GE

Grid Solutions

MiCOM Agile
P342/3/4/5/6
Generator Protection Relays Comprehensive
Protection
Flexible and Reliable Integration of Protection, Control, Monitoring Comprehensive generator protection
and Measurement Functions including generator/transformer
differential protection
Extensive functionality is available to provide complete protection and control, with five
models for a wide range of applications, covering most installations from small generators 100% stator ground fault protection via a
up to sophisticated systems including generator-transformer applications. 3rd harmonic measurement or low
frequency injection techniques (depending
The variable number of opto inputs and output contacts available allow complex on model)
protection schemes to be created using the relay's powerful but easy to use 3 phase tripping with faulted phase
"Programmable Scheme Logic" (PSL). indication

A choice of industry standard protocols are available on the relay, facilitating an easier
integration into both new and existing network control systems. Advanced
The optional redundant Ethernet board reduces the cost of ownership since the relay is
Communications
natively embedded with the switch board. This reduces the amount of standalone switches Redundant Ethernet capabilities
needed, reducing the wiring, power supply and maintenance costs. Furthermore, increasing supporting IEC 62439-3 PRP and HSR
the availability rate decreases the risk allowing bumpless redundancy
of electrical outages. Industry standard communication
protocols including: IEC 61850, DNP 3.0,
Continuous Improvement IEC 60870-5-103, Modbus, and
Courier/K-Bus
Grid Solutions’ philosophy is one of continuous improvement in our products and solutions.
Our emphasis on communication in MiCOM has become a focus which secures leadership Modulated or demodulated IRIG-B or SNTP
in the digital substation. To mark this phase of evolution, the brand “P40 Agile” is applied protocol for time synchronization
to the range. P40 Agile is a mark of performance and quality, proudly available from Grid
Solutions, and only from Grid Solutions. Ease-of-Use
Programmable scheme logic via powerful
S1 Agile configuration for simplified setup
Advanced monitoring features including
circuit breaker state and condition
monitoring
Through fault monitoring, reducing costs
associated with unplanned maintenance

Imagination at work
P342/3/4/5/6 Generator Protection

Application .
The MiCOM Agile P342 is suitable for protection of generators The P346 can be used if additional generator/ transformer
which require cost effective high quality protection. Protection differential protection is required. The P343 is suitable for
includes overcurrent, ground fault, neutral voltage displacement, protection of larger or more important generators, providing
sensitive or restricted ground fault, voltage dependent 100% stator ground fault via a 3rd harmonic measuring technique,
overcurrent or underimpedance, under and overvoltage, under pole slipping and unintentional energisation at standstill
and overfrequency, reverse/forward, under/over power/VAr, field protection, in addition to the features of the P346. The P344 is
failure, negative phase sequence thermal, negative phase similar to the P343 but includes a second neutral voltage input for
sequence overcurrent and overvoltage, turbine abnormal ground fault / interturn protection. The P345 is similar to the P344
frequency, generator thermal and overfluxing, rotor ground fault, but includes 100% stator ground fault protection via a low
rate of change of frequency, check synchronising, transformer frequency injection technique.
thermal and loss of life as well as VT and CT supervision.

2
GEGridSolutions.com
P342/3/4/5/6 Generator Protection

Global Functions
The following global functions are
generally available in all devices:
4 setting groups
Metering
Event recording
Disturbance recording
Fault recording
Trip circuit supervision via PSL
Breaker state and condition monitoring
6 languages - English, French, German,
Spanish, Russian, Chinese

Main Protection Functions


The main protection functions are
autonomous and can be individually
enabled or disabled to suit a particular
application. Each protection function is
available in 4 separate setting groups
which can be individually enabled or
Figure 1 Simple function selection by mouseclick
disabled. 3-phase tripping with faulted
phase indication is provided for all
Functional Overview protection functions.

MiCOM Agile P342/3/4/5/6:


Comprehensive protection for all your generator protection requirements

GEGridSolutions.com 3
P342/3/4/5/6 Generator Protection

Generator/Transformer 100% Stator Ground Fault Phase Overcurrent


Differential (P343/4/5/6 only) 3rd Harmonic Method Four independent overcurrent stages are
3-phase generator differential protection (P343/4/5 Only) available. Each stage may be selected as
is provided to detect stator phase faults. non-directional or directional
Third harmonic neutral undervoltage (forward/reverse). All stages have definite
This can be set as either a percentage protection covers the final 15% of the
bias scheme with a dual slope time (DT) delayed characteristics, two of
stator winding and, in conjunction with the stages may also be independently set
characteristic or as a high impedance the other ground fault elements, provides
scheme. When high impedance is used, to one of nine inverse definite minimum
100% ground fault protection for the time (IDMT) curves (IEC and IEEE) or to
additional stabilising resistance and a stator. This is supervised by a 3-phase
metrosil will be required. 3-phase biased one of 4 user programmable curves.
undervoltage element. Additional
generator-transformer differential supervision using 3-phase active, reactive
protection is provided to detect phase The IDMT stages have a programmable
and apparent power can be enabled if reset timer for grading with
faults. This includes ratio and vector required. A third harmonic neutral
compensation as well as 2nd and 5th electromechanical relays and to reduce
overvoltage protection is also provided for clearance times where intermittent faults
harmonic restraint for transformer applications where the measurement is
inrush currents and overfluxing. occur. The phase fault directional
available at the terminal end of the elements are internally polarised by
Two high set differential elements are generator. The blocking features of the
provided to ensure rapid clearance of quadrature phase-phase voltages,
undervoltage element are not required for and will make a correct directional
high fault currents. this application. decision down to 0.5 V (Vn = 110/120 V) or
2.0 V (Vn = 380/440 V). A synchronous
Interturn (Split Phase) 100% Stator Ground Fault Low polarising signal is maintained for 3.2 s
Differential (P343/4/5/6 Only) Frequency injection Method after voltage collapse to ensure that the
instantaneous and time delayed
On generators with multi-turn coils and (P345 Only) overcurrent elements operate correctly
two or more windings per phase, such as
Injecting a 20 Hz voltage to detect ground for close-up 3-phase faults.
hydrogenerators, interturn (split phase)
differential may be used to detect turn to faults at the neutral point or terminals of
turn faults. The element operates as a generators is a reliable method for Standard Ground Fault
definite time overcurrent function with detecting ground faults in the entire
generator and all electrically connected The standard ground fault element
independant current setting per phase. It operates from a ground fault input
should be noted that when using this equipment. It has an advantage over the
third harmonic method in that it is connection to measure the fault current
function the generator differential in the ground path of the generator. Two
protection is not available. independent of the generator's
characteristics and the mode of independent stages are available. Both
operation. Also, protection is possible at stages have definite time (DT) delayed
Interturn (Residual generator standstill. The protection relay characteristics, the first stage may also be
Overvoltage) measures the injected 20 Hz voltage and independently set to one of ten inverse
the flowing 20 Hz current. When the definite minimum time (IDMT) curves (IEC
On generators with multi-turn or single and IEEE) or to one of 4 user
generator is operating normally, only a
turn coils interturn protection can be programmable curves.
small amount of 20 Hz current will flow as
provided by measuring the residual
a result of the stator capacitance to
voltage across the 3-phase windings. Sensitive Ground Fault
ground. When a ground fault occurs on
To prevent operation for external faults,
the generator stator windings the 20 Hz
a negative phase sequence apparent A core balance CT should be used to
current will increase. Two
power and a directional negative phase drive the sensitive ground fault function.
underresistance and one overcurrent
sequence overcurrent element can be The directionality is provided by the
stage of definite time protection are
used to interlock the residual overvoltage residual voltage.
available. The measurement circuit is also
element in PSL.
monitored with a 20 Hz undervoltage and
undercurrent element which can be used
to block the protection.

The GPM-S-G 20 Hz generator and


GPM-S-B bandpass filter modules can be
used for the 20 Hz injection.

MiCOM Agile P343/4/5:


100% stator ground fault and pole slipping protection for large machines

4
GEGridSolutions.com
P342/3/4/5/6 Generator Protection

Wattmetric Under/Overvoltage Power/Var Protection


The sensitive ground fault protection is Under/overvoltage protection may be Four definite time stages of power/VAr
also suitable for Petersen Coil grounded configured to operate from either phase- protection are provided and each stage
systems by enabling a wattmetric phase or phase-neutral voltage elements. can be independently configured to
element. This form of protection uses the Three independent undervoltage stages operate as under/over and
sensitive ground fault protection and two overvoltage stages with definite forward/reverse. The power protection
directional characteristic, but with a time elements are available for under and can be used to provide simple back-up
directional residual power threshold overvoltage protection. The first stage can overload protection (Overpower),
providing an also be configured to an inverse time or a protection against motoring (Reverse
additional constraint on operation. user programmable curve characteristic. Power), CB interlocking to prevent
overspeeding during machine shutdown
Restricted Ground Fault Under/Overfrequency (Low Forward Power) and motor loss of
load protection (Low Reverse Power).
The restricted ground fault protection may Two independent stages of overfrequency The reverse VAr protection can be
be configured either as a high impedance and four of underfrequency are provided. used to provide simple under
or low impedance biased differential. Each stage functions as a definite excitation protection.
When high impedance is used, additional time element.
stabilising resistance and a metrosil will The P342-6 relays provide a standard 3
be required. Turbine Abnormal `Quency phase power/VAr protection element
and also a single phase sensitive
Voltage Dependent Turbine abnormal frequency protection is power/VAr protection element. The P345
included to protect the turbine blade sensitive power protection can be a
Overcurrent/Underimpedance from potential damage due to prolonged single or wattmetric power/VAr element.
In order to provide backup protection for under/ over-frequency operation of The sensitive power/VAr protection can
phase faults, voltage dependant generators. Up to six frequency bands can be used with dedicated metering class
overcurrent and underimpedance be programmed, each having an CTs using the sensitive current inputs (1
protection are provided. The voltage integrating timer to record the time spent for single phase or 2 for wattmetric).
dependant overcurrent element can be within the band. The time in each band is
stored in battery backed memory so that
selected as voltage controlled or voltage
loss of auxiliary supply to the relay does
Loss Of Field
restrained overcurrent, the timing
characteristic can be set as either definite not lead to a loss of the recorded time. To detect failure of the machine
time or IDMT or to a user programmable When the time within a band has reached excitation, a two stage offset Mho
curve. The under-impedance element is the user set limit, an alarm can be raised impedance element is provided. This
a 2-stage, 3-phase non-directional to initiate investigation and maintenance. allows a small instantaneous
under-impedance element with a definite characteristic to be used to provide fast
time delay. Rate Of Change Of tripping for loss of excitation at high
power outputs, where system stability
Frequency could be affected. The second stage can
Neutral Displacement/Residual be set with a larger time delayed
Four definite time delayed stages of
Overvoltage df/dt protection are included which can characteristic to provide stable, secure
be used for loss of grid or load shedding tripping under low power conditions. A
Residual overvoltage protection is
applications. The number of frequency directional line can be used to supervise
available for detecting ground faults where
averaging cycles, number of protection the Mho characteristics. Integrating
there is an isolated or high impedance
iterations, operating mode - fixed or timers are provided to enable the
ground. The residual voltage can be
rolling window - and direction of impedance characteristic to provide time
measured from a broken delta VT, from
operation can be set to suit the delayed pole slipping protection. A power
the secondary winding of a distribution
application. factor alarm element is also available to
transformer ground at the generator
offer more sensitive protection for
neutral, or can be calculated from the 3-
unusual operating conditions, for
phase to neutral voltage measurements.
example a lightly loaded unit operating
Each stage can be set with a definite time
as an induction generator.
delay, an inverse time delay or a user
programmable curve characteristic.
The P342-6 have 2 measured and 2
calculated stages of residual overvoltage
protection.
The P344/5 have an additional neutral
voltage input and thus have an additional
2 stages of measured residual
overvoltage protection.

GEGridSolutions.com 5
P342/3/4/5/6 Generator Protection

Negative Phase Sequence Pole Slipping (P343/4/5 only) Transformer Thermal


Thermal The pole slipping protection uses the Overload, Loss of Life (LOL)
To protect against unbalanced stator variation in "apparent" impedance as The transformer thermal overload and
currents caused by external faults or seen at the generator's terminals to LoL functions are based on the IEEE
unbalanced loading, two stages of detect pole slipping. If the measured Standard C57.91-1995. Two three-stage
negative sequence protection are impedance crosses the two halves of the definite time-delayed trip elements
provided. These comprise a definite time lens characteristic and spends longer based on hot spot and top oil
alarm stage and a trip stage that operates than a specified time in each half, a pole temperature are available for
with a thermal characteristic. slip is counted. Two zones are created by transformer overload protection. A pre-
a reactance line which is used to trip alarm is also provided. Frequent
distinguish whether the impedance
Negative Phase Sequence centre of the pole slip is located in the
excesses of transformer rated current or
operation at elevated temperatures will
Overcurrent power system or in the generator. shorten the life expectancy of the
Separate counters are used to count transformer. The relay provides a
Four definite time negative phase
pole slips in the 2 zones. A setting is also transformer LoL calculation, using a
sequence overcurrent stages are
provided to determine whether the thermal model that estimates the hot
included. Each stage may be selected as
protection operates in a generating spot temperature.
non-directional or directional
mode, motoring mode or both.
(forward/reverse) and can operate for
remote phase-phase and phase-ground Blocked Overcurrent Logic
faults even with delta-star Resistance Temperature
transformers present. Detectors (RTDS) Each stage of overcurrent and ground
fault protection can be blocked by an
In order to monitor temperatures optically isolated input. This enables the
Negative Phase Sequence accurately, an option allowing overcurrent and ground fault protection
Overvoltage measurement of temperatures using up to be integrated into a blocked
to 10 platinum RTDs is available. This overcurrent busbar protection scheme.
One definite time stage of negative phase
provides an instantaneous alarm and
sequence overvoltage protection is
provided. Negative phase sequence
time delayed trip output for each RTD. Analogue (Current Loop)
overvoltage protection can be used for Inputs And Outputs (CLIO)
the detection of voltage unbalance which Generator Thermal Overload
can quickly lead to overheating and Four analogue (or current loop) inputs
To monitor the thermal state of a are provided for transducers with ranges
damage of generators. generator, a thermal replica protection is of 0-1 mA, 0-10 mA, 0-20 mA or 4-20 mA.
provided. The thermal element has a trip The analogue inputs can be used for
Overfluxing and an alarm stage. Positive and various transducers such as vibration
negative sequence currents are taken monitors, tachometers and pressure
To protect the generator or connected
into account so that any unbalance transducers. Associated with each input
transformer against overexcitation a five
condition can be detected and any there are two time delayed protection
stage V/Hz element is provided. The first
abnormal heating of the rotor can be stages, one for alarm and one for trip.
stage is a definite time alarm, the second
avoided. There are separate time Each stage can be set for 'over' or 'under'
stage can be used to provide an
constants for heating and cooling and in operation. Four analogue (or current
inverse/definite time or user
the event of a loss of auxiliary supply the loop) outputs are provided with ranges of
programmable curve time trip
thermal state is stored in non-volatile 0-1 mA, 0-10 mA, 0-20 mA or 4- 20 mA,
characteristic and stages 3/4/5 are
memory. which can alleviate the need for separate
definite time.
transducers. These may be used to feed
standard moving coil ammeters for
Unintentional Energisation analogue indication of certain measured
at Standstill (P343/4/5 only) quantities or into a SCADA using an
existing analogue RTU.
If the machine circuit breaker is closed
accidentally, when the machine is not
running, very high current will result. A
voltage supervised overcurrent scheme is
available to protect against this condition.
When the machine voltage is low, that is,
the machine is not running, an
instantaneous overcurrent element is
enabled. Timers ensure that the element
will be stable for normal voltage dips that
could occur for system faults or machine
reconnection.

6
GEGridSolutions.com
P342/3/4/5/6 Generator Protection

Rotor Ground Fault Voltage Transformer Plant Supervision


Rotor ground fault protection is used to Supervision Trip Circuit Monitoring
detect ground faults in the excitation Voltage transformer supervision (VTS) is Monitoring of the trip circuit in both
circuit of synchronous machines. The rotor provided to detect loss of one, two or breaker open and closed states can be
ground resistance is measured using an three VT signals, providing indication and realised using the programmable
external low frequency square wave inhibition of voltage dependent scheme logic.
injection, coupling and measurement unit protection elements. An optically isolated
and a P391 connected to the rotor circuit.
The measurement of the rotor resistance
input may also be configured to initiate Circuit Breaker State
the voltage transformer supervision
is passed to the P34x via a current loop alarm and blocking when used with Monitoring
output (0-20mA) on the P391 connected to miniature circuit breakers (MCBs) or An alarm will be generated if there is
one of the four current loop inputs on the other external forms of voltage a discrepancy between the open and
P34x. The rotor ground fault protection is transformer supervision. closed contacts of the circuit breaker.
only available if the relay includes the CLIO
hardware option. Two underresistance
stages of definite time protection are Current Transformer Circuit Breaker Condition
available for alarm and trip. The injection Supervision Monitoring
frequency is selectable at 0.25/0.5/1 Hz via
Current transformer supervision (CTS) is The circuit breaker condition monitoring
a jumper link in the P391.
provided to detect loss of phase CT features include:
signals and inhibit the operation of
Phase Rotation current dependent protection elements. Monitoring the number of breaker trip
CTS is provided for both sets of 3-phase operations
A facility is provided to maintain correct
operation of all the protection functions CTs in the P343/4/5/6 relays. A patented Recording the sum of the broken
even when the generator is running in a differential CTS is also provided to detect current quantity Ix, 1.0 x 2.0
reverse phase sequence. This is achieve loss of phase CT inputs. Operation of the Monitoring the breaker operating time
through user configurable settings differential protection can be blocked
during a CT failure, or alternatively Monitoring the fault frequency counter
available in four setting groups. The phase
rotation for all 3-phase currents and temporarily desensitised to avoid an
voltages can be reversed. Also, for pump unwanted trip. Circuit Breaker Control and
storage applications where 2 phases are Check Synchronising
swapped for pumping operation, the Through Fault Monitoring Circuit breaker control is available from
swapping of the phases can be emulated the front panel user interface, optically
Through faults are a major cause of
in the relay via settings for the 3-phase isolated inputs and remotely via the
currents and voltages. transformer damage and failure, stressing
substation communications. Check
the insulation and mechanical integrity.
synchronising is included to verify that
An I²t calculation based on the recorded
the generator frequency, voltage
Supervisory Functions duration and maximum current is stored
magnitude and phase angle match the
Circuit Breaker Failure for each phase. Cumulative stored
system's before allowing the generator
calculations for each phase are monitored
Protection so that the user may schedule the
breaker to be closed. Transformer vector
compensation is also included.
Two stage circuit breaker failure transformer maintenance or identify
protection may be used for tripping a need for system reinforcement to
upstream circuit breakers and/or the local reduce the fault level based on this data.
secondary trip coil. The circuit breaker
failure logic may also be initiated
externally from other protection devices if
required. The P343/4/5/6 CB fail logic can
be set to use current measurement from
any of the 2 sets of 3-phase current inputs.
Typically CB fail protection uses the CTs on
the busbar side of the generator.

Comprehensive post-fault analysis and communication options

GEGridSolutions.com 7
Programmable Scheme Logic Certification Indication IEC 61850 or DNP 3.0 is available when
the optional Ethernet or redundant
Programmable scheme logic allows the Eighteen tri-colour LEDs (P343/4/5/6) or Ethernet port is ordered. IEC 61850
user to customise the protection and 8 red LEDs (P342) are available for user offers high-speed data exchange, peer-
control functions. It is also used to programming. The P343/4/5/6 LED to-peer communication, reporting,
program the functionality of the optically colours (red, green or yellow) are driven disturbance record extraction
isolated inputs, relay outputs and LED via digital databus signals in PSL and can and time synchronisation.
indications. The programmable scheme be programmed to indicate up to four
logic may be configured using the conditions/states for example. An optional fibre-optic interface is
graphical S1 Agile PC based support G Off - Not in service available for any of the above protocols.
software, as illustrated in figure 2. G Red - CB closed An optional 2nd rear communications
G Green - CB open port with the Courier protocol is
Independent Protection G Yellow - CB not healthy available. This port is intended for
Settings Groups central settings or remote access with
Information Interfaces S1 Agile. Clock synchronisation can be
The settings are divided into two achieved using one of the protocols or
categories: protection settings and Information exchange is done via the using the IRIG-B input or using an opto
control and support settings. Four setting local control panel, the front PC input.
groups are provided for the protection interface, the main rear communications
settings to allow for different operating interface (COMM1/RP1) or an optional
second rear interface (COMM2/RP2). Redundant Ethernet Ports
conditions and adaptive relaying.
(IEC 61850/DNP 3.0)
Control Inputs Local Communication Px4x devices can be enhanced with an
The front EIA(RS)232 Courier optional redundant Ethernet board. The
The ON/OFF status of 32 control inputs redundancy is managed by the market's
can be changed manually or remotely via communication port has been designed
for use with the S1 Studio software and fastest recovery time protocols:
the communications to provide user IEC 62439-3 PRP and HSR allowing
defined control functions. is primarily for configuring the relay
settings and programmable scheme bumpless redundancy and RSTP (Rapid
logic. It is also used to locally extract Spanning Tree) protocol, offering multi-
Function Keys event, fault and disturbance record vendor interoperability. The redundant
(P343/4/5/6 only) information and can be used as a Ethernet board supports either
commissioning tool by viewing all relay modulated or demodulated IRIG-B and
Ten function keys are available for the SNTP protocol for time
measurements simultaneously.
implementing scheme control synchronisation. The redundant Ethernet
functionality. The function keys operate in board also has a watchdog relay contact
two modes, normal and toggled, and Rear Communication and an SNMP interface to alarm in case
activate associated signals in PSL that The main rear communications interface of a failure.
can easily be used to customise the supports the five protocols listed below
application. Each function key has an (selected at time of order) and is
associated tri-color LED (red, green, intended for integration with substation
yellow) allowing for clear indication of the control systems
associated function's state.
Courier/K-Bus
Modbus
IEC 60870-5-103
DNP 3.0
IEC 61850

GEGridSolutions.com
For more information please contact
IEC is a registered trademark of Commission Electrotechnique Internationale. IEEE is a registered
GE Power trademark of the Institute of Electrical Electronics Engineers, Inc.
Grid Solutions
GE and the GE monogram are trademarks of General Electric Company.

Worldwide Contact Center GE reserves the right to make changes to specifications of products described at any time without
notice and without obligation to notify any person of such changes.
Web: www.GEGridSolutions.com/contact
P34x-Brochure-EN-2018-08-Grid-GA-0648. © Copyright 2018, General Electric Company. All rights