P R OT E C T I O N

MiCOM P13x
Feeder Management
Relays

The time-overcurrent protection devices of the


MiCOM P13x range are designed for selective
short-circuit protection, ground fault protection and
overload protection. They can be applied in all types
of medium- and high-voltage systems.

The broad spectrum of protection functions enables


the user to cover a wide range of applications in the
protection of cables and overhead lines, transformers
and motors. In addition, numerous control functions
are available. Thanks to the provision of four setting
compact P130C groups, the P13x devices are readily adapted to
varying conditions in system operation.

The intuitive user interface as well as the various


communication interfaces allow simple and
comprehensive setting as well as access to readings
from extensive recordings. Numerous integrated
communication protocols provide interfacing to
almost any kind of substation control or SCADA
system.

Furthermore the integrated InterMiCOM protection


modular P132 interface provides direct end-to-end communication
between two protection devices.

The particularly flat compact case of the P130C as


well as the standard 19'' modular case of the P132
with a user-selected number of plug-in modules
provide a flexible solution for easy integration of the
devices into the substation. Both case variants are
available for flush mounting and wall-surface
mounting.

Customer Benefits
• 1A/5A software setting
• Two communication
interfaces (for SCADA/RTU
and remote access)
• InterMiCOM protection
interface

AREVA T&D
APPLICATION GLOBAL FUNCTIONS

Overcurrent protection devices MiCOM P13x provide a The following global functions are generally available in
wide range of protection functions. all devices:
For the different requirements in system protection the
> Parameter subset selection
integrated functions follow the availability of CT and VT (4 alternative setting groups)
inputs (order options). As a result the preferred
> Metering
applications are as follows:
> Operating data recording
> P130C with VT: > Overload recording incl. overload data acquisition
Voltage and Frequency Protection > Ground fault recording
> P130C with CT and VT: incl. ground fault data acquisition
Directional Time-Overcurrent Protection > Fault recording of all CT/VT inputs and binary events
> P132 with CT: incl. fault measurands (e.g. fault location).
Non-Directional Time-Overcurrent Protection
> P132 with CT and VT:
Directional Time-Overcurrent Protection

Functions Overview P130C P130C P132 P132


with VT with CT/VT with CT with CT/VT
50/51 P,Q,N DTOC Definite-time o/c protection, - • • •
three stages, phase-selective
51 P,Q,N IDMT resp. Inverse-time o/c protection, - • • •
IDMT1 single-stage, phase-selective
51 P,Q,N IDMT2 Inverse-time o/c protection, - - • •
single-stage, phase-selective x
67 SCDD Short-circuit direction determination - • - •
50/27 SOTF Switch on to fault protection - • • •
85 PSIG Protective signaling - • • •
79 ARC Auto-reclosure control (3-pole) - • • •
25 ASC Automatic synchronism check - - - option
67N GFDSS Ground fault direction determination - x - x
67N TGFD Transient ground fault - - - option
direction determination
37/48/49/ MP Motor protection - • • •
49LR/50S/66
49 THERM Thermal overload protection - • • •
46 I2> Unbalance protection - • • •
27/59 P,Q,N V<> Over-/Undervoltage protection • • - •
81 f<> Over-/Underfrequency protection • • - •
32 P<> Directional power protection - • - •
50BF/62 CBF Circuit breaker failure protection - • • •
30/74 MCMOM Measuring-circuit monitoring • • • •
LIMIT Limit value monitoring - • • •
LOGIC Programmable logic • • • •
DEV Control and monitoring - - option option
of up to 3 switchgear units
ILOCK Interlocking logic - - option option
COMMx 2 comm. interfaces, IRIG-B, protection option option option option
comm. interface InterMiCOM
INP / OUTP Binary inputs / output relays 2/8 2/8 40 / 30 40 / 30
(maximum number)
MEASI / MEASO Analog I/O - - option option
(2x 20 mA outputs, 20 mA input,
RTD inputs)

MiCOM P13x provide a wide range


of protection functions.
2>3
MAIN FUNCTIONS

Main functions are autonomous function groups and


can be individually configured or disabled to suit a
particular application. Function groups that are not
required and have been disabled by the user are
masked completely (except for the configuration
parameter) and functional support is withdrawn from
such groups.

This concept permits an extensive scope of functions


and universal application of the device in a single
design version, while at the same time providing for a
clear and straight-forward setting procedure and Simple Function Selection by Mouseclick
adaptation to the protection and control task under
consideration.

FUNCTION DIAGRAMS

Control/Monitoring of Self Recording


Communication InterMiCOM Overload rec.
up to 3 switchgear units COMM1 COMM2 Monitoring and
Data
Acquisition
to SCADA / substation control / RTU / modem ... Ground flt. rec.
DEV ILOCK
via RS485 or Fibre Optics

using IEC 60870-5-101, -103, Modbus, DNP3,


LIMIT Metering
Courier Fault rec..
85
PSIG LOGIC
Vref

50/51 P,Q,N 51 P,Q,N 51 P,Q,N 67 50/27 49 37/48/49/50S/66 46 30/74 25 79 67N 67N


DTOC IDMT_1 IDMT_2 SCDD SOTF THERM MP I2> MCMON ASC ARC GFDSS TGFD

I
V

27/59 P,Q,N 81 32 50BF/62


V<> f<> P<> CBF
always with further
available VT inputs options Time-Overcurrent Protection P132

Self
Communication InterMiCOM Recording
COMM1 COMM2 Monitoring Overload rec.
and
Data
to SCADA / substation control / RTU / modem ... Acquisition Ground flt. rec.

via RS485 or Fibre Optics


using IEC 60870-5-101, -103, Modbus, DNP3,
Courier LIMIT Metering
85 Fault rec.
PSIG LOGIC

50/51 P,Q,N 51 P,Q,N 67 50/27 49 37/48/49/50S/66 46 30/74 67N


79
DTOC IDMT SCDD SOTF THERM MP I2> MCMON ARC GFDSS

I
V

27/59 P,Q,N 81 32 50BF/62


V<> f<> P<> CBF always with further
available CT inputs options Time-Overcurrent / Frequency Protection P130C

(Description of ANSI code nos. see Functions Overview)


TIME-OVERCURRENT Directional characteristics
PROTECTION in short circuit direction determination

For the overcurrent protection of the three phase Meas. Starting Variables selected for measurement Characteristic
currents, the residual current and the negative- system I V angle αP or αN
meas meas
sequence current the P13x provide definite time
overcurrent protection and inverse time overcurrent P A I V = V - V +45˚
A BC BN CN
protection with a multitude of tripping characteristics.
B I V C = V - V +45˚
B CN AN
A
C IC V AB = V AN - V BN +45˚
The operate values of all overcurrent stages can
dynamically changed (e.g. under cold load pickup A-B IA V BC = V BN - V CN +60˚

conditions). Additionally, some of the phase and B-C IC V AB = V AN - V BN +30˚

negative-sequence current stages can be stabilized C-A IC V AB = V AN - V BN +60˚


under inrush conditions if desired.
A-B-C IC V AB = V AN - V BN +45˚

The residual and negative-sequence current stages G GF IN V NG = -90˚...+90˚

affect the general starting signal. This effect can be 1/3 . (V AN +V BN +V CN ) (adjustable)

suppressed if desired.

Forward decision
I meas

V
meas
(reference var.)
Tripping time characteristics
Backward decision

No. Tripping time characteristic Constants and formulae (t in s)


(k = 0.01...10.00) a b c R
0 Definite Time t=k
Per IEC 255-3
a
1 Normally inverse 0.14 0.02 t=k⋅ b
⎛ I ⎞
2 Very inverse 13.50 1.00 ⎜ ⎟ −1
⎜I ⎟
3 Extremely inverse 80.00 2.00
⎝ re f ⎠ SHORT-CIRCUIT DIRECTION
4 Long time inverse 120.00 1.00 DETERMINATION
Per ANSI/IEEE C37. 112 Trip Release
5 Moderately inverse 0.0515 0.0200 0.1140 4.85 Due to the short-circuit direction determination function,
6 Very inverse 19.6100 2.0000 0.4910 21.60 the P13x can be used as directional time-overcurrent
7 Extremely inverse 28.2000 2.0000 0.1217 29.10 protection devices. For the individual overcurrent stages
the user can select whether the stage shall be forward-
Per ANSI Trip Release directional, backward-directional or non-directional.
8 Normally inverse 8.9341 2.0938 0.17966 9.00 Direction determination is performed in separate
9 Short time inverse 0.2663 1.2969 0.03393 0.50 measuring systems for the phase current and residual
10 Long time inverse 5.6143 1.0000 2.18592 15.75 current elements, respectively.
R
⎡ ⎤ t =k⋅ 2
⎢ ⎥ ⎛ I ⎞
⎢ a ⎜ ⎟ −1
t =k⋅ + c⎥ ⎜I ⎟
⎢ ⎛ I ⎞b ⎥ ⎝ re f ⎠
⎢⎜ ⎟ −1 ⎥
⎣ ⎝ Ire f ⎠ ⎦

Not per standard


1
11 RI-type inverse t =k⋅
0.236
0.339 ⋅
⎛ I ⎞
⎜ ⎟
⎝ Ire f ⎠

Not per standard


⎛ I ⎞
12 RXIDG-type inverse t = k ⋅ ⎜ 5.8 − 1.35 ⋅ ln ⎟
⎝ Ire f ⎠

MiCOM P13x
for rapid and selective
fault clearance in your power system.
4>5
SWITCH ON TO FAULT THERMAL OVERLOAD
PROTECTION PROTECTION

Closing of a circuit breaker might inadvertently lead to a P13x provide thermal overload protection for lines,
short-circuit fault due to a maintenance ground clamp transformers and stator windings of h.v. motors. The
not yet removed, for example. The function 'switch on to highest of the three phase currents serves to track a
fault protection' provides for an undelayed protective first-order thermal replica according to IEC 255-8. For
tripping during a settable time after a manual close the P132 the temperature of the cooling medium can be
command has been issued. taken into account in the thermal replica using the
optional RTD inputs or the optional 20 mA input.
The user has a choice of using a thermal replica on the
MOTOR PROTECTION basis of either relative or absolute temperature.

For the protection of directly switched h.v. induction


motors with thermally critical rotor, the following OVER-/UNDERVOLTAGE
specially matched protection functions are provided: PROTECTION
> Recognition of operating mode The over- and undervoltage protection allows the multi-
> Rotor overload protection using a thermal motor stage evaluation of directly measured and internally
replica calculated voltages.
> Choice of reciprocally quadratic or logarithmic
tripping characteristic
> Inclusion of heat dispersion processes in the rotor OVER-/UNDERFREQUENCY
after several startups PROTECTION
> Separate cooling periods for rotating and stopped
motors The four-stage frequency protection can be operated as
> Startup repetition monitoring with reclosure blocking pure over- and underfrequency monitoring as well as
> Control logic for heavy starting and protection of combined with differential frequency gradient monitoring
locked rotor (df/dt) for system decoupling applications or with
medium frequency gradient monitoring (∆f/∆t) for load
Using the optional RTD inputs, direct monitoring of the shedding applications.
temperature of the stator windings and the bearings can
be set up with the P132.
DIRECTIONAL POWER
PROTECTION

The directional power protection monitors the active and


Overload memory
reactive power limits and detects power drop and
and startup counter
reversal of direction.

Overload memory
100
GROUND-FAULT DIRECTION
m in %
DETERMINATION
80

For the determination of the ground-fault direction in


60
isolated or Peterson-coil compensated power systems
two proven methods are provided:
40

> Wattmetric method (analysis of steady-state signals)


20
> Transient method (analysis of transient signals)
(optional).
0
t

Permissible number of startups Reclosure blocking


3
2
1

t
three successive startups
AUTO-RECLOSING CONTROL CONTROL

The auto-reclosing control (ARC) operates in three- The optional control functions of the P132 are designed
phase mode. ARC cycles with one high-speed reclosing for the control of up to three electrically operated
(HSR) and multiple (up to nine) subsequent time-delay switchgear units equipped with electrical check-back
reclosings (TDR) may be configured by the user. signaling located in the bay of a medium-voltage
substation or a non-complex high-voltage substation.
The switchgear units can be controlled via binary inputs
AUTOMATIC SYNCHRONISM or the optional communication interface.
CHECK

This option for the P132 can be used in conjunction with PROTECTION INTERFACE
automatic or manual (re)closure and the close INTERMiCOM
command of the optional control function. In non-radial
networks this ensures that reclosure will proceed only if Optional InterMiCOM allows high performance
the synchronism conditions are met. permissive and blocking type unit protection to be
configured, plus transfer of any digital status information
between line ends. Intertripping is supported too, with
PROTECTIVE SIGNALING channel health monitoring and cyclic redundancy
checks (CRC) on the received data for maximum
Protective signaling can be used in conjunction with message security.
short-circuit direction determination. For this purpose
the protection devices must be suitably connected by InterMiCOM provides eight end-to-end signal bits,
pilot wires or the optional protection interface assignable to any function within a MiCOM relay's
InterMiCOM on both ends of the line section to be programmable logic.
protected.
For protection devices on the infeed side of radial Default failsafe states can be set in case of channel
networks, teleprotection can also be controlled without outage.
the short-circuit direction determination function.

InterMiCOM
with Compact
Devices

Proven protection
with advanced communication
and comfortable data handling.
6>7
INFORMATION INTERFACES

Information exchange is done via the local control


panel, the PC interface and two optional
communication interfaces.

One of the communication interfaces conforms to IEC


60870-5-103, IEC 60870-5-101, DNP 3.0, Modbus and
Courier and is intended for integration with substation
control systems.

The 2nd communication interface conforms to IEC


60870-5-103 and is intended for central settings or One Record per Fault
remote access. (incl. oscillography, SOE, Fault Measurands)

Clock synchronization can be achieved using one of


the protocols or using the IRIG-B signal input.

Just one Setting File


Device Track Record
>> PS 451 / PM 481: first multi-functional, numerical time-overcurrent
devices launched in 1991, more than 14000 devices installed.
>> PS 441: first directional time-overcurrent device in compact case
design, more than 9000 devices installed since 1994.
>> PS 4x2: numerical time-overcurrent devices with extended
functionality, more than 4000 devices installed since 1998.
>> PS 4x2 MiCOM Design: Adaption of the PS 4x2 to the
MiCOM range design, launched in 2001.
>> MiCOM P13x: Complete integration of the PS 4x2 into the
MiCOM range, extended functionality and realization of a
'compact-solution' in the MiCOM family.

MiCOM is a registered trademark of AREVA. All trade names or trademarks mentioned herein whether registered or not, are the property of their owners. - 389191982 RCS PARIS - Printed in France - SONOVISION-ITEP
AUTOMATION-L3-P13x-BR-01.06-0407c-GB - © - AREVA - 2006. AREVA, the AREVA logo and any alternative version thereof are trademarks and service marks of AREVA.

Our policy is one of continuous development. Accordingly the


AREVA T&D Worldwide Contact Centre: design of our products may change at any time. Whilst every
http://www.areva-td.com/contactcentre/ effort is made to produce up to date literature, this brochure
should only be regarded as a guide and is intended for
Tel.: +44 (0) 1785 250 070 information purposes only. Its contents do not constitute an offer
for sale or advise on the application of any product referred to in
www.areva-td.com it. We cannot be held responsible for any reliance on any
decisions taken on its contents without specific advice.
www.areva-td.com/protectionrelays