The document summarizes the battery calculation for the main fire alarm panel of a two-story train station building complex. It calculates the standing load to be 18 AH from the main fire alarm panel drawing 0.25A continuously for 72 hours. It then calculates the alarm load to be 1.125 AH from breakglass units, LED indicators, and alarm bells during an alarm. The total load is calculated to be 19.125 AH, and with a 10% safety factor the required battery capacity is 22 AH.
The document summarizes the battery calculation for the main fire alarm panel of a two-story train station building complex. It calculates the standing load to be 18 AH from the main fire alarm panel drawing 0.25A continuously for 72 hours. It then calculates the alarm load to be 1.125 AH from breakglass units, LED indicators, and alarm bells during an alarm. The total load is calculated to be 19.125 AH, and with a 10% safety factor the required battery capacity is 22 AH.
The document summarizes the battery calculation for the main fire alarm panel of a two-story train station building complex. It calculates the standing load to be 18 AH from the main fire alarm panel drawing 0.25A continuously for 72 hours. It then calculates the alarm load to be 1.125 AH from breakglass units, LED indicators, and alarm bells during an alarm. The total load is calculated to be 19.125 AH, and with a 10% safety factor the required battery capacity is 22 AH.
BANGUNAN STESEN KOMUTER 2 TINGKAT DENGAN KEMUDAHAN
SOKONGAN (TERMASUK PEJABAT PENGURUSAN, KIOSK JUALAN TIKET, PUSAT PENERANGAN PELANCONGAN, SURAU DAN PENCAWANG ELEKTRIK TNB) DAN JEJANTAS PEJALAN KAKI YANG BERBUMBUNG KE KOMPLEKS PERHENTIAN KAJANG
A) Standing Load Calculation
Qty Current (A) Hours (H) Total (AH) 1 Main Fire Alarm Panel 1 0.25 72 18
Total Standing Load 18
B) Alarm Load Calculation during alarm conditions
Qty Current (A) Hours (H) Total (AH) 1 Breakglass 15 0.015 1 0.225 2 LED for alarm zones, status, bells, etc 30 0.01 1 0.3 3 Alarm Bells 15 0.04 1 0.6 Total Alarm Load 1.125