

Conduits
W JOLO DISEL POWER PLANT PROJECT
Engineering, Instrumentation & Control Division

Conduits
W JOLO DISEL POWER PLANT PROJECT
Engineering, Instrumentation & Control Division

Conduits
5 MW JOLO DISEL POWER PLANT PROJECT
Electical Engineering, Instrumentation & Control Division

Item Rating Rated


Paricular V Hz No. Of Ø X"d PF Breaker Conductor Conduits
No. kW HP Current

A. Lighting System

40 Watts Fluorescent Lighting Fixtures 230 60 1 n/a n/a 5 n/a 21.74 20AT 5.5mm² THW

20 Watts Compact Fluorescent Lighting Fixtures 230 60 1 n/a n/a 5 n/a 21.74 20AT 5.5mm² THW

2x200 Watts Convenience Outlet 230 60 1 n/a n/a 10 n/a 43.48

2x200 Watts Convenience Outlet, Weather Proof 230 60 1 n/a n/a 10 n/a 43.48

Spare 230 60 1 n/a n/a 11 n/a 47.83

Spare 230 60 1 n/a n/a 12 n/a 52.17

B. Airconditioning System

Airconditioning Unit No. 1 230 60 1 n/a n/a 4 - 23.0 14.0mm² THW

Airconditioning Unit No. 2 230 60 1 n/a n/a 4 - 23.0 14.0mm² THW

Airconditioning Unit No. 3 230 60 1 n/a n/a 4 - 23.0 14.0mm² THW

Spare 230 60 1 n/a n/a 4 - 23.0 14.0mm² THW

Spare 230 60 1 n/a n/a 4 - 23.0 14.0mm² THW

C. 230Volts Auxiliary Load


5 MW JOLO DISEL POWER PLANT PROJECT
Electical Engineering, Instrumentation & Control Division

Item Rating Rated


Paricular V Hz No. Of Ø X"d PF Breaker Conductor Conduits
No. kW HP Current
Calculate Size of Transformer & Voltage Drop Due to Starting of large Motors

"Motor Load Details"


Total 3-Phase Full Load Current 322 A
Maximum Locked Rotor Current 450 % <<< - - - - Assuming Motor Code Type "D"
Operating Voltage 480 Volts
"Transformer Detail"
Capacity 500 kVA
Primary Voltage (L-L) 13800 V
Secondary Voltage (L-L) 480 V
Impedance 4 %
Allowable Voltage Drop in the System 10 %
"Calculation"
Transformer Full load current 601.41 A
Short Circuit Current of Transformer @ Secondary 15035.60 A
Maximum kVA of Transformer @ Short Circuit 12500.00 kVA
Motor Inrush kVA @ Starting 1204.64 kVA
Voltage Drop @ X'former Secondary Due to Motor Inrush 9.64 %
Transformer Secondary Voltage 433.74 V
"Conditions"
Motor Full Load Current should be less than 80% of X'former Full Load Current (Yes/No) Yes
Voltage Drop @ Transformer Secondary Due to Motor Inrush (Low/High) Low
Transformer Size (Good/No Good) Good <<< - - - -
POWER GENERATION (EE)
(Typical Generator Power Cable Sizing)

Electrical Requirements
Volts Phase P.F Frequency Amb. Temp. No. Of Run(s)
480 3 0.8 60 36-40 1-3

:CALCULATION:

POWER CABLE SIZING


+15% of Ampacity Correction De-Rating Calculated No. of Parallel Conductor Ampacity shall not be less
Unit(s) Capacity, kW Gen. FLC Type Size (mm²)
Gen. FLC (accdg. PEC) Factor (PEC) Factor (PEC) Ampacity Run per Phase than 115% of Generator FLC
1 600 902.11 1037.43 THHN 125 265 0.91 1 1205.75 5 Yes
2 100 150.35 172.90 THHN 80 205 0.91 1 186.55 1 Yes
3 100 150.35 172.90 THHN 80 205 0.91 1 186.55 1 Yes
4 100 150.35 172.90 THHN 80 205 0.91 1 186.55 1 Yes
5 100 150.35 172.90 THHN 60 170 0.91 1 154.7 1 No

Reference:
PEC 2009 Art.4.45.1.13
WER GENERATION (EE)
cal Generator Power Cable Sizing)

:CALCULATION:

POWER CABLE SIZING

Recommendation

Use this Size


Use this Size
Use this Size
Use this Size
Nope!! To small
Service Transformer

Voltage 230
Phase 1
Frequency 60
Load 100
Length, m 100
Cable Type THHN
R (Ω/305m) 0.05
X (Ω/305m) 0.06
Z (Ω/305m) 0.078
VD 2.561
%VD 1.113

Main Distribution Board

Load 50 Load 55 Load


Length, m 80 Length, m 35 Length, m
Cable Type THHN Cable Type THHN Cable Type
R (Ω/305m) 0.035 R (Ω/305m) 0.035 R (Ω/305m)
X (Ω/305m) 0.028 X (Ω/305m) 0.028 X (Ω/305m)
Z (Ω/305m) 0.045 Z (Ω/305m) 0.045 Z (Ω/305m)
VD 3.149 VD 2.844 VD
%VD 1.369 %VD 1.236 %VD

Panelboard A Panelboard B Panelboard C

Load 80 Load 80 Load


Length, m 50 Length, m 50 Length, m
Cable Type THHN Cable Type THHN Cable Type
R (Ω/305m) 0.035 R (Ω/305m) 0.035 R (Ω/305m)
X (Ω/305m) 0.028 X (Ω/305m) 0.028 X (Ω/305m)
Z (Ω/305m) 0.045 Z (Ω/305m) 0.045 Z (Ω/305m)
VD 6.297 VD 5.992 VD
%VD 2.738 %VD 2.605 %VD

Motor Load 1 Motor Load 1 Motor Load 1

Load 80 Load 80 Load


Length, m 50 Length, m 50 Length, m
Cable Type THHN Cable Type THHN Cable Type
R (Ω/305m) 0.035 R (Ω/305m) 0.035 R (Ω/305m)
X (Ω/305m) 0.028 X (Ω/305m) 0.028 X (Ω/305m)
Z (Ω/305m) 0.045 Z (Ω/305m) 0.045 Z (Ω/305m)
VD 9.729 VD 0.588 VD
%VD 4.230 %VD 0.256 %VD

Motor Load 2 Motor Load 2 Motor Load 2

Load 80 Load 80 Load


Length, m 50 Length, m 50 Length, m
Cable Type THHN Cable Type THHN Cable Type
R (Ω/305m) 0.035 R (Ω/305m) 0.035 R (Ω/305m)
X (Ω/305m) 0.028 X (Ω/305m) 0.028 X (Ω/305m)
Z (Ω/305m) 0.045 Z (Ω/305m) 0.045 Z (Ω/305m)
VD 0.588 VD 0.588 VD
%VD 0.256 %VD 0.256 %VD

Motor Load 3 Motor Load 3 Motor Load 3


80
80
THHN
0.035
0.028
0.045
3.501
1.522

80
50
THHN
0.035
0.028
0.045
6.650
2.891

80
50
THHN
0.035
0.028
0.045
0.588
0.256

80
50
THHN
0.035
0.028
0.045
0.588
0.256