Вы находитесь на странице: 1из 6

The 20th International Symposium on High Voltage Engineering, Buenos Aires, Argentina, August 27 – September 01, 2017

COMPARATIVE STUDY OF EXISTING MONITORING AND


DIAGNOSTIC TECHNIQUES OF METAL-OXIDE SURGE ARRESTER
G. R. S. LIRA1*, V. R. N. BARBOSA1, C. R. C. AMORIM FILHO1, S. L. C. BATISTA1 e E.
G. COSTA1
1
Federal University of Campina Grande, Campina Grande, Brazil

*Email: < george@dee.ufcg.edu.br >

Abstract: Metal-oxide surge arresters are devices used in the electrical power system to
protect against switching and lightning overvoltages that reach or propagate to
transmission lines and power utility substations. Thus, they are used in order to increase
the reliability, economy, and continuity of operation of the electrical systems. Considering
the importance of surge arresters for the electrical power systems, several monitoring and
diagnostic techniques have been studied, developed and improved to estimate the surge
arrester degradation level. However, there is not consensus on the effectiveness of each
one of the existing techniques. This work introduces a comparative study of existing and
recently developed surge arrester monitoring and diagnostic techniques. Procedures
based on the measurement of partial discharges, temperature, total leakage current and
leakage current decomposition in its components were evaluated. The purpose of this study
is to provide subsidies to determine, considering technical and operational aspects, which
it is the most appropriate surge arrester monitoring and diagnostic technique. For this
purpose, the accuracy of the results obtained from the use of the techniques in the
laboratory, the results provided in the references, and the implementation/application of the
techniques, which can be online or offline, were evaluated. Monitoring and diagnostic
procedures based on leakage current measurements are commonly performed online,
which consists of measuring the current through the ground cable (connected in series with
the surge arrester) by an inductive sensor with high magnetic permeability. Some
techniques require the measurement of the voltage signal applied to the surge arrester,
which can be a limitation due to the technical-operational issues. Regarding to techniques
based on temperature measurement and thermal analysis, they are known to be non-
destructive and non-invasive, however, they measure an indirect physical propriety (the
outer temperature of the housing), that are subject to the sensitivity of the measuring
instrument and of the operator. The measurement of partial discharges is usually based on
offline methods performed in laboratory, although some studies report techniques that can
be applied in the field without requiring the surge arrester removal. For the application of
these techniques, magnetic sensors capable of detecting low amplitudes at high
frequencies are used. However, there is still not consolidated procedure or widely
employed by the power utilities, unlike techniques based on leakage current and
temperature measurements. The experimental tests performed so far indicate that the use
of surge arrester monitoring and diagnostic techniques based on the measurement of the
total leakage current are more feasible because they do not require complex arrangements
to be applied in the field, besides providing as physical parameter for diagnostic purposes,
an electric quantity connected directly to the level of degradation of the surge arrester.

1 INTRODUCTION switching surges that affect or propagate in


substations and transmission lines.
The operating voltage level of the Electrical Power
Systems (EPSs) equipment and devices shall not MOSAs have been used for more than 30 years in
exceed its maximum operating voltage [1]. To order to increase the reliability, economy and
guarantee the safety of substation equipment continuity of the electrical systems operation [2, 3].
against voltage and current surges, arresters are Due to the importance of surge arresters for the
used due to their capacity of absorb the energy EPSs, several monitoring and diagnostic
coming from the overvoltages and to limit the procedures of the MOSA degradation level have
voltage level to values supported by the substation been studied, developed and improved. However,
equipment. Thus, high voltage metal-oxide surge there is not consensus on the effectiveness of each
arresters (MOSAs) have been widely used in power of the existing procedures.
systems for protection against atmospheric and
The monitoring procedures are generally classified alternative, some works use the total leakage
according to their operating principle. Thus, there current as an indicator of the degradation level [3,
are procedures based on [4]: disconnectors, 13].
discharge counters, temperature measurement and
leakage current measurement. The first two are of This work intends to carry out a comparative study
low technical complexity and low implementation of the existing and recently developed monitoring
cost, but they have the great disadvantage of being and diagnostic procedures of MOSA based on the
based on electromechanical processes, which are measurement of partial discharges, temperature
subject to a greater probability of failure. The last and leakage current. For this purpose, this
two procedures are the most efficient and used by document was structured as follows. In this section,
power utilities, and are often used together [5-7]. the introductory concepts were introduced. In
Besides these more usual procedures, there are Section 2, the methodology used to study the
those based on the partial discharges procedures will be presented in detail. In Section 3
measurements [8]. will evaluate the procedures. In Section 4, results
and analyzes. In Section 5, conclusions. And in the
The procedures based on the measurement of last two sections, acknowledgments and
partial discharges, provided for by standard [9], references.
normally implemented off-line, are still subject to
uncertainties related to high sensitivity to 2 METHODOLOGY
electromagnetic noise, appropriate measurement
arrangement, appropriate filtering techniques, For the development of this work, two types of
parameterization of data measured, etc. Several methodologies will be adopted: bibliographical and
researches have been developed to address these documentary. In the first one, a bibliographical
uncertainties and to make the way of implementing research will be carried out concerning the studied
procedures based on the measurement of partial subject, more specifically about the monitoring and
discharges online [3, 8]. diagnostic procedures of MOSA, in order to reach
the state of the art of the existing procedures in the
There are several procedures based on external literature. In the second, the procedures will be
temperature measurement by thermographic evaluated qualitatively to determine those that are
analysis [7, 10, 11]. These procedures are quite most promising considering technical and
attractive because they are non-invasive and non- operational aspects. For this purpose, the Ishikawa
destructive, can be applied at the distance of the diagram will be used to facilitate the evaluation of
MOSA, do not require system interventions or the procedures, which is highlighted in Figure 1.
special measurement arrangements. However, they
are also subject to specific characteristics of the
surge arresters or the measuring environment. And
still they are indirect procedures that do not directly
return an electrical quantity, but rather the external
effect of the warming inside the surge arrester due
to the passage of the leakage current. Another
disadvantage is the fact that monitoring is usually
performed on the night, to avoid the influence of the
sun, which makes monitoring in real time
impracticable. Finally, these procedures usually
require expensive instruments, such as, e.g., the
use of an infrared camera [3, 6, 12].

Regarding to monitoring procedures based on the


total leakage current measurement that goes Figure 1: Diagram of the employed methodology.
through the surge arrester during its steady state
operation, they are considered direct procedures
because they provide an electrical quantity related The monitoring and diagnostic procedures of MOSA
to the state of operation of the device. In general, based on the measurements of partial discharges,
these procedures perform the decomposition of the temperature and leakage current have several
total leakage current into components (resistive and characteristics that will be used to perform the
capacitive) and analyze the harmonic content of the comparison. The characteristics presented by the
current, since according to several studies [1, 3, 4, analyzed procedures are these: simplifying
5] the resistive component and its 3rd order premises; mode of implementation (online or
harmonic have significant variations, both in shape offline); cost of instruments; complexity of
and amplitude, proportional to the of surge arrester arrangements; hit rate; condition of monitoring and
degradation level. The main disadvantage of these diagnostic; and use of state classifier.
procedures is the need to measure, on field, the
high voltage applied to the surge arrester. As an
Among the mentioned characteristics, the
parameters that were adopted to carry out the
comparative study are the implementation mode
and monitoring and diagnostic condition. For the
first, the procedure implemented in online mode
stands out in relation to the offline implementation.
For the second, it is known that the procedure can
be applied continuously or needs to be interrupted,
as well as, perform the monitoring and diagnostic in
real time or not. Moreover, the feasibility of the
procedure, from a technical-economic point of view,
was another criterion of comparison adopted. The
procedures should be feasible in the field and be Figure 2: Experimental arrangement diagram used
cost-effective for electric power companies. in the test by the procedure A1 [14].

3 EVALUATED PROCEDURES
3.1.2 Procedure A2
Following is presented some methods, techniques The procedure A2, presented by [1], consisted of
and methodologies based on the measurements of determining, on-line, the harmonic distortion of the
partial discharges, temperature and leakage total current as a new operating status indicator of
current, to highlight the evolution of the researches the surge arrester. The author showed that the
about monitoring and diagnostic of surge arrester. harmonic distortion is proportional to the resistive
This sample of the state of art will be subsidize the current, which enabled monitoring and diagnostic.
procedures comparative study. The procedures For that, it was necessary to consider that the
were organized according to the kind of electrical resistive leakage current consists predominantly of
quantity to be used as an indicator of the level of the fundamental component and 3rd harmonic. Also,
degradation. Thus, they were organized in this way: the harmonics of the capacitive current did not vary
leakage current measurement; partial discharge in proportion to the harmonic distortion variation of
measurement; temperature measurement; leakage the total leakage current, and also did not increase
current and temperature measurement. according to the surge arrester degradation level, so
that the total harmonic distortion would be in
3.1 Leakage current measurement function, predominantly, of the harmonic content of
the resistive current. Thus, the degradation level
3.1.1 Procedure A1 could be estimated only with the analysis of the
The procedure A1, presented by [14], aimed to variation of the harmonic content of the leakage
perform the monitoring and diagnostic of MOSA current.
based only on the measurement of the total leakage
current, avoiding the measurement of the applied 3.2 Partial discharge measurement
voltage to the surge arrester, and others technical
and operational constraints. This procedure, by 3.2.1 Procedure B1
means of extracted characteristics from the The procedure B1, proposed by [8], is a surge
evaluated current signals, performs the database arrester monitoring and diagnostic online
construction to be used in the training and test of a methodology based on the measurement of partial
surge arrester operation status classifier. The discharges. For this purpose, a high frequency
classifier was based on Artificial Neural Networks current transformer (HFCT) is used coupled to the
called Self-Organizing Maps (SOM). The status cable that connects the surge arrester to the
classifier can identify whether the surge arrester is ground, as well as a modular digital oscilloscope
faulty or not. If it is defective, the type of defect is and a computer. By induction effect, information is
presented, such as sealing loss, internal humidity, obtained on the induced voltage, and from this it
superficial pollution, varistor degradation, verifies that the load level (in pC) is in the allowed
displacement along the active column, non-uniform range (below 50 pC). Thus, the authors adopted as
voltage distribution. Satisfactory results were a diagnostic criterion the intensity of the voltage
obtained in the diagnostic, since the hit rate for signal, as well as the number of repetitions of the
identifying defective surge arresters was signal obtained by means of the HFCT. The
approximately 98 %. The experimental arrangement arrangement used to implement the procedure is
used to obtain the total leakage current follows as shown in Figure 3.
shown in Figure 2.
Figure 4: Applied proposal units by procedure C2
[10].
Figure 3: HFCT connected in the grounding cable
[8]. 3.4 Leakage current and temperature
measurement
3.3 Temperature measurement
3.4.1 Procedure D1
3.3.1 Procedure C1 The procedure D1, proposed by [6], consists of
performing the autonomous and online monitoring
The procedure C1, proposed by [11], performs the of the MOSA degradation level based on the
online monitoring and diagnostic of the MOSA leakage current and surge arrester external
degradation level using a neural network temperature measurement. To do so, it is necessary
architecture known as Self-Organizing Maps (SOM) to measure the voltage applied to the surge arrester
of Kohonen. The procedure is based on the analysis to estimate the resistive component of the leakage
of the thermal profile obtained from thermographs of current, as well as the use of infrared camera in
surge arrester under operating voltage. Through the order to obtain thermographs. In the estimation of
thermal profile, with the use of the infrared camera, the resistive current the capacitive compensation
the SOM network can identify if the surge arrester is method is used, that is, the capacitive component is
defective, in addition to determining the type of extracted from the leakage current in order that the
defect. Plausible results were achieved in total current is equal to its resistive component (𝑖𝑡 =
monitoring and diagnostic, since 95.83% of the
𝑖𝑟 ). For thermographic analysis, some parameters
thermal images were classified correctly as
that can influence the results are studied: solar
corresponding to defective and non-defective surge
radiation, wind speed, temperature in a controlled
arresters. environment and the parameters of the infrared
camera.
3.3.2 Procedure C2
The procedure C2, presented by [10], is intended to 3.4.2 Procedure D2
perform online monitoring and diagnostic based on
The D2 procedure, presented by [7], consists in a
the measurement of the surge arrester external
MOSA monitoring and diagnostic hybrid online
temperature. For this, an infrared camera is used to
technique based on leakage current measurement
obtain thermal images of the surge arresters, to
and thermographic analysis. For this, a regression
construct a previous database to perform the
model was used based on the following physical
training of the Neuro-Fuzzy Network (NFN). To
parameters: temperature difference, total leakage
perform the diagnostic of the surge arresters, the
current and its resistive component. Thereby, it was
procedure uses a digital image processing
possible to determine a relation between the
algorithm based on the Watershed Transform. By
maximum temperature difference and the leakage
applying this procedure, it is possible to identify the
current, which is expressed by:
operation status of the MOSAs in: defective, normal,
clean and suspect. In Figure 4 is showed the
𝑌𝑖 = 𝛽0 + 𝛽1 𝑋1 + 𝛽2 𝑋2 + 𝜀𝑖 , (1)
methodology of the procedure C2, from the
acquisition of thermographic images to the
diagnostic stage. Satisfactory results were achieved where 𝑌𝑖 is the maximum temperature difference in
in monitoring and diagnostic, as accuracy rates for the arrester, 𝑋1 corresponds to the resistive current,
identifying defective arresters were approximately 𝑋2 refers to the total leakage current and 𝛽0 , 𝛽1 , 𝛽2
85% and 90% for metal-oxide and silicon carbide and 𝜀𝑖 are, respectively, the intersection of the 𝑌
surge arresters, respectively. axis, the coefficient of the component, the leakage
current coefficient, the total leakage current
coefficient and the random error. Those coefficients
are estimated using the Least Squares method. The subject to interference, leading to distortion of the
results achieved by this procedure in tests with same normally due to white noise; harmonic content
surge arresters installed in the Taiwan substation of only 1% in system voltage can bring about in
were satisfactory. errors of up to 100% in monitoring results; the
orthogonality was refuted by [15] and demonstrated
4 RESULTS AND ANALYSIS that generally this is not true by [5]; the analysis of
the 3rd harmonic of the leakage current may not
Electric utilities are looking for procedures that can indicate the entry of moisture, since the moisture
be used to maintenance of protection devices (e.g., ingress does not affect it, but only the fundamental
MOSA) in order to reduce the risk of failures, to component [12]; the signals of partial discharges in
increase system reliability, to reduce the risk of the field are of low intensity and of high frequency,
interruptions in power supply, to reduce operating so that they can be easily overlaid by the ambient
and maintenance costs of enterprises. It also allows noise; high cost instruments can economically make
more efficient management of the active arresters, the procedure unfeasible; the surge arrester
the estimation of the MOSA lifetime and the thermographs are sensitive to the characteristics of
migration from preventive to predictive the environment; there is not clear rules established
maintenance. for identifying defects in surge arresters, moreover
monitoring and diagnostic have great dependence
The monitoring and diagnostic procedures on the operator who is performing the
evaluated have some undesirable characteristics measurements.
considering technical, operational, and economic
aspects. The comparative study is carried out based In view of the evaluated procedures, the most
on these disadvantages and the adopted criteria. appropriate one to be used in the EPSs is the A1,
Among the existing ones, those that characterize proposed by Lira et al. (2014), because it represents
the procedure as not adequate, are: an online technique, has the capacity to work
continuously, in real time, overcomes theoretical
A. Requirement of the applied voltage signal limitations (simplifying premises). Moreover, the
to the surge arrester; procedure A1 has an electric quantity as an
indicator of the degradation level, state classifier,
B. Vulnerability to errors due to distorted does not require high cost instruments and was
voltage signals; validated in a high voltage laboratory (environment
likely to EPS).
C. Vulnerability to errors due to voltage
harmonics; 5 CONCLUSIONS

D. Based on incorrect assumptions (e.g., This work consists of a comparative study of some
orthogonality between resistive and procedures applied to the MOSAs monitoring and
capacitive components); diagnostic. It was evaluated procedures based on
the measurements of partial discharges,
E. Insensitivity to faults that do not change the temperature, and leakage current. Among the
𝑉 − 𝐼 curve of the non-linear resistors, such results presented in this study, the most important
as, sealing loss; was the systematic analysis of the procedures,
considering its main characteristics, advantages
F. High sensitivity to electromagnetic noise; and the disadvantages, allowing to determine the
most appropriate procedures considering technical,
G. Requirement of expensive instruments; operational, and economical aspects.

H. Results subject to specific characteristics of It was concluded that the more adequate
the surge arresters or the measuring procedures of surge arrester monitoring are that
environment; based on the measurement and analysis only of the
total leakage current, like procedure A1. The
I. Vulnerability to subjective interpretations of employed methodology can contribute to determine
results. ways to future developments in this research area.

The disadvantages (A), (B), (C), (D), (E), (F), (G), ACKNOWLEDGMENTS
(H) and (I) are justified for the following reasons, To those who do the Laboratory of High Voltage
respectively: the applied voltage may not being (LAT), for having given the physical space and
available to be measured or its measurement may technical support. To those who do the CNPq for the
be subject to financial, technical and operational financial support granted for the development of this
limitations that may become the monitoring work. And, also, all those who directly or indirectly
unfeasible; current and voltage signals in contributed to this work.
uncontrolled environments (e.g., substations) are
REFERENCES
[9] IEC. IEC 60099-4 Surge Arresters—Part 4:
[1] D. M. SANTOS, “Estudo do THD da corrente de
Metal-oxide Surge Arresters Without Gaps for
fuga de pararraios como parâmetro indicador
A.C. Systems. [S.l.], 2001.
de degradação”. Rio de Janeiro, Federal
[10] C. A. L. ALMEIDA, A. P. BRAGA, S.
University of Rio de Janeiro, Master
NASCIMENTO, V. PAIVA, H. J. MARTINS, R.
Dissertation in Electrical Engineering), 2015.
TORRES, W. M. CAMINHAS, “Intelligent
[2] E. G. COSTA, “Análise do Desempenho de
Thermographic Diagnostic Applied to Surge
Para-raios de Óxido de Zinco”. Campina
Arresters: A New Approach”. IEEE Transactions
Grande, Federal University of Paraíba,
on Power Delivery, v. 24, n. 2, p. 751-757, April
(Doctoral Thesis in Electrical Engineering),
2009.
1999.
[11] G. R. S. Lira, E. G. Costa and C. W. D. Almeida,
[3] G. R. S. LIRA, “Monitoramento de Para-raios de
"Self-organizing maps applied to monitoring and
Óxido de Zinco com Base na Medição da
diagnosis of ZnO surge arresters," 2010
Corrente de Fuga Total”. Campina Grande,
IEEE/PES Transmission and Distribution
Federal University of Campina Grande,
Conference and Exposition: Latin America
(Doctoral Thesis in Electrical Engineering),
(T&D-LA), Sao Paulo, 2010, pp. 659-664.
2012.
[12] M. E. G. ALVES, “Metodologia para o
[4] IEC 60099-5 Surge Arresters - Selection and
diagnóstico em tempo real de para-raios em
Application Recommendations. [S.l.], 2000.
sistemas de distribuição e transmissão de
[5] C. HEINRICH; V. HINRICHSEN, “Diagnostics
energia elétrica”. São Paulo, University of São
and Monitoring of Metal-Oxide Surge Arresters
Paulo, (Doctoral Thesis in Electrical
in High-Voltage Networks-Comparison of
Engineering), 2013.
Existing and Newly Developed Procedures”.
[13] W. A. B. SILVA; S. C. B. LOPES; G. B. LEAL;
IEEE Transactions on Power Delivery, v. 16, n.
G. R. S. LIRA; E. G. COSTA; M. J. A. MAIA,
1, p. 138-143, January 2001.
“Online Monitoring System of ZnO Surge
[6] W. A. URSINE, J. L. SILVINO, L. G. FONSECA;
Arresters Based on the Measured Leakage
R. M. ANDRADE, “Metal-oxide surge arrester's
Current”. In: International Symposium on High
leakage current analysis and thermography”. In:
Voltage Engineering, 2015, Pilsen. 19th
Lightning Protection (XII SIPDA), 2013
International Symposium on High Voltage
International Symposium on. IEEE, p. 297-303,
Engineering, 2015.
October 2013.
[14] G. R. S. LIRA; E. G. COSTA; T. V. FERREIRA,
[7] S. J. HUANG, C. H. HSIEH, “A method to
“Metal-oxide Surge Arrester Monitoring and
enhance the predictive maintenance of ZnO
Diagnosis by Self-Organizing Maps”. Electric
arresters in energy systems”. In: International
Power Systems Research, v. 108, p. 315-321,
Journal of Electrical Power & Energy Systems,
March 2014.
v. 62, p. 183-188, May 2014.
[15] T. ZHAO; Q. LI; J. QIAN, “Investigation on
[8] H. P. AMORIM, A. T. D. CARVALHO, T. B.
Digital Algorithm for On-Line Monitoring and
RODRIGUÊS, J. B. S. BORGES, C. D. C.
Diagnostics of Metal Oxide Surge Arrester
CUNHA. “Experience with on-line insulation
Based on an Accurate Model”. IEEE
diagnostics of surge arresters by PD
Transactions on Power Delivery, v. 20, n. 2, p.
measurement in the field”. In: Dielectrics (ICD),
751-756, April 2005.
2016 IEEE International Conference on. IEEE,
p. 472-475, July 2016.

Вам также может понравиться