Вы находитесь на странице: 1из 72

Project Name: DPE JAOSB

LOAD SUMMARY
SP/ Fault
Circuit/ Feeder Rating - AMPS
S.
DB No. TP F/S MCB / Duty
No.
ISO ACB MCCB kA

1 JA-MDB TP 2500 50

MDB connected to : DEWA Transformers Total connected load

Contractor :
Type of meter (Rating of incomer): (1) Upto 60 A
(1 Phase)
LOAD DISTRIBUTION SCHEDULE

Owner: DUBAI PETROLEUM

PVC / XLPE Cable Size ECC Connected Load kW


2/3/4C Size-1C Y - Ph B - PH TOTAL
SWA / PVC 2/4 x 1C R - Ph DF
mm2 mm2 mm2 kW kW kW kW
0.00 0.00 0.00 0.00

BY DEWA 0.00 0.80

Total connected load per phase 0.00 0.00 0.00 0.00

Total Connected Load :

Total of MDB Maximum Demands:

Tel : Fax :
(2) Upto 100 A (3) 125 - 160 A
(3 Phase)
Plot No. 513 - 0116 SAIH SHUAIB 1

Proposed Type & No of


Max. kWh meters
Demand 1 - Ph 3 - Ph 3 - Ph
LV/HV Remarks
kW (1) (2) (3) CT (4)
0.00

0.00 1 2400/5 A CT METER

0.00 1 Total

.00 kW

.00 kW

(4) LV CT….../…... 5 A / HV CT……/…...A


Project Name: LEGOLAND DUBAI - THEME PARK

LOAD SUMMARY
SP/ Fault
Circuit/ Feeder Rating - AMPS
S.
DB No. TP F/S MCB / Duty
No.
ISO ACB MCCB kA

1 JA-MDB TP 2500 50

MDB connected to : DEWA Transformers Total connected load

Contractor :
Type of meter (Rating of incomer): (1) Upto 60 A
(1 Phase)
LOAD DISTRIBUTION SCHEDULE
RK
Owner: DUBAI PETROLEUM

PVC / XLPE Cable Size ECC Connected Load kW


2/3/4C Size-1C Y - Ph B - PH TOTAL
SWA / PVC 2/4 x 1C R - Ph DF
mm2 mm2 mm2 kW kW kW kW
0.00 0.00 0.00 0.00

BY DEWA 0.00 0.80

Total connected load per phase 0.00 0.00 0.00 0.00

Total Connected Load :

Total of MDB Maximum Demands:

Tel : Fax :
(2) Upto 100 A (3) 125 - 160 A
(3 Phase)
Plot No. 513 - 0116 SAIH SHUAIB 1

Proposed Type & No of


Max. kWh meters
Demand 1 - Ph 3 - Ph 3 - Ph
LV/HV Remarks
kW (1) (2) (3) CT (4)
0.00

0.00 1 2400/5 A CT METER

0.00 1 Total

.00 kW

.00 kW

(4) LV CT….../…... 5 A / HV CT……/…...A


S/N Distirbution board description PTCL PMDL ITCL IMD
1 JA-OSMDB 171.1 136.84 308.98 247.18
2 JA-WSMDB 212.99 170.392 384.74 307.79
3 JA-YSMDB 194.5 155.6 351.34 281.07
4 JA-JTSMDB 99.35 79.48 179.46 143.57
S/N Distirbution board description PTCL PMDL ITCL IMD
1 JA-OBDB-1
2 JA-OBDB-2
3 JA-OBDB-3
4 JA-OBDB-4
5 JA-WHDB-1
6 JA-WHDB-2
7 JA-WHDB-3
8 JA-WHDB-4
9 JA-WHDB-5
10 JA-JTDB-1
11 JA-JTDB-2
12 JA-JTDB-3
13 JA-YRDB-1
14 JA-YRDB-2
15 JA-YRDB-3
16
17
18
19
20
21
22
23
Project Name: DPE JAOSB
MSB Ref : JA-MDB
Fed From: SUBSTATION TRANSFORMER (JF-173)

SP/ Fault
Circuit/ Feeder Rating - AMPS
S. DB No. TP F/S MCB / Duty
No.
ISO ACB MCCB kA
INCOMER: 4P 2500 50
MOB:GENERATOR 4P 2500 50
OUTGOINGS:
1 JA-OSMDB TP 100 35
2 JA-WSMDB TP 100 35
3 MCC-OW TP 100 35
4 JA-YSMDB TP 100 35
5 JA-JTSMDB TP 600 35
6 Chiller 1 TP 275 35
7 Chiller 2 TP 275 35
8 Chiller 3 TP 275 35
9 JA-ATS TP 400 35
10 JA-Fpump TP 300 35
11 Capacitor Bank TP 800 50

MDB connected to : 1500 KVA Transformer Total connected

Max demand (3 PH) : 564.00 kW

Contractor :
Type of meter (Rating of incomer): (1) Upto 60 A
(1 Phase)
LOAD DISTRIBUTION SCHEDULE

Owner: DUBAI PETROLEUM

PVC / XLPE Cable Size ECC Connected Load kW


Size-1C B - PH TOTAL
SWA / PVC 2/4 x 1C 2/3/4C R - Ph Y - Ph
mm2 mm2 mm2 kW kW kW kW
BY DEWA 188.00 188.00 188.00 564.00
BY DEWA

XLPE/SWA/PVC 0.00
XLPE/SWA/PVC 0.00
XLPE/SWA/PVC 0.00
XLPE/SWA/PVC 0.00
FIRE RATED 0.00
XLPE/SWA/PVC 46.00 46.00 46.00 138.00
XLPE/SWA/PVC 46.00 46.00 46.00 138.00
XLPE/SWA/PVC 46.00 46.00 46.00 138.00
XLPE/SWA/PVC
XLPE/SWA/PVC 1-300 150 50.00 50.00 50.00 150.00
XLPE/SWA/PVC 2-300 2-150 --- --- --- ---

Total connected load per phase 188.00 188.00 188.00 564.00

Total connected load (3 PH)

Tel : Fax :
(2) Upto 100 A (3) 125 - 160 A
(3 Phase)
Plot No. B56CD JAFZA
MSB Location:

Proposed Type & No of


kWh meters
1 - Ph 3 - Ph 3 - Ph LV/HV Remarks
(1) (2) (3) CT (4)
1 2400/5 A

6-601-ATS-EMDPA

SUB STATION-DB

350 kVAR

1 Total

564.00 kW

(4) LV CT….../…... 5 A / HV CT……/…...A


LOAD D
Project Name: LEGOLAND DUBAI - THEME PARK
MSB Ref : SMDB-6-601 Owne
Fed From: MDB-6-601-MSB Consult

SP/ Fault
Circuit/ Feeder Rating - AMPS PVC / XLPE
S.
DB No. TP F/S MCB / Duty SWA / PVC
No.
ISO ACB MCCB kA
1 INCOMER: TP 400 XLPE/SWA/PVC

OUTGOINGS:
1 JA-OBDB-1 TP 100 25 XLPE/SWA/PVC
2 JA-OBDB-2 TP 100 25 XLPE/SWA/PVC
3 JA-OBDB-3 TP 100 25 XLPE/SWA/PVC
4 JA-OBDB-4 TP 100 25 XLPE/SWA/PVC
5
6

MDB connected to : 1500 KVA Transformer Total connected load per phas

Max demand (3 PH) : 68.80 kW at 0.80 Diversity

Contractor :
Type of meter (Rating of incomer): (1) Upto 60 A
(1 Phase)
LOAD DISTRIBUTION SCHEDULE
Plot No. 513 - 0116 SAIH SHUAI
Owner: MERAAS ESTATES (LLC)
Consultants: EXP/KLING Consultants

Proposed Type & No of


Cable Size ECC Connected Load kW
TOTAL kWh meters
2/4 x 1C 2/3/4C Size-1C R - Ph Y - Ph B - PH 1 - Ph 3 - Ph 3 - Ph
mm2 mm2 mm2 kW kW kW kW (1) (2) (3)
4c-300 1c-150 28.53 29.23 28.23 85.99

4c-35 1c-25 13.85 13.45 13.35 40.65


4c-35 1c-25 14.63 15.78 14.88 45.30
4c-36 1c-26 0.05 0.00 0.00 0.05
4c-37 1c-27 0.00 0.00 0.00 0.00

l connected load per phase 28.53 29.23 28.23 85.99

Total Connected Load (3 PH) 85.99 kW

Tel : Fax :
(2) Upto 100 A (3) 125 - 160 A (4) LV CT….../…... 5 A
(3 Phase)

T.C.L. 85.99 KW
Diversity Factor (DF) = 0.9 (90% used) 0.8
Max Demand = 68.79544 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 68.79544 x 1.732 x 0.8 x 400
= 124.1257 Amps
Plus 25% as safety factor
= 124.1257 x 1.25
= 155.1572 Amps

Standard Main Isolator Size = 400A, 4P


Main Feeder Cable = 1 x 4C x 300mm^2, XLPE/SWA/PVC
1 x 1C x 150mm^2 PVC/PVC, Y/G E
513 - 0116 SAIH SHUAIB 1

No of
meters
LV/HV Remarks
CT (4)

Total

/ HV CT……/…...A

(3) x Cos Ø x V
x 1.732 x 0.8 x 400

300mm^2, XLPE/SWA/PVC, Cu
150mm^2 PVC/PVC, Y/G Earth Cable
LOAD DISTRIBUTION SCHEDULE
Project name: DUBAI PETROLEUM
Panel Ref : Owner: DUBAI PETROLEUM ESTABLISHMEN
Fed From:

MCB CCT ECC


RATING OF

RATING OF
INCOMER

RTG. Wire Wire


ELCB

SL NO. CIR. NO. ROOM / AREA


(A) (mm2) (mm2)

1 R1 20 2.5 2.5 Lighting O - (153, 155, 161, 167)

2 Y1 20 2.5 2.5 Lighting O - (118, 119, 120, 144, 148, 151, 152, 167, 175)

3 B1 20 2.5 2.5 Lighitng O - 101

4 R2 20 2.5 2.5 Lighting O - (102, 103, 104, 105, 146)


40A 4P
100MA 5 Y2 20 2.5 2.5 Lighting O - (106, 107, 108, 145, 147, 150)
ELCB-1
6 B2 20 2.5 2.5 Lighting O - (109, 110, 111, 112)

7 R3 20 2.5 2.5 Lighting O - (113, 172, 173, 175)

8 Y3 20 2.5 2.5 Lighitng O - (115, 168, 169, 171)

9 B3 20 2.5 2.5 Lighting O - (116, 117, 151)

10 R4 20 4 4 Receptacle O - (101, 144)

11 Y4 20 4 4 Receptacle O - (102, 103, 104)

12 B4 20 4 4 Receptacle O - (105, 106, 107)

13 R5 20 4 4 Receptacle O - (118, 119, 120)


40A 4P
100MA 14 Y5 20 4 4 Receptacle O - (116, 117, 151)
ELCB-1
15 B5 20 4 4
100A TPN ISOLATOR

Receptacle O - (115, 151, 168)

16 R3 20 4 4 Receptacle O - (144, 145)

17 Y3 20 4 4 Receptacle O - (146, 147, 148)

18 B3 20 4 4 Receptacle O - (108, 109, 110)

19 R4 20 4 4 Receptacle O - 149

20 Y4 20 4 4 Receptacle O - (111, 150, 152)

21 B4 20 4 4 Receptacle O - (112, 113, 173)

22 R5 30 6 6 Receptacle O - 146
40A 4P
100MA 23 Y5 20 4 4 Receptacle O - 147
ELCB-1
24 B5 20 4 4 Receptacle O - 150

25 R3 20 4 4 Receptacle O - 172

26 Y3 20 4 4 Receptacle O - 172

27 B3 20 4 4 Lighting Office 2nd Floor


28 R4 30 6 6 Receptacle 1st Floor

29 Y4 20 4 4 Receptacle O - 147

40A 4P 30 B4 20 4 4 Temp. Contr. VAV 1-4, 13-17


100MA
ELCB-2 31 R5 Spare

32 Y5 Spare

33 B5 20 4 4 Extract Fans PV 4 & 6

CABLE SIZE : 1X4C-35mm2 XLPE/SWA/CU/PVC CABLE + 1X1C-16mm2 PVC ECC Y/G


RIBUTION SCHEDULE
Plot No. B56CD JAFZA
ETROLEUM ESTABLISHMENT Panel Location:

CONNECTED LOADS / POINTS LOAD (Watts)


Watt /
Unit

PUMP
Outlet
13A 15A EX.

Flex.
LTG
S.O.
IK
S.O.
FCU
FAN
R Y B

6 150 900

12 150 1800

15 150 2250

12 150 1800

14 150 2100

12 150 1800

9 150 1350

9 150 1350

10 150 1500

8 200 1600

8 200 1600

8 200 1600

8 200 1600

8 200 1600

8 200 1600

4 200 800

4 200 800

4 200 800

4 200 800

6 200 1200

4 200 800

4 1000 4000

1 200 200

1 200 200

5 200 600

3 200 1000

4 150 600
9 200 400

2 200 1800

8 200 1600

2 300 600

13850 13450 13350

TOTAL 40.65

T.C.L. 40.65 KW
Diversity Factor (DF) = 0.9 (90% used) 0.9
Max Demand = 36.585 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø
= 36.585 x 1.732 x 0.8 x 400
= 66.0093 Amps
Plus 25% as safety factor
= 66.0093 x 1.25
= 82.5116 Amps

Standard Main Isolator Size = 100A, 4P


Main Feeder Cable = 1 x 4C x 35mm^2, XLPE/SWA/PVC, Cu
1 x 1C x 16mm^2 PVC/PVC, Y/G Earth Cable
JAFZA

Remarks
40650

kW

er Cable of LPA Warehouse


(3) x Cos Ø x V
x 1.732 x 0.8 x 400

x 35mm^2, XLPE/SWA/PVC, Cu
x 16mm^2 PVC/PVC, Y/G Earth Cable
LOAD DISTRIBUTION SCHEDULE
Project name: DUBAI PETROLEUM
Panel Ref : Owner: DUBAI PETROLEUM ESTABLISHMEN
Fed From:

MCB CCT ECC


RATING OF

RATING OF
INCOMER

RTG. Wire Wire


ELCB

SL NO. CIR. NO. ROOM / AREA


(A) (mm2) (mm2)

1 R1 20 2.5 2.5 Lighting O - (133, 134, 135)

2 Y1 20 2.5 2.5 Lighting O - (130, 131, 132, 157)

3 B1 20 2.5 2.5 Lighting O - (156, 162)

4 R2 20 2.5 2.5 Lighting O - (128, 128, 154, 159, 160)


40A 4P
100MA 5 Y2 20 2.5 2.5 Lighting O - (125, 126, 127)
ELCB-1
6 B2 20 2.5 2.5 Lighting O - (123, 124, 158, 163, 164, 165)

7 R3 20 2.5 2.5 Lighting O - (137, 138, 139)

8 Y3 20 2.5 2.5 Lighitng O - (140, 141, 142, 143)

9 B3 20 2.5 2.5 Lighting O - (121, 122)

10 R4 20 2.5 2.5 Lighting Stairway

11 Y4 20 2.5 2.5 Lighting Office 1st Floor

12 B4 20 2.5 2.5 Lighting Corridor

13 R5 20 4 4 Receptacle O - (121, 122)


40A 4P
100MA 14 Y5 20 4 4 Receptacle O - (123, 124, 125)
ELCB-2
100A TPN ISOLATOR

15 B5 20 4 4 Receptacle O - (126, 127, 128)

16 R6 20 4 4 Receptacle O - (137, 138, 139)

17 Y6 20 4 4 Receptacle O - (139, 140, 141)

18 B6 20 4 4 Receptacle O - (142, 160, 161)

19 R7 20 4 4 Receptacle O - (129, 130, 131)

20 Y7 20 4 4 Receptacle O (135, 155)

21 B7 20 4 4 Receptacle O - (132, 133, 134)

22 R8 20 4 4 Receptacle O - (143, 164, 165, 167)


40A 4P
100MA 23 Y8 20 4 4 Receptacle O - 166 EWC
ELCB-3
24 B8 20 4 4 Receptacle O - (156, 157)

25 R9 20 4 4 Receptacle O - (162, 163)

26 Y9 20 4 4 Extract Fans PV 1, 3 & 5

27 B9 20 4 4 Temp. Contr. VAV O - 7, 8, 9, 10


28 R10 20 4 4 Receptacle Telephone Room

29 Y10 20 6 6 Receptacle O - 157 Xerox

40A 4P 30 B10 20
30MA
ELCB-4 31 R11 20 6 6

32 Y11 20 6 6 Water Heater

33 B11 20 6 6
CABLE SIZE : 1X4C-35mm2 XLPE/SWA/CU/PVC CABLE + 1X1C-16mm2 PVC ECC Y/G
RIBUTION SCHEDULE
Plot No. B56CD JAFZA
ETROLEUM ESTABLISHMENT Panel Location:

CONNECTED LOADS / POINTS LOAD (Watts)


Watt /
Unit

PUMP
Outlet
13A 15A EX.

Flex.
LTG
S.O.
IK
S.O.
FCU
FAN
R Y B

9 150 1350

9 150 1350

14 150 2100

8 150 1200

8 150 1200

11 150 1650

11 150 1650

11 150 1650

8 150 1200

10 150 1500

3 150 450

12 150 1800

6 200 1200

8 200 1600

8 200 1600

6 200 1200

6 200 1200

8 200 1600

8 200 1600

5 200 1000

8 200 1600

8 200 1600

7 200 1400

5 200 1000

8 200 1600

2 300 600

5 200 1000
2 200 400

4 1000 4000

1333

4000 1333

1333

14633 15783 14883

TOTAL 45.30

T.C.L. 45.30 KW
Diversity Factor (DF) = 0.9 (90% used) 0.9
Max Demand = 40.7691 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø
= 40.7691 x 1.732 x 0.8 x 400
= 73.5586 Amps
Plus 25% as safety factor
= 73.5586 x 1.25
= 91.9482 Amps

Standard Main Isolator Size = 100A, 4P


Main Feeder Cable = 1 x 4C x 35mm^2, XLPE/SWA/PVC, Cu
1 x 1C x 16mm^2 PVC/PVC, Y/G Earth Cable
JAFZA

Remarks
45299

kW

er Cable of LPA Warehouse


(3) x Cos Ø x V
x 1.732 x 0.8 x 400

x 35mm^2, XLPE/SWA/PVC, Cu
x 16mm^2 PVC/PVC, Y/G Earth Cable
LOAD D
Project Name: DPE JAOSB
MSB Ref : JA-WSMDB Owner: DUB
Fed From: JA-MDB

SP/ Fault
Circuit/ Feeder Rating - AMPS PVC / XLPE
S.
DB No. TP F/S MCB / Duty SWA / PVC
No.
ISO ACB MCCB kA
1 INCOMER: TP 400 XLPE/SWA/PVC

OUTGOINGS:
1 LPA Warehouse TP 160 25 XLPE/SWA/PVC
2 LPB Warehouse TP 100 25 XLPE/SWA/PVC
3
4
5
6

MDB connected to : 1500 KVA Transformer Total connected load per phas

Max demand (3 PH) : 88.16 kW at 0.80 Diversity

Contractor :
Type of meter (Rating of incomer): (1) Upto 60 A
(1 Phase)
LOAD DISTRIBUTION SCHEDULE
Plot No.:
Owner: DUBAI PETROLEUM ESTABLISHMENT

Proposed Type & No of


Cable Size ECC Connected Load kW
TOTAL kWh meters
2/4 x 1C 2/3/4C Size-1C R - Ph Y - Ph B - PH 1 - Ph 3 - Ph 3 - Ph
mm2 mm2 mm2 kW kW kW kW (1) (2) (3)
4c-300 1c-150 36.48 37.40 36.31 110.20

4c-70 1c-35 21.00 20.90 20.85 62.75


4c-35 1c-25 15.48 16.50 15.46 47.45
0.00
0.00

l connected load per phase 36.48 37.40 36.31 110.20

Total connected load (3 PH) 110.20 kW

Tel : Fax :
(2) Upto 100 A (3) 125 - 160 A (4) LV CT….../…... 5 A
(3 Phase)

T.C.L. 110.20 KW
Diversity Factor (DF) = 0.9 (90% used) 0.8
Max Demand = 88.156 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 88.156 x 1.732 x 0.8 x 400
= 159.0574 Amps
Plus 25% as safety factor
= 159.0574 x 1.25
= 198.8218 Amps

Standard Main Isolator Size = 400A, 4P


Main Feeder Cable = 1 x 4C x 300mm^2, XLPE/SWA/PVC
1 x 1C x 150mm^2 PVC/PVC, Y/G E
B56CD JAFZA NORTH

No of
meters
LV/HV Remarks
CT (4)

Total

/ HV CT……/…...A

(3) x Cos Ø x V
x 1.732 x 0.8 x 400

300mm^2, XLPE/SWA/PVC, Cu
150mm^2 PVC/PVC, Y/G Earth Cable
LIGHTING CONTROL PANEL SCHED
Project name: DPE JAOSB
Panel Ref : Owner: DUBAI PETROLEUM ESTABLISHMENT
Fed From:

MCB CCT ECC


RATING OF

RATING OF
INCOMER

RTG. Wire Wire


ELCB

SL NO. CIR. NO. AREA / LOAD SERVED


(A) (mm2) (mm2)

1 R1 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

2 Y1 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

3 B1 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

4 R2 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves


40A 4P
100MA 5 Y2 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves
ELCB-1
6 B2 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

7 R3 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

8 Y3 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

9 B3 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

10 R4 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

11 Y4 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

12 B4 20 4 2.5 Warehouse - Storage Rack "C" Bin Shelves

13 R5 20 4 2.5 Warehouse - Cool Storage Room Bin Shelves


40A 4P
100MA 14 Y5 20 4 2.5 Warehouse - Cool Storage Room Bin Shelves
ELCB-2
15 B5 20 4 2.5 Warehouse - Cool Storage Room Bin Shelves

16 R6 20 4 2.5 Warehouse - Cool Storage Room Bin Shelves


160A TPN ISOLATOR

17 Y6 20 4 2.5 Warehouse - Cool Storage Room Bin Shelves

18 B6 20 4 2.5 Warehouse - Cool Storage Room Bin Shelves

19 R4 20 10 2.5 Lighting Outdoor Street Lights

20 Y4 20 4 2.5 Lighting Elect Rm and Chiller Yard

21 B4 20 10 2.5 Lighting Outdoor Street Lights

22 R5 20 4 2.5 Receptacle Warehouse


40A 4P
100MA 23 Y5 20 4 2.5 Receptacle Warehouse Cool Storage Room
ELCB-2
24 B5 20 4 2.5 Receptacle Maintenance

25 R6 20 10 2.5 Lighting Outdoor Street Lights

26 Y6 20 4 2.5 Lighting Outdoor Street Lights

27 B6 20 2.5 2.5 Extract Fans PV 2 and 7


28 R4 20 4 2.5 Receptacle Maintenance Corridor

29 Y4 20 4 2.5 Receptacle Safety Office

30 B4 20 4 2.5 Receptacle Telephone Room

31 R5 20 4 2.5 Spare
40A 4P
100MA 32 Y5 20 4 2.5 Spare
ELCB-2
33 B5 20 2.5 2.5 Lightng Warehouse Office

34 R6 20 4 2.5 Receptacle EWC

35 Y6 20 2.5 2.5 Lightng Warehouse Office

36 B6 20 2.5 2.5 Lightng Warehouse Office

CABLE SIZE : 1X4C-25mm2 XLPE/SWA/CU/PVC CABLE + 1X1C-16mm2 PVC ECC Y/G


G CONTROL PANEL SCHEDULE
Plot No. B56CD JAFZA NORTH
ROLEUM ESTABLISHMENT Panel Location:
Panel Type:

CONNECTED
LOADS LOAD (Watts)
/ POINTS WATT/
ZONE TYPE
UNIT
Remarks
LTG R Y B

F 24 100 2400

F 24 100 2400

F 22 100 2200

F 20 100 2000

F 19 100 1900

F 19 100 1900

F 19 100 1900

F 19 100 1900

F 19 100 1900

F 18 100 1800

F 18 100 1800

F 18 100 1800

F 24 100 2400

F 27 100 2700

F 24 100 2400

F 24 100 2400

F 27 100 2700

F 24 100 2400

31 100 3100

F 17 100 1700

21 100 2100

10 125 1250

8 125 1000

10 125 1250

21 100 2100

11 100 1100

4 125 500
10 125 1250

12 125 1500

F 0 100 0

F 1 150 150

F 0 100 0

F 20 100 2000

F 2 125 250

F 22 100 2200

F 24 100 2400

PVC ECC Y/G 21000 20900 20850 62750


TOTAL 62.75 kW

T.C.L. 62.75 KW
Diversity Factor (DF) = 0.9 (90% used) 0.9
Max Demand = 56.475 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 56.475 x 1.732 x 0.8 x 400
= 101.896 Amps
Plus 25% as safety factor
= 101.896 x 1.25
= 127.37 Amps

Standard Main Isolator Size = 160A, 4P


Main Feeder Cable = 1 x 4C x 70mm^2, XLPE/SWA/PVC, Cu
1 x 1C x 35mm^2 PVC/PVC, Y/G Earth Cable
LIGHTING CONTROL PANEL SCHE
Project name: DPE JAOSB
Panel Ref : Owner: DUBAI PETROLEUM ESTABLISHMENT
Fed From:

MCB CCT ECC


RATING OF

RATING OF
INCOMER

RTG. Wire Wire


ELCB

SL NO. CIR. NO. AREA / LOAD SERVED


(A) (mm2) (mm2)

1 R1 20 4 2.5 Lighting Warehouse Storage Rack "I"

2 Y1 20 4 2.5 Lighting Warehouse Storage Rack "I"

3 B1 20 4 2.5 Lighting Warehouse Storage Rack "I"

4 R2 20 2.5 2.5 Lighting Warehouse Storage Rack "I"


40A 4P
100MA 5 Y2 20 2.5 2.5 Lighting Warehouse Storage Rack "I"
ELCB-1
6 B2 20 2.5 2.5 Lighting Warehouse Storage Rack "I"

7 R3 20 4 2.5 Lighting Warehouse Storage Rack "I"

8 Y3 20 4 2.5 Lighting Warehouse Storage Rack "I"

9 B3 20 4 2.5 Lighting Warehouse Storage Rack "I"

10 R4 20 4 2.5 Lighting Warehouse Storage Rack "I"

11 Y4 20 4 2.5 Lighting Warehouse Storage Rack "I"

12 B4 20 4 2.5 Lighting Warehouse Storage Rack "I"

13 R5 20 4 2.5 Lighting Warehouse Storage Rack "I"


40A 4P
100MA 14 Y5 20 4 2.5 Lighting Warehouse Storage Rack "I"
ELCB-2
15 B5 20 4 2.5 Lighting Warehouse Storage Rack "I"

16 R6 20 2.5 2.5 Lighting Warehouse Storage Rack "I"


63A TPN ISOLATOR

17 Y6 20 2.5 2.5 Warehouse - Cool Storage Room Bin Shelves

18 B6 20 2.5 2.5 Warehouse - Cool Storage Room Bin Shelves

19 R4 20 4 2.5 Lighting Outdoor Street Lights

20 Y4 20 4 2.5 Lighting Elect Rm and Chiller Yard

21 B4 20 4 2.5 Lighting Outdoor Street Lights

22 R5 20 4 2.5 Receptacle Warehouse


40A 4P
100MA 23 Y5 20 4 2.5 Receptacle Warehouse Cool Storage Room
ELCB-2
24 B5 20 4 2.5 Receptacle Maintenance

25 R6 20 2.5 2.5 Lighting Outdoor Street Lights

26 Y6 20 2.5 2.5 Lighting Outdoor Street Lights

27 B6 20 2.5 2.5 Extract Fans PV 2 and 7


28 R4 20 2.5 2.5 Receptacle Maintenance Corridor

29 Y4 20 2.5 2.5 Receptacle Safety Office

30 B4 20 2.5 2.5 Receptacle Telephone Room

31 R5 20 2.5 2.5 Spare


40A 4P
100MA 32 Y5 20 2.5 2.5 Spare
ELCB-2
33 B5 20 2.5 2.5 Lightng Warehouse Office

34 R6 20 2.5 2.5 Receptacle EWC

35 Y6 20 2.5 2.5 Lightng Warehouse Office

36 B6 20 2.5 2.5 Lightng Warehouse Office

CABLE SIZE : 1X4C-25mm2 XLPE/SWA/CU/PVC CABLE + 1X1C-16mm2 PVC ECC Y/G


G CONTROL PANEL SCHEDULE
Plot No. B56CD JAFZA NORTH
ROLEUM ESTABLISHMENT Panel Location:
Panel Type:

CONNECTED
LOADS LOAD (Watts)
/ POINTS WATT/
ZONE TYPE
UNIT
Remarks
LTG R Y B

DL 9 207 1863

F 8 207 1656

F 8 207 1656

F 7 207 1449

F 8 207 1656

F 9 207 1863

F 7 207 1449

F 8 207 1656

F 8 207 1656

F 8 207 1656

F 8 207 1656

F 8 207 1656

F 8 207 1656

F 8 207 1656

F 7 207 1449

F 20 100 2000

F 21 100 2100

F 16 100 1600

4 207 828

F 5 207 1035

10 125 1250

1 1333 1333

1 1333 1333

1 1333 1333

12 125 1500

8 125 1000

10 125 1250
1 50 50

15 100 1500

F 2 125 250

F 1 1700 1700

F 10 125 1250

F 12 125 1500

F 0 125 0

F 0 125 0

F 0 125 0

PVC ECC Y/G 15484 16498 15463 47445


TOTAL 47.45 kW

T.C.L. 47.45 KW
Diversity Factor (DF) = 0.9 (90% used) 0.9
Max Demand = 42.7005 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 42.7005 x 1.732 x 0.8 x 400
= 77.043339 Amps
Plus 25% as safety factor
= 77.043339 x 1.25
= 96.304173 Amps

Standard Main Isolator Size = 100A, 4P


Main Feeder Cable = 1 x 4C x 35mm^2, XLPE/SWA/PVC, Cu
1 x 1C x 25mm^2 PVC/PVC, Y/G Earth Cable
M
Project Name:
MSB Ref :
Fed From:

SP/ Fault
Circuit/ Feeder Rating - AMPS PVC / XLPE
S.
DB No. TP F/S MCB / Duty SWA / PVC
No.
ISO ACB MCCB kA
1 INCOMER: TP 125 XLPE/SWA/PVC

OUTGOINGS:
1 CHWP 1 TP 30 25 XLPE/SWA/PVC
2 CHWP 2 TP 30 25 XLPE/SWA/PVC
3 CHWP 3 TP 30 25 XLPE/SWA/PVC
4 OBAHU1 TP 20 16 XLPE/SWA/PVC
5 OBAHU2 TP 20 16 XLPE/SWA/PVC
6 WHAHU1 TP 20 16 XLPE/SWA/PVC
7 WHAHU2 TP 20 16 XLPE/SWA/PVC
8 WHAHU3 TP 20 16 XLPE/SWA/PVC
9 WHAHU4 TP 20 16 XLPE/SWA/PVC

MDB connected to : 1500 KVA Transformer Total connected load per phas

Max demand (3 PH) : 56.66 kW at 0.80 Diversity

Contractor :
Type of meter (Rating of incomer): (1) Upto 60 A
(1 Phase)
MCC LOAD SCHEDULE
Plot No. 513 - 0116 SAIH SHUAI
Owner:
Consultants:

Proposed Type & No of


Cable Size ECC Connected Load kW
TOTAL kWh meters
2/4 x 1C 2/3/4C Size-1C R - Ph Y - Ph B - PH 1 - Ph 3 - Ph 3 - Ph
mm2 mm2 mm2 kW kW kW kW (1) (2) (3)
4c-50 1c-25 23.61 23.61 23.61 70.83

4c-6 1c-6 3.73 3.73 3.73 11.19


4c-6 1c-6 3.73 3.73 3.73 11.19
4c-6 1c-6 3.73 3.73 3.73 11.19
4c-4 1c-4 3.73 3.73 3.73 11.19
4c-4 1c-4 3.73 3.73 3.73 11.19
4c-4 1c-4 1.24 1.24 1.24 3.72
4c-4 1c-4 1.24 1.24 1.24 3.72
4c-4 1c-4 1.24 1.24 1.24 3.72
4c-4 1c-4 1.24 1.24 1.24 3.72

l connected load per phase 23.61 23.61 23.61 70.83

Total connected load (3 PH) 70.83 kW

Tel : Fax :
(2) Upto 100 A (3) 125 - 160 A (4) LV CT….../…... 5 A
(3 Phase)

T.C.L. 70.83 KW
Diversity Factor (DF) = 0.8 (0.8% used) 0.8
Max Demand = 56.664 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 56.664 x 1.732 x 0.8 x 400
= 102.2373 Amps
Plus 25% as safety factor
= 102.2373 x 1.25
= 127.7966 Amps

Standard Main Isolator Size = 125A, 4P


Main Feeder Cable = 1 x 4C x 50mm^2, XLPE/SWA/PVC
1 x 1C x 25mm^2 PVC/PVC, Y/G E
HP KW DF Current Plus SF
513 - 0116 SAIH SHUAIB 1 Chiller 1 204 68.00 0.8 368.07 460.08949
Chiller 2 204 68.00 0.8 368.07 460.08949
Chiller 3 204 68.00 0.8 368.07 460.08949
CHWP 1 15 11.19 3.73 0.8 20.19 25.237262
CHWP 2 15 11.19 3.73 0.8 20.19 25.237262
No of
meters
CHWP 3 15 11.19 3.73 0.8 20.19 25.237262
LV/HV Remarks OBAHU1 7.5 5.595 1.87 0.8 10.09 12.618631
CT (4) OBAHU2 7.5 5.595 1.87 0.8 10.09 12.618631
WHAHU1 5 3.73 1.24 0.8 6.73 8.4124206
WHAHU2 5 3.73 1.24 0.8 6.73 8.4124206
WHAHU3 5 3.73 1.24 0.8 6.73 8.4124206

Total

/ HV CT……/…...A

(3) x Cos Ø x V
x 1.732 x 0.8 x 400

50mm^2, XLPE/SWA/PVC, Cu
25mm^2 PVC/PVC, Y/G Earth Cable
Isolator CCT ECC
800 2-150 2-75
800 2-150 2-75
800 2-150 2-75
30 6 6
30 6 6
30 6 6
20 4 4
20 4 4
20 4 4
20 4 4
20 4 4
LOAD D
Project Name: DPE JAOSB
MSB Ref : JA-WSMDB Owner: DUB
Fed From: JA-MDB

SP/ Fault
Circuit/ Feeder Rating - AMPS PVC / XLPE
S.
DB No. TP F/S MCB / Duty SWA / PVC
No.
ISO ACB MCCB kA
1 INCOMER: TP 400 XLPE/SWA/PVC

OUTGOINGS:
1
2
3
4
5
6

MDB connected to : 1500 KVA Transformer Total connected load per phas

Max demand (3 PH) : 0.00 kW at 0.80 Diversity

Contractor :
Type of meter (Rating of incomer): (1) Upto 60 A
(1 Phase)
LOAD DISTRIBUTION SCHEDULE
Plot No.:
Owner: DUBAI PETROLEUM ESTABLISHMENT

Proposed Type & No of


Cable Size ECC Connected Load kW
TOTAL kWh meters
2/4 x 1C 2/3/4C Size-1C R - Ph Y - Ph B - PH 1 - Ph 3 - Ph 3 - Ph
mm2 mm2 mm2 kW kW kW kW (1) (2) (3)
4c-300 1c-150 0.00 0.00 0.00 0.00

0.00
0.00
0.00
0.00

l connected load per phase 0.00 0.00 0.00 0.00

Total connected load (3 PH) .00 kW

Tel : Fax :
(2) Upto 100 A (3) 125 - 160 A (4) LV CT….../…... 5 A
(3 Phase)

T.C.L. 0.00 KW
Diversity Factor (DF) = 0.9 (90% used) 0.8
Max Demand = 0 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 0 x 1.732 x 0.8 x 400
= 0 Amps
Plus 25% as safety factor
= 0 x 1.25
= 0 Amps

Standard Main Isolator Size = 400A, 4P


Main Feeder Cable = 1 x 4C x 300mm^2, XLPE/SWA/PVC
1 x 1C x 150mm^2 PVC/PVC, Y/G E
B56CD JAFZA NORTH

No of
meters
LV/HV Remarks
CT (4)

Total

/ HV CT……/…...A

(3) x Cos Ø x V
x 1.732 x 0.8 x 400

300mm^2, XLPE/SWA/PVC, Cu
150mm^2 PVC/PVC, Y/G Earth Cable
LIGHTING CONTROL PANEL SCHED
Project name: DPE JAOSB
Panel Ref : Owner: DUBAI PETROLEUM ESTABLISHMENT
Fed From:

MCB CCT ECC


RATING OF

RATING OF
INCOMER

RTG. Wire Wire


ELCB

SL NO. CIR. NO. AREA / LOAD SERVED


(A) (mm2) (mm2)

1 R1 30 25 10 High Mast Light No. 1

2 Y1 30 25 10 High Mast Light No. 1

3 B1 30 25 10 High Mast Light No. 1

4 R2 30 16 16 High Mast Light No. 2


40A 4P
100MA 5 Y2 30 16 16 High Mast Light No. 2
ELCB-1
6 B2 30 16 16 High Mast Light No. 2

7 R3 30 10 10 High Mast Light No. 3

8 Y3 30 10 10 High Mast Light No. 3

9 B3 30 10 10 High Mast Light No. 3

10 R4 30 16 16 High Mast Light No. 4

11 Y4 30 16 16 High Mast Light No. 4

12 B4 30 16 16 High Mast Light No. 4

13 R5 30 10 10 High Mast Light No. 5


40A 4P
100MA 14 Y5 30 10 10 High Mast Light No. 5
ELCB-2
15 B5 30 10 10 High Mast Light No. 5

16 R6 30 4 4 High Mast Light No. 6


100A TPN ISOLATOR

17 Y6 30 4 4 High Mast Light No. 6

18 B6 30 4 4 High Mast Light No. 6

19 R4 30 4 4 High Mast Light No. 7

20 Y4 30 4 4 High Mast Light No. 7

21 B4 30 4 4 High Mast Light No. 7

22 R5 30 10 10 High Mast Light No. 8


40A 4P
100MA 23 Y5 30 10 10 High Mast Light No. 8
ELCB-2
24 B5 30 10 10 High Mast Light No. 8

25 R6 30 16 16 High Mast Light No. 9

26 Y6 30 16 16 High Mast Light No. 9

27 B6 30 16 16 High Mast Light No. 9


28 R4 30 10 10 High Mast Light No. 10

29 Y4 30 10 10 High Mast Light No. 10

30 B4 30 10 10 High Mast Light No. 10

31 R5 30 16 16 High Mast Light No. 11


40A 4P
100MA 32 Y5 30 16 16 High Mast Light No. 11
ELCB-2
33 B5 30 16 16 High Mast Light No. 11

34 R6 30 25 16 High Mast Light No. 12

35 Y6 30 25 16 High Mast Light No. 12

36 B6 30 25 16 High Mast Light No. 12

CABLE SIZE : 1X4C-25mm2 XLPE/SWA/CU/PVC CABLE + 1X1C-16mm2 PVC ECC Y/G


G CONTROL PANEL SCHEDULE
Plot No. B56CD JAFZA NORTH
ROLEUM ESTABLISHMENT Panel Location:
Panel Type:

CONNECTED
LOADS LOAD (Watts)
/ POINTS WATT/
ZONE TYPE
UNIT
Remarks
LTG R Y B

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000
FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

FL 2 1000 2000

PVC ECC Y/G 24000 24000 24000 72000


TOTAL 72.00 kW

T.C.L. 72.00 KW
Diversity Factor (DF) = 0.9 (90% used) 0.9
Max Demand = 64.8 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 64.8 x 1.732 x 0.8 x 400
= 116.917 Amps
Plus 25% as safety factor
= 116.917 x 1.25
= 146.146 Amps

Standard Main Isolator Size = 100A, 4P


Main Feeder Cable = 1 x 4C x 35mm^2, XLPE/SWA/PVC, Cu
1 x 1C x 25mm^2 PVC/PVC, Y/G Earth Cable
LOAD DISTRIBUTION SCHEDULE
Project name: DPE JAOSB
Panel Ref : Owner: DUBAI PETROLEUM ESTABLISHMEN
Fed From:

MCB CCT ECC


RATING OF

RATING OF
INCOMER

RTG. Wire Wire


ELCB

SL NO. CIR. NO. ROOM / AREA


(A) (mm2) (mm2)

1 R2 20 4 4 Lighting Bay 1
40A 4P
100MA 2 Y2 20 4 4 Lighting Bay 1
ELCB-1
3 B2 20 2.5 2.5 Lighting Bay 1

4 R1 20 2.5 2.5 Lighting Bay 2

5 Y1 20 2.5 2.5 Lighting Bay 2

40A 4P 6 B1 20 2.5 2.5 Lighting Bay 2


40A TPN ISOLATOR

100MA
ELCB-2 7 R2 20 4 4 Lighting Bay 3

8 Y2 20 4 4 Lighting Bay 3

9 B2 20 2.5 2.5 Lighting Bay 3

10 R2 20 4 4 Receptacle Bay 1
40A 4P
100MA 11 Y2 20 4 4 Receptacle Bay 2
ELCB-3
12 B2 20 2.5 2.5 Receptacle Bay 3

13 R2 20 4 4 Spare
40A 4P
100MA 14 Y2 20 4 4 Spare
ELCB-3
15 B2 20 2.5 2.5 Spare

CABLE SIZE : 1X4C-35mm2 XLPE/SWA/CU/PVC CABLE + 1X1C-16mm2 PVC ECC Y/G


RIBUTION SCHEDULE
Plot No. B56CD JAFZA NORTH
ETROLEUM ESTABLISHMENT Panel Location: Pipe Yard
Panel Type:

CONNECTED LOADS / POINTS LOAD (Watts)


Watt /

MOTOR
Unit

Outlet
13A 15A EX.

Flex.
LTG
S.O.
IK
S.O.
FCU
FAN
R Y B

3 200 600

3 200 600

3 200 600

3 200 600

3 200 600

3 200 600

3 200 600

3 200 600

3 200 600

3 400 1200

3 400 1200

3 400 1200

3 400 1200

3 400 1200

3 400 1200

4200 4200 4200

TOTAL 12.60

T.C.L. 12.60 KW
Diversity Factor (DF) = 0.9 (90% used) 0.9
Max Demand = 11.34 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø
= 11.34 x 1.732 x 0.8 x 400
= 20.4605 Amps
Plus 25% as safety factor
= 20.4605 x 1.25
= 25.5756 Amps

Standard Main Isolator Size = 40A, 4P


Main Feeder Cable = 1 x 4C x 10mm^2, XLPE/SWA/PVC, Cu
1 x 1C x 10mm^2 PVC/PVC, Y/G Earth Cable
JAFZA NORTH
d

Remarks

12600

kW

er Cable of LPA Warehouse


(3) x Cos Ø x V
x 1.732 x 0.8 x 400
x 10mm^2, XLPE/SWA/PVC, Cu
x 10mm^2 PVC/PVC, Y/G Earth Cable
LOAD D
Project Name: DPE JAOSB
MSB Ref : JA-WSMDB Owner: DUB
Fed From: JA-MDB

SP/ Fault
Circuit/ Feeder Rating - AMPS PVC / XLPE
S.
DB No. TP F/S MCB / Duty SWA / PVC
No.
ISO ACB MCCB kA
1 INCOMER: TP 400 XLPE/SWA/PVC

OUTGOINGS:
1
2
3
4
5
6

MDB connected to : 1500 KVA Transformer Total connected load per phas

Max demand (3 PH) : 0.00 kW at 0.80 Diversity

Contractor :
Type of meter (Rating of incomer): (1) Upto 60 A
(1 Phase)
LOAD DISTRIBUTION SCHEDULE
Plot No.:
Owner: DUBAI PETROLEUM ESTABLISHMENT

Proposed Type & No of


Cable Size ECC Connected Load kW
TOTAL kWh meters
2/4 x 1C 2/3/4C Size-1C R - Ph Y - Ph B - PH 1 - Ph 3 - Ph 3 - Ph
mm2 mm2 mm2 kW kW kW kW (1) (2) (3)
4c-300 1c-150 0.00 0.00 0.00 0.00

0.00
0.00
0.00
0.00

l connected load per phase 0.00 0.00 0.00 0.00

Total connected load (3 PH) .00 kW

Tel : Fax :
(2) Upto 100 A (3) 125 - 160 A (4) LV CT….../…... 5 A
(3 Phase)

T.C.L. 0.00 KW
Diversity Factor (DF) = 0.9 (90% used) 0.8
Max Demand = 0 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 0 x 1.732 x 0.8 x 400
= 0 Amps
Plus 25% as safety factor
= 0 x 1.25
= 0 Amps

Standard Main Isolator Size = 400A, 4P


Main Feeder Cable = 1 x 4C x 300mm^2, XLPE/SWA/PVC
1 x 1C x 150mm^2 PVC/PVC, Y/G E
B56CD JAFZA NORTH

No of
meters
LV/HV Remarks
CT (4)

Total

/ HV CT……/…...A

(3) x Cos Ø x V
x 1.732 x 0.8 x 400

300mm^2, XLPE/SWA/PVC, Cu
150mm^2 PVC/PVC, Y/G Earth Cable
LOAD D
Project Name: DPE JAOSB
MSB Ref : JA-WSMDB Owner: DUB
Fed From: JA-MDB

SP/ Fault
Circuit/ Feeder Rating - AMPS PVC / XLPE
S.
DB No. TP F/S MCB / Duty SWA / PVC
No.
ISO ACB MCCB kA
1 INCOMER: TP 400 XLPE/SWA/PVC

OUTGOINGS:
1
2
3
4
5
6

MDB connected to : 1500 KVA Transformer Total connected load per phas

Max demand (3 PH) : 0.00 kW at 0.80 Diversity

Contractor :
Type of meter (Rating of incomer): (1) Upto 60 A
(1 Phase)
LOAD DISTRIBUTION SCHEDULE
Plot No.:
Owner: DUBAI PETROLEUM ESTABLISHMENT

Proposed Type & No of


Cable Size ECC Connected Load kW
TOTAL kWh meters
2/4 x 1C 2/3/4C Size-1C R - Ph Y - Ph B - PH 1 - Ph 3 - Ph 3 - Ph
mm2 mm2 mm2 kW kW kW kW (1) (2) (3)
4c-300 1c-150 0.00 0.00 0.00 0.00

0.00
0.00
0.00
0.00

l connected load per phase 0.00 0.00 0.00 0.00

Total connected load (3 PH) .00 kW

Tel : Fax :
(2) Upto 100 A (3) 125 - 160 A (4) LV CT….../…... 5 A
(3 Phase)

T.C.L. 0.00 KW
Diversity Factor (DF) = 0.9 (90% used) 0.8
Max Demand = 0 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 0 x 1.732 x 0.8 x 400
= 0 Amps
Plus 25% as safety factor
= 0 x 1.25
= 0 Amps

Standard Main Isolator Size = 400A, 4P


Main Feeder Cable = 1 x 4C x 300mm^2, XLPE/SWA/PVC
1 x 1C x 150mm^2 PVC/PVC, Y/G E
B56CD JAFZA NORTH

No of
meters
LV/HV Remarks
CT (4)

Total

/ HV CT……/…...A

(3) x Cos Ø x V
x 1.732 x 0.8 x 400

300mm^2, XLPE/SWA/PVC, Cu
150mm^2 PVC/PVC, Y/G Earth Cable
LOAD DISTRIBUTION SCHEDULE
Project name: DPE JAOSB
Panel Ref : Owner: DUBAI PETROLEUM ESTABLISHMEN
Fed From:

MCB CCT ECC


RATING OF

RATING OF
INCOMER

RTG. Wire Wire


ELCB

SL NO. CIR. NO. ROOM / AREA


(A) (mm2) (mm2)

1 R1 20 2.5 2.5 Lighting Security Office

2 Y1 20 2.5 2.5 Lighting Guard Room

3 B1 20 2.5 2.5 Lighting Spot and Canopy

4 R2 20 4 4 Receptacle Toilet
40A 4P
100MA 5 Y2 20 4 4 Receptacle Guard Room
ELCB-1
6 B2 20 2.5 2.5 Extract Fans 15
63A TPN ISOLATOR

7 R3 20 2.5 2.5 Gate Barrier Ent and Ext

8 Y3 20 2.5 2.5 Fire Alarm Panel

9 B3 20 2.5 2.5 Gate Barrier Trailer Truck

10 R4 20 2.5 2.5

11 Y4 20 2.5 2.5 Package AC

40A 4P 12 B4 20 2.5 2.5


100MA
ELCB-2 13 R5 20 4 4

14 Y5 20 4 4 Water Heater

15 B5 20 4 4

CABLE SIZE : 1X4C-35mm2 XLPE/SWA/CU/PVC CABLE + 1X1C-16mm2 PVC ECC Y/G


RIBUTION SCHEDULE
Plot No. B56CD JAFZA NORTH
ETROLEUM ESTABLISHMENT Panel Location:
Panel Type:

CONNECTED LOADS / POINTS LOAD (Watts)


Watt /

MOTOR
Unit

Outlet
13A 15A EX.

Flex.
LTG
S.O.
IK
S.O.
FCU
FAN
R Y B

6 150 900

6 150 900

6 150 900

2 200 400

6 200 1200

2 200 400

1 400 400

1 200 200

1 400 400

746

2238 746

746

1333

4000 1333

1333

3779 4379 3779

TOTAL 11.94

T.C.L. 11.94 KW
Diversity Factor (DF) = 0.9 (90% used) 0.9
Max Demand = 10.7433 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø
= 10.7433 x 1.732 x 0.8 x 400
= 19.3838 Amps
Plus 25% as safety factor
= 19.3838 x 1.25
= 24.2298 Amps

Standard Main Isolator Size = 63A, 4P


Main Feeder Cable = 1 x 4C x 35mm^2, XLPE/SWA/PVC, Cu
1 x 1C x 25mm^2 PVC/PVC, Y/G Earth Cable
JAFZA NORTH

Remarks

11937

kW

er Cable of LPA Warehouse


(3) x Cos Ø x V
x 1.732 x 0.8 x 400
x 35mm^2, XLPE/SWA/PVC, Cu
x 25mm^2 PVC/PVC, Y/G Earth Cable
LOAD DISTRIBUTION SCHEDULE
Project name: DPE JAOSB
Panel Ref : LPE Radio Room Owner: DUBAI PETROLEUM ESTABLISHMEN
Fed From:

MCB CCT ECC


RATING OF

RATING OF
INCOMER

RTG. Wire Wire


ELCB

SL NO. CIR. NO. ROOM / AREA


(A) (mm2) (mm2)

1 R1 20 4 4
63A 4P
100MA 2 Y1 20 4 4 CRAC 1 & 1A
ELCB-1
3 B1 20 4 4

4 R2 20 4 4 Server Rack S.O. 1


40A 4P
40A TPN ISOLATOR

100MA 5 Y2 20 4 4 Server Rack S.O. 2


ELCB-1
6 B2 20 4 4 Server Rack S.O. 3

7 R3 20 4 4 Battery Charger
63A 4P
100MA 8 Y3 20 4 4 Battery Charger
ELCB-1
9 B3 20 4 4 Communication Equipment

10 R4 20 4 4 Radio Tower Lights


40A 4P
100MA 11 Y4 20 4 4
ELCB-1
12 B4 20 4 4

CABLE SIZE : 1X4C-35mm2 XLPE/SWA/CU/PVC CABLE + 1X1C-16mm2 PVC ECC Y/G


RIBUTION SCHEDULE
Plot No. B56CD JAFZA NORTH
ETROLEUM ESTABLISHMENT Panel Location:
Panel Type:

CONNECTED LOADS / POINTS LOAD (Watts)


Watt /
Unit

PUMP
Outlet
13A 15A EX.

Flex.
LTG
S.O.
IK
S.O.
FCU
FAN
R Y B

6116

18348 6116

6116

4840

4840

4840

11440

11440

4400

700

23096 22396 15356

TOTAL 60.85

T.C.L. 60.85 KW
Diversity Factor (DF) = 0.9 (90% used) 0.9
Max Demand = 54.7632 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø
= 54.7632 x 1.732 x 0.8 x 400
= 98.8077 Amps
Plus 25% as safety factor
= 98.8077 x 1.25
= 123.51 Amps

Standard Main Isolator Size = 63A, 4P


Main Feeder Cable = 1 x 4C x 35mm^2, XLPE/SWA/PVC, Cu
1 x 1C x 25mm^2 PVC/PVC, Y/G Earth Cable
JAFZA NORTH

Remarks

60848

kW

er Cable of LPA Warehouse


(3) x Cos Ø x V
x 1.732 x 0.8 x 400

x 35mm^2, XLPE/SWA/PVC, Cu
x 25mm^2 PVC/PVC, Y/G Earth Cable
T.C.L. 18.00 KW
Diversity Factor (DF) = 0.9 (90% used) 0.9
Max Demand = 16.2 KW

Calculation of Main Isolator and Main Feeder Cable of LPA Warehouse


Current = P / Sqrt (3) x Cos Ø x V
= 16.2 x 1.732 x 0.8 x 400
= 29.22921 Amps
Plus 25% as safety factor
= 29.22921 x 1.25
= 36.53652 Amps

Standard Main Isolator Size = 100A, 4P


Main Feeder Cable = 1 x 4C x 35mm^2, XLPE/SWA/PVC, Cu
1 x 1C x 16mm^2 PVC/PVC, Y/G Earth Cable
LPE/SWA/PVC, Cu
VC/PVC, Y/G Earth Cable