30072-452-92 Altivar® 71 Programming Guide

01/2010 [1.8 FAULT MANAGEMENT] (FLt-)

Code Name/Description Adjustment range Factory setting

OPL- [OUTPUT PHASE LOSS]

OPL [Output Phase Loss] [Yes] (YES)

nO [No] (nO): Function inactive


YES [Yes] (YES): Tripping on OPF fault with freewheel stop.
OAC [Output cut] (OAC): No fault triggered, but management of the output voltage in order to avoid an overcurrent when
the link with the motor is re-established and catch on the fly performed (even if this function has not been
configured). This configuration is not possible at and above 55 kW (75 hp) for ATV71pppM3X and at and above 90
kW (120 hp) for ATV71pppN4 if [Motor control type] (Ctt), page 74 = [Sync. mot.] (SYn) or [Sync.CL] (FSY).

NOTE: Note: [Output phase loss] (OPL) is forced to [No] (nO) if [Motor control type] (Ctt), page 74 = 
[Sync. mot.] (SYn). For other [Motor control type] (Ctt) configurations, [Output phase loss] (OPL) is forced to [Yes]
(YES) if brake logic control is configured (see page 173).

Odt [OutPh time detect] 0.5 to 10 s 0.5 s


 Time delay for taking the [Output Phase Loss] (OPL) fault into account.

IPL- [INPUT PHASE LOSS]

IPL [Input phase loss] According to drive


rating

nO [Ignore] (nO): Fault detection ignored, to be used when the drive is supplied via a single phase supply or by the DC
bus.
YES
[Freewheel] (YES): Fault with freewheel stop.
If one phase disappears, the drive switches to fault mode [Input phase loss] (IPL) but if 2 or 3 phases disappear, the
drive continues to operate until it trips on an undervoltage fault.

Factory setting: [Ignore] (nO) for ATV71p037M3 to U30M3, [Freewheel] (YES) for all others.

 Parameter that can be modified during operation or when stopped.

© 2010 Schneider Electric All Rights Reserved 235