MiCOM P13x
Feeder Management
Relays
Customer Benefits
• 1A/5A software setting
• Two communication
interfaces (for SCADA/RTU
and remote access)
• InterMiCOM protection
interface
AREVA T&D
APPLICATION GLOBAL FUNCTIONS
Overcurrent protection devices MiCOM P13x provide a The following global functions are generally available in
wide range of protection functions. all devices:
For the different requirements in system protection the
> Parameter subset selection
integrated functions follow the availability of CT and VT (4 alternative setting groups)
inputs (order options). As a result the preferred
> Metering
applications are as follows:
> Operating data recording
> P130C with VT: > Overload recording incl. overload data acquisition
Voltage and Frequency Protection > Ground fault recording
> P130C with CT and VT: incl. ground fault data acquisition
Directional Time-Overcurrent Protection > Fault recording of all CT/VT inputs and binary events
> P132 with CT: incl. fault measurands (e.g. fault location).
Non-Directional Time-Overcurrent Protection
> P132 with CT and VT:
Directional Time-Overcurrent Protection
FUNCTION DIAGRAMS
I
V
Self
Communication InterMiCOM Recording
COMM1 COMM2 Monitoring Overload rec.
and
Data
to SCADA / substation control / RTU / modem ... Acquisition Ground flt. rec.
I
V
For the overcurrent protection of the three phase Meas. Starting Variables selected for measurement Characteristic
currents, the residual current and the negative- system I V angle αP or αN
meas meas
sequence current the P13x provide definite time
overcurrent protection and inverse time overcurrent P A I V = V - V +45˚
A BC BN CN
protection with a multitude of tripping characteristics.
B I V C = V - V +45˚
B CN AN
A
C IC V AB = V AN - V BN +45˚
The operate values of all overcurrent stages can
dynamically changed (e.g. under cold load pickup A-B IA V BC = V BN - V CN +60˚
affect the general starting signal. This effect can be 1/3 . (V AN +V BN +V CN ) (adjustable)
suppressed if desired.
Forward decision
I meas
V
meas
(reference var.)
Tripping time characteristics
Backward decision
MiCOM P13x
for rapid and selective
fault clearance in your power system.
4>5
SWITCH ON TO FAULT THERMAL OVERLOAD
PROTECTION PROTECTION
Closing of a circuit breaker might inadvertently lead to a P13x provide thermal overload protection for lines,
short-circuit fault due to a maintenance ground clamp transformers and stator windings of h.v. motors. The
not yet removed, for example. The function 'switch on to highest of the three phase currents serves to track a
fault protection' provides for an undelayed protective first-order thermal replica according to IEC 255-8. For
tripping during a settable time after a manual close the P132 the temperature of the cooling medium can be
command has been issued. taken into account in the thermal replica using the
optional RTD inputs or the optional 20 mA input.
The user has a choice of using a thermal replica on the
MOTOR PROTECTION basis of either relative or absolute temperature.
Overload memory
100
GROUND-FAULT DIRECTION
m in %
DETERMINATION
80
t
three successive startups
AUTO-RECLOSING CONTROL CONTROL
The auto-reclosing control (ARC) operates in three- The optional control functions of the P132 are designed
phase mode. ARC cycles with one high-speed reclosing for the control of up to three electrically operated
(HSR) and multiple (up to nine) subsequent time-delay switchgear units equipped with electrical check-back
reclosings (TDR) may be configured by the user. signaling located in the bay of a medium-voltage
substation or a non-complex high-voltage substation.
The switchgear units can be controlled via binary inputs
AUTOMATIC SYNCHRONISM or the optional communication interface.
CHECK
This option for the P132 can be used in conjunction with PROTECTION INTERFACE
automatic or manual (re)closure and the close INTERMiCOM
command of the optional control function. In non-radial
networks this ensures that reclosure will proceed only if Optional InterMiCOM allows high performance
the synchronism conditions are met. permissive and blocking type unit protection to be
configured, plus transfer of any digital status information
between line ends. Intertripping is supported too, with
PROTECTIVE SIGNALING channel health monitoring and cyclic redundancy
checks (CRC) on the received data for maximum
Protective signaling can be used in conjunction with message security.
short-circuit direction determination. For this purpose
the protection devices must be suitably connected by InterMiCOM provides eight end-to-end signal bits,
pilot wires or the optional protection interface assignable to any function within a MiCOM relay's
InterMiCOM on both ends of the line section to be programmable logic.
protected.
For protection devices on the infeed side of radial Default failsafe states can be set in case of channel
networks, teleprotection can also be controlled without outage.
the short-circuit direction determination function.
InterMiCOM
with Compact
Devices
Proven protection
with advanced communication
and comfortable data handling.
6>7
INFORMATION INTERFACES
MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-P13x-BR-01.06-0407c-GB - © - AREVA - 2006. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.