Ferroresonance can occur when voltage The value of the magnetizing reactance
transformer (VT) primaries are connected of the VT is a function of the flux in the
line-to-ground in a circuit that is normally iron core. The coupling capacitance of
ungrounded or that can become each phase of the system is the value of
ungrounded during certain switching capacitance between the primary phase
operations. When the VTs are connected conductor and ground. The magnetizing
line-to-ground on an ungrounded system, reactance and coupling capacitance form
the VT primary becomes a principal path a parallel circuit of capacitance (C) and
for system ground current. inductance (L) from line to ground, in
other words, an LC circuit. If the VT
Ferroresonance can occur when a system
operates in its linear magnetic range, no
transient occurs that causes a ringing
particular problem exists. However, the
current (resonance) between the
LC circuit requires only a relatively small
magnetizing reactance of the VT and
voltage transient to make the circuit ring
coupling capacitance to ground, under
at the resonant frequency of the LC
conditions in which the VT secondary
circuit. Once the circuit begins to ring
circuit is lightly loaded.
(resonate), constructive interference
IEEE 100, formally referred to as The during the oscillations causes the voltage
Authoritative Dictionary of IEEE to increase to high levels. When the
Standards Terms, contains this definition voltage reaches a sufficiently high level,
(among others): the VT magnetic circuit is driven into
saturation, causing the reactance to
"Ferroresonance...A phenomenon usually
collapse. However, the charge trapped in
characterized by overvoltages and very
the capacitance at this high voltage level
irregular wave shapes and associated
is still significant, and the capacitive
with the excitation of one or more
charge is discharged through the (low)
saturable inductors through capacitance
saturated VT reactance.
in series with the inductor."
If the VT secondary circuit is lightly
This definition elegantly describes the
loaded, there is very little resistance
phenomenon, but more importantly
(losses) and the current through the VT
gives an indication of the problem
winding can easily reach levels that will
ferroresonance poses for the system. The
damage the VT winding before the VT
overvoltages that result from
fuse interrupts. (In this respect, it should
ferroresonance will overstress the
be noted that primary fuses for VTs do
dielectric capabilities of the system and
not protect the VTs from damage by
also will likely damage the voltage
overcurrent, but are intended to separate
transformers.
the VTs from the power system so that a
Now, some more discussion of what complete power system shutdown is
actually happens during a ferroresonance avoided.)
condition.

Ferroresonance in ungrounded systems with voltage transformers


connected line-to-ground

Answers for energy.


The "classic" method to deal with this In either case, VTs must be rated for full
situation is to add resistance (R) to the line-to-line voltage.
circuit, converting it from a simple LC
Ferroresonance is an infrequent
circuit to a RLC (damped) circuit. Two
occurrence, very much influenced by
methods are commonly used to avoid
system topology and conditions. It is also
problems with ferroresonance:
influenced by the inductance of the VT
1. Connect the VTs with primary windings and the nature of system transients.
connected in grounded wye, with Thus, ferroresonance does not happen in
secondary windings connected in open every system. For those applications in
delta, with a loading resistor across the which ferroresonance is a problem,
open delta (probably most common). loading resistance in the VT secondary
The resistance value should be chosen circuit is normally sufficient to alleviate
so that dissipation during ground fault the affects of ferroresonance.
conditions is approximately 50 percent
of the continuous VA rating of a single
VT.
2. Connect the VTs with both primary and
secondary in wye, with a loading
For more information, please contact
resistor across the secondary of each
your local Siemens representative.
VT. Various references indicate that the
resistor dissipation during ground fault
conditions should be in the range of
the excitation watts of the VT, up to 50
percent of the continuous VA of a
single VT. Problems have been
reported with the lower value, and a
higher value is recommended.

Published by and copyright © 2009: For more information, contact Siemens Energy, Inc. All rights reserved.
Siemens AG +1 (800) 347-6659 E50001-E710-A121-X-4A00 Trademarks mentioned in this document are
the property of Siemens AG, its affiliates or
Energy Sector www.usa.siemens.com/energy
their respective owners.
Freyeslebenstrasse 1
91058 Erlangen, Germany Subject to change without prior notice.
The information in this document contains
Siemens Energy, Inc. general descriptions of the technical options
available, which may not apply in all cases.
7000 Siemens Road
The required technical options should therefore
Wendell, North Carolina 27591 USA be specified in the contract.

www.usa.siemens.com/energy

Вам также может понравиться