PCS S Series

Protection Automation Control


Smart solution for intelligent grids
History and Data

LFP RCS PCS PCS S

1990 2000 2008 2018


First generation Protection up to UAPC platform Protection for
digital relay 1000kV HVAC for digital SS smart grid

www.nrec.com 2
History and Data

1,700,000+ 42.2% 1,500+


IEDs installed in Transmission Digital
more than 100 protection substations
countries market share in application
China

www.nrec.com 3
PCS S Protection Automation Control

Smart

Reliable

Flexible

www.nrec.com 4
Smart

Integrated protection , Full support for digital Distributed Energy


automation, measurement, substation application Resource (DER) system
PMU(2019), traveling wave - SV,R-GOOSE, PRP/HSR, protection improvement
locator (2019) and arc IEC61850Ed2

protection

Multi- DER
Digital SS
Functions

www.nrec.com 5
Reliable

Double A/D real-time Fault detect and protection Reliable protection DPFC
sampling and verification trip 2 out 2 technology,
with each other Cyber Security

Advanced
Redundancy Safety Technology

www.nrec.com 6
Flexible

Flexible modular software Advanced logic compatible Multiple options for


and hardware, easy for with IEC61131-3 installation
customized application - flush mounting, semi-flush
mounting, surface mounting,
wall mounting,etc.

Advanced Installation
Customized
logic

www.nrec.com 7
PMU Integrated

⚫ Integrated PMU function to make grid smarter


- IEEE C37.118 series of standards
➢ TVE (Total Vector Error)<1.0%
➢ Frequency error<0.005Hz phasor1
相量 1
1
δ12 2 phasor2
相量 2

- Support two kinds of measuring


GPS

WAMS
➢ Protection class:P_Class U 1 1
Control center
U 2 2
node1 node2
➢ Measurement class:M_Class G1 T system

相量
phasor1
1 相量
phasor2
2

δ1 1 Ref δ2 Ref

PMU1 PMU2

www.nrec.com 8
Travelling Wave Fault Location

⚫ Line protection integrated travelling wave fault


location function
- High-accuracy fault location
➢ Reach 150m (Better than 150m)

- Combine the advantages of protection and fault location


➢ Real time fault locator
➢ Single end traveling wave distance measurement based on impedance
method
➢ Self learning technique of wave velocity

www.nrec.com 9
Full Support for Digital Substation

⚫ Support the standard ethernet communication protocol of


native PRP/HSR and RSTP
⚫ Fully compliant to IEC61850 Ed1&2
⚫ MMS, GOOSE, SV, IEEE-1588 hybrid network
⚫ NCIT and traditional CT hybrid application

www.nrec.com 10
Reliable Design Philosophy

⚫ Double AD real-time sampling and verification with


each other
⚫ Independently controllable output control power
and fault detect signal, and real-time monitoring
loop

CT AC Binary Binary
LPF AD Input
VT Current/Voltage input
CPU1
Binary Binary
Power LPF AD Output Output
Pwr
Supply

LCD for HMI


Ethernet CPU2 Printer
Serial Ports Clock Syn
Power +

www.nrec.com 11
DPFC Philosophy

www.nrec.com 12
Cyber Security Integration

⚫ Multilayered security mechanisms –


Maximum possible security and availability
Production control zone Data management zone

Dispatching data
Integrated data
network
Danger1
network
Danger1
Operation and
maintenance work
router
Danger 1
Longitidinal encryption
firewall
authentication device

Safety Danger2
management background
Danger1 workstation
system gateway

Danger3
Forward and reverse firewall
isolation device

Station level network

Danger2

Bay level IED

www.nrec.com 13
Cyber Security Integration

⚫ System security configuration


- System boundary protection
- Partition data isolation
- Vertical authentication encryption
- Station security management system

⚫ IED
- Authenticate and encrypt

⚫ Management
- Data and control partitions

www.nrec.com 14
Cyber Security Integration

IED
LCD HMI

Configuration Access Control


RBAC
LCD HMI

Four safety
control system
RB
AC

• Access control
Audit Trail


IEC 61850

A-Profile
Audit record

Tools Communication

T-Profile
Process
Test Safety
Storage
communication
Security Network Stack Common Network Stack
• Safety tool
1. Configuration
2. RBAC:View、Timed Log out...
3. Download:Authentication、DS...

Security Network Stack S.N.S C.N.S

T-Profile Conf View

A-Profile Download

Client Tools

www.nrec.com 15
Cyber Security Integration

Detail design
Technical
proposal
Supported
standard
IEC 62443
IEC 62351 • IEEE1686
• IEC62351
IEEE 1686
user
Product • IEC62443
requiremenet
• NERC-CIP
NERC CIP

ISO 27000

Energy
Policy Industral automation
requirement
Informaiton System

www.nrec.com 16
Higher reliable and Multiple applications

⚫ Highly integrated and simplified design, less components


and higher MTBF (Mean Time Between Failures)

⚫ Multiple applications
- Multiple variants with housing width 1/1 or 1/2 or
1/3 ×19”, flexible extension of hardware
- Support flush mounting, semi-flush mounting,
surface mounting, rack and LCD separation, wall
mounting and other installation methods
- Multi-size LCD display unit, navigation, control and
multi-function buttons
- Protection class of front side is up to IP54

www.nrec.com 17
Improved Performance

⚫ High sampling performance


- High sampling accuracy, linear range (40In, 300V)

- Continuous thermal withstand (20A)

- Software compensation scheme

⚫ CT inputs 1A/5A configurable by software


⚫ Flexible I/O, push button and LED configuration
⚫ High recording sample rate up to 9.6k/s

www.nrec.com 18
New I/O and terminal options
⚫ Modular I/O could be ⚫ High density of I/O
replaced quickly terminals
⚫ Online Self diagnosis

⚫ Cross screw I/O,


CT/PT terminals
supporting AWG12
specification ferrule
and 4mm2 lead

www.nrec.com 19
Flexible Function Logic

⚫ Easy to deploy function modules

- Standard modular design Function modules Products

- Different devices are generated 50/51


PCS-931S

through a unified module library 81


PCS-902S
68
- User interface unification
87 PCS-978S

79 PCS-9611S
21

www.nrec.com 20
Engineering Tools

⚫ PCS-Studio - Configuration and testing tool

www.nrec.com 21
Engineering Tools

⚫ Torch - MOT tool

www.nrec.com 22
PCS Studio Engineering Tool

⚫ Range from device configuration to full substation


design of bay integration
⚫ Offline visual programming configuration
⚫ Device drive file generation
⚫ Device drive file upgrading and importing

www.nrec.com 23
PCS Studio Engineering Tool
⚫ Online debugging and download
⚫ GOOSE-SV configuration function

www.nrec.com 24
Certificates

IEC61850Ed2,PRP/HSR,GOOSE,DNP Certificates

KEMA KEMA KEMA KEMA


IEC61850Ed2 PRP/HSR GOOSE DNP

www.nrec.com 25
Test Report

TUV Type Test and NERC CIP Compliance report

TUV EMC TUV LVD NERC CIP

www.nrec.com 26
PCS S Series IEDs

Generation Transmission Distribution

PCS-902S

PCS-931S

PCS-9705S PCS-9705S PCS-902S

PCS-9705S PCS-915SC PCS-978S PCS-915SC PCS-931S PCS-9611S

G C

www.nrec.com 27
PCS S Series IEDs

Application PCS-931S PCS-902S PCS-915SC PCS-978S PCS-9705S PCS-9611S

Line Distance Protection ■ ■

Line Differential Protection ■

Busbar Protection ■

Transformer Protection ■

Reactor Protection ■

Feeder Protection ■

BCU ■

www.nrec.com 28
PCS-902S Line Distance Protection

⚫ Application

- Overhead line, cables, hybrid transmission lines,various voltage


levels
- Two- to three- terminal lines
- Double circuit breakers
configuration
- Integrates main and back-up
protection functions
- Comprehensive protection and
control solutions

www.nrec.com 29
PCS-902S Line Distance Protection
Tran

⚫ Features smis
sion
Line
Prote

- Fast distance protection ction

➢ Clear the fault with high speed and reliability


➢ Typical operation time is 3~10ms

- Distance protection adopted the half-wave


algorithm
➢ Typical operation time is 12-15ms

- Unique power swing blocking releasing


logic
➢ Properly supervise distance protection during
power swing
➢ Ensures to operate correctly for internal faults
during power swing
➢ Prevents from mal-operation during power swing

www.nrec.com 30
PCS-902S Line Distance Protection

⚫ Functions - Six zone phase-to-ground


and phase-to-phase distance
protection (21Q/21M)
- One zone phase-to-ground
and phase-to-phase distance
protection for pilot scheme
(85)
- High-speed DPFC distance
protection (21D)
- Pilot directional earth-fault
protection (85)
- Six stages phase overcurrent
protection (67P, 50/51P)
- Optional PMU

www.nrec.com 31
PCS-931S Line Differential Protection

⚫ Application
- Overhead line, cables, hybrid
transmission lines of various voltage
levels
- Two- to five- terminal lines
- Double circuit breakers configuration
- Integrates main and back-up
protection functions
- Comprehensive protection and
control solutions
- Optional PMU
- Optional travelling wave fault locator

www.nrec.com 32
PCS-931S Line Differential Protection

⚫ Features - Phase-segregated differential protection employs


DPFC and steady quantities
➢ Easy to set
➢ Quick to clear the fault
➢ High sensitivity
➢ Immune to power swing and load fluctuation
- Dynamic capacitive current compensation
➢ Compensate both steady-state capacitive current and
transient capacitive current
➢ Increases the sensitivity to high-impedance faults in long
distance transmission lines
- Current differential protection supports double
fiber channel
➢ Parallel and independent
➢ Either can be selected as main channel
➢ Seamlessly switched to standby channel when
main channel is abnormal

www.nrec.com 33
PCS-931S Line Differential Protection

⚫ Functions
- DPFC current differential
protection (87L)
- Steady-state current
differential protection (87L)
- Neutral current differential
protection (87L)
- Six zone phase-to-ground
and phase-to-phase
distance protection
(21Q/21M)
- High-speed DPFC distance
protection (21D)
- Two-end fault locator
…..

www.nrec.com 34
PCS-9611S Feeder Protection

⚫ Application

- Overhead line, underground


cable, capacitor, transformer
and motor etc.
- Comprehensive protection ,
control and monitoring

www.nrec.com 35
PCS-9611S Feeder Protection
⚫ Features

- Integrates protection and control


function of line, capacitor, motor
and transformer etc.

- Steady-state distance protection

- Optional PMU and arc flash


protection

www.nrec.com 36
PCS-9611S Feeder Protection
⚫ Functions - Six-stage phase overcurrent
protection (50/51P, 67P)
- Optional six zone phase-to-ground
and phase-to-phase distance
protection (21Q/21M)
- Thermal overload protection (49)
- Zero sequence overcurrent
protection (50/51G, 67G)
- Sensitive earth fault protection
(51SEF, 67SEF)
- Negative sequence overcurrent
protection (50/51Q)
- Broken conductor protection (46BC)
- Restricted earth fault
protection(64REF)
- ……

www.nrec.com 37
PCS-978S Transformer Protection
⚫ Application

- Two-winding transformers,
three-winding transformers
(up to 6 branches), auto-
transformers in any voltage
level.

- Comprehensive protection ,
control and monitoring

www.nrec.com 38
PCS-978S Transformer Protection

⚫ Features
- Self-adaptive inrush current blocking
criterion
➢ Fast operation for transformer
energized on to a slight fault

- Biased DPFC differential protection


➢ Immune to heavy load current
➢ Sensitive to small internal fault current

- Reliable differential CT circuit failure


supervision

www.nrec.com 39
PCS-978S Transformer Protection
⚫ Functions

www.nrec.com 40
PCS-978S Transformer Protection

- Transformer differential protection (87T)

- Inrush 、CT saturation and Over-excitation blocking

- Overexcitation protection (24)

- Phase overcurrent protection (67P, 50/51P)

- Four zone phase-to-ground and phase-to-phase distance


protection (21Q/21M)

- …….

www.nrec.com 41
PCS-915SC Centralized Busbar Protection

⚫ Application
- Various busbar scheme protection
- Maximum to 6 buses and 36 bays

www.nrec.com 42
PCS-915SC Centralized Busbar Protection

⚫ Features - Phase segregated differential protection


➢ Adopts both of deviation of power frequency
component (DPFC) and steady-state
component

- DPFC differential protection


➢ Patented adaptive-weight anti-saturation
algorithm and harmonic restrain algorithm
➢ Operates fast and not affected by load current
➢ Typical operation time is within 20ms

- No mal-operation of external fault with


or without CT saturation
- Fast operation of internal fault in the
case of the correct transfer time of CT is
no less than 3ms
www.nrec.com 43
PCS-915SC Centralized Busbar Protection

⚫ Functions
} 87B 50BF 50DZ FR 62P D 50/51

3 CTs 3 CTs 3 CTs

* * *
52 52 52
…… } 27P 59P 81O 81U

Bay 1 Bay 2 Bay n


* 50S OTF
Busbar 1 3 CTs

Bus
52
coupler
Busbar 2

- Busbar current differential protection (87B)


- Bus coupler/section protection (50BF , 50DZ , SOTF, 50/51P, 50/51G)
- Feeder protection (50BF , 50DZ, 50/51P, 50/51G)
- Undervoltage protection (27P)
- Overvoltage protection (59P)
- Over-frequency and Under-frequency protection (81O/81U) ……

www.nrec.com 44
PCS-9705S Bay Control Unit

⚫ Application
- Single circuit breaker (double or single bus)
configuration, double circuit breakers configuration

- Switchgear with breaker-and-a-half configuration


for a complete diameter

- Max. 4 buses supervision

- 2 or 3-windings transformer configuration,auto-


transformer, main transformer with auxiliary
transformer, reactor

- Multi-bay (max. 6 bays + 2 buses) configuration


and I/O-box, etc.

www.nrec.com 45
PCS-9705S Bay Control Unit

⚫ Features
- Complete backup protection
- Optional Phasor Measurement Unit (PMU)
- Max 15th harmonics, energy metering and
Power Quality Supervision (Total Harmonic
Distortion (THD) and current/voltage total
demand distortion (TDD))
- Rich control functions

➢ Optional synchronization, reclosing and AVR,


etc

www.nrec.com 46
PCS-9705S Bay Control Unit

⚫ Functions
- Optional backup bay protections
(overcurrent, voltage)

- Automatic reclosing function and


synchrocheck for line protection
applications with 1-pole and 3-pole
tripping
- Control, synchrocheck and
switchgear interlocking
- Voltage controller for transformer
- On load tap changing for
transformer
……

www.nrec.com 47
Thanks.
www.nrec.com

Version 2018
Copyright 2018 All Copyrights Reserved by NR Electric Co., Ltd.