ANNEXURE-III

Scope of Supply and Technical Specifications of LED Luminaries

A. Scope of Supply
Details of LED luminaries to be supplied for illumination at Outdoor Locations
on the Offshore Drilling Rigs are given below:
Table-1
Sl Qty
Description Application Location of installation
No (Nos.)
LINEAR LED LUMINARIES
Hazardous Location 442
To replace conventional 2
Linear LED (Class1 Div 2 Group A, B,
1 X 40 W, 4 Ft Tube light
Luminaries C,D or Zone 2 Group IIC.)
luminaries
To replace conventional 2 2567
Linear LED Weather Proof, Marine
2 X 40 W, 4 Ft Tube light
Luminaries Outside .
luminaries
To replace conventional 2 345
Linear LED Weather Proof, Marine
3 X 20 W, 2 Ft Tube light
Luminaries Outside .
luminaries
FLOOD LIGHT LUMINARIES
To replace conventional Hazardous Location 383
4 LED Flood luminaries 400W Flood light (Class1 Div 2 Group A, B,
luminaries C,D or Zone 2 Group IIC.)

B. Technical Specifications for Linear LED Luminaries (Item no 1 to 3)


Following specifications indicate, the minimum technical requirement, base
line specifications and guidelines for Linear LED luminaries for illumination
at Outdoor Locations on the Offshore Drilling Rigs.
Sl No Parameter Specification
1.1 General features, mounting and environment conditions
1.1.1 Mounting Mounting bracket to be included
1.1.2 Environment Minimum Ambient Temp : 0 deg Celsius
conditions
Maximum Ambient Temp : 45 deg Celsius
Relative Humidity : upto 95%
1.1.3 General feature Information as per attached “data-sheet” (Annexure-1) to be
furnished by the bidder/ manufacturer
1.1.4 General feature High power SMD (Surface Mounted Device) / COB (Chip on Board)
LED’s to be used in the Linear LED Luminaries.
1.1.5 General feature The Linear LED luminaries offered should be of standard model
of manufacture and should be constructed of first quality virgin
material and designed in conformance with applicable standards
as stated/ required in this specifications
1.2 Technical Parameters

Tender No P48DC20001
1.2.1 Location of Hazardous Location (Class1 Div 2 Group A,B,C,D or Zone 2 Group
installation IIC.) Applicable for Sl. No.: 1 type of fitting (Table-1).
For Sl. Nos.: 2 & 3 of above Table-1, Weather Proof, Marine
Outside type.
1.2.2 Temperature Class Minimum T4* ( *applicable for Sl-No: 1 type of fitting)
1.2.3 Supply Voltage & Fittings shall be suitable for operating at 120 Volts +/- 10%,
Frequency available Single Phase AC, 60 Hz +/- 3%
on rig
1.2.4 Correlated Colour Range: 4000 K – 6000 K
Temp (CCT)
1.2.5 Luminous Efficacy in Minimum 100
Lumens/ Watt
1.2.6 CRI Minimum 80
1.2.7 Total Lumens with Minimum 5,000 for Sl-No-1 & 2 type of fittings of Table-1 above
diffuser
Minimum 2,500 for Sl-No:3 type of fittings of Table-1 above
1.2.8 Length Following is only for information purpose: Bidders are advised to
fill the dimensions of the offered fitting(s) in the attached Data
Sheet at Annexure-1;
Nominal fixture length = 4 feet (approximately) for Sl-No: 1 & 2
type of fittings of Table-1 above
Nominal fixture length = 2 feet (approximately) for Sl-No: 3 type
of fitting of Table-1 above
1.2.9 Beam Distribution 120 degrees or Medium Wide or equivalent
1.2.10 Power Factor >0.9
1.2.11 Surge Protection 4 KV as per IEC/EN61000-4-5
1.2.12 LED light colour In line with Correlated Colour Temp (CCT)
1.2.13 Ingress Protection IP 66/ NEMA 4X
1.2.14 Life expectancy Minimum 40,000 Hours
1.2.15 Warranty in years Five Years
1.3 Constructional Features, Name plate / marking details and painting:
1.3.1 Impact resistant diffuser
1.3.2 Terminal Block/ Fitting should have loop in and loop out facility or through wiring
Connection or connector as the case may be.
1.3.3 Material of fixture Manufacturer standard material Compatible for marine outside
application
1.3.4 Data Sheet Enclosed as per Annexure-1
1.3.5 Painting As per manufacturers standard practice, conforming to marine
application
Name plate / marking details:

Tender No P48DC20001
a) Manufacturer’s name or trade name
b) Type designation or Model no.
c) Rated voltage.
d) Rated Wattage
1.4 Codes and Standards, Test certificate/ Reports for LED fixtures:
Test reports from any of the laboratories approved by an accreditation body which is a signatory to
ILAC MRA (International Laboratory Accreditation Cooperation Mutual Recognition Agreement)
such as NVLAP (National Voluntary Laboratory Accreditation Program, USA or NABL (National
Accreditation Board for Testing and Calibration Laboratories, India) are to be submitted by the
bidder along with the bid.
1.4.1 (1)as per LM-79 (IESNA) for:
Total Luminous Flux
Luminous Intensity Distribution
Electrical Power Characteristics
Luminous Efficacy (Calculated)
Colour Characteristics
1.4.2 (2) as per as per LM-80 (lESNA) for lumen maintenance and LED
lifetime projections shall be made using TM-21 method.
In Situ Temperature Measurement Test (ISTMT) temperature shall
be used while generating LM-80 report and TM-21 projection.
The LED Fixture shall comply to IEC/NEC/equivalent standard
for Electro Magnetic radiation Compliance(EMC)
1.4.3 LED Make: Any reputed make. Chip manufacturer shall have LM80 & TM21
certificate from recognised lab.
1.4.4 Codes and Standards Control components defined by this specifications must have
(latest shall be requirements of latest applicable IS or its equivalent international
considered) standards, e.g. IEC/NEC/EN/BS etc. (Annexure- 3 may be
referred for broad and general standards). However, bidders are
advised to comply all applicable standards for the offered
fittings. North American product offerings as per NEC/UL
Standards shall comply to UL 1598A.
1.4.5 Hazardous location Certification for Hazardous location only: IECEx/ ATEX/ India
certification: (PESO)/ UL 844 or equivalent shall be submitted along with bid.
1.4.6 Compliance to BIS Vendors must mandatorily provide compliance to BIS Standard IS
Standards 10322 (relevant sections) for all types of Lighting Fixtures, prior
to dispatch of material *
1.5 MISCELLANEOUS:
1.5.1 Literature, manual, drawings & other relevant Documents etc –
Mounting instruction sheet shall be furnished
1.5.2 After sales service & spare, if any - as per NIT
1.5.3 Manufacturing test certificates - warranty/guarantee certificate
and other relevant test certificates listed in 1.4 of this document.

Tender No P48DC20001
1.5.4 Packing details: Shall be Sea Worthy.
The supplier shall ensure that the Goods/Equipment is securely
and adequately packed to ensure safe arrival at the destination
fully withstanding all hazards such as rough handling etc. during
transit.
Packing list is to be furnished
1.5.5 Inspection Procedure: Inspection shall be carried out in
accordance with the standards/ specifications and
Manufacturer’s standard practice by ONGC nominated Third
Party Inspection Agency at the cost of ONGC.

(*)As per the law of land, this is a must, as without which the fittings can’t be
imported. Bidders to kindly take note of the same and comply accordingly.

ANNEXURE - 1 (Data sheet for linear LED luminaire)


Sl No Description / parameter
1 Operational voltage : Volts
2 Rated Wattage : Watts
3 Light Output : Lumens
4 Luminaries Efficacy : Lumens / Watt
5 CRI :
6 CCT : K
7 Beam Distribution : degrees
8 Dimensions : mm
9 Design Life : Hours
10 IP Rating :
11 Construction features :
12 Reference Standards :
13 Approximate weight : gms
Approval/ Certifications; LM 79, LM
80, LM 80&TM21, UL1598A Marine
14 :
Outside Type, Certificates for
hazardous location.
15 LED make :

(Sign & Stamp by bidder/ Manufacturer)

Tender No P48DC20001
C. Technical Specifications: Flood Light Luminaries (Item No. 4)
Following specifications indicate, the minimum technical requirement, base
line specifications and guidelines for Flood Light Luminaries for illumination
at Outdoor Locations on the Offshore Drilling Rigs.
Sl No Parameter Specification
4.1 General features, mounting and environment conditions
4.1.1 Mounting Trunnion with mounting bracket to be included
4.1.2 Environment conditions Minimum Ambient Temp : 0 deg Celsius
Maximum Ambient Temp : 45 deg Celsius
Relative Humidity : upto 95%
4.1.3 General feature Information as per attached “data-sheet” ( Annexure-2)
to be furnished by the bidder / manufacturer
4.1.4 General feature High power SMD ( Surface Mounted Device) / COB ( Chip
on Board) LED’s to be used in the LED Flood luminaries
4.1.5 General feature The LED Flood luminaries offered should be of standard
model of manufacture and should be constructed of first
quality virgin material and designed in conformance with
applicable standards as stated / required in this
specifications
4.2 Technical Parameters
4.2.1 Location of installation Hazardous Location (Class1 Div 2 Group A,B,C,D or
Zone 2 Group IIC.)
4.2.2 Temperature Class Minimum T3
4.2.3 Rated Voltage & Frequency 120+/-10% Volts, Single Phase AC, 60 Hz ± 3%

4.2.4 Correlated Colour Temp (CCT) Range: 5000 K – 6000 K


4.2.5 Luminus Efficacy in Lumens/Watt Minimum 100
4.2.6 CRI ≥70
4.2.7 Total Lumens with clear lens Minimum 19,000
4.2.8 Beam Distribution NEMA 7 x 6 or wide or equivalent
4.2.9 Power Factor >0.9
4.2.10 Surge Protection 4 KV as per IEC/EN61000-4-5
4.2.11 Flood light colour In line with Correlated Colour Temp (CCT)
4.2.12 Ingress Protection IP 66 / NEMA 4X
4.2.13 Life expectancy Minimum 40,000 Hours
4.2.14 Warranty in years Five Years
4.3 Constructional Features , Name plate / marking details and painting:

Tender No P48DC20001
4.3.1 Impact resistant clear lens
4.3.2 Lifting Eye Bolt or suitable arrangement for lifting such as
lifting bracket etc.,
4.3.3 Material of fixture Manufacturer standard material. Compatible with
marine outside application
4.3.4 Data Sheet Enclosed as per Annexure 2
4.3.5 Painting As per manufactures standard practice, conforming to
marine application
Name plate / marking details:
a) Manufacturer’s name or trade name
b) Type designation or Model no.
c) Rated voltage.
d) Rated Wattage
4.4 Codes and Standards, Test certificate/Reports for LED fixtures:
Test reports from any of the laboratories approved by an accreditation body which is a signatory to
ILAC MRA (International Laboratory Accreditation Cooperation Mutual Recognition Agreement) such
as NVLAP (National Voluntary Laboratory Accreditation Program, USA or NABL (National Accreditation
Board for Testing and Calibration Laboratories, India) are to be submitted by the bidder along with
the bid.
4.4.1 as per LM-79 (IESNA) for:
Total Luminous Flux
Luminous Intensity Distribution
Electrical Power Characteristics
Luminous Efficacy (Calculated)
Colour Characteristics
4.4.2 (2) as per as per LM-80 (lESNA) for lumen maintenance
and LED lifetime projections shall be made using TM-21
method.
In Situ Temperature Measurement Test (ISTMT)
temperature shall be used while generating LM-80 report
and TM-21 projection.
The LED Fixture shall comply to IEC/NEC/equivalent
standard for Electro Magnetic radiation
Compliance(EMC)
4.4.3 LED Make: Any reputed make. Chip manufacturer shall have LM80
& TM21 certificate from recognised lab.
4.4.4 Codes and Standards (latest shall Control components defined by this specifications must
be considered) have requirements of latest applicable IS or its
equivalent international standards, e.g.
IEC/NEC/EN/BS etc. (Annexure- 3 may be referred for
broad and general standards). However, bidders are
advised to comply all applicable standards for the offered

Tender No P48DC20001
fittings. North American product offerings as per
NEC/UL Standards shall comply to UL 1598A.
4.4.5 Hazardous location certification: Certification for Hazardous location only: IECEx/ ATEX/
India (PESO)/ UL 844 or equivalent shall be submitted
along with bid.
4.4.6 Compliance to BIS Standards Vendors must mandatorily provide compliance to BIS
Standard IS 10322 (relevant sections) for all types of
Lighting Fixtures, prior to dispatch of material *
4.5 MISCELLANEOUS:
4.5.1 Literature, manual, drawings & other relevant
Documents etc – Mounting instruction sheet shall be
furnished
4.5.2 After sales service & spare, if any - as per NIT
4.5.3 Manufacturing test certificates - warranty/guarantee
certificate and other relevant test certificates listed in 4.4
of this document.
4.5.4 Packing details: Shall be Sea Worthy. The supplier shall
ensure that the Goods/Equipment is securely and
adequately packed to ensure safe arrival at the
destination fully withstanding all hazards such as rough
handling etc. during transit. Packing list is to be
furnished
4.5.5 Inspection Procedure: Inspection shall be carried out in
accordance with the standards/ specifications and
Manufacturer’s standard practice by ONGC nominated
Third Party Inspection Agency at the cost of ONGC.

(*) As per the law of land, this is a must, as without which the fittings can’t be
imported. Bidders to kindly take note of the same and comply accordingly.

ANNEXURE - 2 (Data sheet for flood light LED luminaire)

Sl No Description / parameter
1 Operational voltage : Volts
2 Rated Wattage : Watts
3 Light Output : Lumens
4 Luminaries Efficacy : Lumens / Watt
5 CRI :
6 CCT : K
7 Beam Distribution : degrees
8 Dimensions : mm

Tender No P48DC20001
9 Design Life : Hours
10 IP Rating :
11 Construction features :
12 Reference Standards :
13 Approximate weight : gms
Approval/ Certifications; LM 79,
LM 80, LM 80&TM21, UL1598A
14 Marine Outside Type, UL 1598 wet :
location, Certificates for hazardous
location.
15 LED make :

D. Published Indian Standards on LED or Its Equivalent International


Standards e.g. IEC/EN/BS, etc.
Annexure-3: Common to both Technical Specification given above at A & B.
Sl IS No Title
No

1 16101 General Lighting - LEDs and LED modules – Terms


and Definitions

2 16104 DC. or AC Supplied Electronic Control Gear for LED


Modules – Performance Requirements

3 16108 Photo biological Safety of Lamps and Lamp Systems

4 16107 Luminaries Performance

5 10322 (Part 5/ Section 5): 2013 Flood Lights