Академический Документы
Профессиональный Документы
Культура Документы
SCHEDULE-III (Volume-B)
(ii) It is not the intent to specify completely herein all the details of the design
and construction of material. The material shall, however, conform in all
respects to high standards of engineering, design and workmanship and shall
be capable of performing for continuous commercial operation in a manner
acceptable to the purchaser, who will interpret the meanings of drawings and
specification and shall have the power to reject any work or material which in
his judgment is not in accordance therewith. The offered LT TVM shall be
complete with all accessories, software and components necessary for their
effective and trouble free operation. Such components shall be deemed to be
within the scope of Bidder's supply irrespective of whether those are
specifically brought out in this specification and/or the commercial order or
not.
(iii) The meter shall be ISI mark & bidder shall furnish the details of ISI license at
the time of bid or within 60 days from the date of opening of bid.
B) REQUIREMENT
The meter shall be suitable for full power factor range from zero (lagging)
through unity to zero (leading). The meter should work as an active energy and
reactive (lag & lead) energy meter.
The supply system shall be 3x415V Phase to Phase, 3 phase 4 wires. The
extreme power supply variations for which an operating meter should withstand
without damage and without degradation of its meteorological character-statics when
it is subsequently operated under its normal operating conditions shall be as follows:
-
However, the bidder can offer meter, which can withstand higher variations. The
limit of power supply variations should be as per IS: 14697-1999.
2423-Spec -4-
3.07 ACCURACY:
Class of accuracy of the meter shall be 0.5S. The accuracy should not drift
with time.
(i) Voltage circuit: The active and apparent power consumption in each voltage
circuit including the power supply of meter at reference voltage, reference
temperature and reference frequency shall not exceed 1.0 Watt per phase and
8 VA per phase respectively.
(ii) Current circuit: The apparent power taken by each current circuit at basic
current, reference frequency and reference temperature shall not exceed 1 VA
per phase.
The meter should start registering the energy at 0.1% Ib and unity power
factor.
ii) All the materials and electronic power components used in the manufacture of
the meter shall be of highest quality and reputed make to ensure higher
reliability, longer life and sustained accuracy.
iii) (a) The manufacturer should use application specific integrated circuit (ASIC) for
metering functions.
(b) The meter should not have any form of mechanical adjustment such as
trim-pots, potentiometer etc. for calibration. The meter shall be factory
2423-Spec -5-
calibrated and no adjustment of calibration shall be possible at site by any
means.
(c) The electronic components shall be mounted on the printed circuit board
using latest Surface Mount Technology (SMT). The PCB material should be
made of glass epoxy FR-4 grade conforming to relevant standards or better
grade.
iv) All insulating materials used in the construction of meters shall be non-
hygroscopic, non ageing and of tested quality. All parts that are likely to
develop corrosion shall be effectively protected against corrosion by providing
suitable protective coating.
v) The meter shall have test out put device in the form of calibrating LED
accessible from the front and capable of being monitored conveniently with
suitable testing equipment.
vi) The meter shall conform to the degree of protection IP 51 of IS: 12063/IEC:
60529 for protection against ingress of dust, moisture and vermin.
vii) The meter shall either remain immune to tamper through application of
external magnetic field (AC electro magnet or DC magnet) as per value
specified in CBIP 325 or if the metering gets affected then meter shall record
energy at Imax, rated voltage and unity P.F. as per CBIP 325 and same
should also be logged as event.
viii) The meter should continue to function even if any spurious signals are
injected on the neutral of the meter such as D.C signals through diodes etc.
and /or High Frequency Signals.
ix) The meter shall be supplied with a transparent extended terminal-block cover
(ETBC).
x) The meter shall have two push buttons, one for forward scrolling and other
for reverse scrolling of different parameters available in push button mode.
(a) The meter -base, meter cover; terminal block and ETBC shall be made of
unbreakable, high grade, flame retardant polycarbonate with thickness more
than 2.0 mm, and of good dielectric and mechanical strength. The material of
meter base & terminal block shall be glass reinforced.
(b) Meter cover and extended terminal block cover (ETBC) should be injection
moulded in UV stabilized polycarbonate in natural color. The ETBC shall be
kept fully transparent and the meter cover except the window portion shall be
semi-transparent / non-transparent/corrugated. The moulded meter case and
terminal cover(s) should not change in color, shape, size, and dimensions,
when subjected to 200 hours on UV ageing test. It should withstand 650 deg.
C glow wire test and heat deflection test as per ISO 75.
2423-Spec -6-
(c) The manufacturer shall emboss/ engraved/ laser marked on the base & cover,
the name of the material they have used in an abbreviated from e.g. PCFR 10
GF (to denote that they have used polycarbonate flame retardant 10 % glass
filled polycarbonate).
(e) The meter cover shall be ultrasonically welded with the meter base. The
sample meter to be sent along with bid may not be ultrasonically welded with
the meter base, as at the time of sample testing it has to be opened to
ascertain conformity of meter as per specification. However, before
commencement of supply, sample has to be got approved with ultrasonically
welded meter by the successful bidder
(a) The detachable terminal block shall be moulded type made of non-hygroscopic,
flame retardant material having good dielectric and mechanical strength. The
moulded terminal block shall be made from best quality phenol formaldehyde or
10-20% glass filled polycarbonate material or any equivalent/better material
conforming to FH-1 of IS 11731 (Part-I) having adequate insulating properties
and mechanical strength with brass inserts for connecting terminals.
The terminal block should satisfy all the conditions specified in IEC-
62052 & IS-14697 and shall be made from best quality phenol formaldehyde or
10-20% glass filled polycarbonate material or any equivalent/better material. The
glass filled polycarbonate should fulfill the requirement of following tests
(b) The terminal block, the ETBC and the meter case shall ensure reasonable safety
against the spread of fire and shall not be ignited by the thermic overload of
live parts in contact with them
(c) The current circuit conductors of a meter shall be connected to its current
terminals inside the meter terminal block adopting procedure prescribed either B-
1 or B-2 of the recommended methods under Clause 6.4-Annexure-B of IS
14697. Any other method which meets this requirement in a better manner/way
shall also be considered. The bidder should elaborate the arrangement adopted.
2423-Spec -7-
(d) The meter terminal block shall have tin- plated brass terminal/Nickel plated.
The terminals shall have suitable construction with barriers and transparent
cover to provide firm and safe connections of incoming and out going leads. The
terminal screws shall have flat bottom so as not to pierce in the external
conductors. The terminal be of suitable rating to carry continuous Imax current
and should be made of electroplated (or tinned) brass/nickel-plated and shall be
of non-replicable type. Any other provision which meets this requirement in a
better manner/ way shall also be considered. The bidder should elaborate the
procedure adopted.
e(1) The manner of fixing the external conductors to the terminal block shall
ensure adequate and durable contact such that there is no risk of loosening or
undue heating. Screw connections transmitting contact force and screw
fixings, which may be tightened and loosened several times during the life of
the meter, shall screw into the body of brass terminal.
All parts of each terminal shall be such that the risk of corrosion is minimized.
Two screws shall be provided in each current terminal for effectively clamping
the external leads or thimbles. Each clamping screw shall engage a minimum
of three threads in the terminal. The ends of screws shall not pierce and cut
the conductors used. Electrical connection shall be so designed that contact
pressure shall not be transmitted through insulating materials. If the manner
of fixing of terminals is through thimbles /lugs/reducer type terminals. The
supplier shall supply a set of the same along with each meter.
(2) The internal diameter of the terminal hole shall be minimum 4.0mm. The
holes in the insulation material of the terminal block, which form an extension
of the terminal holes, shall be of sufficient size to accommodate the insulation
of the conductors also. The clearance and creepage distance shall not be less
than the values specified in clause 6.6 of IS 14697:1999.
Further, the supporting webs between two terminals of the terminal block
should be sufficiently high to ensure that dust does not bridge the two
neighboring terminals or a flash over does not take place.
f) The fixing screw(s) used on the ETBC for fixing and sealing of extended
terminal cover shall be held captive on the terminal cover.
xiii) The termination of current circuit wires inside the meter (i.e. CT primary
conductor) on the terminal block shall be through lugs and washers of proper
size. The loop length of the primary current circuit should be kept minimum.
Alternatively the CT primary conductor may be flattened to form a ‘lug’ like
shape for proper termination on terminal block without using lug or any other
better arrangement may also be provided.
2423-Spec -8-
xiv) The meter shall have minimum three fixing holes, one at the top and other
two inside the terminal block. The top hole shall be key-hole type on the back
of the meter base so that the hanging-screw is not accessible after fixing of
the meter and it shall not be possible to remove the meter from the hanging-
screw without removing the terminal cover and screw(s) from the terminal
block. Any alternate better arrangement shall also be considered for
acceptance.
The lower fixing holes shall be provided under the extended terminal cover. A
set of fixing screws shall be supplied with each meter.
xv) Extended terminal block cover shall be provided to ensure that the internal
parts are not accessible for tampering etc. without breaking the seals. The
ETBC shall be extended by Minimum 30 mm below the terminal block. A firm
connection shall be established with in the meter case to energies the voltage
circuit.
Arrangement for display, optical port, auxiliary supply source, push buttons
for manual mode, meter nameplate and display sequence should be made in
such a manner that it is accommodated in size of 170 mm(W) x 140 mm (H)
from opposite side of ETBC. This is required for facilitating of fixing of the LT
Tri-vector meter in LT panel box.
All the material, electronics and power components, ICs used in the
manufacture of the meter shall be of highest quality and repudiated
make (as per Annexure-H) to ensure higher reliability, longer life
and sustained accuracy. The verification of the components shall be
carried out at manufacturers’ works before offering material before
inspection.
d) Prior to final testing and calibration, all electronic components of the meter
shall be subjected to accelerated ageing test to eliminate infant mortality.
iv) The bidders should submit the list of all major components used in meter
along with the offer.
v) A detailed list of bought-out items, which are used in the manufacture of the
meter, should be furnished indicating the name of firms from whom these
items are procured. The bidder shall also give the details of quality assurance
procedures followed by him in respect of the bought-out items.
At least two sealing screws shall be provided for proper fixing of meter cover so that
access to the working parts shall not be possible without breaking the seals. One
screw provided on left side shall be used by manufacturer to provide his own sealing
with high quality double anchor polycarbonate seal bearing laser etched monogram
of JVVNL along with meter serial number and other provided on right side by
purchaser, which should be left unsealed. Provision shall also be kept for one no.
seal on terminal cover. All the sealing screws shall be captive type so that they
cannot be detached when they are in open condition. The holes in the head of
sealing screw shall be of min. 2mm dia. The sealing screws for meter base and cover
shall be unidirectional and slot less (2 No.) .Two No. tamper indicative paper seal(s)
on either side of the meter case shall be provided by the manufacturer. For this, at
least two (2) Nos. seals on meter body and provision for, one (1) no. seal on meter
terminal cover and one (1) no. seal on communication port shall be provided.
For the above sealing arrangement for the purchaser, the manufacturer shall provide
at least one seal on the meter body at the factory after calibration and testing.
Provision for all the seals should be provided on front side only. Rear side sealing
arrangement will not be accepted. The Suppliers in their offer should explain the
sealing arrangement.
The connection diagram of the meter shall be clearly shown for 3 phase 4 wire
system as well as 3 phase 3 wire system/ with or without installation of 4 th CT in
neutral line, on inside portion of the terminal cover and shall be of permanent
nature. The meter terminals shall also be marked and this marking should appear in
the above diagram.
i) Software for reading, down loading meter data, as well as configuration change
activity in meter shall be as per Table 31 of ETD13(6211), normally resident in the Hand
Held Unit (HHU); Software suitable for MS Window XP or higher version. The software shall
be installed in and be compatible to all makes of the HHUs (Analogic/Sands/any other make)
and PC/Laptop as well as supplied separately in the form of floppies/CDs.
iii) The meter data should download with the speed of 9600BPS.
i) The BCS should show electrical conditions existing at the time of reading
the meter in tabular forms as well as in graphical format (Phasor diagram).
ii) All the information about energy, maximum demand and their respective
TOD register readings, billing register readings and billing history readings
should be shown in a manner which user can understand quickly,
preferably in tabular format.
iii) All the load survey data should be available in numerical as well as
graphical format. It should also be possible to view this data in daily,
weekly and monthly formats. The load survey graph should show values
where the cursor/pointer is placed for the selected or all parameters.
iv) All the information about tamper events should be accompanied with date
and time stamping along with the ‘snap-shots’ (details) of the respective
electrical conditions. This information should be displayed in the sequence
in which it happened, in cumulative format as well as in summary format.
The cumulative format should segregate a particular tamper information
and summary report shall show count of tamper occurrence and the
duration for which meter has remained under tamper condition.
There should be "user friendly" approach for viewing meter data for the
reading collected now or for the reading collected in the past. All information
about a particular consumer should be segregated and available at one place
so that locating any consumer's past data is easy. It should be possible to
locate/retrieve data on the basis of one of the following particulars:
i) Consumer ID/Number.
ii) Meter Sr. No.
iii) Date of meter reading.
iv) Location.
(e) Security:
The BCS shall have multi level password for data protection and security. The
first level shall allow the user to enter the system. The different software features
shall be protected by different passwords. The configuration of passwords shall be
user definable. The software installed on one PC shall not be copiable on to another
PC.
ii) The meter display shall have phase indicators to indicate the status of phase
voltages, which shall keep coming with every display.
iii) The meter should work accurately irrespective of phase sequence of the mains
supply.
v) The meter should remain powered up and functional even when either of any
two phases or any one-phase along with neutral is available to the meter.
vi) The meter should continue to record accurately as per prevailing electrical
conditions even if the neutral of potential supply gets disconnected.
vii) In power on mode meter shall have scroll lock facility to display any one
desired parameter continuously from display parameter for 30 minutes, which
will keep on displaying for 30 minutes or till the lock is released". Any
parameters can be locked/unlocked by continuous pressing of forward &
reverse Push button for 5 seconds.
viii) The meter should continue to function even if any spurious signals are
injected on the neutral of the meter, such as D.C signals through diodes etc.
ix) The meter reading count should increase by one digit every time the meter is
read successfully through HHU or computer or any other device and be
available at BCS end. The meter reading count should increase by one digit
every time the meter is read successfully through HHU or computer or any
other device and should be available at BCS end.
2423-Spec - 13 -
xi) The meter shall be capable of detecting condition of power-off if mains supply
is not present. It shall record such occurrence and restoration of power
failures as separate events in the meter memory with date and time stamp.
Snapshot of electrical parameters is not necessary during this condition.
xii) The meter shall have provision to be read in the absence of power through an
external /internal source as per provision of Annex G14 of IS 14697/1999 such
that it should not be possible to damage the internal circuitry of the meter by
applying any voltage on /through the device /port provided for powering up
the meter in the absence of power supply. The bidder should explain the
method adopted by them for this purpose in their offer.
xiii) The LTTVM shall record active/apparent energy in forward direction even if
one or more CT’s are reversed. The current vector direction shall always be
considered as positive(import) for the computation of 3 phase active energy,
which shall be added in the main active (import) energy register and KVAh
computation shall be based on reactive lag and lead energy.
The data should not be lost in the event of power failure and should be stored
in non-volatile memory. The non-volatile memory should retain data for a period of
2423-Spec - 14 -
not less than 10 years under un-powered condition i.e. the non-volatile memory shall
have a storage life (without use) of ten (10) years. Battery backup memory will not
be considered as NVM.
The register shall be able to record and display starting from zero, for a
minimum of 1500 hours, the energy corresponding to rated maximum current at
reference voltage and unity power factor. The register should not roll over in
between this duration.
Meter serial number shall also be programmed in to meter memory for identification
through HHU/meter reading print out. Serial No. of meter will be as under:-
“The meter shall display the required parameters as per IS: ETD 13(6211):
2010” for C-type meters.
In addition to above the meter shall also record the Name plate details,
2423-Spec - 15 -
programmable parameters (readable as profile), occurrence and restoration of
tamper events along with the parameters as per Clause No. 3.28 of this
Specification.
Detail of category wise parameters requirement suitable for specific location such as
feeder/DT metering, interface points/boundary points is given in following
tables of guidelines document enclosed as annexure: (as per IS: ETD
13(6211): 2010).
The maximum demand integration period may be set at 30 minute. Meter shall
be programmable for integration period of 15 minutes also.
(C) MD RESET
To enable local reading of meters data a DLMS compliant HHU shall be used. The
HHU shall be as per specification given in the guidelines document prepared by CEA
& CPRI. It shall be compatible to the DLMS compliant energy meters that are to be
procured/ supplied on the basis of this specification. The HHU shall be supplied by
the meter manufacturer along with the meter @ 1% of ordered quantity.
The meter shall work satisfactorily under presence of various influencing conditions
like External Magnetic Field, Electromagnetic Field, Radio Frequency Interference,
harmonic Distortion, Voltage/Frequency Fluctuations, and electromagnetic High
Frequency Fields etc. The meter should immune to any type of radio frequency
interface, harmonic distortion, voltage/ frequency fluctuations, electromagnetic high
frequency fields and abnormal voltage/ frequency generating device and shall
record the occurrence and restoration of such tamper events along with
parameters such as current, voltages, kWh, power factor, event code, date & time
etc.
i) HHU.
ii) Remote access through suitable communication network.
Minimum 200 numbers of events (occurrences & restoration with date & time)
should be available in the meter memory.
The meter shall have a test output accessible from the front and be capable of
being monitored with suitable testing equipment. The operation indicator, if fitted,
must be visible from the front. Test output device shall be provided in the form of
one common LED for kWh, kVArh and optionally kVAh with the provision of selecting
the parameter being tested. Alternatively, test output device in the form of separate
LEDs for kWh, kVArh and optionally kVAh is also acceptable.
The relation between test output and the indication on display shall comply
with the marking on the name plate (imp per Kwh and imp per KVARh or KVAh).
2423-Spec - 17 -
The bidder shall state the necessary number of pulse count(s) to ensure
measurement accuracy of at least 1/10 th of class of the meter at the different test
points.
The resolution of the test output pulse(s) should be sufficient to enable
conduction of the starting current in less than 10 minutes and accuracy test at the
lowest load with desired accuracy within 5 minutes.
The meter shall continuously monitor and calculate the average demand in
KVA during the integration period set and the maximum, out of these, shall be stored
along with date and time when it occurred in the meter memory. The maximum
registered value shall also be made available on meter-display.
The maximum demand will be computed from the main apparent energy register.
The rising demand under the current integration period should be displayed along
with the elapsed time.
The integration period shall be set as 30 minutes, on real time basis starting from
00.00 H
The principle of maximum demand calculation used by the Bidder should be
explained in the offer.
Meter shall continuously monitor and calculate the average maximum demand
of each demand interval time of 30 minutes on real time basis and maximum of
these in a calendar month shall be stored. The maximum demand shall
automatically reset at 24.00 hrs. of the last date of each calendar month for which
minimum 30 years calendar shall be programmed by the manufacturer. The
cumulative kWh should also be recorded at 24.00 hrs. On the last date of each
calendar month for previous 6 months.
The auto reset facility of MD at pre-defined date & time shall be provided. The
meter shall log on in the meter memory, average value of voltage & current for
15/30 minutes integration period, the maximum demand reset count, which should
increment by one digit every time the MD is reset.
For category “C” meter, load survey parameter shall be current-IR, current-IY,
Current-IB, block Energy-KWh and block Energy- KVAh. Load survey period
shall be 75 days with 30 minutes integration period.
Meter Serial Nos. should be printed in each page of load survey sheet.
The BCS parameters should not be editable.
2423-Spec - 18 -
The programmable parameters shall be as per table No. 31 of IS: ETD
13 (6211).
2423-Spec - 19 -
3.25 HARMONICS MEASUREMENTS:
The accuracy of the meter shall not be affected by harmonics circulating in the
system of magnitudes within permissible limits stipulated in relevant ISS/ IEC/
CBIP Standards and CEA Regulations-2004. The meter shall display Total
Energies as per IS: ETD 13(6211): 2010 and same shall be logged in
meter memory and be capable to download at BCS end through HHU.
d) CT Short (Bypass) & Current Circuit Open (Failure): The meter shall be
capable of detecting and recording occurrences and restoration of shorting
(bypassing) and opening (failure) of any one or two phases of current circuit
when the meter is connected to a 3 phase 4 wire system or 3 phase 3 wire
system. The No-load condition should not be recorded as tamper.
f) Magnetic Influences:
The meter should record the presence of abnormal external magnetic fields
along with date and time. Snapshots (numerical values) of voltage, current, power
factor and energy (kWh) readings as well as the date and time of logging of the
2423-Spec - 20 -
occurrence and restoration of all tamper events, subject to meter-memory space as
described herein under, should be logged in the meter-memory and available for
retrieving through the meter's optical port via CMRI and downloading to the BCS.
g) Cover Open Tamper – If the meter cover is opened, the meter shall log this
as tamper and shall display “Open” with date and time of such opening and
should not restore in any condition (in power on as well as power off
condition) in blinking display on the LCD along with other display parameters,
so that it is immediately noticed by the meter reader and same shall be
downloaded in CMRI.
h) High voltage and high frequency- The accuracy of the meter should not
be affected with the application of abnormal voltage/ frequency generating
device such as spark discharge of approximately 35 KV. The meter shall be
tested by feeding the output of such device(s) to meter in any of the following
manner for 10 minutes:-
The accuracy of the meter shall be checked before and after the application of
above device(s) with site conditions.
The meter shall meet the requirement of dry heat / cold / damp heat / cold /
damp heat cyclic test as per the relevant standards described in clause 3.02 of
this specification.
The tenderer should have the necessary testing facility for carrying out the
following tests: -
i. AC voltage test.
ii. Insulation resistance test.
2423-Spec - 22 -
iii. Test of limits of errors.
iv. Test of meter constant.
v. Test of starting condition.
vi. Test of no load condition.
vii. Repeatability of error test.
viii. Test for power consumption
ix. Vibration test.
x. Tamper conditions-as per purchaser specification.
xi. Shock test.
Notes: -
a) Manufacturer should possess fully computerized Meter Test Bench
system for carrying out the relevant routine/acceptance tests as well facility to
generate Test Reports for each and every meter tested.
3.35 TESTS:
The test reports/certificate/records for all type tests specified having been
successfully performed on the type of the meter offered shall be submitted with the
tender. The bidder shall clearly bring out the deviations from this specification clause
whether on account of tests or manufacturing process or features incorporated in the
meter. The tender lacking with above information and without supporting test
reports for meter meeting the requirement of tests laid in this specification are likely
to be rejected.
a) Type tests :
The Energy meter compatible with DLMS protocol offered shall be fully type
tested at any NABL accredited test laboratories as per relevant standards. The bidder
shall furnish two sets of type test reports along with the bid. The Type test reports
shall not be more than two years old from the date of opening of bid.
Beside above bidder should also submit the test report from CPRI,
Bangalore/Bhopal/ ERDA, Vadodara /government approved/ government
recognized/NABL accredited laboratory along with the bid for the latest version of the
“Indian standard on data exchange for electricity meter reading, tariff and load
control-companion specification” ETD(13)6211 released by BIS.
b) Acceptance tests :
The Supplier in the presence of the Purchaser’s representative shall carry out
all acceptance tests as stipulated in the relevant standards. The following additional
2423-Spec - 23 -
tests shall also be carried out on meters from each lot offered for inspection as per
the relevant standards on selected samples:
- Shock test.
- Vibration test.
- Magnetic Induction of External Origin, and
- Verification of tamper and fraud detection features and threshold values as per
specifications and subsequent agreement between the Supplier and Purchaser.
Note: Where testing facilities do not exist at the Supplier’s works for shock and
vibration testing as per the relevant standards, these two tests may be carried
out in accordance with the provisions of IS: 3010 with latest amendments.
c) Routine test :
All routine tests as stipulated in the relevant standards shall be carried out and
routine test certificates/reports shall be submitted to the Purchaser for approval and
also placed inside individual meter packing.
The supplier should furnish detailed write up for the procedure to be adopted
for error testing of the meters in the laboratory and at site/field.
The bidder shall furnish one sample of LT TVM conforming to this specification duly
sealed along with the routine test certificates directly in the office of the
Superintending Engineer(M&P), JVVNL Jaipur one day prior from the date of opening
of Tender, If the sample(s) are not received the bid shall be considered as Non-
responsive. In case sample meter submitted with bid don’t conform the Type tests,
Addl. Type Tests and Tamper tests of specifications/IS, the financial bid of offer shall
not be opened
One sample of LT-TVM of 0.5S class along with HHU meeting the requirements of
this specification should be furnished along with bid for checking and testing in our
Meter Testing Laboratory at Jaipur in presence of bidders representative or at
independent test laboratory, at the discretion of purchaser.
After finalization of the tender, the bidder(s) will collect their sample(s) so submitted
otherwise department does not hold itself responsible for safe custody of sample(s)
so received. The offer received without sample(s) is liable to be ignored.
The meter cover shall be ultrasonically welded with the meter base. The
sample meter to be sent along with bid may not be ultrasonically welded with the
meter base, as at the time of sample testing it has to be opened to ascertain
conformity of meter as per specification. However, before commencement of supply,
2423-Spec - 24 -
sample has to be got approved with ultrasonically welded meter by the successful
bidder.
The meter sample should be sealed with the bidder’s seal(s). The details of
logic and threshold values for various kinds of tampers as proposed and incorporated
by the bidder in their meter samples shall be furnished along with the meter
sample(s).
Tests to be conducted:
a) The successful bidder shall furnish one nos. pre commencement sample
of each type of offered tri-vector meters fully meeting the requirement
of specification directly in the office of the Superintending Engineer
(M&P), JVVNL Jaipur within one month from the date of receipt of
Purchase Order for Nigam’s approval. The samples shall be tested at
Nigam’s own lab or CPRI/NABL accredited lab, at the discretion of the
purchaser. The testing charges in case samples are sending to third
party lab, shall be borne by the supplier. The bidder shall supply the
meters only after approval of pre-commencement of sample.
b) The purchaser shall reserve the right to pick up energy meter at
random from the lot(s) offered and get the meter tested at third party
lab i.e. CPRI /NABL accredited lab at the sole discretion of the
purchaser . The supplier has no right to contest the test results of the
third party lab or for additional tests and has to replace /take corrective
action at the cost of the supplier.
It shall be responsibility of the supplier to arrange such test and
purchaser shall be inform of the date and time of conduction of tests
well in advance to enable him to witness such tests. Test charges of
the testing authority for such successful type tests shall be borne by
the purchaser and in case of unsuccessful type test, same shall be
borne by the supplier.
3.38 QUALITY ASSURANCE PLAN:
The Bidder shall invariable furnish the following information along with bid,
failing which his bid shall be liable for rejection. Information shall be separately
given for individual type of material offered.
2423-Spec - 25 -
i) Statement giving list of important raw materials, names of sub-suppliers for
the raw materials, list of standards according to which the raw materials are
tested, list of tests normally carried out on raw materials in presence of
Bidder’s representative and copies of test certificates.
ii) Information and copies of test certificates as in (i) above in respect of bought
out accessories.
iv) Level of automation achieved and list of areas where manual processing exists.
vi) List of testing equipment available with the bidder for final testing of
equipment specified and test-plant limitations, if any, vis-à-vis the type,
special acceptance and routine tests specified in the relevant standards and
this specification. These limitations shall be very clearly brought out in a
separate schedule of deviations from specified test requirements.
i) List of raw materials as well as bought out accessories and the names of
sub-suppliers selected from those furnished along with offers.
ii) Type test certificates of the raw materials and bought our accessories if
required by the purchaser.
iii) Quality assurance plan (QAP) with hold points for purchaser’s inspection.
The quality assurance plan and purchasers hold points shall be discussed
between the purchaser and bidder before the QAP is finalized.
The successful bidder shall submit the routine test certificates of bought out
accessories and central excise passes for raw material at the time of routine testing if
2423-Spec - 26 -
required by the purchaser and ensure that Quality Assurance requirements of this
specification are followed by the sub-contractors.
The Quality Assurance programme of the contractor shall consist of the quality
systems and quality plans with the following details:
i) Quality System :
- The structure of the organization.
- The duties and responsibilities assigned to staff ensuring quality of work.
- The system for purchasing, taking delivery and verification of materials.
- The system for ensuring quality workmanship.
- The system for retention of records.
- The arrangements for contractor’s internal auditing.
- A list of administration and work procedures required to achieve and verify
contract’s quality requirements. These procedures shall be made readily
available to the project manager for inspection on request.
3.39 GUARANTEE:
The supplier shall also furnish an undertaking that there shall be no drift in
the accuracy class of the meter for a minimum period of 10 years from the date of
supply.
The supplier shall arrange to provide free training at places as desired by the
purchaser for use of meter/Computer Software etc. The supplier shall provide
competent and timely after sales service support.
3.40 INSPECTION:
All acceptance tests including other special tests as given in this specification
and inspection shall be gone at the place of the manufacturer unless otherwise
especially agreed upon by the Bidder and Purchaser at the time of purchase.
The supplier shall give 15 days advance intimation to enable the purchaser to
depute his representative for witnessing the acceptance and routine tests. Material
shall be dispatched only after getting the dispatch authorization from the purchaser
or his authorized representative, after successful inspection/testing.
The bidder shall afford the inspectors representing the purchaser all
reasonable facilities without charge, to satisfy him that the equipment is being
furnished in accordance with this specification during stage inspection, if any, and
final inspection.
The recommended sampling plan and the criteria for acceptance of the lot
shall be as per Annexure-E of IS: 14697:1999 for the type of meters covered in this
specification.
3.42 PACKING:
3.43 DOCUMENTATION:
One set of routine test certificate shall accompany each dispatch consignment.
2423-Spec - 29 -
The acceptance test certificates, in case pre-despatch inspection or routine
test certificates, in cases where inspection is waived, shall be got approved from the
purchaser.
3.44 SCHEDULES:
The tenderer shall fill in the following schedules, which are part and parcel of
the tender specification and offer. If the schedules are not submitted duly filled in
with the offer, the offer shall be liable for rejection.
All deviations from the specification shall be brought out in the schedules of
deviations (Schedule VI, VII). The discrepancies, if any between the specification and
the catalogues and / or literatures submitted as part of the offer by the bidders shall
also be brought out.
Commencement period 30 days from the date of receipt of purchase order and
completion within 7 months at equal monthly rate from the date of approval of pre
commencement sample. Firm is required to furnish pre commencement sample
within 15 days of receipt of purchase order. The delay in furnishing of pre
commencement sample beyond 15 days shall be on the part of the supplier and such
delayed period shall be reduced from the stipulated delivery schedule. It will be
ensured by Nigam to convey approval of pre-commencement sample within 15 days
of receipt of sample.
Repeat orders for additional quantities, upto 50% of original ordered quantities, may
be placed by the Nigam, on the same rates, terms and conditions given in the
contract.
3.47 In addition to the above following additional features are required in the
meter:-
3.48- A committee comprising of M&P wing and IT wing will examine the
Communication capability of sample meter and CMRI with different make of
meters supplied in the Discoms as per requirement of the technical
specification at the time of approval of pre commencement sample.
Common protocol will be ensured for all required DLMS parameters and the
other non DLMS parameters of each supplier shall be able to be downloaded by their
respective software.
2423-Spec - 31 -
(b) For any further query regarding DLMS protocol refer to document IS:
ETD 13(6211): 2010 for Data Exchange for Electricity meter reading,
tariff and load control.
--------------------------
2423-Spec - 32 -
Annexure- A
Tamper Logics for LT-TVM
Persistence time: 5 Min. Restoration Time: 1 Min.
(60 Sec.)
4. CT Bypass
a. By Pass Current > 20% Ib < 10% Ib
(current in
tampered phase)
5. Current unbalance
a. Maximum current – Minimum > 30% Ib < 10% Ib
current
6. Neutral Disturbance
a. DC current injected on neutral from If meter detect removal of DC
load side by mean of electronic circuit voltage greater injection
using diodes after removal/ than 1.25 times of
disconnection of neutral. Vref.
7. Interference of Magnetic field
a. Presence of Magnetic field Magnetic field removal of
which affects magnetic field.
accurate Meter
recording.
2423-Spec - 33 -
SCHEDULE-A-I
GUARANTEED PARTICULAR FOR 3 PHASE 4 WIRE LT TRIVECTOR METER OF
ACCURACY CLASS 0.5S WITH DLMS PROTOCOL CATEGORY “C”.
7. Memory
a) Type (Non volatile or Non volatile memory
battery backed)
b) Non volatile memory Minimum 10 Years
retention time in
absence of power
2423-Spec - 37 -
8. Whether meter remains Yes, meter will
in powered up condition remain powered up
in the event of non- as long any two live
availability of any one of wires are connected
three potential and or to the meter including
neutral i.e. with any two Neutral or Not.
potentials and neutral?
9. Maximum demand
registration & load
survey capability
i. Integration period for 30 minutes, block
maximum demand in integration period.
KVA. Real Time basis
14 Whether meter is
capable of detecting
following common ways
of tampering:
tamper events?
17 Minimum number of Compartment No. 1: 40%
tampers events, which of total tamper memory for
the meter can record. the current related
Explain tamper logic. tampers.
Compartment No. 2: 40%
of total tamper memory for
the potential related
tampers .
Compartment No. 3: 20%
of total tamper memory for
the other tampers .
20 Energy measurement
details: -
a) Type of registering Electronic non-volatile
mechanism memory & LCD display.
COMPONENT SPECIFICATION
2 USE Engineering
3 Softness Hard
3. Colour of Seal:
The female portion of the Polycarbonate Seal(s) shall be available in
Clear /Red/Green colour and should be transparent (see through) type,
which shall give complete visualization of its fixing mechanism and shall
show clear indication if tampered.
a) Design : The seal shall be Double Anchor (Push Fit) type tamper
evident with double locking. There shall not be any change in size, shape or
design of the seal than the approved samples. If the seal is found different
than the approved design / shape / size, the same shall be out rightly rejected.
The double anchor should not be so soft that it can be easily pressed before
sealing, so that after pressing the seal can not be opened.
c) Serial No. of the Seal : Serial No. of the Seal shall be as per Meter
serial No. and shall be laser etched / embossed during moulding (it shall not be
screen printed ) in contrast colour on one side of capsule body (female ). The
Sr. No. shall also be laser etched / embossed on top of the male part . The laser
etched printing shall be through complete thickness of the polycarbonate.
2423-Spec - 48 -
d) Monogram : The seal shall have embossed/ laser etched printed of
monogram of JVVNL on front side and month and year of manufacture in figure
embossed on the backside. The laser etched printing should be through
complete thickness of polycarbonate.
The seal wire insert hole should be just sufficient for passing the seal wire and
hole of larger dia is discouraged.
5. General Construction :
The seal shall be capable to withstand temperature upto 147 o C without any
damage / deformation.
The seal shall be designed for a single use only and if tampered with the help
of plier, knife or any other sharp instruments, the seal shall be damaged and due to
its transparent property, the sign of internal tampering shall be easily detected. Also
once opened, it can not be re-used. The seal shall be made in such a way that, it
can be easily locked with the help of finger and thumb pressing no tools shall be
required to close the seal in the laboratory or at site. Both the parts shall be
designed in such a way that they can not be separated and the attachment shall be
flexible and shall not break. After inserting the seal wire through female part, the cap
of the male part shall be fitted in the female part in such a way that it should not
leave any space to avoid insertion of any sharp tools for opening of seal body of the
female part in hot or cold condition. The seal shall have also the following features:-
a) Tamper resistance and reliable.
b) Environmentally safe as it does not contain any lead.
c) Withstand long-term exposure to direct sunlight.
d) Required no tools for installation.
e) Transparent.
f) Heat resistance.
6. Testing :
2423-Spec - 49 -
The seals shall be inspected / tested as a acceptance test at the
manufacture’s works before dispatch in presence of authorized representative of
purchaser for the following tests:
ii) Boiling Water Test: The seal when emerged in the boiling water for two
hours there shall not be any affect on the seal and it shall remain intact
condition i.e. the seal should not become soft, but instead should turn out to
trail and easily break thus showing easily the tampering signs if it eventually
happens. Even, with the help of any sharp instrument, pulling with plier i.e.
by applying mechanical force, the male portion shall not come out from the
female part (body seal). In case, it comes out, the same shall damage the
seal, so that it can not be re-used.
iii) Pull Out Test: After locking the seal, if the male part / insert is pulled with
mechanical force with the help of plier or any other instrument, sharp
instrument etc. at normal condition, the seal should not get unlocked without
any damage and when such condition occurs, it should leave traces of
tampering.
iv) Seal Wire : In case, if someone tries to pull the seal wire and in any of the
tests as mentioned above at (ii) & (iii) in that case the male / female portion
of the seal should be damaged and the same can be seen visually being a
transparent one.
v) Chemical Test: The seals shall be kept in the concentrated acid for
minimum one hour in locked condition. The same shall remain in tact
condition and if try to unlock the seal, the same shall be damaged.
In short, if the seal is tested for any of the above tests, in no condition
the male and female part shall be separated out without affecting / damaging
the seal. In case, if they are separated, the seal shall have sufficient tamper
evident. Also, if seal wire is pulled out from the seal in any of the above tests,
it shall not come out from the seal without damaging seal.
2423-Spec - 50 -
SCHEDULE-‘A’
------------------