Вы находитесь на странице: 1из 2

International

Organization for
SAFETY STANDARDS Standardization

This checklist is a summary of the provisions of ANSI All SPRAYDRENCH® safety stations (except units with self-
Z358.1-2004 relating to eye or eye/face wash and shower closing valves) meet or exceed the provisions of - DIN
combination stations. Please refer to standard for a 12899-3 : 2008 - EN 15154-1: 2008 - EN 15154-2 : 2006 - ANSI
358.1 : 2004- I.SO. 9001 - 2000.
complete listing of these provisions.

At 1520 mm above floor, the


water pattern must be at
least 508 mm in diameter.
Connect unit to
uninterruptible water supply
delivering required flow when
Shower head shall be all components are operated
between 2080 mm and simultaneously.
2500 mm above the floor.

Unit must deliver at least


11.4 litres (for eye/face wash)
or 1.5 litres (for eye wash) Valve actuator shall be easy to
for 15 minutes. locate and readily accessible
to user.

Easily located, accessible


actuator no higher than
“Hands-free” stay-open
1730 cm above floor.
valve activates in one second
or less.

Protect outlets heads from


Outlet heads should be
airborne contaminants.
positioned between 840 cm
and 1140 cm from the floor.

Shower shall provide


75.7 litres of water per
minute for 15 minutes.
Identification
Identify eye wash with highly
visible sign. Area around eye
wash shall be well-lit.

Location Water Temperature Training Maintenance


Install safety station within Water delivered by safety Instruct all employees in Activate the safety station
10 seconds of hazard, on station shall be tepid the location and proper at least weekly. Inspect
the same level as hazard (lukewarm). use of the safety station. annually for compliance
and with unobstructed with standard.
travel path.

01
International
Organization for
Standardization

SAFETY STANDARDS
All SPRAYDRENCH® eye wash units (except units with This checklist is a summary of the provisions of ANSI
self-closing valves) meet or exceed the provisions of f - Z358.1-2004 relating to emergency eye washes. Please
DIN 12899-3 : 2008 - EN 15154-1: 2008 - EN 15154-2 :
2006 - ANSI 358.1 : 2004- I.SO. 9001 - 2000. refer to standard for a complete listing of these provisions.

83mm
Use test gauge to test
water flow

Valve actuator shall be


32mm
easy to locate and readily
Protect spray heads from accessible to users.
airborne contaminants

Controlled low velocity


flow rinses both eyes and
is not injurious to user.

Unit must deliver at least “Hands-free” stay-open


11.4 litres of water per valve activates in one
minute for 15 minutes. second or less.

Connect unit to
83.8-114.3cm uninterruptible water
supply delivering at least
Outlet heads should be 11,4 l/min.
positioned between 83.8 cm
and 114.3 cm from the floor
and at least 15.3 cm from the
wall or nearest obstruction. Identification
Identify eye wash with highly
visible sign. Area around eye
wash shall be well-lit.

Location Water Temperature Training Maintenance


Install eye wash unit within Water delivered by safety Instruct all employees in Activate the safety station
10 seconds of hazard, on station shall be tepid the location and proper at least weekly. Inspect
the same level as hazard (lukewarm). use of the safety station. annually for compliance
and with unobstructed with standard.
travel path.