NOTE: Note: [Output phase loss] (OPL) is forced to [No] (nO) if [Motor control type] (Ctt), page 74 =
[Sync. mot.] (SYn). For other [Motor control type] (Ctt) configurations, [Output phase loss] (OPL) is forced to [Yes]
(YES) if brake logic control is configured (see page 173).
nO [Ignore] (nO): Fault detection ignored, to be used when the drive is supplied via a single phase supply or by the DC
bus.
YES
[Freewheel] (YES): Fault with freewheel stop.
If one phase disappears, the drive switches to fault mode [Input phase loss] (IPL) but if 2 or 3 phases disappear, the
drive continues to operate until it trips on an undervoltage fault.
Factory setting: [Ignore] (nO) for ATV71p037M3 to U30M3, [Freewheel] (YES) for all others.